For more information, visit www.fmiproducts.com
SAVE THIS BOOKThis book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain re-placement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fire-place or for use with a vented gas log approved to ANS Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard. A An ap-proved hood must be installed when using a vent-free log heater (see Accessories, page 18).
This firebox meets the construction and safety stan-dards of H.U.D. for application in mobile homes when installed according to these instructions.
FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to deter-mine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance.CONSUMER: Retain this manual for future reference.
Wood burning FireplaceoWner’S operaTion and
inSTallaTion Manual
Model c36MW
ICBO #ER-3507
PFS ®
USC
www.fmiproducts.com 108918-01K2
SaFeTy• TheStyleCrest,Inc.warrantywillbevoidedbyandStyleCrest,Inc.disclaimsanyre-sponsibilityforthefollowingactions.a.Modification of the fireplace, com-ponents, doors, air inlet system anddampercontrol.
b.Useofanycomponentpartnotmanu-facturedorapprovedbyStyleCrest,Inc.incombinationwithaStyleCrest, Inc.fireplacesystem.
Properinstallationisthemostimportantstepinensuringsafeandcontinuousoperationoffireplace.Consultthelocalbuildingcodesastotheparticularrequirementsconcernedwiththeinstallationofallfactorybuiltfireplaces.
WARNING: Do not install a fireplace insert in this box unless the manufacturer's instructions with the insert specifically state this fireplace has been tested for use with this insert.
WARNING: Use solid wood or processed solid fuel fire logs only. When processed wood fuel fire logs are used, do not poke or stir the logs while they are burn-ing. Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.
This fireplace is not intended to be used as a substitute for a fur-nace to heat an entire home. Use for supplemental heat only.
WARNING: Improper instal-lation, adjustment, alteration, service or maintenance can cause injury, property damage or loss of life. Refer to this manual for assistance or additional in-formation. Consult a qualified installer or local distributor.
IMPORTANT: Check local codes before installing this fireplace.
FOR YOUR SAFETY• Do not store or use gasoline
or any other flammable vapors or liquids in the vicinity of this or any other appliance.
• Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
• Do not place clothing or other flammable materials on or near the appliance.
• Never leave children unat-tended when a fire is burning in the fireplace.
Beforebeginninginstallationofthisfireplace,readtheseinstructionsthroughcompletely.• ThisStyleCrest,Inc.fireplaceanditscom-ponentsaresafewheninstalledaccordingtothisinstallationmanual.UnlessyouuseStyleCrest,Inc.components,whichhavebeendesignedandtestedforthefireplacesystem,youmaycauseafirehazard.
Table oF conTenTSSafety.................................................................. 2Specifications...................................................... 3FireplaceInstallation............................................ 4VentingInstallation.............................................. 7OptionalGasLineInstallation............................ 13
OperationandMaintenance.............................. 14TechnicalService............................................... 15Parts.................................................................. 16ReplacementParts............................................ 18Accessories....................................................... 18
This wood burning fireplace complies with UL127-CAN/ULC-S610-M87 standard as a FACTORY BUILT APPLIANCE.
www.fmiproducts.com108918-01K 3
SpeciFicaTionS
8.125"12.875"
10.188"
9.625"
37.25"
33"
38"36"
21.5" 32"
6.75"
34.75"
14.438"
19.375"
1"
14"
38"
1.75"
0.750"
22.5"
21.125"
0" TOBOTTOM
OUTSIDE AIR(LEFT SIDE
ONLY)
TOP SPACERS
0.75" AIR SPACEBACK AND SIDES
HEARTH EXTENSION52" X 16"12"
EACH SIDE
NOT LESSTHAN 14" TO
PERPENDICULARSIDEWALL
1" AIRSPACETO COMBUSTIBLE
COMBUSTIBLEWALL BOARD
0" TO
MATERIAL NO COMBUSTIBLEMATERIAL ON FACE
SQUARE CHASE-TOPTERMINATION
GAS LINEKNOCK OUTAIR KIT
KNOCK OUT
ROUND TOP TERMINATION
www.fmiproducts.com 108918-01K4
Fireplace inSTallaTionSELECTING LOCATIONTodeterminesafestandmostefficientlocationforfireplace,youmusttakeintoconsiderationthefollowingguidelines:1. Locationmustallowforproperclearances
(seeFigures1and2).2. Considera locationwherefireplacewill
notbeaffectedbydrafts,airconditioningducts,windowsordoors.
3. Alocationthatavoidscuttingofjoistsorroofrafterswillmakeinstallationeasier.
4. An outside air kit is availablewith thisfireplace (seeOptional Outside Air Kit,page7).
MINIMUM CLEARANCE TO COMBUSTIBLESBackandsidesoffireplace 3/4"minimum*Floor** 0"minimumPerpendicularwalltoopening 14"minimumTopspacers 0"minimumMantelclearances seeMantels,page6Chimneyouterpipesurface 1"minimum*Notrequiredatnailingflanges**Seestep2ofFraming
WARNING: Do not pack re-quired air spaces with insulation or other materials.
Minimum/Maximum Chimney HeightMinimumheightofchimney,measuredfrombaseoffireplacetofluegasoutletoftermina-tion,is11.5feetforstraightflueorafluewithoneelbowset.Maximumdistancebetweenelbowsis2feet.Forsystemswithtwoelbowsets,minimumheight is 22 feet.Maximumheightofanysystemis50feet.Thismeasure-mentincludesfireplace,chimneysectionsandheightofterminationassemblyatleveloffluegasoutlet(seeFigure18,page11).
FRAMING1. Frameopeningforfireplaceusingdimen-
sionsshowninFigures1and2.2. If fireplace is to be installeddirectly on
carpeting,tile(otherthanceramic)oranycombustiblematerial other thanwoodflooring,fireplacemustbeinstalleduponametalorwoodpanelextendingfullwidthanddepthoffireplace.
22"
37.625"
38.25"
Figure 1 - Framing Dimensions
47 3/8"
13 3/4"
19 1/2"
66 7/8"
Maintain 3/4"Clearance at
Sides andBack of
Fireplace
3/4" Clearance Not Required at Nailing Flanges
Figure 2 - Corner Installation
3. Setfireplacedirectlyinfrontofthisopen-ingandslideunitbackuntilnailingflangestouchsideframing.
4. Check level of fireplace and shimwithsheetmetalifnecessary.
5. Before securing fireplace to preparedframing,emberprotectormustbeplacedbetweenhearthextension(notincluded)andunderbottomfrontedgeoffireplacetoprotectagainstglowingembersfallingthrough.Iffireplaceistobeinstalledonaraisedplatform,aZ-typeemberprotec-tor (not included)mustbe fabricated tofityour requiredplatformheight.Emberprotectorshouldextendunderfireplaceaminimumof11/2".Emberprotectorshouldbemadeofgalvanizedsheetmetal (28gaugeminimum)topreventcorrosion.
6. Usingscrewsornails,securefireplacetoframingthroughflangeslocatedonsidesoffireplace.
www.fmiproducts.com108918-01K 5
HEARTH ExTENSIONAhearthextensionprojectingaminimumof16"infrontofandaminimumof8"beyondeachsideoffireplaceopeningisrequiredtoprotectcombustiblefloorconstructioninfrontof fireplace. Fabricate a hearth extensionusingamaterialwhichmeets the followingspecifications: a layer of noncombustible,inorganicmaterialhavingathermalconductiv-ityofK=0.84BTUIN/FT,HR.F(orless)at1"thick.Forexample, ifmaterialselectedhasaK factor of 0.25, suchasglass fiber, thefollowingformulawouldapply: 0.25x1.0"=0.30"thicknessrequired 0.84Thermalconductivity"K"ofmaterialscanbeobtained frommanufacturer or supplier ofnoncombustiblematerial.Ifhearthextensionistobecovered,usenoncombustiblemate-rialsuchastile,slate,brick,concrete,metal,glass,marble,stone,etc.Provideameanstopreventhearthextensionfromshiftingandsealgapbetweenfireplaceframeandhearthextensionwith a noncombustiblematerial(seeFigure3).
WARNING: Hearth extension is to be installed only as shown in Figure 3.
Fireplace inSTallaTionContinued
Figure 3 - Hearth Extension
SealGapFireplaceFront
EmberProtector
FireplaceFrontRaisedHearth
FireplaceFrontElevated
EmberProtector
EmberProtector
SealGap
HearthExtension
SealGapFireplaceFront
EmberProtector
FireplaceFrontElevated
DoNotBlockLouver
EmberProtector
SealGap
HearthExtension
Hearth Extension, Circulating Modes
Hearth Extension, Noncirculating Models
NO
www.fmiproducts.com 108918-01K6
Fireplace inSTallaTionContinued
Figure 4 - Mantel Clearances to Combustible Material
ElectricalBushing
ElectricalCoverPlate
RockerSwitch
Figure 6 - Fan Switch-Electrical Bushing
ElectricalHousing
WireNut(3x)(NotSupplied)
OuterWrapperofFireplace
ElectricalCoverPlateandElectricalBushing
FireplaceChassisGround
ToPowerSource
Receptacle(Supplied)
PowerSourceWiring(NotSupplied)
PrewiredReceptacleandGround
MANTELSAmantelmay be installed if desired (seeFigure 4).Woodwork such aswood trims,mantels or any other combustiblematerialprojectingfromfrontfacemustnotbeplacedwithin9"offireplaceopening(andwithin9"oftoplouveropening).Combustiblemateri-alsabove9"andprojectingmorethan11/2"fromfireplacemustnotbeplacedlessthan12"fromtopopeningoffireplace(NFPASTD211,Sec.7-3.3.3).Mantels or any other combustiblematerialmaycomeuptosideedgeofblackmetalfaceoffireplaceifprojectionfromfrontfacefallswithinlimitsshowninFigure5.
12 1/4" Ref.
1 1/2"Max.
Upper Sectionof Circulating
Fireplace
6"Ref.
6"Min.
33°
3" Nom. *Note: DrawingNot To Scale
Safe Zone ForProjection ofCombustibleMaterials
CombustibleMaterial
12"Min.
9"Min.
Fireplace Opening
Top of LouveredOpening
FAN/BLOWER KIT ASSEMBLYFanorblowerkitisoptionalwiththisfireplace(forcirculatingmodelsonly).UseofblowersorfansotherthanmodelBK3voidswarranty.Fan is operated by pressing rocker switch(seeFigure6) inlowerrighthandcorneroffireplaceface.Blowerisoperatedbyturningcontrolknob(notshown).Fan/blower kit electrical connections aremadethroughelectricalcoverplateonsideoffireplaceashowninFigure6.
Wiring Instructions
FIREBOX
SAFE ZONE
Figure 5 - Side Mantel Clearance
TopViewofFireplace
Min.12"fromPerpendicularSideWall
1"
0.625"Max.
33°9"
1. Removeelectricalcoverplatewithbush-ing fromfireplaceby removing2 sheetmetalscrewsasshowninFigure6.
2. Slidepowersourcewiringthroughelectri-calbushingopeningandelectricalcoverplate andmake all necessary connec-tions.
3. Slideallwiringconnections inelectricalhousingasshowninFigure6.
4. Secureelectricalcoverplatewithscrewspreviouslyremoved.
Note: Electrical housing and cover plate have sharp edges. Wear protective gloves.
SheetMetalScrews
www.fmiproducts.com108918-01K 7
Figure 8 - Lineal Gain
LINEAL GAINPART NO. DESCRIPTION GAIN
36" Fireplace 371/2"12-8DM12-8HT
PipeSection 105/8"
18-8DM18-8HT
PipeSection 165/8"
24-8DM24-8HT
PipeSection 235/8"
36-8DM36-8HT
PipeSection 345/8"
48-8DM48-8HT
PipeSection 465/8"
RT-8DMRT-8HT
RoundTermination 67/8"*
RTL-8DMRTL-8HT
RoundTermination 73/4"*
RTT-8DMRTT-8HT
RoundTerminationwithSlipSection
67/8"to231/8"*
RTTL-8DMRTTL-8HT
RoundTerminationwithSlipSection
81/2"to211/2"*
ET-8DMET-8HT
SquareChase-Top 12"*
ETO-8DMSquareChase-Top
withMesh12"*
ETL-8DMETL-8HT
SquareChase-TopwithSlipSection
7"to15"*
ETLO-8DMSquareChase-TopwithMesh&Slip
Section
12"to251/2"*
*Thelinealgainfortheterminationsismea-suredtothefluegasoutletheight.
HemmedEnd
8"StainlessInnerPipe
123/8"GalvanizedOuterPipe
Figure 7 - Outside Air Kit
SecuretoCollarswithMetalTape,ScrewsorStraps(Min.of1/4"x20"insize)
AirInletLocationMustAllowForBushesorSnow
VentHoodRequiredforWallInstallation
AirInletEyebrow
VentedCrawlSpace(CheckLocalCodesBeforeInstallinginaVentedCrawlSpace)
VenTing inSTallaTionOPTIONAL OUTSIDE AIR KIT (MODEL AK4/AK4F)Installationofoutsideairkit shouldbeper-formedduringroughframingoffireplaceduetothenatureofit'slocation.Outsidecombus-tionair isaccessedthroughaventedcrawlspace (AK4F) or througha sidewall (AK4).SeeFigure24onpage15forinstructionofoperatingairkit.
CAUTION: Combustion air inlet ducts shall not terminate in attic space.
The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.
CHIMNEY PIPEThe chimney system approved for thisfireplace consists of 12", 18", 24", 36" and48" snap-lock, double-wall pipe segments,plannedformaximumadaptabilitytoindividualsiterequirements.Actuallengthsgainedafterfittingoverlapsmustbetakenintoconsider-ation(linealgain)andaregiveninlinealgainchart(seeFigure8).Linealgainisactualmeasurablelengthofapartaftertwoormorepartsareconnected.
WARNING: The opening in collar around chimney at top of fireplace must not be obstructed. Never use blown insulation to fill chimney enclosure.
www.fmiproducts.com 108918-01K8
VenTing inSTallaTionContinued
Figure 9 - Typical Offset Installation
ReturnElbow
OffsetElbow
ReturnElbow Offset
Elbow
6'Max.
6'Max.
6'Max.
6'Max.
6'Max.
6'Max.
ReturnElbow
OffsetElbow
OffsetElbow
ReturnElbow
A B C
OffsetElbow
CeilingSupportPipe12S-8DM
ReturnElbow
ASSEMBLY AND INSTALLATION OF DOUBLE WALL CHIMNEY SYSTEMEachdoublewallchimneysectionconsistsofagalvanizedouterpipe,astainlesssteelinnerfluepipeandawirespacer.Pipesec-tionsmustbeassembledindependentlyaschimneyisinstalled.Whenconnectingchim-neydirectlytofireplace,innerfluepipesec-tionmustbeinstalledfirstwithlancedsideup.Outerpipesectioncanthenbeinstalledoverfluepipesectionwithhemmedendup.Pressdownoneachpipesectionuntillancessecurely engage hemon fireplace starter.Wirewill assure proper spacing betweeninnerandouterpipesections.Note: For Canada, use chimney parts des-ignated HT.
Opening in collar around chimney at top of fireplace must not be obstructed. Never use blown insulation to fill chimney enclosure.
Continue toassemblechimneysectionsasoutlined,making sure that both inner andouterpipesectionsarelockedtogether.When
installingdoublewallsnap-lockchimneyto-gether,itisimportanttoassurejointbetweenchimneysectionsislocked.Checkbypullingchimneyupwardafter locking.Chimneywillnot comeapart if properly locked. It is notnecessarytoaddscrewstokeepchimneyto-gether(exception-seeFigure11,page9).
USING ELBOW OFFSETS (30E-8DM)1. Toachievedesiredoffset,youmayinstall
combinations of 12", 18", 24", 36" and48"lengthofdoublewallpipe(seeoffsetchart,page7,andFigure9).
Note: For systems with 2 elbow sets, mini-mum height is 22 feet. Maximum height for any system is 50 feet.
2. Chimneyweight above offset rests onreturn elbow.Strapsmust be securelynailedtoraftersorjoists(seeFigure10,detailsAandB,page9).
3. Maximumlengthofpipebetweensupports(returnelbowor12S-8DM)is6'ofanglerun.Maximumoftwo6'anglerunsectionsperchimneysystem(seeFigure9).
4. Allpipeconnectionsbetweenoffsetandreturnmustbesecuredwithtwoscrewsonouterpipeonly(seeFigure11,page9).Donotpenetrateinnerstainless.
www.fmiproducts.com108918-01K 9
Figure 11 - Elbow Offset
B
A
Screws
Figure 10 - Ceiling Support Pipe 12S-8DM
OFFSET RISE CHIMNEY LENGTHA B 48" 36" 24" 18" 12"
43/8" 163/8" ELBOWSETONLY93/4" 251/2" 1123/4" 303/4" 115" 343/4" 118" 40" 1 1
211/4" 461/4" 1233/4" 491/4" 1 1273/4" 563/4" 130" 603/4" 1 133" 66" 1 136" 71" 1 1
381/4" 75" 2411/4" 801/4" 1 1 145" 863/4" 2
463/4" 891/2" 1 1 151" 97" 1 1
531/4" 101" 2 1561/4" 1061/4" 2591/4" 1111/2" 1 1 1613/4" 1151/2" 2 1643/4" 1203/4" 2 1681/4" 127" 1 270" 130" 2 1 1
741/4" 1371/2" 1 2 1763/4" 1411/2" 1 2 1793/4" 1463/4" 4
OFFSET CHART (22-50 FT. SYSTEM HEIGHT)
2"Min.
Straps StrapsStrapsStraps
DetailAReturnElbow
DetailBAngleFirestop
SeeDetailA
SeeDetailB
CeilingSupportPipe12S-8DM
VenTing inSTallaTionContinued
www.fmiproducts.com 108918-01K10
VenTing inSTallaTionContinued
14 3/8"(36.5 cm) 30"
(76.2 cm)1"
(2.5cm)
1"(2.5cm)
Minimum Measurements
1"(2.5 cm)
Opening "A"
Pitch Slope Opening "A" Max.
Used Flashing Model No.
Flat 0° 15" V6F-8DM0-6/12 26.6° 161/8" V6F-8DM
6/12-12/12 45.0° 203/8" V12F-8DM
4. Removeshinglesaroundopeningmea-sured.Cutoutthissection.
5. Add next sections of pipe until endpenetrates roof line.Check to see thatproperclearancesaremaintained.Extendchimneybyaddingsectionsofdoublewallpipeuntilpipe isminimumof30"abovehighestpointof roof cutout.Terminationandchimneymustextendaminimumof36"abovehighestpointwhere itpassesthroughroof.
Figure 14 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)Determineflashingtobeusedwithroofopen-ingchart.Slideflashingoverpipeuntilbaseisflatagainstroof.Replaceasmanyshinglesasneededtocoverexposedareaandflashingbase.Secure inpositionbynailing throughshingles(seeFigure15,page11).DONOTNAILTHROUGHFLASHINGCONE.
Installing Flashing on a Metal RoofWhen installing flashingonametal roof, itisrequiredthatputtytapebeusedbetweenflashingandroof.Flashingmustbesecuredtoroofusing#8x3/4"screwsandthensealedwithroofcoatingtopreventleakagethroughscrewholes.Aroofcoatingmustalsobeap-pliedaroundperimeterofflashingtoprovideaproperseal.
FIRESTOP SPACERS (3600FS-8DM-1)Firestopspacersarerequiredateachpointwhere chimney penetrates a floor space.Their purpose is to establish andmaintainrequired clearance between chimney andcombustiblematerials.When pipe passesthroughaframedopeningintoalivingspaceabove,firestopmustbeplacedontoceilingfrombelowasshowninFigure12.Theyalsoprovidecompleteseparationfromonefloorspacetoanotheroratticspaceasrequiredbymostcodes.Whendoublewallpipepasses througha framedopening intoanatticspace,firestopmustbeplacedintoanatticfloorasshowninFigure13.
Figure 12 - Firestop Spacer with Living Space Above Ceiling
Figure 13 - Firestop Spacer with Attic Space Above Ceiling
PENETRATING ROOFTomaintaina2"clearancetopipeonaroofwithapitch,arectangularopeningmustbecut.1. Determine center pointwhere pipewill
penetratetheroof.2. Determinecenterpointoftheroof.Pitch
isthedistancetheroofdropsoveragivenspan,usually12".A6/12pitchmeansthattheroofdrops6" foreach12"measurehorizontallydownfromroofrafters.
3. Use roof opening chart (Figure 14) todetermine correct opening length andflashingrequired.
Ifareaaboveisalivingspace,installfirestopbelowframedhole.
Ifareaaboveisanatticorinsulatedarea,installfirestopaboveframedhole.
www.fmiproducts.com108918-01K 11
NailOnlyOuterPerimeterofFlashing
StormCollar
UnderlapShinglesatBottom
OverlapShinglesTopandSidesOnly
Figure 15 - Flashing Installation
Figure 16 - Storm Collar
ChimneyPipe
WaterproofCaulk
StormCollar Flashing
Storm Collar Installation (SC1 or SC2)Placestormcollaroverpipeandslidedownuntilitissnugagainstopenedgeofflashing(seeFigure16).UseSC1 forall round ter-minationsandSC2forall terminationswithslipsections.Applywaterproofcaulkaroundperimeterofcollartoprovideaproperseal.
Terminations/Spark ArrestorFireplace systemmust be terminatedwithlistedroundtoporchaseterminations.Inanycase,refertoinstallationinstructionssuppliedwith termination.Terminationsapproved forthisfireplaceareRT-8DMandRTL-8DMthatcanbeused for flashingor chaseandET-8DM,ETO-8DM,ETL-8DMandETLO-8DMfor chase style termination only. Figure 17showsanRTL-8DMroundtoptermination.
CAUTION: Do not seal open-ings on the rooftop flashing. Fol-low the installation instructions provided with the termination being used.
FlashingCone
VenTing inSTallaTionContinued
AttachBracketTabstoOuterPipe(3Places)SecurewithScrews
RTL-8DM LevelofFlueGasOutlet
Caulk
Collar
Flashing
UnderlapShinglesBottomOnly
Figure 17 - Termination
OverlapShinglesTopandSides
Terminationswith16"slippipesectionsareavailable. RTT-8DM and RTTL-8DM areapproved for flashing installations.Whenneeded, theseadjustable terminationsmaybeusedincombinationwithpipeassemblytoachievecorrectchimneyheight.Note: In the rare instance there is a problem with side driven rain or wind or chimney is not drafting properly, an ADS-8DM (Anti-Draft Shield) can be used with round terminations.
FluePipeofRTL-8DMInsideInnerPipeofChimney
CHASE INSTALLATIONSInstructionsforchaseinstallationsareinclud-edwithchasestyleterminationchosen.Inamultiplechaseinstallation,besuretoprovideadequatedistancebetween terminations topreventsmokespillagefromoneterminationtoanother.Wesuggestthatterminationsbeseparatedatleast24",centertocenterandstackedataverticalheightdifferenceof18"(seeFigure18).Note: If a decorative shroud is to be installed, contact manufacturer for specifications.
18" MIN. TYP.24" MIN.
24" MIN.
Figure 18 - Multiple Chase Installation
www.fmiproducts.com 108918-01K12
10'
2'Min.
10'
3'Min.
2'Min.3'Min.
LevelofFlueGasOutlet
Figure 19 - 10 Foot Rule
10 FOOT RULEAllfluegasoutletchimneyterminationsmustextendaminimumof3feetinheightabovehighestpointwhereitpassesthroughroofandmustbeatleast2feetabovehighestpointoftheroofthatiswithinahorizontaldistanceof10feet(seeFigure19).
VenTing inSTallaTionContinued
FINISHING FIREPLACECombustiblematerials, such aswallboard,gypsumboard,sheetrock,drywall,plywood,etc.,maymakedirectcontactwithsidesandtoparoundfireplaceface.Itisimportantthatcombustiblematerials do not overlap faceitself.Brick,glass,tileorothernoncombustiblematerialsmay overlap front face providedtheydonotobstructessentialopeningssuchas louvered slots.When overlappingwithanoncombustible facingmaterial, useonlynoncombustiblemortaroradhesive.
30E-8DM
EFFECTIVE HEIGHT OF TERMINATION CAP
EFFECTIVE HEIGHT OF TERMINATION CAP
EFFECTIVE HEIGHT OF TERMINATION CAP
EFFECTIVE HEIGHT OF TERMINATION CAP
MINIMUMHEIGHT
11.5 FT.MINIMUM
UP TO 6FT. MAX.
UP TO 6FT. MAX.
HEIGHT
11.5 FT.
MIN. HEIGHT OF 22 FT. (WITH2 ELBOW SETS)MAX. HEIGHT OF50 FT.
MAX. HEIGHT50 FT.(ANY SYSTEM)
30E-8DM
Figure 20 - Typical Residential Installations
www.fmiproducts.com108918-01K 13
opTional gaS line inSTallaTion
Figure 21 - Gas Line Knockout
SideFirebrickFinishedSide
RefractoryKnockoutPlug
OutsideofFireplace
GasLineConduit
Insulation
GasConduitCover
1/2"Dowel
Gas line hook up should be done by yoursupplieroraqualifiedserviceperson.Note: Before you proceed, make sure your gas supply is turned off.Useonlya1/2"blackironpipeandappropri-atefittings.1. Removeknockoutindentationonrefracto-
ryorfirebrickwalllocatedaboverefractoryhearth floor.Knockout indentationmustbe firmly tappedwith any solid object,suchasa1/2"dowel,untilitisreleased.Removefragmentedportionsofrefractory(seeFigure21).
2. Removegaslinecoverplatelocatedoneithersideoffireplaceandpulloutinsu-lationfromgaslineconduitsleeve.Saveinsulationforreuse.
3. Runa1/2"blackirongaslineintofire-place through rear at gas line conduitsleeve (if using a raised platform, addheight).Provide sufficient gas line intofireplacechamberforfittingconnection(seeFigure22).
Note: Secure incoming gas line to wood framing to provide rigidity for threaded end.
4. Repackinsulationaroundgaslineandintosleeveopening.Sealanygapsbetweengaslineandrefractoryknockoutholewithrefractorycementorcommercialfurnacecement. Installgasapplianceorcapoffgaslineifdesired.
CAUTION: All gas piping and connections must be tested for leaks after installation is com-pleted. After ensuring that gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
Note: An approved hood must be installed when using an unvented gas log set (see Accessories on page 18).
WARNING: Do not operate an unvented gas log set in this fire-place with chimney removed.
If you install a decorative gas appliance(ventedgas log), decorative gasappliancemustcomplywiththeStandard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANS Z21.60 or Z21.84 andshallalsobeinstalledinaccordancewiththeNational Fuel Gas Code, ANSI 7223NFPA 54 latest edition.
WARNING: To avoid the risk of damaging fireplace materi-als and increasing the risk of spreading a fire, do not use fire-place to cook or warm food.
SealOpeningwithRefractoryCement
OutsideofFireplace
GasLineConduit
RepackInsulation
Incoming1/2"BlackIronPipe
SideFirebrickFinishedSide
ProvideEnoughThreadedEndforFittingConnection
Figure 22 - Gas Line Installation
www.fmiproducts.com 108918-01K14
opTional gaS line inSTallaTionContinued
WARNING: If the fireplace has been used for wood burn-ing, firebox and chimney must be cleaned of soot, creosote and ashes be a qualified chimney cleaner. Creosote will ignite if heavily heated.
operaTion and MainTenance
Figure 23 - Glass Doors
Cleaning GlassClean glass with any commercial glasscleanerorsoapandwater.Donotuseanyabrasivematerialtocleantheglass.Donotcleanglasswithanycoolwaterifglassisstillhotfromfireandsmoke.Agaslineorgasloglightermaybeinstalledforthepurposeofinstallingaventedorvent-freedecorativegasapplianceincorporatinganautomaticshutoffdeviceandcomplyingwiththeStandard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60 orAmerican Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces, Draft NO. 4datedAugust,1993.Ifyouwishtoinstallanunvented(vent-free)gaslogset,onlyunventedgaslogsetswhichhavebeenfoundtocomplywiththestandardforunventedroomheaters,ANSIZ21.11.2aretobeinstalledinthisfireplace.
WARNING: When using a decorative vented gas log, damper must be removed or permanently locked in fully open position and glass doors must be in fully open position.
GLASS DOORSGlassdoorsarestandardwiththisfireplace.Whenfireplaceisinoperation,doorsmustbefullyopenedorfullyclosedpositiononlyorafirehazardmaybecreated(seeFigure23).Afireplaceequippedwithglassdoorsoper-atesmuchdifferentlythanafireplacewithanopenfront.Afireplacewithglassdoorshasalimitedamountofairforcombustion.Exces-siveheatwithinfireplacecanresultiftoolargeafireisbuiltorifcombustionairgateisnotcompletelyopen.Thefollowingtipsshouldbeusedtoassurethat both fireplace and glass door retaintheirbeautyandfunctionproperly.Boththefluedamper andglass doorsmust be fullyopenedbeforestartingafire.Thiswillprovidesufficient combustionair andmaintain safetemperaturesinfirebox.IMPORTANT: The glassmust be allowedtowarmslowlyandevenly.Temperedglasswillwithstandagradual temperatureriseto550°F,whichismorethananormalfirewillgenerate.Suchmaterialsaspitch/waxladenlogs, very drymill end lumber and largeamounts of paper or cardboard boxes cancreateanexcessivelyhotfireandshouldnotbeburnedinthisfireplace.Alwayskeepfireback fromdoorsandneverallowflames tocontactglass.
WARNING: Fireplaces equipped with glass doors should be operated only with doors fully opened or doors fully closed. Doors, if left partly open, may draw gas and flame out of the fireplace opening creating risks of both fire and smoke.
DoorsFullyClosed
DoorsFullyOpened
FireplaceFront
FireplaceFront
www.fmiproducts.com108918-01K 15
Figure 24 - Damper Handle Location
operaTion and MainTenanceContinued
DAMPER HANDLE OPERATIONDamper handle, which opens and closesdamper blade, is located inside firebox atcenter towards backwall (seeFigure 24).Pushing handle back into keyway slotwillfree damper blade to automatically open.Toclose,pushhandlebackintokeyholeslotthenpulldownandforwardtolockitinplace(seeFigure25).
WARNING: Risk of fire! Replace grate with model 107001-01 only. This grate has been designed to keep the op-eration of your fireplace safe and efficient.
For further operating guidelines, instruc-tions and warranty information, please re-fer to your homeowner's guide or contact your authorized dealer.
DamperHandle
1 2
3 1 2
3
DamperWeight
ToCloseDamper ToOpenDamper
Figure 25 - Damper Rod
Technical SerViceYoumayhavefurtherquestionsaboutinstal-lation, operation, or troubleshooting. If so,contact StyleCrest at 1-800-231-4822 orwriteto:
StyleCrestServiceP.O.Box19110
Wichita,KS.67204
When calling orwriting, please have yourmodel and serial numbers of your heaterready.
www.fmiproducts.com 108918-01K16
parTS
WOOD BURNING FIREPLACE MODEL C36MW
11
27
30 23
22
24
10
14
25
4
17
3
2
1
18
5
20
2812
7
15
9
16
13
8
26
6
29
19
21
www.fmiproducts.com108918-01K 17
parTSWOOD BURNING FIREPLACE MODEL C36MWThislistcontainsreplaceablepartsusedinyourfireplace.
KEYNO. PART NO. DESCRIPTION QTY.
1 ** InsulationPan 12 ** AirSeparator 13 ** FireboxTop 14 111431-01 AirDeflector 15 ** FireplaceTop 16 ** FireboxWrapper 17 ** OuterWrapper/InsulationAssembly 18 ** FireboxFloor 19 ** WrapperBottom 110 ** FrontFaceWeldment 111 106971-01 LeftSideBrickLiner 112 106969-01 RearBrickLiner 113 106970-01 RightSideBrickLiner 114 106972-01 BottomBrickLiner 115 106973-01 FrontBottomBrickLiner 116 21198 BlowerAccessPlate 117 20027 RefractoryRetainer 218 ** TopInsulation 119 ** InsulationRetainer 120 20280 TopStandoff 421 20023 ChimneyStarterCollar 122 20088 DoorStop 123 11418 PushOnNut 224 20090 SpringClip 225 107001-01 WoodBurningGrate 126 106539-01 GrateRetainer 227 107127-01 Screen 128 ** SideDamperWeldment 129 107128-01 GasConduit 430 20806 ScreenRod 2
PARTS AVAILABLE - NOT SHOWN
14607 RockerSwitch 1109989-01 ElectricalDuctAssembly 117207 FlexDuct6"x371/2" 120093 EmberProtector 2BDB36 Bi-FoldGlassDoor(Black) 1
**Notafieldreplaceablepart
www.fmiproducts.com 108918-01K18
ROOF FLASHING0 TO 6/12 PITCH - V6F-8DM6/12 TO 12/12 PITCH - V12F-8DM
acceSSorieS
DOUBLE WALL PIPE12-8DM18-8DM24-8DM36-8DM48-8DM
ANTI-DRAFT SHIELD(Round Top Termination Only)ADS-8DM
30° OFFSET AND RETURN30E-8DM, 30E-HT
ADjUSTABLE HOODAntique Brass Finish - GA6053Black Painted Finish - GA6050Requiredwheninstallingavent-freegasloginthisfireplace.
STORM COLLARSC1-1 For RT-8DM and RTL-8DMSC2-1 For RTT-8DM and RTTL-8DM
BI-FOLD GLASS DOOR(Black included on unit)BDB36B - Brushed BrassBDB36P - Platinum
FIRESTOP SPACER3600FS-8DM-1
FAN KIT - BK3
FACE ExTENSIONFE3602
www.fmiproducts.com108918-01K 19
ROUND TOP TERMINATIONSRT-8DM, RTL-8DM
ROUND TOP TERMINATIONS WITH SLIP SECTIONRTT-8DM, RTTL-8DM
OUTSIDE AIR KIT FOR SIDE WALL INSTALLATION - AK4
OUTSIDE AIR KIT FOR FLOOR INSTALLATIONAK4F
SQUARE CHASE-TOP TERMINATIONET-8DM, ET-8DM
SQUARE TOP TERMINATION WITH SLIP SECTIONETL-8DM, ETL-8DM
acceSSorieSContinued
VENT KIT* DESCRIPTIONMW8K
(8' Vent Kit)MW9K
(9' Vent Kit)36-8DM 36"DoubleWallPipe 2 224-8DM 24"DoubleWallPipe 1 018-8DM 18"DoubleWallPipe 0 2FST-A AdjustableFirestopThimble 1 1V6F-8DM RoofFlashing 1 1SC1-1 StormCollar 1 1RTL-8DM RoundCapTermination 1 1
*UseforMostCommonManufactured(Mobile)HomeInstallations
108918-01Rev.K09/09