8
Presentation The MX 32 is a compact, low-profile controller that continuously monitors gas detection, including 4-20 mA, dry logic input, MODBUS RS485 signal from compatible detectors. Controller MX 32 Features Analog and digital controller Up to eight detectors Fully scalable SIL1 reliability

Upload: others

Post on 05-Aug-2020

7 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

PresentationThe MX 32 is a compact, low-profile controller that continuously monitors gas detection, including 4-20 mA, dry logic input, MODBUS RS485 signal from compatible detectors.

Controller

MX 32

Features

• Analog and digital controller

• Up to eight detectors

• Fully scalable

• SIL1 reliability

Page 2: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

MX 32

Different modules can be connected to improve the capabilities of the controller.

Modules

4 or 8-relay module

16-logic-input module

Addressable module of 16 logic input for recovery of digital information such as fire or intrusion alarms, emergency stop, limit switch activation, etc.

8-analog-input

4-analog-output

Programmable 4 or 8--relay module can be located closer to the actuators for cost savings.

Can connect standard analog transmitters (gas or flame detectors for instance) on a digital line for cost savings.

Addressable 4-analog-output module that delivers four analog 4-20mA signal outputs (detector output copy, min, max,average of a group of detectors) for connection to a datalogger, a PLC, a Building Management System (BMS), etc.

Controller

Page 3: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

MX 32

Five programmable events per detector

Smart keys make embedded multi-language

menus simple to use

5” LCD back-lit graphic display

MX 32 takes analog and digital inputs and covers all needs for a wide variety of applications.

The MX 32 digital technology allows up to eight detectors to be distributed on two lines for increased cost savings.

Lockable toggle latch

Four on-board relays and one fault relay

Power supply 100-240Vac (optional)

RS485 output (optional)

Controller

Page 4: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

0-100 %LIE méthane

Capteurprécéd.

Capteursuivant

Voir 4capteurs

Menu Courbe

Turbine gaz Sud L02M01

%LIECH47

MOY 8h:0

Capteur OK

Au moins 1 ligne à l’arrêt

100

0

50

30

15

12

3

4

5

6

7

0-100 %LIE méthane

Zoom +Zoom -

Turbine gaz Sud OLC T100 L02M01

50%LEL

14:43:51

Gaz: 50%LIE

0

30/07/10

Zoom

Capteur

Zéro

Sens

Fin

1

2

3

4

5

0-100 %LIE méthane

Capteurprécéd.

Capteursuivant

Voir 4capteurs

Menu Courbe

Turbine gaz Sud L02M01

%LIECH440

MOY 8h:22

Capteur OK

Fonctionnement normal

100

0

50

30

88

AL14

1

2

35

Pageprécéd.

Pagesuivante

Voir 8capteurs

Menu

Extracteurs

%LIECH41

100

0

Turbine gaz Sud

%LIECH47

100

0

Local variateur

%LIECH47

100

0

Compression

%LIECH421

100

0

1

MX 32

1 Measure Range, gas and detector tag 2 Detector address 3 Current value with unit and detected gas 4 Averaged value on the last eight hours 5 Bar graph with alarm thresholds 6 Detector status (OK, OFF, FAULT) 7 MX 32 status information

1 Calibration curve 2 Cursors for span settings 3 Measured value 4 Calibration gas value 5 Detector selection, zeroing and spanning

Normal mode

Simplified procedure that enables time savings(i.e. non-intrusive and one-man calibration).

Alarm mode

Grayscale mode in alarm conditions for immediate identification of the concerned detector.

1 Current value with unit and detected gas 2 Averaged value on the last eight hours 3 Detector status (OK, OFF, FAULT) 4 MX 32 status information 5 Detector in alarm

Simultaneous display of several detectors

1 Up to eight detectors displayed simultaneously

Calibration curve

Controller

Page 5: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

Pageprécéd.

Pagesuivante

Dernièrepage

E�acer Echap.

Alarmes gaz 64/64

Turbine gaz Sud

Turbine gaz Sud

Turbine gaz Sud

Turbine gaz Sud

AL1

AL2

AL1

AL2

ON

ON

OFF

OFF

13 01 10

13 01 10

13 01 10

13 01 10

18:22:19

18:22:19

18:22:31

18:22:31

1 2

3

4

Level 1

OK Cancel

Level 5Level 3 Level 4

Alarm 1

Compressor A-2

Alarm 1

Compressor A-3

Alarm 2

Compressor A-1

Alarm 2

Compressor A-2

Alarm 2

Compressor A-3

Alarm 1

Compressor A-1

Alarm 1

Compressor A-3

Alarm 1

Compressor A-2

Alarm 1

Compressor A-2

Level 2

VOTING

OR OR

OR

Siren

=

=

= =

=NAND=ORANDNORNANDVOTING

2 /3

MX 32

1 Simple relay programming 2 Up to five embedded functions: OR, AND, NOR, NAND, VOTING 3 Multiple timers available 4 Advanced management of audible alarms (acknowledgment, reactivation, evacuation)

1 Calibration curve 2 Cursors for span settings 3 Measured value 4 Calibration gas value 5 Detector selection, zeroing and spanning

1 Detector tag 2 Event 3 Date and time of events appearance or clearance 4 Page number (up to 64 pages)

COM 32 configuration software

By default, the MX 32 can store up to 512 alarm events,512 fault events and 512 system events.

Ordering information

MX32-A-B-C-D-E-F

Version

1- 1 channel 2- 2 channels3- Wheatstone bridge

Power supply

1- 24Vdc 2- 100/240Vac

Language

1 - French2 - English

Strobe and Audible

alarm combination

0- Without1- Red2- Blue

RS 485 serial

output

0 - Without 1 - With

COM 32 software

0 - Without

1 - With (USB cable included)

f.i: MX32-1-2-2-2-1-1 for MX32 1 channel, 100/240Vac, English menu, Blue strobe & horn, RS485 output and COM 32 software

Data-logging

Controller

Page 6: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

Liaison analogiqueLiaison numérique

OLC 100

Confi guration Pont de Wheatstone

OLCT100

OLCT10N OLCT10N OLCT10N

Confi guration 1 ligne analogique + 1 ligne numérique

MX 32Controller

Configuration examples

RS485 output to supervision

Digital detectors

4 or 8 relay module

16-logic-input module

Analog detectors

8-analog-input module 4-analog-output module

Analog signal Digital signal

Channel 1

Channel 2

iTrans2

OLCT 80 OLCT 10N

2 digital channel confi guration

Analog recorders

OLCT 710

OLCT 100 MultiFlame DF-TV7-T

Page 7: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

MX 32Controller

Model MX 32 gas detection control panel

Dimensions (w*h*d) 265 x 266 x 96 mm (10.4 x 10.5 x 3.8 inches)

Ingress protection IP55

Cable entries (wall-mounted version) 5 M16 cable glands, 4 to 8 mm2 (8 to 11 AWG) outer diameter cable

2 M20 cable glands, 6 to 12 mm2 (7 to 9 AWG) outer diameter cable

Display LCD back-lit display + smart keys

Display in grayscale mode in case of fault

Customizable by user (display 1 to 8 channels simultaneously, fixed or scrolling, on events...)

Bar graph with alarm threshold

Visual indicators 7 LEDs per line for Detector status

1 common LED for Fault condition

1 common LED for Power condition

Buttons 5 smart keys

1 audible alarm accept/reset button

Operating use

Operating temperature -20°C to +50°C (-4°F to +122°F)

Storage temperature -20°C to +50°C (-4°F to +122°F)

Humidity 5 to 95% RH

Power input 100-240Vac 50-60Hz (35W) or 22-28Vdc (92W)

Consumption 250mA max. (without module or detector)

Measurement lines

Digital lines 2 maximum

RS-485 communication, proprietary protocol, 9600 Baud

2 twisted shielded-pair cable

Analog channels 2 maximum (4-20mA or Wheatstone Bridge)

0-23mA analog signal input (4 to 20mA reserved for measurement) or OLC 10, OLC 10Twin

and OLC 100 flammable gas detectors (Wheatstone bridge type)

120 Ohm load resistance

2 or 3 core shielded cable depending on detector

Maximum current output per line 0.42A (@ 50°C) to 1A (@ 30°C) with internal AC power or 1.5A with external DC power

Maximum current output for the 2 lines 0.42A (@ 50°C) to 1A (@ 30°C) with internal AC power or 2x1.5A with external DC power

Alarms

Per channel

5 Alarm levels (A1, A2, A3, Overscale, Underscale) + 1 Fault

Catalytic bead over range protection

Programmable thresholds on instantenous or averaged values, rising or falling alarms, manual or automatic

acknowledgement

Output

On-board relays 4 fully programmable alarm relays + 1 fault relay (non-configurable)

Dry contact relay, DPCO relays, contact rating 5A / 250 Vac - 30Vdc

External relays Up to 16 fully programmable alarm relays

Dry contact relay, DPCO relays, contact rating 5A / 250 Vac - 30Vdc

Digital outputs RS-485 Modbus RTU

Analog outputs Up to 8 outputs (4-20mA)

Approvals

EMC According to EN 50270:15

Low voltage directive According to EN 61010-1:10

ATEX Metrological performances according to EN 60079-29-1:2016 and EN 50271:10

CSA CAN/CSA-C22.2 No. 0-10; CAN/CSA-C22.2 No. 61010-1-12; UL Std. No. 61010-1 (3rd Edition)

Functional safety

(reliability data)

SIL1 capability according to EN 50271:2010

du =1,60 to 1,80.10-6, PFDavg=7,10 to 8,02.10-3, Ti=1 year, MTBF=25 to 28 years, SFF 60%

Page 8: MX 32 - Teledyne Gas and Flame Detection · 2019-12-30 · MX 32 Five programmable events per detector Smart keys make embedded multi-language menus simple to use 5” LCD back-lit

Copyright © 2020 Teledyne Technologies. All rights reserved. GF-00226G-EN [email protected]

AMERICAS 4055 Technology Forest Blvd.The Woodlands, TX 77381USA.Tel.: +1-713-559-9200Fax: +1-713-893-6729

EMEAZI Est, Rue Orfila,CS 2041762027 ARRAS CEDEX, FranceTel.: +33-3-21-60-80-80Fax: +33-3-21-60-80-00

ASIA PACIFIC290 Guiqiao RoadPudong, Shanghai 201206People's Republic of ChinaTel.: +86-21-3127-6373Fax: +86-21-3127-6365

www.teledynegasandflamedetection.com