meter pedestal specifications - hawaiian electric

1
. ..,. N APPROVED RAIN TIGHT METER SOCKET /MAIN BREAKER--r------ x 2w x W THICK ANGLE IRON WELDED TO PIPE • LL.I 1- o . z ..,. N LL.I LL.I ti> 6" .. Jl!l f -- CAP 3" PIPE -- 3" ROUND PIPE GALVANIZED STEEL SEE NOTE I CUSTOMER'S CONDUCTORS <18" MIN. COIL> CUSTOMER TO PROVIDE PROVISIONS FOR SEAL BY HAWAl'I ELECTRIC LIGHT ,_____..--1800• MULETAPE PULLING LINE OR EQUIVALENT GROUND CLAMPS CONCRETE FOOTING <2 EACH> GROUND RODS APART PER 3'-0" MAX. LINE <HAWAl'I ELECTRIC LIGHT> FRONT GENERAL NOTES I. WHERE CT METERING IS INSTALLED, THE MINIMUM PIPE DIAMETER FOR SUPPORT FRAMES SHALL BE 4-INCHES AND THE CONCRETE FOOTING THICKNESS SHALL BE INCREASED TO 30-INCHES <MINIMUM>. 2. METER SOCKET CENTER LINE ELEVATION SHALL BE BETWEEN 5'-0" AND 6'-0" ABOVE FINISHED GRADE. 3. PLYWOOD BACKBOARDS SHALL NOT BE USED FOR MOUNTING SERVICE ENTRANCE AND METERING EQUIPMENT. 4. TWO <2>GROUND RODS SHALL BE INSTALLED AND SEPARATED BY A MINIMUM DISTANCE OF 6'-0". 5. SEE ESIM SECTION 4.8 FOR BONDING. BOND TO CONNECTION TO STEEL FRAME ALSO. 6. 4 'x4 'x 7' CLEAR SPACE REQUIRED IN FRONT OF METER EQUIPMENT. 7. PLANS SHOWING ANY DEVIATION FROM THIS DESIGN MUST BE SUBMITTED TO HAWAl'I ELECTRIC LIGHT FOR APPROVAL. IN LIEU OF ANGLE IRON,STAINLESS STEEL OR GALVANIZED UNI-STRUT CHANNEL BOLTED TO VERTICAL PIPE SUPPORT MAY BE ACCEPTABLE. CONSULT WITH THE COMPANY PRIOR TO FABRICATION. . 6" LOAD <CUSTOMER> x 8' i! 6 F NEC 250 6" SIDE •• ....... HAWAl'I LICHT ELECTRIC ENGINEERING DEPARTMENT .._0, HAWAII FREE STANDING STEEL POST STRUCTURE CESIM PG 56·57> EST J REO. NO. OESIGNEO / ORAWN MM/KO CHK 'O/ APP'O SCALE NTS PROJ. NO . JP. NO. OATE q/8/17 T.M .K. NUMBER PEDSTL RAIN TIGHT SPLICE CAN t CUSTOMER HAWAl'I ELECTRIC LIGHT

Upload: others

Post on 16-Oct-2021

5 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Meter Pedestal Specifications - Hawaiian Electric

...,. N

APPROVED RAIN TIGHT METER SOCKET /MAIN BREAKER--r-----­

2~· x 2w x W THICK ANGLE IRON WELDED TO PIPE •

• LL.I ~ 1­~ o . z..,. N LL.I

LL.I ti>

6"

..

Jl!l

f - ­ CAP 3" PIPE

- ­ 3" ROUND PIPE --------<~1 GALVANIZED STEEL SEE NOTE I

CUSTOMER'S CONDUCTORS <18" MIN. COIL>

CUSTOMER TO PROVIDE PROVISIONS FOR SEAL BY HAWAl'I ELECTRIC LIGHT

,_____..--1800• MULETAPE PULLING LINE OR EQUIVALENT

GROUND CLAMPS

CONCRETE FOOTING

<2 EACH> ~· GROUND RODS APART PER

3'-0" MAX.

LINE <HAWAl'I ELECTRIC LIGHT>

FRONT GENERAL NOTES •• I. WHERE CT METERING IS INSTALLED, THE MINIMUM PIPE DIAMETER

FOR SUPPORT FRAMES SHALL BE 4-INCHES AND THE CONCRETE FOOTING THICKNESS SHALL BE INCREASED TO 30-INCHES <MINIMUM>.

2. METER SOCKET CENTER LINE ELEVATION SHALL BE BETWEEN 5'-0" AND 6'-0" ABOVE FINISHED GRADE.

3. PLYWOOD BACKBOARDS SHALL NOT BE USED FOR MOUNTING SERVICE ENTRANCE AND METERING EQUIPMENT.

4. TWO <2>GROUND RODS SHALL BE INSTALLED AND SEPARATED BY A MINIMUM DISTANCE OF 6'-0".

5. SEE ESIM SECTION 4.8 FOR BONDING. BOND TO CONNECTION TO STEEL FRAME ALSO.

6. 4 'x4 'x 7' CLEAR SPACE REQUIRED IN FRONT OF METER EQUIPMENT.

7. PLANS SHOWING ANY DEVIATION FROM THIS DESIGN MUST BE SUBMITTED TO HAWAl'I ELECTRIC LIGHT FOR APPROVAL.

• IN LIEU OF ANGLE IRON,STAINLESS STEEL OR GALVANIZED UNI-STRUT CHANNEL BOLTED TO VERTICAL PIPE SUPPORT MAY BE ACCEPTABLE. CONSULT WITH THE COMPANY PRIOR TO FABRICATION.

. 6"

LOAD <CUSTOMER>

x 8' • i! 6 F

NEC 250

6"

SIDE

••• .......• • HAWAl'I LICHTELECTRIC ENGINEERING DEPARTMENT

.._0, HAWAII

FREE STANDING STEEL POST STRUCTURE CESIM PG 56·57>

EST J REO. NO. OESIGNEO / ORAWN MM/KO CHK 'O/ APP'O SCALE NTS PROJ. NO . JP. NO. OATE q/8/17 T.M .K. NUMBER PEDSTL

RAIN TIGHT SPLICE CAN

t CUSTOMER

HAWAl'I ELECTRIC LIGHT