Page 1: Micro BBU (8)

Installation Guide

2 Pole AC Breaker Kit

Art. 351425.033 Issue 1, 2005-09

Page 2: Micro BBU (8)

2 Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09

Index General ....................................................................................................................................... 2 Recommended tools ................................................................................................................... 2 Torque settings ........................................................................................................................... 2 Ordering information.................................................................................................................. 2 Scope of delivery........................................................................................................................ 3 Installation.................................................................................................................................. 4

General The 2 Pole AC Breaker Kit is intended for installing an internal AC breaker into the MicroPower Outdoor Cabinet. Installation must be done by authorized personnel only. Eltek Energy recommends that the system is powered down before installation of the kit.

Recommended tools Standard equipment used by an authorized electrician. NOTE: All tools must be insulated.

Torque settings All terminals on the AC breaker (CBI) must be tightened with 3.0Nm.

Ordering information

Part number Description Net weight 105422 2 Pole AC Breaker Kit 80gr

Page 3: Micro BBU (8)

Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09 3

Installation manual

Eltek

Xxx xxxxxxx

Xxx xxxxxxxXxx xxxxxxx

5

Scope of delivery Part Note Quantity Unit CB CBI QZ 35A 2 pole Curve 1 1 1 pcs

Loom AC Mains Micro Power PRSB 2 1 pcs

STRAP PLT 1,5mm 0 PANDUIT 3 4 pcs

Labels ‘N’ plus ‘L’ 4 1 plus 1 pcs

Manual 5 1 pcs

1

3 2

4

Page 4: Micro BBU (8)

4 Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09

Installation Step Description Comment OK 1 The mains input

must be turned off during the installation. It is possible to mount this kit without removing the battery shelf. However Eltek recommend removing the batteries and battery shelf before installing the AC breaker kit.

Turn off the external mains input breaker!

2 NOTE! If the OVP Kit is installed always mount this kit beside the mains input terminal blocks. Move the OVP kit to the right hand side. The drawing to the right shows how to install both kits.

282/

284

WAG

O

281/

282

L1L1

282/

284

WAG

O

281/

282

N N

PE

E

N L

TRIP

35A

CBI

I

0CURVE 1

UL1077

QZ-2(13)-D

LN

OBO

V25-B+C

OBO

C25-B+C

N-PE

CombiController CombiController

Best.-Nr. 5097 06 1 Best.-Nr. 5095 60 3

IP20 CE IP20 CE

N

L PE

Page 5: Micro BBU (8)

Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09 5

3 Remove the End Stop on the right hand side of the mains input terminal blocks. Mount the double pole breaker on the DIN bar. Push the AC breaker against the terminal blocks. Lock the AC breaker with the End Stop.

282/

284

WAG

O

281/

282

L1L1

282/

284

WAG

O28

1/28

2

N N

E

TRIP

35A

CBI

I

0CURVE 1

UL1077

QZ-2(13)-D

4 Connect the mains input earth cable at the green/yellow terminal block. Connect the mains input cables L and N at the bottom of the AC breaker. The kited cables must be connected from the top of the AC breaker to the terminal blocks for Live (brown) and Neutral (blue). Torque: 3Nm. Fix the cables with straps.

282/

284

WAG

O28

1/28

2L

1L1

282/

284

WAG

O28

1/28

2

N N

PE

E

N L

TRIP

35A

CBI

I

0CURVE 1

UL1077

QZ-2(13)-D

LN

Page 6: Micro BBU (8)

6 Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09

5 The internal AC breaker has now been installed. Remount the battery shelf and the batteries if they have been removed. The internal AC breaker must be turned on. Turn on the external AC breaker to start up the system.