ABB SACE 1
MOTOR SWITCHING AND PROTECTION
IEC 947-4
![Page 2: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/2.jpg)
ABB SACE 2
MOTOR DATA
• P = Rated motor power (kW)• V = Supply voltage (V)• cos = Power factor = efficency
P
In = ------------------------ = rated current
V x 1.73 x cos x
![Page 3: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/3.jpg)
ABB SACE 3
MOTOR CURRENTS
• In = Rated nominal current • Ia = Rated starting current (8-10 x
In)
• Ip = Maximum peak inrush current (13 - 15 x In)
![Page 4: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/4.jpg)
ABB SACE 4
MOTOR STARTING CURRENT
In
Ia
Ip
t (s)
I (A)
![Page 5: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/5.jpg)
ABB SACE 5
MOTOR PROTECTION
1
2
3
![Page 6: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/6.jpg)
ABB SACE 6
TIME - STARTING CURVES
• 1 MOTOR START UP
• 2 OVERLOAD PROTECTION (THERMAL)
• 3 SHORT CIRCUIT PROTECTION (MAGNETIC)
![Page 7: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/7.jpg)
ABB SACE 7
DIAGRAM A
M
2 CONTACTOR (Switching device)
3 THERMAL OVERLOAD RELEASE
1 CIRCUIT BREAKER WITHMAGNETIC RELEASE
(Short circuit protecting device)
(Overload protection)
![Page 8: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/8.jpg)
ABB SACE 8
DIAGRAM B
M
1 CIRCUIT BREAKER WITHELECTRONIC RELEASE
2 CONTACTOR
(Short circuit and overload protecting device)
(Switching device)
![Page 9: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/9.jpg)
ABB SACE 9
DIAGRAM C
M
1 CIRCUIT BREAKER WITH ELECTRONIC RELEASE
(Short circuit and overload protecting device and switching device)
![Page 10: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/10.jpg)
ABB SACE 10
DIAGRAM A
• High number of motor switcing• TOR on contactor• Most common application up to
now
![Page 11: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/11.jpg)
ABB SACE 11
DIAGRAM B
• High number of motor switching• No TOR on contactor• PR212/MP electronic release• New and future application
![Page 12: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/12.jpg)
ABB SACE 12
DIAGRAM C
• No contactor and TOR• Low number of motor switching• ACB with electronic release• Typical application for big motor
sizes (Power > 250 kW/400 V)
![Page 13: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/13.jpg)
ABB SACE 13
PR 222MP
t5
t
I1
Class
L
I3I50.4 x In
4 sec
U
I
R
I
I: istantaneous adjustable short circuit
I3=6-7-8-9-10-11-12-13 x In
L: Inverse long delay overload
I1=0.4-1 x In step 0.01 x In
R: Locked rotor protection
I5=3-4-5-6-7-8-10 x In
t 5=1-4-7-10 sec.
U: Phase loss/unbalance
OFF or ON: 4 sec. Tripping time @
one phase current 0.4 times I1
![Page 14: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/14.jpg)
ABB SACE 14
CLASS
starting class
according to IEC 947- 4
CLASS
starting class
according to IEC 947- 4
L Protection
against overloadL Protection
against overload
R Protection
against locked rotorR Protection
against locked rotor
I Protection
against short circuit
I Protection
against short circuit
U Protection
against phase loss/unbalance
U Protection
against phase loss/unbalance
PR 222MP
![Page 15: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/15.jpg)
ABB SACE 15
TRIPPING CLASS
Tripping class from 10 A to 30 defines the time-current curves of the thermal overload release during starting and on duty service (overload and phase loss)
10 A - 10 - 20 - 30
![Page 16: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/16.jpg)
ABB SACE 16
TRIPPING CLASS
10 - 10 A (Normal starting) Pump - Compressor10-20 (Normal starting) Ventilator
30 (Heavy duty) Mill
![Page 17: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/17.jpg)
17
SHORT CIRCUIT TESTDuty cicle:
O - CO at “Iq” current
O : tripping of the circuit breakerunder short circuit condition
CO : Closing by contactor undershort circuit condition and tripping
of the breaker
Motor protection
![Page 18: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/18.jpg)
ABB SACE 18
COORDINATION TYPE
Type 1
Damage to the contactor and/or thermal overload releaseis acceptable as two condition are fulfilled:- there is no risk to the operator;- no device other than contactors and/or overload releasecan be
replaced.
![Page 19: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/19.jpg)
ABB SACE 19
COORDINATION TYPE
Type 2
The only risk permitted is light welding of the contactor, i,e. the contactor can easily be separated either by electrical control or using a screwdriver.
After the coordination test:- all the protection device functions must still be operational;- the manufacturer must prove that the contactor is still operational for further service.
![Page 20: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/20.jpg)
ABB SACE 20
COORDINATION COMPARISON
Type 1
- - Lower investment cost
- Expansive maintenance
- Maintenance stop plant
![Page 21: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/21.jpg)
ABB SACE 21
COORDINATION COMPARISON
Type 2
- Higher investment cost- Cheaper maintenance- Continuity of service
![Page 22: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/22.jpg)
ABB SACE 22
STAR-DELTA STARTING
K 1 K 2 K 3
M
![Page 23: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/23.jpg)
ABB SACE 23
COORDINATION TABLE SELECTION CHART
1 Coordination type 2 Starter
“1” or “2”Direct or Star-Delta
3 Starting type Normal or Heavy duty
MOTORPOWER(kW)
CIRCUIT BREAKER
CONTACTOR
TOR
Only magnetic
With PR222MP
Name Name
(N.A. for 222MP)or
4 Voltage level and short circuit current “Iq”
![Page 24: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/24.jpg)
ABB SACE 24
![Page 25: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/25.jpg)
ABB SACE 25
500 V 50 kA type “2” star delta
MCCB O/L relayRated Output
Rated Current
Line Delta Star
Pe Ie
[kW] [A]75 110 T4H250 MA125 A95 A95 A50 TA80DU8090 132 T4H250 MA160 A110 A110 A75 TA110DU90110 158 T4H250 MA200 A110 A110 A95 TA110DU110132 192 T4H250 PR221-I In250 A145 A145 A95 E200DU200160 230 T4H320 PR221-I In320 A145 A145 A110 E200DU200200 279 T5H400 PR221-I In400 A210 A210 A145 E320DU320250 335 T5H630 PR221-I In630 A210 A210 A185 E320DU320290 394 T5H630 PR221-I In630 A260 A260 A210 E320DU320315 440 T5H630 PR221-I In630 A300 A300 A210 E320DU320
TypeMotor
TypeContactor
![Page 26: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/26.jpg)
ABB SACE 26
COORDINATION TABLES
![Page 27: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/27.jpg)
ABB SACE 27
ACB MOTOR CORDINATION TABLE
D.O.L. STARTING
Power(kW)
In(A)
Op. Nr.(AC3)
ACB(Type)
Icu(kA)
Release(A)
Type CT(A)
Up to450
800 10000 E1B 40 1250 PR112 1250
Up to630
1140 12000 E2N 65 1600 PR112 1600
Up to630
1140 12000 ES3 75 1600 PR112 1600
Up to630
1140 12000 E3H 100 1600 PR112 1600
![Page 28: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/28.jpg)
ABB SACE 28
Rated uninterrupted current, Iu [A] 160 250 250 400Rated service current, In 1…100 100…200 80…250 320, 400Poles 3 3 3 3Rated service voltage, Ue (AC) 50-60Hz [V] 690 690 690 690Rated impulse withstand voltage, Uimp [kV] 8 8 8 8Rated insulation voltage, Ui [V] 800 800 1000 1000Test voltage at industrial frequency 1 min. [V] 3000 3000 3500 3500
Rated ultimate short-circuit breaking capacity N S H L N S N S H L V N S H L VIcu AC 50-60 Hz 380/415 V [kA] 36 50 70 85 36 50 36 50 70 120 200 36 50 70 120 200
Rated service short-circuit breaking capacityIcs AC 50-60 Hz 380/415 V [kA] 36 50 70 70 27 27 36 50 70 120 200 36 50 70 120 200
Rated service short-circuit breaking capacityIcm AC 50-60 Hz 380/415 V [kA] 75,6 105 154 187 75,6 105 75,6 105 154 264 440 75,6 105 154 264 440
Isolation behaviour
Reference Standards IEC 60947-2 IEC 60947-2IEC 60947-2
IEC 60947-4-1 (with PR222MP)IEC 60947-2
IEC 60947-4-1 (with PR222MP)
Protection against short-circuitMagnetic only release MA (1) Electronic release PR221DS-I
Integrated protectionElectronic release PR222MP
Mechanical life 25000 25000 20000 20000Electrical life @ 415 V AC 8000 8000 10000 7000
Fixed dimensionsW 3p 90 105 105 140D 70 70 103,5 103,5H 130 150 205 205
(1) MF up to In=12,5A
T2 T3 T4 T5
![Page 29: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/29.jpg)
ABB SACE 29
ACB with microprocessor based motor protection
release PR 112/113
B - N - S - H
40 - 65 - 75 - 100 kA @ 400 V
800 -1250 - 1600 A
Release range:
From R800 A
EMAX E1-E2-E3
to R1600 A
![Page 30: Motor Switching and Protection](https://reader033.vdocuments.mx/reader033/viewer/2022042513/54696016b4af9fe0338b4c37/html5/thumbnails/30.jpg)
ABB SACE 30
AND NOW… MOTOR IS READY TO
START !