MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Upload: milo-spencer

Post on 11-Jan-2016

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY

THE WIRING CODE OF TRINIDAD AND TOBAGO

TTS 171 PART ONE

Page 2: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

PRESENTED BY

• HAYDEN BATSON

• ELECTRICAL INSPECTOR 1 GOVERNMENT ELECTRICAL INSPECTORATE

Page 3: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Annex C

• Provides Sub-Circuit rating and requirements.

• C.1 Gives the maximum sub-circuit ratings for domestic, commercial and industrial premises.

• C.2 Gives the sub-circuit requirements.

Page 4: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Table C-1

Page 5: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Section B gives those that are not shown before

Page 6: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

C.2.1• Ground-fault Circuit Interrupter

protection shall be provided for personnel (ref sec 210-8 NEC 1999) in:

• a) Bathrooms

• b) Outdoor receptacles

• c) Garages

• d) Counter tops

• e) Other required locations.

Page 7: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

C.2.2Additional requirements for

conformity.• Receptacle outlets shall be spaced

approx. 4M along walls in rooms.

• Receptacle outlet and lighting circuits shall be separated except by special permission of the CEI.

Page 8: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

• The rating for a general purpose domestic receptacle is 180 VA.

• The minimum height of the service entrance connection shall be 4M, observing the minimum clearance of 6M over road ways.

• We will maintain the IEE color code.

Page 9: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

INSTALLATION METHODS

The exact current carrying capacity of conductors is

affected by a number of factors besides CSA, one of which is the

way they are installed.

Two examples are are shown using table D.5.D.1

Page 10: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE
Page 11: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Example 1

Installing a run of 10 mm2 XLPE insulated multi-core armored cable:

Using Method 1, a 3 or 4 core cable connected to a 3-ph ac supply will carry

73A.

Using Method 11, a 3 or 4 core cable connected as above will carry 78A.

Page 12: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Example 2

Installing a run of 95mm2 XLPE insulated multi-core armoured cable.

Using Method 1, a 3 or 4 core cable connected to a 3-ph ac supply will

carry 289A.

Using Method 11, a 3 or 4 core cable connected to a 3-ph ac supply will

carry 304A.

Page 13: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

• When using cards with current rating tables the method of installation for those values must be observed.

Page 14: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

VOLTAGE DROP CONSIDERATIONS

Apart from voltage drop and installation methods, factors such as

–ambient temperature –grouping–thermal insulation–operating temperature

of the cable also weigh in cable selection.

Page 15: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Emphasis however must be placed on voltage drop.

WHY?

This value should not exceed 3% in the circuit of which that cable forms

apart.

Page 16: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Not more than 6.90 V for a 230V 1-ph circuit

Not more than 14.4V for a 480V 3-ph circuit.

Page 17: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Note also that the maximum allowable drop from the POE to fixed current using equipment

must not exceed 4%.

Page 18: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

VOLTAGE DROP TABLES

These are tabulated for a current of 1 Amp and a

length of 1 Metre along the route taken.

Page 19: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

For a balanced 3-ph system the tables relate to line voltage.

Page 20: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Therefore the total voltage drop per run

Vd = mV x I x L 1000

Where I = current in amps L = length in metres

& mV = approx voltdrop/amp/metre.

Page 21: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Example:

Consider a run of 200M to be installed in air (ref method 13) to

carry a current of 100A from a supply of 415V 3-ph ac, the cable being of copper conductor, XLPE insulated,

armoured and PVC sheathed.

Page 22: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Let mV be voltage drop in millivolts

Then Vd = mV x I x L 1000

Transposing mV= Vd x 1000 I x L

Page 23: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Max permissible voltage drop= 3% of 415V

=12.45V

Inserting values for I, L and max permissible voltage drop

Then mV= 12.45 x 1000 =0.62 mV

100 x 200

Referring to the following table.

Page 24: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Select value = to or just less than 0.62mV i.e. 60mV.

Page 25: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

Apply current carrying capacity table.

Page 26: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

This shows that we may have used a 25 mm2

cable without voltage drop consideration.

Page 27: MINIMUM ACCEPTABLE LEVELS OF SAFETY & RELIABILITY THE WIRING CODE OF TRINIDAD AND TOBAGO TTS 171 PART ONE

THE END