Modular Metering Canadian Version

Upload: others

Post on 04-Oct-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Modular MeteringCanadian Version

Page 2: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

1

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Meter Centres and Tenant Breakers ..................................................................2

Industrial Multi-Metering ........................................................................................3

Main Service Modules ..............................................................................................4

Main Terminal Boxes .................................................................................................7

Main Circuit Breakers ................................................................................................8

Main Fusible Switches ..............................................................................................9

TMPC Meter Stack Modules ................................................................................ 10

TMPC Residential Meter Stack Modules ........................................................ 11

TMPC Main Tenant Circuit Breakers ................................................................ 12

Commercial Meter Stack Modules................................................................... 14

TMPC Meter Stack Accessories ......................................................................... 15

Meter Centre Diagrams and Dimensions ..................................................... 16

Meter Centre Wiring Diagrams ......................................................................... 19

Ordering Information ............................................................................................. 20

Page 3: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

2

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Catalogue Number DescriptionTMPC3L4R Tap box 400A max., 1ph or 3ph; (1) 600MCM max or (2) 250MCM max.

TMPC3L6R Tap box 600A max., 1ph or 3ph; (2) 250-500MCM max.

TMPC3L8R Tap box 800A max., 3ph; (4) 250-500MCM Note: Use this tap box when 3 X 250MCM at 600A

TMPC3FT8 Feed-thru tap box 800A max., 1ph or 3ph; (4) 250-500MCM in and out

Meter Centre Tap Boxes for 4 Jaw, 5 Jaw and 7 Jaw Stacks(jumper kits and ground bus kits NOT required)

Catalogue Number DescriptionTMPC8612R Meter stack, 6HI, 125A max., 5 Jaw, 3ph Hor. Bus; note: 3ph incoming

TMPC8312R Meter stack, 3HI, 125A max., 5 Jaw, 3ph Hor. Bus; note: 3ph incoming

TMPC612R Meter stack, 6HI, 125A max., 4 Jaw, 1ph Hor. Bus; note: 3ph incoming

TMQRL21100 2P 100A stack brk for 125A stacks, 10KAIC @ 208v

TMQRHL21100 2P 100A stack brk for 125A stacks, 22KAIC @ 208v

TMQRL21125 2P 125A stack brk for 125A stacks, 10KAIC @ 208v

TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v

Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks(jumper kits and ground bus kits NOT required)

Catalogue Number DescriptionTMPC312410R Meter stack, 4HI, 100A max., 7Jaw, 3ph in and out

TMQG32100 3P 100A stack brk for 100A stacks, 65kaic @ 208v

TMPC312420R Meter stack, 4HI, 200A max., 7Jaw, 3ph in and out

TMQE32100 3P 100A stack brk for 200A stacks, 65KAIC @ 208v

TMQE32125 3P 125A stack brk for 200A stacks, 65KAIC @ 208v

TMQE32150 3P 150A stack brk for 200A stacks, 65KAIC @ 208v

TMQE32200 3P 200A stack brk for 200A stacks, 65KAIC @ 208v

Meter Centre and Tenant Breakers for 7 Jaw Stacks(jumper kits and ground bus kits NOT required)

Catalogue Number DescriptionTMPCP Blank Meter socket cover

Meter Centre Accessories for all Stacks

Meter Centres and Tenant Breakers

Page 4: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

3

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Designed for Main and Sub-Service switching and Metering of residential, commercial, and industrial applications.

Suitable for single-phase, three-wire 120/240 Vac or three-phase, four-wire 120/208 Vac systems, and sub service ratings of 100, 125 and 200 Amp. Available with a selection of Meter modules that have three or six Meter sockets and a main service module that can be provided with a choice of Lug, Breaker or Fusible device. Metering also available for applications that require 7 jaw, 3 phase in, 3 phase out [4w/4w] with one or four socket(s). GE Industrial Meter centres are designed to meet CSA requirements for “cold Metering”.

Industrial Multi-Metering

Page 5: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

4

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

— Offering: main terminal/lug compartment, main circuit

breaker, main fusible switch.

— Mechanically and electrically built for use with TMPC

modular Metering stacks.

— Due to 800A cross bus rating on 5 Jaw design, if main is

rated higher than 800A, modular Metering stacks must be

centre fed from the main service module.

— Type 3R enclosure (rainproof).

Residential Modular Metering Stacks - 5 Jaw Design

— Mechanically and electrically built to bolt-up with main

service modules and commercial modular Metering stacks.

— Offered with four horizontal cross bus

(for 3-phase incoming voltage systems).

— All devices include fifth jaw as standard

— Type 3R enclosure (rainproof).

Main Service Modules - 5 Jaw and 7 Jaw Design

Main Service Modules

Page 6: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

5

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

— Mechanically and electrically built to bolt-up with main

service modules and commercial modular Metering stacks.

— All commercial modular Metering stacks contain four

horizontal cross.

— Applications:

- Light commercial multiple Metering projects

- 3ph in 3ph out (4W/4W)

- Type 3R enclosure bus.

Commercial Modular Metering Stacks - 7 Jaw Design

Main Service Modules

Page 7: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

6

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Main Service Modules

— Main Terminal Box.

— Main Circuit Breaker.

— Main Fusible Switch.

— Three-phase mains couple to any modular Metering stack

TMPC for both 5 and 7 jaw stacks.

— 3-phase mains require 3-phase bussed stacks. These

modular Metering stacks are TMPC styles.

— Since TMPC 5 Jaw Meter stacks have a horizontal

bus rating of 800A, any main device rated more than 800A

needs to centre feed these downstream Meter stacks.

— Enclosures EEMAC, 3R.

— All main service modules include both left and right

horizontal bus closure plates.

— Feed through cable connection tap box available for TMPC

design.

— For Service Entrance rating or grounding,

use GRDKIT.

Main Terminal Box

Main Circuit Breaker

Main Fusible Switch

Main Service Modules

Page 8: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

7

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

— Top/bottom feed

— Phase and neutral lugs included with the following devices.

— Terminal box CSA listed short circuit rating is the least AIC rating of any installed main tenant breaker - to

a maximum of 100 kaic RMS symmetrical amperes.

— Enclosure type 3R rainproof, order Myers type hubs for outdoor use.

— Refer to page 17 for dimensions.

(1) Main devices with a rating of greater than BOOA can be used in centre feed applications only with residential type Meter stacks. (2) To obtain (4) 1/0-300 kcmil or (2) 1/0-750 kcmil cables per phase - order catalogue number TMPP3L8BLK, one lug kit per cable tap box required. (3) To obtain (6) 1/0·300 kcmil or (3) 750 kcmil cables per phase - order catalogue number TMPP3L12BLK, one lug kit per cable tap box required. (4) For compression lug landing kit, order TMPPLK2 Kit includes lug landings for 3 phases and neutral(5) For compression lug landing kit, order TMPP3LKBLK. Kit includes lug landings for 3 phases and neutral. (6) To obtain (1) 750 kcmil cables per phase - order catalogue number TMPPLK2,one lug kit per pole or neutral required. (7) To obtain (3) 1/0-250 kcmil cables per phase - order catalogue number 3MTB600BLK, one lug kit per cable tap box required.

Main Terminal Box

AmpereRating

System Voltage

Line Side Lug and Wire SizesLugs included with Terminal Box

120/240V AC 1-Phase, 3-Wire

120/208V AC 3-Phase, 4-Wire

Catalogue Number Catalogue Number

400 Use 3 Phase TMPC3L4R (1) #6-600 kcmil or (6) (7) (2) 1/0-250 kcmil

600 Use 3 Phase TMPC3L6R (2) 250-500 kcmil (4) (6) (7)

800 TMPCL8R TMPC3L8R (4) 250-500 kcmil (2) (5)

1200 TMPCL12R(1) TMPC3L12R(1) (4) 250-500 kcmil (3) (5)

Main Terminal Boxes

Page 9: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

8

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Main Circuit Breaker — Phase and neutral lugs included with the

following devices.

— Top/Bottom feed.

— For shunt trip mains, order the field

installable shunt trip kit.

— Main breaker included.

— Enclosure type 3R use Myers type hubs for

outdoor use.

— Can be factory supplied as “Reverse Fed.”

Must be specified at time of purchase.

(1) Main devices with a rating of greater than 800A can be used with residential modular stacks but only as a centre fed main. (2) Add CL to end of catalogue number for compression lug pad (includes lug pads for lines and neutral). (3) If (3) 500-750 kcmil are needed, order TCAL124. Order one kit per pole. (4) If additional neutral lugs are needed, order TMP3B12NLK [(3) 1/0-750 kcmil or (6) 1/0-300 kcmil].(5) If (2) 500-750 kcmil are needed, order TCAL124. Order one kit per pole. (6) If (1) 750 kcmil are needed, order 800 Amp SK frame/400 Amp Rating Plug and TCAL124 Lugs.

MainAmpereRating

MainCircuit

BreakerType Feed A/C

System Voltage

Line Side Lug and Wire Sizes,Lugs included with Main Breaker

120/240V AC 1-Phase3-Wire

120/20BV AC a-Phase4-Wire

Catalogue # Catalogue #200 SGH Top/Bottom 65k TMPCSB4R + SRPG400A200 TMPC3SB4R + SRPG400A200

(2) 3/0-250 kcmil or (1) 2/0-500 kcmil(4)

250SGH Top/Bottom 65k TMPCSB4R + SRPG400A250 TMPC3SB4R + SRPG400A250

SGH Top/Bottom 100k TMPCSHB4R + SRPG400A250 TMPC3SHB4R + SRPG400A250

300SGH Top/Bottom 65k TMPCSB4R + SRPG400A300 TMPC3SB4R + SRPG400A300

SGL Top/Bottom 100k TMPCSHB4R + SRPG400A300 TMPC3SHB4R + SRPG400A300

350SGH Top/Bottom 65k TMPCSB4R + SRPG400A350 TMPC3SB4R + SRPG400A350

SGL Top/Bottom 100k TMPCSHB4R + SRPG400A350 TMPC3SHB4R + SRPG400A350

400SGH Top/Bottom 65k TMPCSB4R(2)(6) TMPC3SB4R(2)(6)

SGL Top/Bottom 100k TMPCSHB4R(2)(6) TMPC3SHB4R(2)(6)

500SGH Top/Bottom 65k TMPCSB6R + SRPG600A500 TMPC3SB6R + SRPG600A500

(2) 300-500 kcmil (4)SGL Top/Bottom 100k TMPCSHB6R + SRPG600A500 TMPC3SHB6R + SRPG600A500

600SGH Top/Bottom 65k TMPCSB6R(2) TMPC3SB6R(2)

SGL Top/Bottom 100k TMPCSHB6R(2) TMPC3SHB6R(2)

700 SKH Top/Bottom 65k TMPCSB8R + SRPK800A700 TMPC3SB8R + SRPK800A700 (3) 300-400 kcmil (4) (5)

800 SKH Top/Bottom 65k TMPCSB8R(2) TMPC3SB8R(2)

900 SKH Top/Bottom 65k TMPCSB10R(1)(2) + SRPK1200A900 TMPC3SB10R(1)(2) + SRPK1200A900

(4) 4/0-500 kcmil (3) (4)1000 SKH Top/Bottom 65k TMPCSB10R(1)(2) TMPC3SB10R(1)(2)

1200 SKH Top/Bottom 65k TMPCSB12R(1)(2) TMPC3SB12R(1)(2)

Main Circuit Breakers

Page 10: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

9

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

— Fuses not included.

— Main lugs and neutral included with device.

— Enclosure type 3R rainproof, order Myers type

hubs (page 12) for outdoor use.

— 100 kaic rating on switches with Class T fuses installed. If

converted to Class H, the AIC rating is 10k and if converted

to Class R, or J fusing the AIC rating is 200k.

Main Fusible Switches

(1) If Class H fuse clips are needed, use catalogue number WCG3HK400. If Class R fuse clips are needed, order catalogue number DS56FK in addition to WCG3HK400. In order to go from T to R, the device must first be converted to H. Kits are field installable and each kit will convert 1 pole.

(2) If Class H fuse clips are needed, use catalogue number WCG3HK600. If Class R fuse clips are needed, order catalogue number DS66FK in addition to WCG3HK600. In order to go from T to R, the device must first be converted to H. Kits are field installable and each kit will convert 1 pole.

NOTE: Class J Fuse Clip Kit for 400 and 600A use TMPCJ6 ® Class T fuse clips provided are field convertible to Class L by repositioning. No kit is needed. (3) lf compression lugs are being used, order TMPP3F8CLL1. This compression lug kit includes four pads (3 poles and neutral). (4) If compression lugs are being used, order 3MFS800CLKT Top Feed. This compression lug kit includes four pads (3 poles and neutral). (5) For top feed application cables must be looped. (6) To obtain (1) 750 kcmil order 1 MFS600BLK one lug kit per pole required.(7) To obtain (3) 750 kcmil cable per phase order TMPIF12NLK, one lug kit per pole required. (8) If additional neutral lugs needed order 1MFS1200LKN (3) 750 kcmil! cables per phase.

AmpereRating Feed

System Voltage ClassFuse ClipsFuses NotIncluded

Line Side Box Lugs and Wire Sizes included with Switch

120/240V AC 1-Phase, 3-Wire

120/20BV AC 3-Phase, 4-Wire

Catalogue # Catalogue #

400Bottom TMPCFB4R TMPC3FB4R T(1) (2) 1/0-300 kemil or (1) 750 kcmil (4)

Top TMPCFT4R TMPC3FT4R T(1) (2) 1/0-300 kemil or (1) 750 kcmil (5)

600Bottom TMPCFB6R TMPC3FB6R T(2) (2) #2-600 kcmil (4)(7)(9)

Top TMPCFT6R TMPC3FT6R T(2) (2) #2-600 kcmil (5)(7)

800Bottom TMPCFB8R TMPC3FB8R T(2) (4) #3/0-750 kcmil (4)

Top TMPCFT8R TMPC3FT8R T(2) (4) #3/0-750 kcmil (5)

1200 Bottom TMPCFB12R(6) TMPC3FB12R(6) L (4) #2 to 500 kcmil (8)

Main Fusible Switches

Page 11: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

10

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

A. Barrier Meter socket and tenant main breaker/wireway sections are separated by a solid metal barrier to guard unMetered bus against power theft.

B. Tenant Breaker Reliable busbar-to-busbar connection. 200 ampere modules accept bolt-on breakers (not Sal) 60-200 amperes. 125 ampere modules accept 15-125 ampere plug-on breakers.

C. Factory Phase Balanced All Meter centres are factory phase balanced for ease and speed of installation.

D. Neutral Assembly A convenient termination for neutral conductors is in the wireway of each module.

E. Enclosed Horizontal Bus Added security because a non-removable barrier exercises 800 ampere horizontal bus passing through tenant breaker section on 5 Jaw design.

F. Equipment Ground Bar Factory installed in side gutter, a standard feature that’s movable to the top or bottom gutter.

G. Continuous Ground A convenient lay-in lug is attached to the back of all cells. No longer do you need to purchase ground bar kits. Just remove knockouts and run your ground cable from cell to cell.

H. Raintight Cap Shipped on all TMPC Meter modules. Enclosure type 3R rainproof.

I. Knockouts Tangential in top and bottom, concentric in removable backwall plate

J. Superior Finish Rust inhibiting phosphate primer and grey baked enamel is standard. All outdoor enclosures are of galvanized steel construction

K. Meter Socket Our unique Meter socket base is installed without any fasteners reducing chances for hot spots, easily replaceable, and improves connection to vertical bus.

L. Bus Connection Mains and modules slip together quickly, smoothly with front-accessible captive bolts securing the juncture without removing socket interiors or bus access plate. No additional Bus Links required. Main bus joint bolts torque to 25 foot pounds.

M. Separate Wireway Cover Separate covers allow easy access to tenant breaker and wireway section, permit work on breakers or in wireway without disturbing Meters or Meter covers (not shown).

N. Vertical Busbar One-piece vertical busbar removes most of the standard electrical joints to the Meter socket. Eliminating any chance of “hot spots” from multiple connection points.

O. Horizontal Mounting Rail To speed up and simplify installations, a two piece Mounting Rail is included with each Meter stack. Swing away feet located at the top and bottom of structure can be utilized for wall mounting (not shown).

P. Padlock HASP Included for additional security when required (not shown).

TMPC Meter Stack Modules

Page 12: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

11

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Lug in Meter Socket Modules Wire Size, AI/CuBranch Neutral #6-2/0

125A socket module

Branch Neutral #1/0-300 kcmil

200A socket module

Equipment Ground Bar #14-#2

125A socket module

Equipment Ground Bar #14-2/0

200A socket module

Optional Ground Bar (1 MMGBK) #6-2/0

— Stacks with 1-phase horizontal bus are rated 240/120V, 1-phase, 3-wire. Stacks with 3-phase horizontal bus are rated 208Y/120V,

3-phase, 4-wire but can be used on 240/120V, 3-phase, 4-wire delta systems.

— All 3-phase horizontal bus modules have 4-wire, 800A cross bus and all stacks are factory balanced for ease of installation.

— Short circuit ratings up to 100,OOOA RMS symmetrical depending upon Ale rating of installed main tenant circuit breakers and

main device.

— Lay-in Lug is attached to back of every cell. Removal of K/O allows ground cable to run from cell to cell.

— Main tenant feeders can exit top or bottom. Knockouts are available at all exit locations.

— Type 3R enclosure. If being used in outdoor application and exiting the top, mount Myer type hubs on rainproof cap.

— Provision for 2-pole breaker. Plug-on type for 125A Meters and bolt-on type for 200A Meters. Circuit breakers not included.

— Available in three and six Meter socket configuration, 5 jaw standard.

Wire Sizes: Neutral and Ground Lugs — Each stack includes a neutral and ground bar.

— If an extra ground bar is needed order 1 MMGBK

TMPC Residential Meter Stack Modules - 5 Jaw Design

Amperesper Meter

Socket

Numberof MeterSockets

BusAmpacity

EnclosureType

1-Phase Horizontal Bus (3 Horizontal Bus Bars -

A, B and Neutral)

3-Phase Horizontal Bus (4 Horizontal Bus Bars -

A, B, C and Neutral)

Main TenantBreaker Type

For Specific CatalogueNumber refer to pages 22 to 23Catalogue Number Catalogue Number

1253

Indoor &Outdoor

- TMPC8312R(1) Plug on Type TMQRL

TMQRHL TMQL6 800

Indoor &Outdoor

TMPC612R(1) TMPC8612R(1)

200 3 800Indoor &Outdoor

TMPC320R(1) TMPC8320R(1)

Bolt-on Type TMQRD

TMQ TMQRHD

(1) Fifth jaw at 9 o’clock position included as standard. Can be field adjusted to the 3, or 6, or 12 o’clock position.

TMPC Residential Meter Stack Modules - 5 Jaw Design

Page 13: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

12

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

— The following breakers are to be used on TMPC6 and TMPC8 modular Metering stacks.

— 120/240V AC - field installed.

Feed through Cable Connection Tap Box - 5 Jaw and 7 Jaw Design

Description# of

Poles

Main TenantCircuit BreakerAmpere Rating

10,000 AIC 22,000 AIC 25,000 AIC 42,000 AIC 100,000 AICCatalogue

NumberCatalogue

NumberCatalogue

NumberCatalogue

NumberCatalogue

Number

Plug-in type circuit breakers

used with TMPC 125A modular

stacks

2 60 TMQRL2160 TMQRHL2160 - TMQL2160 -

2 70 TMQRL2170 TMQRHL2170 - TMQL2170 -

2 80 TMQRL2180 TMQRHL2180 - TMQL2180 -

2 90 TMQRL2190 TMQRHL2190 - TMQL2190 -

2 100 TMQRL21100 TMQRHL2100 - TMQL21100 -

2 110 TMQRL21110 TMQRHL21110 - TMQL21110 -

2 125 TMQRL21125 TMQRHL21125 - TMQL21125 -

Bolt-on (1) (2)

circuitbreakersused with

TMPC 200Amodularstacks

2 60 - - - - TMQV22060MM

2 70 - - - - TMQV22070MM

2 80 - - - - TMQV22080MM

2 90 - - - - TMQV22090MM

2 100 TMQRD22100 - TMQRHD22100 - TMQV22100MM

2 125 TMQRD22125 - TMQRHD22125 - TMQV22125MM

2 150 TMQRD22150 - TMQRHD22150 - TMQV22150MM

2 175 TMQRD22175 - TMQRHD22175 - TMQV22175MM

2 200 TMQRD22200 - TMQRHD22200 - TMQV22200MM

2 225 - - - - TMQV22225MM

3 60 - - - - TMQV32060

3 70 - - - - TMQV32070

3 80 - - - - TMQV32080

3 90 - - - - TMQV32090

3 100 - - - - TMQV32100

3 125 - - - - TMQV32125

3 150 - - - - TMQV32150

3 175 - - - - TMQV32175

3 200 - - - - TMQV32200

3 225 - - - - TMQV32225

(1) Mounting hardware kit for TMQRD AND TMQRHD type (bolt-on) breakers included in 200A Meter stack. (2) Load side lugs included with 200 Amp Stack Breaker.

AmpereRating Entry Side

System Voltage120/208V 3ph 4W

H W D

Conductors Per Phase CU/AL “IN” and “OUT” Lugs

supplied with BoxCatalogue Number

800 Top/Bottom TMPC3FT8(1) 46 1/8” 26 1/2” 8 1/2”(4) 250-500 kcmil “IN”

(4) 250-500 kcmil “OUT”

1200 Top/Bottom TMPC3FT12(2) 50 3/4” 26 5/8” 9” same as above

1) To obtain (4) 1/0 - 750 kcmil or (8) 1/0 - 300 kcmil cables per phase - order catalogue number TMPCFT8LUG. 2) To obtain (3) #2 - 750 kcmil (2 in/2 out) cables per phase - order catalogue number TMPCFT12LUG. NOTES: • Feed through Tap Boxes are required when cables enter and exit at the same end of the Meter Centre.

No KO’s are provided. • Cable connection Tap Boxes may be used for Subfeeds. Mount on opposite end to main cable entry.

TMPC Main Tenant Circuit Breakers – 5 Jaw Design

TMPC Main Tenant Circuit Breakers – 5 Jaw Design

Page 14: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

13

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

TMPC Main Tenant Circuit Breakers - 7 Jaw Design

Feed Through Cable Connection Tap Boxes - TMPC Design

— The following breakers are to be used on TMPC 7 Jaw modular Metering stacks .

— 120/208V AC - field installed.

— Use 3 pole tenant breaker (see chart below)

NOTE: Reference to Bolt-on Breakers, is not the former BQL frame, it represents a commercial grade Bolt-on moulded case frame. 1) Mounting hardware kit for TMQE type breakers included in 200A Meter stack. TMQG mounting hardware is included with the breakers.2) Mounting hardware kit includes 3TA225FD (#4-4/0) lugs for standard 200A applications. If other lugs are required, they must be purchased separately.

1) To obtain (4) 1/0 - 750 kcmil or (8) 1/0 - 300 kcmil cables per phase - order catalogue number TMPCFT8LUG. 2) To obtain (3) #2 - 750 kcmil (2 in/2 out) cables per phase - order catalogue number TMPCFT12LUG. NOTES: • Feed through Tap Boxes are required when cables enter and exit at the same end of the Meter Centre.

No KO’s are provided. • Cable connection Tap Boxes may be used for Subfeeds. Mount on opposite end to main cable entry.

DescriptionNumberof Poles

Main Tenant Circuit Breaker Ampere Rating

65,000 AIC 100,000 AICCatalogue # Catalogue #

Bolt-on type circuit breakers used with TMPC 7Jaw 100A

Modular Metering Stacks

3 60 TMQG32060 -

3 70 TMQG32070 -

3 100 TMQG32100 -

Bolt-on circuit breakers used with

TMPC 7Jaw 200A Modular Metering Stacks

3 100 TMQE32100

Consult GE

3 125 TMQE32125

3 150 TMQE32150

3 175 TMQE32175

3 200 TMQE32200

AmpereRating Entry Side

System Voltage120/208V 3ph 4W

H W D

Conductors Per Phase CU/AL “IN” and “OUT” Lugs

supplied with BoxCatalogue Number

800 Top/Bottom TMPC3FT8(1) 46 1/8” 26 1/2” 8 1/2”(4) 250-500 kcmil “IN”

(4) 250-500 kcmil “OUT”

1200 Top/Bottom TMPC3FT12(2) 50 3/4” 26 5/8” 9” same as above

TMPC Main Tenant Circuit Breakers - 7 Jaw Design

Page 15: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

14

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Wire Sizes: Neutral and Ground Lugs

Each stack includes a neutral and ground bar. If an extra ground bar is needed order 1 MMGBK

— TMP Series Commercial Meter Stack Modules: 7 Jaw Meter stacks are available in 100 and 200 amps. 3 phase in, 3 phase out

(4W/4W), 240V AC max.

— Short circuit ratings up to 100,000A RMS symmetrical depending upon AIC rating of installed main tenant

circuit breakers and main device.

— Lay-in Lug is attached to the back of every cell. Removal of K/O allows ground cable to run from cell to cell.

— Main tenant feeders can exit top or bottom. Knockouts are available at all exit locations. Type 3R enclosure. If being used in

outdoor application and exiting the top, mount Myer type hubs on rainproof cap.

Lugs in Meter Socket Modules Wire Size, AI/Cu

Branch Neutral - #1/0 - 300MCM

100A Socket Module

Branch Neutral - #1/0 - 300MCM

200A Socket Module

Equipment Ground Bar #6 - 2/0

100A Socket Module

Equipment Ground Bar #6 - 2/0

200A Socket Module

Optional Ground Bar (1 MMGBK) #6 - 2/0

Amperes per Meter Socket

Numberof Metersper Stack

BusAmpacity Enclosure Type

3-Phase Horizontal Bus(4 Horizontal Bus Bars -

A, B, C and Neutral)

Main TenantBreaker TypeFor Specific

Catalogue Numbers100 4 1200 Indoor & Outdoor TMPC312410R Bolt on Type TMQG 3 pole

2001 1200 Indoor & Outdoor TMPC312120R

Bolt on Type TMQE 3 pole4 1200 Indoor & Outdoor TMPC312420R

Commercial Meter Stack Modules - TMP Series 7 Jaw Design

Commercial Meter Stack Modules - TMP Series 7 Jaw Design

Page 16: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

15

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Lexan Blank Cover Wall Mounting Rail Indoor Corner Elbow

Accessories for TMPC Modular Metering StacksDescription Application Catalogue Number

Lexan Blank Cover Circular cover mounted on device preventing access to Meter socket while Meter is not in place. Includes 4 plastic. TMPCP

Wall Mounting Rail Rails are 4 feet (1219.20mm) in length. Bolted on wall for stacks and mains to be hung. TMPZR

Indoor Corner Elbow 12 inch (303.8mm) indoor corner elbow. 1200 ampere, 3-phase, 4-wire. TMPCE12A

Indoor Corner Elbow 16 inch (406.4mm) indoor corner elbow. 1200 ampere, 3-phase, 4-wire. TMPCE12

Lexan Blank Cover without tabs TMPCA

Blank Meter Socket Cover 1PH 125A TMPCB12B

Blank Meter Socket Cover 1PH 200A TMPCB20B

Blank Meter Socket Cover 3PH 100A TMPCB310C

Blank Meter Socket Cover 3PH 200A TMPCB320C

TMPC Meter Stack Accessories

Page 17: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

16

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Main Service Modules

Main Circuit Breakers, Terminal Boxes Bottom Feed Fusible Switch

Top Feed Fusible Switch

Meter Centre Diagrams and Dimensions

Page 18: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

17

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Approximate Dimensions(not to be used for construction purposes)

MainDevice

Width Height Depth Mounting

Centre Line of Wall Mounting

Bracket

Knock-Outs in Bottom End walls except

No KOs for Top Feed Switch Conduit DiaMeter-InchesA B C D E F

inches mm inches mm inches mm inches mm inches mm inches mm inches mm

Terminal Box (1) 2-1/2-3(1) 63.50-76.20-88.90-

101.60 (1) 12.7

400 & 600 Ampere 13-1/2 3425 48-3/4 12383 7 177.8 0 0 54 1371.6 30-5/8 777.883-1/2, 4 (1) 1/2

Terminal Box 800 & 1200 Ampere

20 508 47-5/8 1209.7 11-3/4 298.46 12 304.8 51-1/2 1308.1 30-5/8 777.88(2) 1/2-3/4-1(4) 2 2-112-3-1/2-4

(2) 1270-19.05-2540 (4) 50.80-63.50-76.20-

88.90-101.60

Main Circuit Breaker with Box Lugs 400 & 800 Ampere

20 508 47-5/8 1209.7 11-3/4 298.46 12 304.8 51-1/2 1308.1 30-5/8 777.88(2) 1/2-3/4-1(4) 2 2-112-

3-1/2-4

(2) 1270-19.05-2540 (4) 50.80-63.50-76.20-

88.90-101.60

Main Circuit Breaker with Compression Lugs 400 & 800 Ampere

20 508 61 1549.4 11-3/4 298.46 12 304.8 65 1651 44 1777.6(2) 1/2-3/4-1(4) 2 2-1/2-3-1/2-4

(2) 1270-19.05-2540 (4) 50.80-63.50-76.20-

88.90-101.60

Main Fusible Switch - Bottom Feed

20 508 47-5/8 1209.7 11-3/4 298.46 12 304.8 51-1/2 1308.1 30-5/8 777.88(2) 1/2-3/4-1(4) 2 2-1/2-3-3-1/2-4

(2) 1270-19.05-2540 (4) 50.80-63.50-76.20-

88.90-101.60

Main Fusible Switch - Top Feed

20 508 47-5/8 1209.7 11-3/4 298.46 12 304.8 51-1/2 1308.1 18-1/8 460.38(2) 1/2-3/4-1(4) 2 2-1/2-3-3-1/2-4

(2) 1270-19.05-2540 (4) 50.80-63.50-76.20-

88.90-101.60

Main Fusible Switch - 1200 Ampere

20 508 52-3/4 1339.9 11-7/8 301.63 16 406.4 56-1/4 1428.8 30-3/4 871.05(5) 3-1/2-4-5(1) 3/4-1-1-1/4-1-1/2

(5) 88.90-101.60-127.00 (1) 19.05-25.40-31.75-

38.10

Meter Centre Diagrams and Dimensions

Page 19: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

18

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

TMPC, 125A - 5 Jaw Design

TMPC8312R

TMPC, 200A - 5 Jaw Design TMPC, 100A & 200A - 7 Jaw Design

TMPC612R / TMPC8612R

TMPC320R / TMPC8320R TMPC312420R / TMPC312410R

TMPC312120R

Meter Centre Diagrams and Dimensions

Page 20: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

19

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

— All GE meter centres are factory phase balanced

Wiring Diagrams & Typical Nameplate Information (240VAC max.)

Meter Centre Wiring Diagrams

Page 21: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

20

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Meter Stacks

Elbow Section

Feed Through Cable Tap Boxes

Tap Boxes

Catalogue Number DescriptionTMPC612R 6HI 125A 4jaw, 800A 1ph hor Bus

TMPC320R 3HI 200A 4jaw, 800A 1ph hor Bus

TMPC8612R 6HI 125A 5jaw, 800A 3ph hor Bus

TMPC8312R 3HI 125A 5jaw, 800A 3ph hor Bus

TMPC8320R 3HI 200A 5jaw, 800A 3ph hor Bus

TMPC312410R 4HI 100A 7jaw, 1200A 3ph hor Bus

TMPC312120R 1HI 200A 7jaw, 1200A 3ph hor Bus

TMPC312420R 4HI 200A 7jaw, 1200A 3ph hor Bus

Catalogue Number DescriptionTMPC3FT8 800A 3ph Feed Thru Tap Box

TMPC3FT12 1200A 3ph Feed Thru Tap Box

Feed Through Lugs

TMPCFT8LUG 800A 750mcm Lug Kit Feed Thru

TMPCFT12LUG 1200A 750mcm Lug Kit Feed Thru

Catalogue Number DescriptionTMPCL8R 800A 1ph Main Lug Module 1/3R

TMPCL12R 1200A 1ph Main Lug Module 1/3R

TMPC3L4R 400A 3ph Main Lug Module 1/3R

TMPC3L6R 600A 3ph Main Lug Module 1/3R

TMPC3L8R 800A 3ph Main Lug Module 1/3R

TMPC3L12R 1200A 3ph Main Lug Module 1/3R

Catalogue Number DescriptionTMPCE12A 12” 1200A 3ph Bussed Elbow

TMPCE12 16” 1200A 3ph Bussed Elbow

Ordering Information

Page 22: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

21

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Catalogue Number DescriptionTMPCSB4R 400A Main Bkr 1 Ph 240V 42KAIC

TMPCSHB4R 400A Main Bkr 1Ph 240V 100KAIC

TMPCSB6R 600A Main Bkr 1 Ph 240V 42KAIC

TMPCSHB6R 600A Main Bkr 1 Ph 240V 100KAIC

TMPCSB8R 800A Main Bkr 1 Ph 240V 65KAIC

TMPCSB10R 1000A Main Bkr 1 Ph 240V 65KAIC

TMPCSB12R 1200A Main Bkr 1 Ph 240V 65KAIC

TMPC3SB4R 400A Main Bkr 3Ph 240V 42KAIC

TMPC3SHB4R 400A Main Bkr 3Ph 240V 100KAIC

TMPC3SB6R 600A Main Bkr 3Ph 240V 42KAIC

TMPC3SHB6R 600A Main Bkr 3Ph 240V 100KAIC

TMPC3SB8R 800A Main Bkr 3Ph 240V 65KAIC

TMPC3SB10R 1000A Main Bkr 3Ph 240V 65KAIC

TMPC3SB12R 1200A Main Bkr 3Ph 240V 65KAIC

Main Breaker Section

Main Switch SectionCatalogue Number DescriptionTMPCFB4R 400A Main Sw 1 Ph 240V Bot Feed

TMPCFT4R 400A Main Sw 1 Ph 240V Top Feed

TMPCFB6R 600A Main Sw 1 Ph 240V Bot Feed

TMPCFT6R 600A Main Sw 1 Ph 240V Top Feed

TMPCFB8R 800A Main Sw 1 Ph 240V Bot Feed

TMPCFT8R 800A Main Sw 1 Ph 240V Top Feed

TMPCFB12R 1200A Main Sw 1 Ph 240V Bot Fed

TMPC3FB4R 400A Main Sw 3Ph 240V Bot Feed

TMPC3FT4R 400A Main Sw 3Ph 240V Top Feed

TMPC3FB6R 600A Main Sw 3Ph 240V Bot Feed

TMPC3FT6R 600A Main Sw 3Ph 240V Top Feed

TMPC3FB8R 800A Main Sw 3Ph 240V Bot Feed

TMPC3FT8R 800A Main Sw 3Ph 240V Top Feed

TMPC3FB12R 1200A Main Sw 3Ph 240V Bot Fed

Ordering Information

Page 23: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

22

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Accessories

Circuit Breakers

Catalogue Number DescriptionTMPCP Lexan Blank Cover

TMPZR Wall Mounting Rail - Resi Style

TMPC12 125A Ring Cover

TMPC20 200A Ring Cover

TMPBC12 125A Tenant Breaker Cover

TMPBC20 200A Tenant Breaker Cover

TSPR3 Sealing Ring-Stnless Screw type

TMPPLK2 600A 750mcm Lug Kit

TMPP3L8BLK 800A 750mcm Main Lug Kit

TMPP3L12BLK 1200A 750mcm Main Lug Kit

TMP3B12NLK Neutral Lug

TMPP3F8CLL1 Fs Sw Compression Lug Landings

TMP3F12NLK 1200A 750mcm Fs Sw Neutral kit

TMP1F12NLK 1200A 750mcm Fs Sw Lug Kit

TMPCJ6 J Fuse Clips 400AMP / 600AMP

Catalogue Number DescriptionTMQRL2160 60A 2P 120/240V 10KAIC TMQRL

TMQRL2170 70A 2P 120/240V 10KAIC TMQRL

TMQRL2180 80A 2P 120/240V 10KAIC TMQRL

TMQRL2190 90A 2P 120/240V 10KAIC TMQRL

TMQRL21100 100A 2P 120/240V 10KAIC TMQRL

TMQRL21110 110A 2P 120/240V 1 OKAIC TMQRL

TMQRL21125 125A 2P 120/240V 1 OKAIC TMQRL

TMQRHL2160 60A 2P 120/240V 22KAIC TMQRHL

TMQRHL2170 70A 2P 120/240V 22KAIC TMQRHL

TMQRHL2180 80A 2P 120/240V 22KAIC TMQRHL

TMQRHL2190 90A 2P 120/240V 22KAIC TMQRHL

TMQRHL21100 100A 2P 120/240V 22KAIC TMQRHL

TMQRHL21110 110A 2P 120/240V 22KAIC TMQRHL

TMQRHL21125 125A 2P 120/240V 22KAIC TMQRHL

Ordering Information

Page 24: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres

23

1-800-GE-1STOPData subject to change without notice ca.geindustrial.com

Catalogue Number DescriptionTMQL2160 60A 2P 120/240V 42KAIC

TMQL2170 70A 2P 120/240V 42KAIC

TMQL2180 80A 2P 120/240V 42KAIC

TMQL2190 90A 2P 120/240V 42KAIC

TMQL21100 100A 2P 120/240V 42KAIC

TMQL21125 125A 2P 120/240V 42KAIC

TMQRD22100 100A 2P 120/240V 10KAIC TMQRD

TMQRD22125 125A 2P 120/240V 10KAIC TMQRD

TMQRD22150 150A 2P 120/240V 1 OKAIC TMQRD

TMQRD22175 175A 2P 120/240V 10KAIC TMQRD

TMQRD22200 200A 2P 120/240V 1 OKAIC TMQRD

TMQRHD22100 100A 2P 120/240V 25KAIC TMQRHD

TMQRHD22125 125A 2P 120/240V 25KAIC TMQRHD

TMRHD22150 150A 2P 120/240V 25KAIC TMQRHD

TMQRHD22175 175A 2P 120/240V 25KAIC TMQRHD

TMQRHD22200 200A 2P 120/240V 25KAIC TMQRHD

TMQV22060MM 60A 2P 120/240V 100KAIC

TMQV22070MM 70A 2P 120/240V 100KAIC

TMQV22080MM 80A 2P 120/240V 100KAIC

TMQV22090MM 90A 2P 120/240V 100KAIC

TMQV22100MM 100A 2P 120/240V 100KAIC

TMQV22125MM 125A 2P 120/240V 100KAIC

TMQV22150MM 150A 2P 120/240V 100KAIC

TMQV22175MM 175A 2P 120/240V 100KAIC

TMQV22200MM 200A 2P 120/240V 100KAIC

TMQV22225MM 225A 2P 120/240V 100KAIC

TMQV32060 60A 3P 120/240V 100KAIC

TMQV32070 70A 3P 120/240V 100KAIC

TMQV32080 80A 3P 120/240V 100KAIC

TMQV32090 90A 3P 120/240V 100KAIC

TMQV32100 100A 3P 120/240V 100KAIC

TMQV32125 125A 3P 120/240V 100KAIC

TMQV32150 150A 3P 120/240V 100KAIC

TMQV32175 175A 3P 120/240V 100KAIC

TMQV32200 200A 3P 120/240V 100KAIC

TMQV32225 225A 3P 120/240V 100KAIC

TMQE32100 100A 3P 208V 65KAIC for 200A - 7 jaw stack

TMQE32125 125A 3P 208V 65KAIC for 200A - 7 jaw stack

TMQE32150 150A 3P 208V 65KAIC for 200A - 7 jaw stack

TMQE32175 175A 3P 208V 65KAIC for 200A - 7 jaw stack

TMQE32200 200A 3P 208V 65KAIC for 200A - 7 jaw stack

TMQG32060 60A 3P 208V 65KAIC for 100A - 7 jaw stack

TMQG32070 70A 3P 208V 65KAIC for 100A - 7 jaw stack

TMQG32100 100A 3P 208 65KAIC for 100A - 7 jaw stack

Circuit Breakers

Ordering Information

Page 25: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

Meter Centres Section 2

NOTES:

24

1-800-GE-1STOP

ca.geindustrial.comData subject to change without notice

Page 26: Modular Metering · TMQRHL21125 2P 125A stack brk for 125A stacks, 22KAIC @ 208v Meter Centre and Tenant Breakers for 5 Jaw and 4 Jaw Stacks (jumper kits and ground bus kits NOT required)

GE 41 Woodford Avenue Plainville, CT 06062 1-800-431-7867 www.geindustrial.com

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions.©2018, General Electric Company and/or its affiliates. All rights reserved.

4.18 DET1032