2 Pole AC Breaker Kit
Art. 351425.033 Issue 1, 2005-09
2 Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09
Index General ....................................................................................................................................... 2 Recommended tools ................................................................................................................... 2 Torque settings ........................................................................................................................... 2 Ordering information.................................................................................................................. 2 Scope of delivery........................................................................................................................ 3 Installation.................................................................................................................................. 4
General The 2 Pole AC Breaker Kit is intended for installing an internal AC breaker into the MicroPower Outdoor Cabinet. Installation must be done by authorized personnel only. Eltek Energy recommends that the system is powered down before installation of the kit.
Recommended tools Standard equipment used by an authorized electrician. NOTE: All tools must be insulated.
Torque settings All terminals on the AC breaker (CBI) must be tightened with 3.0Nm.
Ordering information
Part number Description Net weight 105422 2 Pole AC Breaker Kit 80gr
Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09 3
Installation manual
Eltek
Xxx xxxxxxx
Xxx xxxxxxxXxx xxxxxxx
5
Scope of delivery Part Note Quantity Unit CB CBI QZ 35A 2 pole Curve 1 1 1 pcs
Loom AC Mains Micro Power PRSB 2 1 pcs
STRAP PLT 1,5mm 0 PANDUIT 3 4 pcs
Labels ‘N’ plus ‘L’ 4 1 plus 1 pcs
Manual 5 1 pcs
1
3 2
4
4 Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09
Installation Step Description Comment OK 1 The mains input
must be turned off during the installation. It is possible to mount this kit without removing the battery shelf. However Eltek recommend removing the batteries and battery shelf before installing the AC breaker kit.
Turn off the external mains input breaker!
2 NOTE! If the OVP Kit is installed always mount this kit beside the mains input terminal blocks. Move the OVP kit to the right hand side. The drawing to the right shows how to install both kits.
282/
284
WAG
O
281/
282
L1L1
282/
284
WAG
O
281/
282
N N
PE
E
N L
TRIP
35A
CBI
I
0CURVE 1
UL1077
QZ-2(13)-D
LN
OBO
V25-B+C
OBO
C25-B+C
N-PE
CombiController CombiController
Best.-Nr. 5097 06 1 Best.-Nr. 5095 60 3
IP20 CE IP20 CE
N
L PE
Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09 5
3 Remove the End Stop on the right hand side of the mains input terminal blocks. Mount the double pole breaker on the DIN bar. Push the AC breaker against the terminal blocks. Lock the AC breaker with the End Stop.
282/
284
WAG
O
281/
282
L1L1
282/
284
WAG
O28
1/28
2
N N
E
TRIP
35A
CBI
I
0CURVE 1
UL1077
QZ-2(13)-D
4 Connect the mains input earth cable at the green/yellow terminal block. Connect the mains input cables L and N at the bottom of the AC breaker. The kited cables must be connected from the top of the AC breaker to the terminal blocks for Live (brown) and Neutral (blue). Torque: 3Nm. Fix the cables with straps.
282/
284
WAG
O28
1/28
2L
1L1
282/
284
WAG
O28
1/28
2
N N
PE
E
N L
TRIP
35A
CBI
I
0CURVE 1
UL1077
QZ-2(13)-D
LN
6 Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09
5 The internal AC breaker has now been installed. Remount the battery shelf and the batteries if they have been removed. The internal AC breaker must be turned on. Turn on the external AC breaker to start up the system.
Installation Guide 2 Pole AC Breaker Kit, 351425.033, v1-2005-09 7
ELTEK Energy P-O- BOX 2340 StØmsØ N-3003 DRAMMEN NORWAY Phone: +4732203200 Telefax: +47 32203210 Internet: http://www.eltekenergy.com e-mail: [email protected]