myers models cgl, cg, cgnc, cwhv3, cwhv4 …files.pentairliterature.com/myers/k3215.pdf myers ®...

4
WWW.FEMYERS.COM MYERS ® MODELS CGL, CG, CGNC, CWHV3, CWHV4 AND CNC SINGLE AND THREE-PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Upload: dangnga

Post on 20-Mar-2018

223 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: MYERS MODELS CGL, CG, CGNC, CWHV3, CWHV4 …files.pentairliterature.com/Myers/K3215.pdf myers ® models cgl, cg, cgnc, cwhv3, cwhv4 and cnc single and three-phase simplex and duplex

WWW.FEMYERS.COM

MYERS®

MODELS CGL, CG, CGNC, CWHV3, CWHV4 AND CNCSINGLE AND THREE-PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Page 2: MYERS MODELS CGL, CG, CGNC, CWHV3, CWHV4 …files.pentairliterature.com/Myers/K3215.pdf myers ® models cgl, cg, cgnc, cwhv3, cwhv4 and cnc single and three-phase simplex and duplex

2

SINGLE AND THREE-PHASE SIMPLEX AND DUPLEX CONTROL PANELS

MYERS®

Quality Electrical Components Assure Reliable, Automatic Pump Operation• IEC horsepower-rated motor contactors/starters rated at over 1 million cycles.• Designed for use with standard mercury float switches. Uses three for simplex (off-on-alarm), four for duplex (off-on-override-alarm).• Solid state alternating relay to equalize pump wear (duplex only).• Override relay to start second pump if first one fails for any reason (duplex panels only).

Corrosion-Resistant for Long Life• Outdoor NEMA 3R enclosures of galvanized steel with gray enamel finish and steel back panels (except CGL).• Weathertight NEMA 4X fiberglass enclosures with aluminum back panels (CGL only).

Meets NEC and UL (508) Standards for Safety• UL-approved panel designs (label installed only on

request).• Individual pump circuit breakers.• Control circuit transformer with primary fusing.• Separate control and alarm circuit fuses.

Single-Phase Enclosure DimensionsPanel CGL

Simplex 1 ph.CG, CNC,CWHHV

Simplex 1 ph.CGL

Duplex 1 ph. CG, CNC, CWHV

Duplex 1 ph. Material Fiberglass Fiberglass Fiberglass Fiberglass

A 15-1/2 17-1/2 19-5/8 19-5/8B 13-3/8 15-7/16 17-1/2 17-1/2C 7-3/4 7-11/16 10-5/8 10-5/8D 14-5/8 16-3/4 18-7/8 18-7/8E 10 12 12 12F 5/16 5/16 5/16 5/16

Three-Phase Enclosure DimensionsPanel CGL

SimplexCGL Duplex 1 – 15 HP

Simplex1 – 15 HP Duplex

20 – 60 HP Simplex

20 – 60 HP Duplex

208/230V 460V 208/230V 460V 20-25 HP 30-60 HP 20-25 HP 30-60 HPMaterial Fiberglass Fiberglass Steel Steel Steel Steel

A 17-1/2 19-5/8 22 26 32 26 32 38 36B 15-7/16 17-1/2 20 24 20 24 24 36C 7-11/16 10-5/8 8-3/8 8-3/8 8-3/8 8-3/8 12-3/8D 16-3/4 18-7/8 21 25 31 25 31 31 37E 12 12 13 17 13 17 17 27F 5/16 5/16 3/8 x 1/2 3/8 x 1/2 3/8 x 1/2 3/8 x 1/2G –– –– 20 24 30 24 30 30 36

A D G

EB

C

F

• Elapsed Time Meter• Alarm Bell or Horn• Alarm Bell or Horn with Silence Switch• Auxiliary Alarm Contacts• Condensation Heater• Convenience Outlet• Intrinsically Safe Relays• Lightning Arrestor• Full Inner Door (CGL only)• Cycle Counter• 115 or 24 Volt Control Circuit Transformer• Transfer Switch/Generator Receptacle• Lag Pump Delay Circuitry (duplex only)• Low Level Cut-Off and Alarm• Low Voltage Circuitry

Panel Dimensions and Optional Features

Other options available. Consult factory for applications.

NOTE: Some options may increase enclosure size.

Page 3: MYERS MODELS CGL, CG, CGNC, CWHV3, CWHV4 …files.pentairliterature.com/Myers/K3215.pdf myers ® models cgl, cg, cgnc, cwhv3, cwhv4 and cnc single and three-phase simplex and duplex

3WWW.FEMYERS.COM

SINGLE AND THREE-PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Standard Panel Features for CGLA. Corrosion-Resistant Enclosure NEMA 4X fiberglass (outdoor).

B. Aluminum Back PanelC. IEC Motor Starter/ContactorsD. Pump Circuit Breaker(s)E. Control Circuit Fuse 1 Amp.

F. Alarm Circuit Fuse 1 Amp.

G. Hand-Off-Auto Switch Momentary in-hand.

H. Pump Run Light Amber.

I. Seal Leak Light Red (only on units with detector).

J. Terminal BlocksK. Ground LugL. Flashing Alarm Light Mounted on top of enclosure (red).

M. Solid State FlasherN. Override Relay In event of first pump failure (duplex only).

O. Alternator Relay Solid state (duplex only).

P. Control Circuit Transformer (Three-phase only).

Q. Start Winding Relay(s) (Single-phase only).

R. Starting Capacitor(s) (Single-phase only).

S. Running Capacitor(s) (Single-phase only).

T. Klixon® Overload (Single-phase only).

AP

Q

R

D

E F

H

I

G

J K

L

S

Q

T

B

C

M

Single-Phase Simplex

N

R

SC C

G

JK

B

EF

GH HI IJ

L

T

O

QD D

K

M

S

R

Q

T

Single-Phase Duplex

C

A

B

G

J

L

D

EF

H

I

K

P

MThree-Phase Simplex

M

C

G

J

K

E

F

HHI I

L

N PO

G

J

D D

C

K

A

B

Three-Phase Duplex

A

A

Page 4: MYERS MODELS CGL, CG, CGNC, CWHV3, CWHV4 …files.pentairliterature.com/Myers/K3215.pdf myers ® models cgl, cg, cgnc, cwhv3, cwhv4 and cnc single and three-phase simplex and duplex

740 EAST 9TH STREET, 269 TRILLIUM DRIVE, KITCHENER, ASHLAND, OHIO 44805 ONTARIO, CANADA N2G 4W5 WWW.FEMYERS.COM WWW.FEMYERS.COM

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.K3215 09/18/14 © 2014 Pentair Ltd. All Rights Reserved.

Full Inner Door Front View

Three-Phase Simplex

G D

A

EF

H

N

B C

M

MM

JI

O

P

K LR

Q

Full Inner Door Front View

Three-Phase Duplex

O

R

KL

I

J

Q

S C

A

B

EF

H

T

IL

DDG

R

KM M M

M

C

M

Full Inner Door Front View

C C

A

E F

G

I I

L

M

O

V

S

U

X

R T

BQ

K

NN

R

W

JL

K W

XD D

MMM

VSingle-Phase Duplex

Full Inner Door Front View G

K

JY

MN

U

V

W

A

DEF

I

O

X

Q

M

Single-Phase Simplex

A. Corrosion-Resistant Enclosure

B. Back PanelC. IEC Motor Starter 3-Pole bi-metal overload relay

(three-phase only), 1-Pole bi-metal overload relay (single-phase only – not on CWHV3).

D. Pump Circuit Breaker(s) Lock-out tab(s).

E. Control Circuit FuseF. Alarm Circuit FuseG. Control Circuit BreakerH. Control Circuit

Transformer (Three-phase only).

I. Hand-Off-Auto Switch Momentary in-hand position.

J. Alarm Test SwitchK. Pump Run Light(s) Amber.

L. Seal Leak Light(s) Red (except CWHV3).

M. Terminal BlocksN. Ground LugsO. Flashing Alarm Light Mounted on top of enclosure (red).

P. Full Inner DoorQ. Solid State Flasher

R. Overload Reset Button (Not on CWHV3 single-phase).

S. Override Relay In event of first pump failure

(duplex only).

T. Alternator Relay Solid state (duplex only).

U. Incoming Power Terminal Blocks

(Single-phase only).

V. Start Winding Relay(s) (Single-phase only).

W. Starting Capacitor(s) (Single-phase only).

X. Running Capacitor(s) (Single-phase only).

Y. IEC Motor Contactor(s) (Single-phase CWHV3 only).

Standard Panel Features for CG, CGNC, CNC, CWHV3 and CWHV4

P

B

P

N N