meter pedestal specifications - hawaiian electric
TRANSCRIPT
...,. N
APPROVED RAIN TIGHT METER SOCKET /MAIN BREAKER--r-----
2~· x 2w x W THICK ANGLE IRON WELDED TO PIPE •
• LL.I ~ 1~ o . z..,. N LL.I
LL.I ti>
6"
..
Jl!l
f - CAP 3" PIPE
- 3" ROUND PIPE --------<~1 GALVANIZED STEEL SEE NOTE I
CUSTOMER'S CONDUCTORS <18" MIN. COIL>
CUSTOMER TO PROVIDE PROVISIONS FOR SEAL BY HAWAl'I ELECTRIC LIGHT
,_____..--1800• MULETAPE PULLING LINE OR EQUIVALENT
GROUND CLAMPS
CONCRETE FOOTING
<2 EACH> ~· GROUND RODS APART PER
3'-0" MAX.
LINE <HAWAl'I ELECTRIC LIGHT>
FRONT GENERAL NOTES •• I. WHERE CT METERING IS INSTALLED, THE MINIMUM PIPE DIAMETER
FOR SUPPORT FRAMES SHALL BE 4-INCHES AND THE CONCRETE FOOTING THICKNESS SHALL BE INCREASED TO 30-INCHES <MINIMUM>.
2. METER SOCKET CENTER LINE ELEVATION SHALL BE BETWEEN 5'-0" AND 6'-0" ABOVE FINISHED GRADE.
3. PLYWOOD BACKBOARDS SHALL NOT BE USED FOR MOUNTING SERVICE ENTRANCE AND METERING EQUIPMENT.
4. TWO <2>GROUND RODS SHALL BE INSTALLED AND SEPARATED BY A MINIMUM DISTANCE OF 6'-0".
5. SEE ESIM SECTION 4.8 FOR BONDING. BOND TO CONNECTION TO STEEL FRAME ALSO.
6. 4 'x4 'x 7' CLEAR SPACE REQUIRED IN FRONT OF METER EQUIPMENT.
7. PLANS SHOWING ANY DEVIATION FROM THIS DESIGN MUST BE SUBMITTED TO HAWAl'I ELECTRIC LIGHT FOR APPROVAL.
• IN LIEU OF ANGLE IRON,STAINLESS STEEL OR GALVANIZED UNI-STRUT CHANNEL BOLTED TO VERTICAL PIPE SUPPORT MAY BE ACCEPTABLE. CONSULT WITH THE COMPANY PRIOR TO FABRICATION.
. 6"
LOAD <CUSTOMER>
x 8' • i! 6 F
NEC 250
6"
SIDE
••• .......• • HAWAl'I LICHTELECTRIC ENGINEERING DEPARTMENT
.._0, HAWAII
FREE STANDING STEEL POST STRUCTURE CESIM PG 56·57>
EST J REO. NO. OESIGNEO / ORAWN MM/KO CHK 'O/ APP'O SCALE NTS PROJ. NO . JP. NO. OATE q/8/17 T.M .K. NUMBER PEDSTL
RAIN TIGHT SPLICE CAN
t CUSTOMER
HAWAl'I ELECTRIC LIGHT
•