Page 2: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

Voltage input AC 110 / 220 / 380VCurrent input AC 5A or 1AInput loss/element V: 0.3VA, C: 0.5VA

Max. inputoverload

Voltage(PT) 150% for 10secCurrent(CT) 1000% for 10sec

Frequency 50 / 60Hz

IndicatorLED(Red)

Fault OnNormal Off

LED (Green) Flicker at the load input

Aux. power supply AC110/220V±15V 50/60HZ 1.5VADC Volt ±10% 1W

pulse output specification계기정수(Pulse/Kwh) : 10000외부출력 펄스 : 1Pulse=0.1Wh(Ic<10mA, Vcc<30V, 펄스폭 70mS)

Communication Modbus

TemperatureRange

Storage -20~70

Operating -10~60

Operating humidity 20~90%RH (Non-condensing)

Accuracy(at 25) ±0.5%

Temp. influence ±0.01% /

Insulation resistance 100MΩ more with DC500V

Dielectric test AC 2000V / 1minute

Mounting Wall or DIN Rail(35mm)

Size 150(W) × 75(H) × 112(D)mm

Case material ABS Resin

Weight Approx. 500g

P×W PT ratio CT Cal.Watt Code

1×2110V 5A 550W A220V 5A 1100W D

Others Others Others S

3×3220V 5A 2200W D380V 5A 3800W G

Others Others Others S

3×4190/110V 5A 1650W K380/220V 5A 3300W L

Others Others Others S

통신 Type Pulse output Type

1 2Modbus(RS-485)

모든 전기량

계기정수(Pulse/Kwh) : 10000외부출력 펄스 : 1Pulse=0.1Wh

DT-CWH SERIES는 AC 전기량의 검침 값을 데이터 통신을

통해 외부로 전송할 수 있는 인터페이스를 지원하는 변환기

입니다.

DT - CWH- - 1) 2) 3) 4) 5) 1) CONNECTION 12 : 1Phase 2Wire 33 : 3Phase 3Wire

34 : 3Phase 4Wire

2) INPUT

3) OUTPUT

4) AUX. POWER A : AC 110/220V B : AC 115/230V C : AC 120/240V D : DC 24V E : DC 48V F : DC 110V G : DC 115V H : DC 220V

MULTI TRANSDUCER (RS485 Modbus Communication) DT - CWH Series

Specifications

MODEL CODE

Characteristics

교류전용 CPU를 채택하여 전기 계측에 신뢰성과 정밀성

을 높였습니다.

다양한 통신방식이 가능한 유연한 시스템방식인 ModBus

(RS-485)통신방식을 수용하여 실시간으로 모니터링이

가능합니다.

유.무효 누적량은 최대 6digit(999,999kWh)까지 가능하고

자동 Reset됩니다.

검침 데이터 보존 기능 - 비휘발성 메모리를 채택하여 정전

시에도 데이터를 영구 보존합니다.

정밀 sensor 사용으로 0.5% 이하로 정밀측정이 가능합니다.

전압은 PT 없이 AC 380V까지 가능하며 전류는 CT 2차측

AC 5A까지 입력 가능합니다.

1

Page 3: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

계측항목 요 소 계측항목 요 소

전 압 R,S,T - 상전압 전 류 R,S,T

송전유효전력 (-역방향) R,S,T,⅀ 수전유효전력 (+정방향) R,S,T,⅀송전무효전력 (-역방향) R,S,T,⅀ 수전무효전력 (+정방향) R,S,T,⅀

송전유효전력량 (-역방향) ⅀ 수전유효전력량 (+정방향) ⅀송전진상무효전력량 (-역방향) ⅀ 수전진상무효전력량 (+정방향) ⅀송전지상무효전력량 (-역방향) ⅀ 수전지상무효전력량 (+정방향) ⅀

역 율 R,S,T 주 파 수 -

※ 상기 표시 범위는 CT, PT 2차측 기준이므로 배율을 곱하여 사용하여야 하며 아랫방법을 참고 하시기 바랍니다.

1) 전압

- 데이터 통신을 통해 계측된 전압을 사용하면 됩니다. - 기본 상전압이기 때문에 3P4W에서 선간전압으로 표시를 원하실 경우 PT비율을 곱해서 사용 합니다. ex) PT가 380/220V일 경우 PT비는 1.727 이므로 220V × 1.727 = 380V가 됩니다.

2) 전류

- 데이터 통신을 통해 계측된 전류에 CT비율을 곱해서 사용하면 됩니다. ex) 계측된 전류 : 2A, CT비 : 200/5A일 경우 - 계측된 전류 × CT비 = 2A × 40 = 80A가 됩니다. 3) 유효전력•전력량 및 무효전력•전력량

- 데이터 통신을 통해 계측된 유효전력에 승율(CT비 × PT비)을 곱해서 사용합니다. ex) 측정된 유효전력: 825W, CT비 : 200/5A, PT비 : 380/190V일 경우

유효전력값 × CT비 × PT비 = 825W × 40 × 2 = 66KW로 표시가 되도록 프로그램을 작성하여 사용

하십시오.

- 유효전력량 또한 계측된 유효전력량에 승율(CT비 × PT비)을 곱해 사용하십시오. ex) 측정된 유효전력량: 2500WH, CT비 : 200/5A, PT비 : 380/190V일 경우

유효전력량값 × CT비 × PT비 = 2500WH × 40 × 2 = 200KWH로 표시가 되도록 프로그램을 작성

하여 사용 하십시오.

4) 역율

- 데이터 통신을 통해 계측된 값을 사용하면 됩니다.

5) 주파수

- 데이터 통신을 통해 계측된 값을 사용하면 됩니다.

Data setting

Measurement

2

Page 4: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

2 4 6 8

1 3 5 7 9 11

P1 P3P2

1S

P0

2S1L 3S2L

16

3L

141210

171513

-+-+

~

~

+

DC Volt

AC 110V

-

AC 220V

KwhFault

21

N3

LOADLINE

3P4W

PULSE 통신출력

42

1

6

3 119

P3P2P1

1L1S

16

3L3S

10 12 14

15 1713

-+-+

~

~

-+

DC Volt

AC 220V

AC 110V

Fault Kwh

21

3

3P3W

LOADLINE

PULSE 통신출력

42

31

P1 P2

1L1S

14 1610 12

13 15 17

+ -+-

~DC Volt

~

-+

AC 220V

AC 110V

KwhFault

21LINE

통신출력

1P2W

LOAD

PULSE

Connection diagram

Dimensions

3

Page 5: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

Full Scale inputDC Voltage (0 ~ 300V)

DC Current (0~50mA)

TemperatureRange

Storage -20°C ~ 70°C

Operating -10°C ~ 60°C

Operating humidity 20~90%RH (Non-condensing)

Accuracy(at 25) ±0.5%

Temp. influence ±0.01%/°C

Linearity ±0.02% F.S

Response time 0.4sec(0~90%)

Communication Modbus RS-485

Aux. power supply 110/220VAC ±15V,50/60Hz,4VADC Volt ±10% 2W

Operating humidity 20~90%RH (Non-condensing)

Insulation resistance 100MΩ more with DC500V

Dielectric test AC 1500V / 1minute

Isolation Input/Output/Power/Case

Mounting Wall or DIN Rail(35mm)

Size 150(W) × 75(H) × 112(D)mm

Case material ABS Resin

Weight Approx. 500g

Code Input Input ResistanceA DC 4~20mA 250Ω

B DC 0~1mA 1.5KΩ

C DC 0~50mV 1MΩ

D DC 0~100mV 1MΩ

E DC 0~1V 1MΩ

G DC 0~5V 1MΩ

H DC 0~10V 1MΩ

S Specify current : less than 50mASpecify voltage : less than 300V

통신 Type 1 RS-485(Modbus)

Specifications MODEL CODE

Characteristics

Data Setting

DT-MT-SC SERIES는 다양한 DC 전압 및 전류의 입력값을

테이터 통신을 통해 외부로 전송할 수 있는 인터페이스를

지원하는 변환기입니다.

DT-MT-SC- 1) 2) 3) 1) INPUT

2) OUTPUT

3) AUX. POWER A : AC 110/220V B : AC 115/230V C : AC 120/240V D : DC 24V E : DC 48V F : DC 110V G : DC 115V H : DC 220V

- DC입력에 관계없이 모든 계측값은 최소값 0 , 최대값 1 로 계측 됩니다. - 계측된 데이터 값에 표시하고자 하는 값을 곱해서 사용하면 됩니다. ex) 인버터 주파수 0~10KHz일 때 발생되는 0~10VDC를 변환기(DT-MT-SC)에 연결시켜 RS485(Modbus) 로 0 ~ 1의 계측값이 측정됨. 최소값 = 0Hz × 0(계측값) = 0 Hz 중간값 = 10000Hz × 0.5(계측값) = 5000 Hz 최대값 = 10000Hz × 1(계측값) = 10000 Hz입니다. 그러므로 측정치 = 입력최대치 × 계측값 공식으로 계산하면 됩니다.

4-CHANNEL SIGNAL CONVERTER MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series

입력받는 DC전압 ⋅ 전류의 값을 0.5%이하로 정밀하게

측정하여 신뢰성과 정밀성을 높였습니다.

다양한 통신방식이 가능한 유연한 시스템방식인 RS-485

(Modbus) 통신방식을 수용하여 실시간으로 모니터링이

가능합니다.

1

Page 6: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

Dimensions

Connection diagram

2

Page 7: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

ACMax. Voltage input 0 ~ 520VMax. Current input 0 ~ 5A Input loss V: 0.3VA, C: 0.5VA

DCVoltage input 0 ~ 300V

Current Input 0 ~ ±100mVFrequency 50/60Hz

Aux. power supply 110/220VAC ±15V,50/60Hz,4VADC Volt ±10% 2W

Communication RS-485(Modbus)

TemperatureRange

Storage -20 ~ 70

Operating -10 ~ 60

Operating humidity 20~90%RH (Non-condensing)Accuracy(at 25) ±0.5%

Temp. influence ±0.01% /

Insulation resistance 100MΩ more with DC500V

Dielectric test AC 1500V / 1minute

Mounting Wall or DIN Rail(35mm)Size 150(W) × 75(H) × 112(D)mmCase material ABS ResinWeight Approx. 700g

CodeINPUT

AC V AC A DC V DC A DC AA 150V 5A 150V 50mV ±50mVB 520V 5A 150V 50mV ±50mVC 150V 5A 300V 50mV ±50mVS Others

통신 Type 1 RS-485(Modbus)

Data Setting

DT-MT-REC SERIES는 정류기반의 AC, DC 전압 및 전류의

검침 값을 데이터 통신을 통해 외부로 전송할 수 있는

인터페이스를 지원하는 변환기입니다.

DT-MT-REC-

1) 2) 3) 4)

1) INPUT

2) OUTPUT

3) AUX. POWER A : AC 110/220V B : AC 115/230V C : AC 120/240V D : DC 24V E : DC 48V F : DC 110V G : DC 115V H : DC 220V

1) 전압

- AC 전압 입력에 관계없이 모든 계측값은 최소값 0 , 최대값 1 로 계측 됩니다. - 입력이 0~520V일 경우

최소값 = 0V × 계측값 0 = 0V 최대값 = 520V × 계측값 1 = 520V입니다. 그러므로 측정값 = 입력최대값 × 계측값 공식으로 계산하면 됩니다.

2) 전류

- 데이터 통신을 통해 계측된 최소값 0 , 최대값 1 에 전류 CT비율을 곱해서 사용하면 됩니다. ex) 계측된 전류 : 2A(2차측), CT비 : 200/5A일 경우 데이터 측정값은 0.4가 측정이 됩니다. 그러므로 전류값 = 200A(1차값) × 0.4(데이터 측정값) = 80A가 됩니다.

DCA : DC Current with shunt

RECTIFIER PANEL MULTI TRANSDUCER (RS485 Modbus Communication) DT-MT-REC Series

Specifications

MODEL CODE

Characteristics

입력받는 AC전압 전류 및 DC전압 전류의 값을 0.5%이하

정밀하게 측정하여 신뢰성과 정밀성을 높였습니다.

다양한 통신방식이 가능한 유연한 시스템방식인 RS-485

(ModBus)통신방식을 수용하여 실시간으로 모니터링이

가능합니다.

1

Page 8: MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series 입력받는 DC전압 ⋅ 전류의 값을

3) DC전압

- 데이터 통신을 통해 계측된 최소값 0 , 최대값 1 에 DC전압을 곱해서 사용하면 됩니다. ex) 입력이 DC 0~150V일때

- 입력전압 : DC 110V일 경우 데이터 측정값은 0.7333가 측정이 됩니다. 그러므로 전압값 = 150V(최대값) × 0.7333(데이터 측정값) = DC 110V가 됩니다.

4) DC전류(단방향) - 데이터 통신을 통해 계측된 최소값 0 , 최대값 1 에 DC전류를 곱해서 사용하면 됩니다. ex) 입력이 DC 0~150A일때

- 입력전류 : DC 50A일 경우 데이터 측정값은 0.3333가 측정이 됩니다. 그러므로 전류값 = 150A(최대값) × 0.3333(데이터 측정값) = DC 50A가 됩니다.

5) DC전류(양방향) - 데이터 통신을 통해 계측된 최소값 -1 , 최대값 1 에 DC전류를 곱해서 사용하면 됩니다. ex) 입력이 DC 0~150A일때

- 입력전류 : DC 50A일 경우 데이터 측정값은 0.3333가 측정이 됩니다. 그러므로 전류값 = 150A(최대값) × 0.3333(데이터 측정값) = DC 50A가 됩니다. - 입력전류 : DC -50A일 경우 데이터 측정값은 -0.3333가 측정이 됩니다. 그러므로 전류값 = 150A(최대값) × -0.3333(데이터 측정값) = DC -50A가 됩니다.

2

Dimensions

Connection diagram