memoria de calculo ac com cÁlc de fan-coil
TRANSCRIPT
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
1/271
MEMORIA 1
DOCUMENTO N 1, MEMORIA.
NDICE GENERAL:
1.1 MEMORIA DESCRIPTIVA...2
1.2 CLCULOS... 22
1.3 ANEJOS.122
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
2/271
MEMORIA 2
1.1 MEMORIA DESCRIPTIVA.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
3/271
MEMORIA 3
1.1 MEMORIA DESCRIPTIVA.
NDICE:
1.1 MEMORIA DESCRIPTIVA5
1.1.1 OBJETO DEL PROYECTO.5
1.1.2 DESCRIPCIN DEL EDIFICIO........ 5
1.1.3 DATOS DE PARTIDA. 6
1.1.3.1 CONDICIONES EXTERNAS.. 6
1.1.3.2 CONDICIONES INTERNAS... 6
1.1.3.3 CARACTERSTICAS CONSTRUCTIVAS7
1.1.3.4 CONDICIONES DE USO..8
1.1.3.5 NIVELES DE VENTILACIN..10
1.1.4 CLCULO DE CARGAS ..11
1.1.4.2 CLCULO DE CARGAS DE VFRANO.......11
1.1.5 DISEO DE EQUIPOS...11
1.1.5.1 DISEO DE FAN COILS........12
1.1.5.2 DISEO DE CLIMATIZADORES........13
1.1.5.3 DISEO DE CLIMATIZADORES DE AIRE EXTERIOR........13
1.1.5.4 DISEO DE CONDUCTOS.......14
1.1.5.5 DIFUSORES15
1.1.5.6 DISEO DE REJILLAS15
1.1.5.7 DISEO DE LOS VENTILADORES...16
1.1.5.8 DISEO DE TUBERAS. .17
1.1.5.9 DISEO DE LAS BOMBAS.18
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
4/271
MEMORIA 4
1.1.5.10 DISEO DE LA CALDERA.. 19
1.1.5.11 DISEO DEL EQUIPO REFRIGERADOR.19
1.1.5.12 DISEO DE ELEMENTOS AUXILIARES..19
1.1.6 BIBLIOGRAFA21
1.1.7 COSTE TOTAL DE LA INSTALACIN...21
1.1 MEMORIA DESCRIPTIVA.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
5/271
MEMORIA 5
1.1.1 OBJETO DEL PROYECTO.
El objeto de este proyecto consiste en la climatizacin de un aeropuerto situado en
Talavera de la Reina. Para lo cual desarrollaremos a lo largo del mismo las
condiciones tcnicas y legales a las que debern ajustarse las instalaciones de
climatizacin de dicho aeropuerto. Cumpliendo el Apndice 07.1 del Reglamento de
Instalaciones Trmicas de los Edificios, adems de todos los captulos de la RITE,
con su contenido simplificado y ajustado al tipo de instalacin.
Las instalaciones a desarrollar comprendern la totalidad de los sistemas de
refrigeracin y calefaccin necesarios durante todos los das del ao para una
instalacin de las caractersticas de un aeropuerto.
1.1.2 DESCRIPCIN DEL EDIFICIO.
El edificio es un aeropuerto situado en la provincia de Toledo en el lmite con la de
Madrid, con una superficie a climatizar aproximadamente de 70000 m2. Dicho
aeropuerto consta de dos plantas situadas a diferentes cotas:
Una primera planta 0,00 m.: no acondicionada en la que se sitan
principalmente zonas de almacenamientos, salas de mquinas y cintas para
transporte de equipaje desde facturacin a los aviones..
Una segunda planta +5,00 m.: planta acondicionada en la que se centra el
desarrollo del proyecto. En est planta se encuentran las zonas: Vestbulo de
entrada, facturacin, equipaje, polica, prensa, zonas comerciales, zonas de
oficinas y zonas de trnsito.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
6/271
MEMORIA 6
1.1.3 DATOS DE PARTIDA.
1.1.3.1 CONDICIONES EXTERNAS.
Los valores adoptados como condiciones exteriores de clculo de este proyecto se
han obtenido de manual CARRIER para la provincia de Madrid dada la situacin del
aeropuerto y son:
Altitud: 667 m.
Latitud: 40 25
- Condiciones normales de verano: percentil del 95% a las 15 horas solares del
mes de Julio:
Temperatura seca: 34 C.
Temperatura hmeda: 30,1 C
Variacin diurna: 15
- Condiciones de invierno:
Temperatura seca: -3 C
Temperatura hmeda: - 0,9 C
1.1.3.2 CONDICIONES INTERNAS.
Condiciones de verano:
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
7/271
MEMORIA 7
Para lograr el bienestar trmico, se aplicar la norma ITE 02.2 sobre condiciones
interiores, por lo que se tendr en cuenta la norma UNE-EN ISO 7730, en la que se
determina que la temperatura interior para condiciones de verano deber estar entre
23 y 25 C. Las condiciones de los diferentes locales para la planta +5,00 m sern,
considerndose en todos los casos una humedad relativa del 50 %:
Vestbulo de entrada: 25 1C
Facturacin: 25 1C
Zonas de trnsito: 25 1C
Equipajes: 25 1C
Zonas de oficinas: 24 1C
Zonas comerciales: 25 1C
Condiciones de invierno:
Las condiciones establecidas para lograr el bienestar trmico en cada uno de los
locales a climatizar en invierno sern los siguientes, considerando para todos los
casos una humedad relativa del 50%:
Vestbulo de entrada: 22 1C
Facturacin: 22 1C
Zonas de trnsito: 22 1C
Equipajes: 22 1C
Zonas de oficinas: 22 1C
Zonas comerciales: 22 1C
1.1.3.3 CARACTERSTICAS CONSTRUCTIVAS.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
8/271
MEMORIA 8
Los coeficientes K de transmisin han sido calculados siguiendo lo especificado en
la norma NBE-CT-79. De esta forma los valores dados para el clculo de nuestro
proyecto han sido los siguientes:
- Cristales (F.G.S): 0,48
- Cristales (K): 2,6 W/m2.C.
- Muros exteriores (K): 1,45 W/m2.C.
- Tabiques LNA (K): 1,69 W/m2.C.
- Tejados (K): 0,63 W/m2.C.
- Suelos interiores (K): 1,07 W/m2.C.
- Suelos exteriores (K): 0,63 W/m2.C.
- Techos LNA (K): 1,07 W/m2.C.
- Puertas (K): 2 W/m2.C.
1.1.3.4 CONDICIONES DE USO.
Niveles de ocupacin:
Se han considerado los siguientes niveles de ocupacin para los distintos locales de
la cota +5,00 m.:
Vestbulo de entrada: 4 m2/persona
Facturacin: 4 m2/persona
Zonas de trnstito: 10 m2/persona
Equipajes: 4 m2/persona
Zonas de oficinas: 7-10 m2/persona
Zonas comerciales: 7 m2/persona
Niveles de actividad considerados:
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
9/271
MEMORIA 9
Los niveles de actividad considerados para el clculo de cargas sern los sigueientes:
Carga sensible:
Vestbulo de entrada: 70,7 W/persona
Facturacin: 70,7 W/persona
Zonas de trnsito: 70,7 W/persona
Equipajes: 70,7 W/persona
Zonas de oficinas: 70,7 W/persona
Zonas comerciales: 70,7 W/persona
Carga latente:
Hall de entrada: 68,12 W/persona
Facturacin: 68,12 W/persona
Zonas de paso: 68,12 W/persona
Equipajes: 68,12 W/persona
Zonas de oficinas: 68,12 W/persona
Zonas comerciales: 68,12 W/persona
Cargas elctricas:
Las cargas elctricas consideradas para el clculo de cargas son las siguientes:
- Vestbulo de entrada:
Iluminacin: 20 W/m2.
Sealtica y monitores: 3 W/m2.
- Facturacin:
Iluminacin: 20 W/m2.
Sealtica y monitores: 3 W/m2.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
10/271
MEMORIA 10
- Zonas de trnsito:
Iluminacin: 20 W/m2
.
Sealtica y monitores: 3 W/m2.
- Equipajes:
Iluminacin: 20 W/m2.
Sealtica y monitores: 3 W/m2.
- Zonas de oficinas:
Iluminacin: 20 W/m2.
Cargas elctricas: 20 W/m2.
- Zonas comerciales:
Iluminacin: 20 W/m2.
Cargas elctricas: 20 W/m2.
1.1.3.5 NIVELES DE VENTILACIN.
Siguiendo las especificaciones indicadas en la norma UNE se han establecido los
siguientes niveles de ventilacin:
Vestbulo de entrada: 10 l/s persona.
Facturacin: 10 l/s persona.
Zonas de trnsito: 10 l/s persona.
Equipajes: 10 l/s persona.
Zonas de oficinas: 10 l/s persona.
Zonas comerciales: 10 l/s persona.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
11/271
MEMORIA 11
1.1.4 CLCULO DE CARGAS.
1.1.4.1 CLCULO DE CARGAS DE INVIERNO.
Con las condiciones exteriores para invierno fijadas en el apartado 1.1.3.1 se ha
procedido al clculo de las necesidades trmicas de cada una de las zonas del
aeropuerto.
En este clculo solo se ha considerado la transmisin en los muros, ya que tanto la
radiacin, iluminacin y equipos y ocupacin son favorables en invierno, por lo que
ayudaran en la calefaccin de nuestro local y no han de ser tenidas en cuenta. Los
locales tendrn una sobrepresin, por lo que la infiltracin no ser tenida en cuenta.
Se asegura de este modo que en las condiciones ms desfavorables de proyecto, es
decir cuando arranque el sistema antes de la jornada y an no haya ocupacin, ni
estn encendidos los equipos, el equipo pueda responder a las necesidades del local
que sern las indicadas anteriormente para cada uno de los locales.
1.1.4.2 CLCULO DE LAS CARGAS DE VERANO.
Para el clculo de las cargas de verano se realizar un clculo reiterativo para estimar
la hora y el mes ms desfavorables para las condiciones de proyecto seleccionadas,
en funcin de la orientacin de cada uno de los locales.
De cada local se calcularn los valores de transmisin en muros, radiacin,
iluminacin y equipos y ocupacin. Una vez ms la infiltracin no ser tenida en
cuenta debido a la sobrepresin.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
12/271
MEMORIA 12
Se asegurar de este modo que los equipos podrn aportar las necesidades de
refrigeracin dadas para cada local en las condiciones ms desfavorables de
proyecto.
1.1.5 DISEO DE EQUIPOS.
1.1.5.1 DISEO DE FAN-COILS.
Se han seleccionado Fan-Coils para cubrir las necesidades trmicas y frigorficas de
varias oficinas y zonas comerciales. Los equipos seleccionados sern unidades
verticales con mueble y unidades horizontales ocultas en el falso techo, los distintos
modelos seleccionados del catlogo para cada uno de los locales sern expuestos en
el apartado de clculos.
En ningn caso ser necesario el empleo de glicol en tuberas. Los equipos podrn
ser de dos tubos o cuatro tubos, en funcin de que locales tengan o no unas
necesidades trmicas suficientes como para considerar utilizar tuberas para el agua
caliente de calefaccin.
El criterio de seleccin de los equipos ha sido realizado mediante el clculo del
aporte de agua necesario para que puedan hacer frente a las cargas latente y sensible
de verano y a la carga total de calefaccin en invierno. Cumpliendo con niveles de
ruido permitidos.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
13/271
MEMORIA 13
1.1.5.2 DISEO DE LOS CLIMATIZADORES.
Se han seleccionado climatizadores para cumplir las necesidades del vestbulo de
entrada, facturacin, equipaje, y aquellas oficinas y zonas comerciales cuyas
dimensiones exigen la colocacin de un climatizador.
La seleccin de climatizadores se ha realizado calculando las potencias necesarias de
refrigeracin y calefaccin. El punto de impulsin se ha fijado en un intervalo de
13,5 a 14,5 C, mediante el empleo del diagrama psicromtrico y las condiciones
externas e internas del edificio se han calculado las potencias de los equipos. Una vez
conocidas las potencias y fijados los caudales de impulsin, ventilacin y retorno se
ha seleccionado el equipo mediante un programa de un TROX. Para la temperatura
de impulsin fijada no ser necesario el empelo de glicol en las tuberas.
Cada equipo estar compuesto por una batera de fro, una batera de calor, un
ventilador de impulsin, un ventilador de retorno, dos filtros G4 y F8 segn UNE EN
779 y tres compuertas, una para expulsar aire al exterior, una segunda compuerta
para recircular aire de la habitacin y una tercera para tomar aire del exterior.
1.1.5.3 DISEO DE LOS CLIMATIZADORES DE AIRE EXTERIOR.
En aquellos locales en los que se ha dispuesto un Fan Coil ser necesario el
climatizador de aire exterior. Este climatizador se disea para varios locales, siendo
el caudal de impulsin el mismo que el de ventilacin de cada local.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
14/271
MEMORIA 14
El climatizador no contar con un ventilador de retorno por lo que no existir el
punto de mezcla, las condiciones a las que llega el aire a las bateras son las del
exterior. El climatizador impulsar durante todo el ao el aire a 22C.
Este aire de ventilacin se llevar hasta el falso techo lo ms cerca posible del Fan
Coil. Se realizar una extraccin de todos aquellos locales a los que impulsa aire el
climatizador de aire exterior, dicha extraccin ser del 80% del caudal de ventilacin
para cada local.
Los elementos que componen principalmente el climatizador son: la batera de fro,
la batera de calor, el ventilador de impulsin, dos filtros G4 y F8 segn UNE EN
779 y la compuerta para el aire exterior de ventilacin.
1.1.5.4 DISEO DE CONDUCTOS.
Los conductos empleados para la climatizacin sern rectangulares, el material
empleado ser acero galvanizado.
Como criterio para la seleccin de los conductos necesarios, tanto para la impulsin
como para retorno, es que la velocidad no ser superior en ningn caso a los 10m/s y
la prdida de carga por metro lineal de conductos no podr superar los 1,2 Pa/m.
Para los climatizadores se trabajar siempre a baja velocidad, mientras que en los
Fan-Coils emplearemos media velocidad.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
15/271
MEMORIA 15
1.1.5.5 DIFUSORES.
Los difusores empleados sern de la serie ADLQ 250-300-400-500-600, los diversos
tamaos sern en funcin de los caudales de impulsin calculados para las
necesidades de cada local.
Como criterio los difusores estarn distribuidos siempre de la forma ms simtrica
posible en nuestro local.
1.1.5.6 DISEO DE REJILLAS.
Las rejillas son las encargadas de permitir retornar el aire desde el local. El modelo
de rejillas seleccionas son AT, de lamas mviles regulables individualmente, con un
rango de caudales de 100 a 6000 m3
/h. El nmero de rejillas necesario para cada
local vendr dado en funcin del caudal de retorno y el tamao seleccionado para la
rejilla en cada caso.
Su disposicin en el local no tiene porque ser simtrica por lo que se dispondr de la
forma ms conveniente para poder retornar el aire hasta el climatizador o en su caso
al Fan Coil, en el caso de los Fan Coils la mejor disposicin de est ser justo debajo
del equipo.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
16/271
MEMORIA 16
1.1.5.7 DISEO DE LOS VENTILADORES.
Tanto el ventilador de impulsin como el de retorno tendr suficiente para vencer la
prdida de carga que se producirn en los conductos, habr que tener en cuenta
tambin la perdida que se produce en los difusores y rejillas.
El ventilador de impulsin se disea teniendo en cuenta el caudal de impulsin al
local y la prdida de carga que se produce el conducto de impulsin desde el
climatizador al difusor ms alejado de este.
El ventilador de retorno se disea teniendo en cuenta el caudal extraccin, que ser la
suma de los caudales de expulsin y de retorno, y considerando la mayor prdida de
carga que se produce en el conducto desde la rejilla ms alejada al climatizador.
Los ventiladores de extraccin se han diseado para aquellos locales que tenemos
climatizador de aire exterior y Fan Coils, dependern del caudal de extraccin y de la
prdida de carga que se produce en el conducto desde la rejilla ms alejada al
ventilador.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
17/271
MEMORIA 17
1.1.5.8 DISEO DE TUBERAS.
Se realizarn dos circuitos cerrados de tuberas independientes, uno para los
climatizadores y otro para los Fan-Coil, cada uno a su vez con dos circuitos
independiente de tuberas para la batera de fro y para la batera de calor.
En el sistema de tuberas de los Fan-Coil, tendremos las siguientes temperaturas:
Calefaccin:
Temperatura de entrada del agua 50 C.
Incremento de temperatura en el agua 5 C.
Refrigeracin:
Temperatura de entrada del agua 7 C.
Incremento de temperatura en el agua 5 C.
Los Fan-Coil sern de cuatro tubos, en algunos casos el sistema de calefaccin no
ser necesario.
En el sistema de tuberas empleado para los climatizadores, los valores de
temperaturas considerados sern los siguientes:
Batera de agua fra:
Temperatura de entrada del agua: 7 C.
Temperatura de salida del agua: 14 C.
Batera de agua caliente:
Temperatura de entrada del agua: 85 C.
Temperatura de salida del agua: 65 C.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
18/271
MEMORIA 18
La regulacin del caudal de entrada a los Fan-Coil se realizar mediante vlvulas de
tres vas, que nos permitirn el paso de una mayor o menor caudal a nuestro equipo
en funcin de las necesidades de refrigeracin y trmicas en nuestro local
dependiendo de los distintos valores de cargas que se puedan dar en las diferentes
horas del da.
Los criterios de seleccin para las tuberas sern que la velocidad nunca sea superior
a 2,1 m/s y que la prdida de carga mxima permitida por metro lineal de tubera ser
de 25 mm.c.a.
El material empleado ser acero negro no galvanizado.
1.1.5.9 DISEO DE LAS BOMBAS.
Las bombas se han diseado para cada uno de los cuatro circuitos de la instalacin.
Para los Fan Coils y climatizadores se han considerado los caudales necesarios para
los circuitos de fro y de calor.
Las bombas se han diseado considerando la mayor prdida de carga que se produce
en los circuitos de tuberas, y que se producir desde la batera del Fan Coil o del
climatizador ms alejada hasta la bomba.
En total se han dispuesto cuatro bombas, para circuito de fro y circuito de calor de
Fan Coils y para circuito de fro y circuito de calor de climatizadores.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
19/271
MEMORIA 19
1.1.5.10 DISEO DE LA CALDERA.
La caldera se disear en funcin de las necesidades de calefaccin de los
climatizadores y de los Fan-Coils.
La potencia de la caldera ser suficiente para cubrir las necesidades de calefaccin
del aeropuerto. En total se han seleccionado cuatro calderas, de forma que tres de
ellas estarn operativas y una permanecer parada. Las calderas se irn alternando en
su funcionamiento, la caldera parada nos permitir un margen de seguridad ante
posibles averas o demandas ms altas de la instalacin.
Las cuatro calderas sern de modelo EUROBLOC-SUPEREX 1.627..
1.1.5.11 DISEO DEL EQUIPO REFRIGERADOR.
El equipo de refrigeracin se disear funcin de las necesidades de refrigeracin de
los climatizadores y Fan Coils. Se ha considerado la potencia total de refrigeracin
de los equipos y el caudal de agua necesario para la batera de fro de los mismos.
En total se han seleccionado seis enfriadoras de agua de condensacin por aire de la
marca Carrier del modelo 30 XA 1702 situadas en la cubierta del edificio
1.1.5.12 DISEO DE ELEMENTOS AUXILIARES.
Compuerta cortafuegos:
En aquellas zonas que sean de seguridad en caso de incendio y estn atravesadas por
conductos de impulsin o retorno del aire se dispondr de compuertas cortafuegos.
Vlvulas de interrupcin y regulacin:
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
20/271
MEMORIA 20
En todos los Fan Coils, climatizadores, equipos de refrigeracin, calderas y bombas
se dispondrn de vlvulas de interrupcin y regulacin, que nos permitirn regular el
caudal necesario que debe pasar por la tubera hasta la batera de fro o de calor del
equipo. Ests vlvulas vendrn con sistema de memorizacin mecnica de posicin.
Vlvulas de corte:
Sern necesarias para todos los equipos disponer de vlvulas de corte. Se dispondrn
vlvulas de bola para tuberas menores de DN50 y vlvulas de mariposa para tuberas
mayores de DN65.
Vlvulas de control:
La regulacin del caudal necesario en cada momento en las bateras de los Fan-Coils
y climatizadores se realizar mediante el empleo de vlvulas de tres vas.
Filtros:
En todos los equipos ser necesario disponer de filtros para asegurar la limpieza del
agua del sistema.
Equipos de medida:
Para el sistema de tuberas ser necesario disponer de equipos de medida que nos
permitan conocer el caudal y la temperatura del agua en todo momento, para lo que
ser necesario disponer de termmetros y manmetros diferenciales en todos los
equipos.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
21/271
MEMORIA 21
1.1.6 BIBLIOGRAFA.
[CARR03] Manual de aire acondicionado, Autor: Carrier. Editorial:
MARCOMBO, S.A. [2003].
Catlogo Fan-Coil de CARRIER.
Catlogo Climatizadores de TROX.
Catlogo de difusores y rejillas de TROX.
Catlogo de bombas de GRUNDFOS.
Catlogo de enfriadoras de agua de CARRIER.
Catlogo de calderas de VULCANO-SADECA.
1.1.7 COSTE TOTAL DE LA INSTALACIN.
El coste total de nuestra instalacin de climatizacin para el aeropuerto ser de
2.960.975 .
Madrid, 22 de junio de 2008
JAVIER ARIAS ORTIZ
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
22/271
MEMORIA 22
1.2 CLCULOS.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
23/271
MEMORIA 23
1.2 CLCULOS.NDICE:
1.2 CLCULOS....................................................................................................25
1.2.1 CLCULO DE CARGAS........................................................................25
1.2.1.1 CLCULO DE CARGAS DE VERANO. ........................................25
1.2.1.1.1 TRANSMISIN..........................................................................25
1.2.1.1.2 RADIACIN SOLAR. ...............................................................27
1.2.1.1.3 INTERNAS. ................................................................................27
1.2.1.1.4 INFILTRACIONES....................................................................29
1.2.1.1.5 CARGA SENSIBLE Y CARGA LATENTE. ............................ 29
1.2.1.1.6 RESULTADOS. ..........................................................................29
1.2.1.2 CLCULO DE PRDIDAS EN INVIERNO...................................32
1.2.1.2.1 TRANSMISIN EN MUROS Y TECHOS. ..............................33
1.2.1.2.2 TRANSMISIN EN CRISTALES.............................................33
1.2.1.2.3 TRANSMISIN EN PARTICIONES........................................33
1.2.1.2.4 INFILTACIONES. .....................................................................34
1.2.1.2.5 RESULTADOS. ..........................................................................34
1.2.1.3 RESULTADOS FINALES. ...............................................................37
1.2.2 CLCULO DE CAUDALES DE VENTILACIN. ...............................42
1.2.3 CLCULO DE EQUIPOS.......................................................................47
1.2.3.1 CLCULO DE CLIMATIZADORES.............................................47
1.2.3.2 CLCULO DE CLIMATIZADORES DE AIRE PRIMARIO. ......63
1.2.3.4 DIFUSORES......................................................................................74
1.2.3.8 TUBERAS. .....................................................................................115
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
24/271
MEMORIA 24
1.2.3.9 SELECCIN DE LAS BOMAS. ....................................................118
1.2.3.10 SELECCIN DE LA CALDERA.................................................120
1.2.3.11 SELECCIN DEL EQUIPO DE REFRIGERACIN................121
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
25/271
MEMORIA 25
1.2 CLCULOS.
1.2.1 CLCULO DE CARGAS.
Para el clculo de cargas hemos dividido el aeropuerto en diversas zonas numeradas,
para las que especificaremos su ocupacin y superficie.
1.2.1.1 CLCULO DE CARGAS DE VERANO.
Para el clculo de las cargas de verano tendremos en cuenta los siguientes puntos:
Transmisin.
Radiacin solar.
Internas.
Infiltraciones.
1.2.1.1.1 TRANSMISIN.
El clculo de la transmisin se divide en los siguientes apartados:
Transmisin en muros y techos:
La transmisin que se produce en el muro ha sido calculada mediante la siguiente
frmula:
eqmuro
TSKT =
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
26/271
MEMORIA 26
Siendo la expresin para el clculo de la temperatura equivalente:
)( esemm
a
eseq ttRRbtaT ++=
Donde:
a: factor de correccin.
est : diferencia equivalente de temperatura a la hora considerada para la pared a la
sombra.
emt : diferencia equivalente de temperatura a la hora considerada para la pared
soleada.
b: coeficiente que considera el color de la cara exterior de la pared.
aR : mxima insolacin correspondiente al mes y latitud supuestos, a travs de una
superficie acristalada vertical u horizontal para la orientacin considerada.
mR : mxima insolacin en el mes de Julio, a 40 de latitud Norte, a travs de una
superficie acristalada vertical u horizontal para la orientacin considerada.
Transmisin en cristales:
La transmisin en el cristal viene dad por la siguiente expresin:
)( intTTSKT extcristalcristal =
Transmisin en particiones:
Se consideran particiones aquellos locales que no estn acondicionados y para los
que su temperatura se supone la mitad del incremento de temperatura que se produce
entre el exterior y el interior.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
27/271
MEMORIA 27
2
)( intTTSKT extLNCParticin
=
1.2.1.1.2 RADIACIN SOLAR.
El clculo de la radiacin solar vendr afectado por la orientacin del local
considerado y por la hora y mes a la que se realiza dicho clculo. Para asegurar que
nuestro local puede ser climatizado, an en las peores condiciones de proyecto, se ha
considerado para la elaboracin del clculo de la radiacin la hora y mes ms
desfavorables. La obtencin de la hora y el mes ms desfavorables se ha realizado
para cada local, repitiendo el clculo mediante hojas Excel hasta obtener un mximo
de radiacin.
La formula empleada para el clculo de la radiacin:
... SGFGSRadiacin cristal =
Siendo:
cristalS : la superficie de cristal del local considerado.
G : la ganancia solar en el cristal.
F.G.S. : factor de ganancia solar.
1.2.1.1.3 INTERNAS.
El valor de la carga interna de pender de la iluminacin, equipos y ocupacin que se
den el local considerado, por lo que dividimos el clculo en los siguientes apartados:
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
28/271
MEMORIA 28
Iluminacin:
La carga de iluminacin depender de los valores de iluminacin especificados para
cada local. Una vez conocida la superficie del local considerado el resultado de carga
de iluminacin se obtiene:
.arg)()(min 22
mWacmSWacinIlu =
Equipos:
La carga generada por lo equipos depender de los valores considerados para cada
local en funcin de la zona del aeropuerto. El valor de dicha carga vendr dado de
esta forma:
.arg)()( 22
mWacmSWEquipos =
Ocupacin:
En funcin de los valores para los niveles de actividad realizados para cada zona del
aeropuerto y de la ocupacin considerada podremos calcular los diferentes valores de
carga sensible y de carga latente.
.arg)(
= personaWacocupantesnWC sensiblesensible
.arg)(
=persona
WacocupantesnWC latentelatente
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
29/271
MEMORIA 29
1.2.1.1.4 INFILTRACIONES.
Debido a la sobrepresin que producimos en los locales el valor de las infiltraciones
ser nulo para todos los locales considerados.
1.2.1.1.5 CARGA SENSIBLE Y CARGA LATENTE.
Una vez realizado el clculo de los apartados anteriores podemos obtener los valores
de carga sensible y carga latente total de nuestro local.
Siendo la carga sensible total de local la suma de los valores obtenidos para la
transmisin, en muros, cristales y ventanas, la radiacin producida en los cristales, y
las cargas internas, tanto de iluminacin, equipos y ocupacin sensible del local.
El valor de la carga latente vendr dado en funcin nicamente de la ocupacin.
latenteL CC =
1.2.1.1.6 RESULTADOS.
En las siguientes tablas se muestra un resumen de los valores de transmisin,
radiacin, iluminacin y equipos, carga sensible y carga latente obtenidos para cada
uno de los locales a climatizar.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
30/271
MEMORIA 30
Transmisin
Zonamuro y
techo (W)cristales
(W)particiones
(W)radiacin
(W)
iluminacin
y equipos(W)
cargasensible (W)
carga
latente(W)
H1.01 545 0 221 0 487 164 158
H1.02 0 0 1060 0 2341 658 634
H1.03 0 0 1060 0 2341 658 634
H1.04 0 0 698 0 1538 575 554
H1.05 0 0 740 0 1630 493 475
H1.06 0 0 809 0 1788 575 554
H1.07 0 0 881 0 1943 658 634
H1.08 0 0 363 0 799 247 238
H1.09 0 0 300 0 664 247 238
H1.10 0 0 335 0 740 247 238H1.11 0 0 388 0 857 329 317
H1.12 0 0 388 0 857 329 317
H1.13 0 0 391 0 862 329 317
H1.14 0 0 391 0 862 329 317
H1.15 0 0 667 0 1473 575 554
H1.16 0 0 2567 0 5663 1644 1584
H1.17 0 0 812 0 1792 658 634
H1.18 0 0 188 0 414 164 158
H1.19 0 0 207 0 458 164 158
H1.20 0 0 528 0 1164 493 475
H1.22 0 0 472 0 1043 329 317H1.23 3799 0 3893 0 9127 3864 3723
H1.24 192 0 547 0 1207 493 475
H1.25 0 0 414 0 914 411 396
H1.26 0 0 2479 0 5470 2302 2218
H1.27 185 0 1186 0 2618 1069 1030
H1.28 6459 0 9760 0 21538 6330 6099
H1.29 2244 0 2207 0 5173 1480 1426
H1.30 2609 0 8067 0 17798 5261 5069
H1.31 0 0 5630 0 12425 3617 3485
H1.32 0 0 1700 0 3752 1069 1030
H1.33 0 0 719 0 1585 493 475
H1.34 0 0 1472 0 3248 1151 1109
H1.35 0 0 486 0 1074 411 396
H1.36 0 0 4686 0 10338 3042 2931
H1.37 0 0 11777 0 25985 7645 7366
H2.01 0 0 3105 0 6850 2877 2772
H2.02 0 0 4079 0 8999 2960 2852
H2.03 0 0 698 0 1538 493 475
H2.04 0 0 981 0 2166 740 713
H2.05 0 0 530 0 1169 411 396
H2.06 0 0 226 0 497 164 158
H2.07 0 0 149 0 328 82 79
H2.08 0 0 216 0 476 164 158H2.09 0 0 226 0 497 164 158
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
31/271
MEMORIA 31
H2.10 0 0 198 0 434 164 158
H2.11 0 0 107 0 234 82 79
H2.12 0 0 516 0 1140 411 396H2.13 0 0 886 0 1956 740 713
H2.14 0 0 698 0 1538 575 554
H2.15 0 0 214 0 469 164 158
H2.16 0 0 419 0 922 329 317
H2.17 0 0 737 0 1625 575 554
H2.18 0 0 698 0 1538 575 554
H2.19 0 0 1819 0 4011 1315 1267
H2.20 0 0 4709 0 10391 3782 3644
H2.21 0 0 698 0 1538 575 554
H2.22 0 0 2198 0 4847 3535 3406
H2.23 0 0 416 0 920 329 317H2.24 0 0 765 0 1690 658 634
H2.25 0 0 698 0 1538 575 554
H2.26 0 0 10788 0 23804 9947 9584
H3.01 0 0 8498 0 18749 7892 7604
H3.02 0 0 8177 0 18041 7563 7287
H3.03 0 0 698 0 1538 658 634
H3.04 537 0 1521 0 3358 1233 1188
H3.05 478 0 1356 0 2991 1069 1030
H3.06 497 0 533 0 1249 493 475
H3.07 0 0 435 0 962 329 317
H3.08 0 0 442 0 973 329 317
H3.09 0 0 558 0 1232 411 396
H3.10 0 0 728 0 1606 575 554
H3.11 0 0 472 0 1042 411 396
H3.12 0 0 765 0 1690 493 475
H3.13 0 0 663 0 1463 575 554
H3.14 0 0 398 0 875 329 317
H3.15 0 0 381 0 840 329 317
H3.16 0 0 835 0 1844 658 634
H3.18 0 0 781 0 1724 658 634
H3.19 0 0 3453 0 7620 3699 3564
H3.20 0 0 856 0 1887 658 634
H3.21 0 0 856 0 1887 658 634H3.22 0 0 151 0 336 82 79
H3.23 0 0 151 0 336 82 79
H3.24 0 0 151 0 336 82 79
H3.25 0 0 105 0 233 82 79
H3.26 0 0 188 0 414 164 158
H3.27 0 0 151 0 336 82 79
H3.28 0 0 151 0 336 82 79
H3.29 0 0 151 0 336 82 79
H3.30 0 0 165 0 363 164 158
H3.31 0 0 288 0 637 247 238
H3.32 0 0 807 0 1779 658 634H3.33 0 0 495 0 1091 411 396
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
32/271
MEMORIA 32
H3.34 0 0 195 0 431 164 158
H3.35 0 0 300 0 661 247 238
H3.36 0 0 170 0 376 164 158H3.37 0 0 479 0 1057 329 317
H3.38 0 0 440 0 970 329 317
H3.39 0 0 419 0 924 329 317
H3.40 0 0 353 0 783 247 238
H3.41 0 0 516 0 1141 411 396
H3.42 0 0 819 0 1807 493 475
H3.43 0 0 188 0 414 82 79
H3.44 0 0 247 0 542 164 158
H3.45 0 0 442 0 973 329 317
H3.46 0 0 442 0 973 329 317
H3.47 0 0 714 0 1577 575 554H3.48 0 0 1958 0 4319 1562 1505
H3.49 0 0 374 0 829 329 317
H3.50 0 0 642 0 1418 493 475
H3.51 0 0 1900 0 4190 1562 1505
H3.52 0 0 812 0 1792 658 634
H3.53 0 0 247 0 542 164 158
H3.54 0 0 226 0 496 164 158
H3.55 0 0 535 0 1183 411 396
H3.56 0 0 630 0 1390 493 475
H3.57 0 0 2544 0 5614 2055 1980
1.2.1.2 CLCULO DE PRDIDAS EN INVIERNO.
Para l clculo de las prdidas producidas solo se tendrn en cuentan los valores de
transmisin, ya que tanto la radiacin como las cargas internas favorecen en
invierno.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
33/271
MEMORIA 33
1.2.1.2.1 TRANSMISIN EN MUROS Y TECHOS.
La transmisin que se produce en invierno en el muro viene dada por la siguiente
expresin:
)( int extmuromuromuro TTSKT =
Siendo:
intT : el valor de la temperatura interior del local considerado, y que ser la
temperatura de confort que queremos obtener en el local. Dicho valor ser de 22 C
para todas las zonas.
extT : el valor de la temperatura exterior, 0 C para invierno en Jan.
1.2.1.2.2 TRANSMISIN EN CRISTALES.
La transmisin en el cristal viene dada por la siguiente expresin:
)( int extcristalcristalcristal TTSKT =
1.2.1.2.3 TRANSMISIN EN PARTICIONES.
Se consideran particiones aquellos locales que no estn acondicionados y para los
que su temperatura se supone la mitad del incremento de temperatura que se produce
entre el interior y el exterior.
2
)( int extLNCParticin
TTSKT
=
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
34/271
MEMORIA 34
1.2.1.2.4 INFILTRACIONES.
Debido a la sobrepresin no se considerarn infiltraciones en invierno.
1.2.1.2.5 RESULTADOS.
En las siguientes tablas se muestran los valores obtenidos para las cargas de invierno,
para este caso, como se ha especificado anteriormente, solo se tomarn los valores de
transmisin de nuestro local. Para cada uno de los locales se resumen los valores
obtenidos por transmisin en muros y techos, cristales y particiones.
Transmisin
Zona muro ytecho (W)
cristales(W)
particiones(W)
H1.01 710 0 553
H1.02 0 0 2663
H1.03 0 0 2663
H1.04 0 0 1749
H1.05 0 0 1853
H1.06 0 0 2035
H1.07 0 0 2212
H1.08 0 0 909
H1.09 0 0 756H1.10 0 0 842
H1.11 0 0 974
H1.12 0 0 974
H1.13 0 0 981
H1.14 0 0 981
H1.15 0 0 1677
H1.16 0 0 6444
H1.17 0 0 2040
H1.18 0 0 470
H1.19 0 0 521
H1.20 0 0 1323H1.22 0 0 1186
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
35/271
MEMORIA 35
H1.23 5753 0 10386
H1.24 680 0 1372
H1.25 0 0 1042H1.26 0 0 6223
H1.27 656 0 2979
H1.28 8842 0 24507
H1.29 2212 0 5886
H1.30 3017 0 20251
H1.31 0 0 14137
H1.32 0 0 4270
H1.33 0 0 1805
H1.34 0 0 3695
H1.35 0 0 1223
H1.36 0 0 11763H1.37 0 0 29567
H2.01 0 0 7795
H2.02 0 0 10240
H2.03 0 0 1749
H2.04 0 0 2465
H2.05 0 0 1330
H2.06 0 0 565
H2.07 0 0 374
H2.08 0 0 542
H2.09 0 0 565
H2.10 0 0 493
H2.11 0 0 267
H2.12 0 0 1298
H2.13 0 0 2226
H2.14 0 0 1749
H2.15 0 0 535
H2.16 0 0 1049
H2.17 0 0 1849
H2.18 0 0 1749
H2.19 0 0 4565
H2.20 0 0 11823
H2.21 0 0 1749
H2.22 0 0 5516H2.23 0 0 1047
H2.24 0 0 1923
H2.25 0 0 1749
H2.26 0 0 27086
H3.01 0 0 21335
H3.02 0 0 20528
H3.03 0 0 1749
H3.04 1902 0 3819
H3.05 1695 0 3405
H3.06 1607 0 1421
H3.07 0 0 1093H3.08 0 0 1107
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
36/271
MEMORIA 36
H3.09 0 0 1402
H3.10 0 0 1826
H3.11 0 0 1186H3.12 0 0 1923
H3.13 0 0 1665
H3.14 0 0 995
H3.15 0 0 956
H3.16 0 0 2098
H3.18 0 0 1960
H3.19 0 0 8672
H3.20 0 0 2147
H3.21 0 0 2147
H3.22 0 0 381
H3.23 0 0 381H3.24 0 0 381
H3.25 0 0 265
H3.26 0 0 472
H3.27 0 0 381
H3.28 0 0 381
H3.29 0 0 381
H3.30 0 0 414
H3.31 0 0 723
H3.32 0 0 2023
H3.33 0 0 1242
H3.34 0 0 491
H3.35 0 0 751
H3.36 0 0 428
H3.37 0 0 1202
H3.38 0 0 1105
H3.39 0 0 1051
H3.40 0 0 891
H3.41 0 0 1298
H3.42 0 0 2056
H3.43 0 0 472
H3.44 0 0 616
H3.45 0 0 1107
H3.46 0 0 1107H3.47 0 0 1793
H3.48 0 0 4914
H3.49 0 0 942
H3.50 0 0 1614
H3.51 0 0 4767
H3.52 0 0 2040
H3.53 0 0 616
H3.54 0 0 565
H3.55 0 0 1347
H3.56 0 0 1581
H3.57 0 0 6388
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
37/271
MEMORIA 37
1.2.1.3 RESULTADOS FINALES.
Finalmente podemos ver en las siguiente tabla los resultados finales para de las
cargas de verano e invierno. Para verano se dan los valores de carga sensible y carga
latente, as como las sumas de las dos. Para invierno se da el valor de la carga total.
Para cada local se ha especificado la ocupacin, en nmero de personas, y la
superficie en metros cuadrados.
Verano Invierno
Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)
H1.01 2 17,4 1776 1597 179 1553
H1.02 4 43,6 3896 3540 356 3371
H1.03 8 83,6 5286 4572 714 3272
H1.04 7 54,9 3791 3166 625 2149
H1.05 6 58,2 3760 3224 536 2278
H1.06 7 63,9 4199 3574 625 2500
H1.07 8 69,42 4636 3922 714 2717
H1.08 3 28,52 1853 1586 267 1117H1.09 3 23,7 1631 1364 267 929
H1.10 3 26,44 1757 1490 267 1035
H1.11 4 30,58 2129 1773 356 1198
H1.12 4 30,58 2129 1773 356 1198
H1.13 4 30,8 2137 1781 356 1206
H1.14 4 30,8 2137 1781 356 1206
H1.15 7 52,61 3685 3060 625 2060
H1.16 20 202,26 12905 11121 1784 7917
H1.17 8 64,02 4387 3673 714 2506
H1.18 2 14,78 1043 864 179 578
H1.19 2 16,33 1113 934 179 641H1.20 6 41,53 2997 2461 536 1627
H1.21 1 6,79 494 404 90 266
H1.22 4 37,24 2434 2078 356 267
H1.24 6 43,08 3317 2781 536 2522
H1.25 5 32,67 2407 1960 447 1280
H1.26 28 195,36 14044 11546 2498 7646
H1.27 13 93,48 6891 5730 1161 4466
H1.32 13 134 8506 7345 1161 5246
H1.33 6 56,61 3853 3262 591 2384
H1.34 14 115,98 7941 6692 1249 4658
H1.35 5 38,37 2747 2300 447 1621
H1.37 93 928,06 60637 51479 9158 36828
H2.03 6 54,91 3609 3073 536 2149
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
38/271
MEMORIA 38
H2.04 9 77,35 5181 4378 803 3029
H2.05 5 41,74 2937 2490 447 1800
H2.06 2 17,73 1256 1077 179 808H2.07 1 11,72 796 706 90 573
H2.08 2 17,01 1222 1043 179 779
H2.09 2 17,73 1256 1077 179 808
H2.10 2 15,49 1152 973 179 720
H2.11 1 8,36 633 543 90 447
H2.12 5 40,71 2852 2405 447 1708
H2.13 9 69,85 5064 4261 803 3066
H2.14 7 54,91 3903 3278 625 1243
H2.15 2 16,8 1219 1040 179 784
H2.16 4 32,9 2323 1965 358 1415
H2.17 7 58,1 4161 3536 625 2603H2.18 7 54,9 3903 3278 625 2315
H2.21 7 54,9 3791 3166 625 2149
H2.23 4 32,8 2233 1875 358 1286
H2.24 8 60,4 4448 3733 715 2695
H2.25 7 54,9 3903 3278 625 2315
H3.01 96 669,6 48395 39830 8565 26587
H3.02 92 644,3 46478 38270 8208 25552
H3.03 8 54,9 4086 3371 715 2315
H3.11 5 37,2 2701 2254 447 1584
H3.12 6 60,4 4083 3547 536 2695
H3.13 7 52,2 3780 3155 625 2212
H3.14 4 31,3 2248 1890 358 1349
H3.15 4 30,0 2189 1831 358 1300
H3.16 8 65,8 4587 3872 715 2743
H3.17 4 30,0 2189 1831 358 1300
H3.18 8 61,6 4390 3675 715 2574
H3.19 45 272,2 20764 16749 4015 10821
H3.20 8 67,4 4630 3915 715 2764
H3.21 8 67,4 4630 3915 715 2764
H3.37 4 37,3 2686 2328 358 1809
H3.38 4 34,6 2429 2071 358 1523
H3.39 4 33,0 2467 2109 358 1623
H3.40 3 27,9 1938 1671 267 1260H3.41 5 49,7 2889 2442 447 1760
H3.42 6 64,5 4161 3625 536 2645
H3.43 1 14,8 946 856 90 706
H3.44 2 19,4 1337 1158 179 884
H3.45 4 34,7 2406 2048 358 1486
H3.46 4 34,7 2406 2048 358 1486
H3.47 7 154,3 3966 3341 625 2370
H3.48 19 29,6 10750 9055 1695 6334
H3.49 4 29,6 2197 1839 358 1323
H3.50 6 50,6 3497 2961 536 2109
H3.51 19 149,6 10540 8845 1695 6450H3.52 8 64,0 4474 3759 715 2631
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
39/271
MEMORIA 39
H3.53 2 19,4 1337 1158 179 884
H3.54 2 17,7 1349 1170 179 945
H3.55 5 42,2 2927 2480 447 1780H3.56 6 49,6 3481 2945 536 2109
H3.57 25 200,5 13845 11615 2230 8015
Vestbulo de entrada:
La zonas Vestbulo corresponde con zonas que dan a las fachada norte
respectivamente del edificio, hemos considerado una zona de influencia desde la
fachada de cinco metros.
Verano Invierno
Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)
Vestbulo 1.1 160 639,7 80309 66036 14273 23821
Vestbulo 2.1 339 1354,7 140507 110266 30241 69035
Vestbulo 2.2 412 1648,3 179565 142812 36753 83998
Vestbulo 3.1 149 596,9 60342 47050 13292 27686
Comercios:
Verano Invierno
Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)
H1.31 44 443,7 28333 24408 3925 17370
H1.36 37 369,2 24102 20459 3643 14617
H2.01 35 244,7 17575 14453 3122 9578
H2.20 46 371,1 25738 21634 4104 15067
H2.20 37 296,0 20585 16942 3643 11586
H2.26 121 850,1 61411 50616 10795 33945
Equipaje:
Verano Invierno
Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
40/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
41/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
42/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
43/271
MEMORIA 43
Zona Ocupacin Qv(l/s) Qv(m3/h)H1.01 2 20 72
H1.02 4 40 144
H1.03 8 80 288
H1.04 7 70 252
H1.05 6 60 216
H1.06 7 70 252
H1.07 8 80 288
H1.08 3 30 108
H1.09 3 30 108
H1.10 3 30 108
H1.11 4 40 144H1.12 4 40 144
H1.13 4 40 144
H1.14 4 40 144
H1.15 7 70 252
H1.16 20 200 720
H1.17 8 80 288
H1.18 2 20 72
H1.19 2 20 72
H1.20 6 60 216
H1.21 1 10 36
H1.22 4 40 144H1.24 6 60 216
H1.25 5 50 180
H1.26 28 280 1008
H1.27 13 130 468
H1.32 13 130 468
H1.33 6 60 216
H1.34 14 140 504
H1.35 5 50 180
H1.37 93 930 3348
H2.03 6 60 216
H2.04 9 90 324H2.05 5 50 180
H2.06 2 20 72
H2.07 1 10 36
H2.08 2 20 72
H2.09 2 20 72
H2.10 2 20 72
H2.11 1 10 36
H2.12 5 50 180
H2.13 9 90 324
H2.14 7 70 252
H2.15 2 20 72
H2.16 4 40 144
H2.17 7 70 252
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
44/271
MEMORIA 44
H2.18 7 70 252
H2.21 7 70 252
H2.23 4 40 144H2.24 8 80 288
H2.25 7 70 252
H3.01 96 960 3456
H3.02 92 920 3312
H3.03 8 80 288
H3.11 5 50 180
H3.12 6 60 216
H3.13 7 70 252
H3.14 4 40 144
H3.15 4 40 144
H3.16 8 80 288H3.17 4 40 144
H3.18 8 80 288
H3.19 45 450 1620
H3.20 8 80 288
H3.21 8 80 288
H3.37 4 40 144
H3.38 4 40 144
H3.39 4 40 144
H3.40 3 30 108
H3.41 5 50 180
H3.42 6 60 216
H3.43 1 10 36
H3.44 2 20 72
H3.45 4 40 144
H3.46 4 40 144
H3.47 7 70 252
H3.48 19 190 684
H3.49 4 40 144
H3.50 6 60 216
H3.51 19 190 684
H3.52 8 80 288
H3.53 2 20 72
H3.54 2 20 72H3.55 5 50 180
H3.56 6 60 216
H3.57 25 250 900
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
45/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
46/271
MEMORIA 46
Trnsito:
Zona Ocupacin Qv(l/s) Qv(m3/h)Trnsito 124 1240 4464
Recogida de equipajes:
Zona Ocupacin Qv(l/s) Qv(m3/h)Sector 1.1 2206 22060 79416
Sector 2.1 2356 23560 84816
Sector 2.2 2860 28600 102960
Sector 3.1 1302 13020 46872
Polica Municipal:
Zona Ocupacin Qv(l/s) Qv(m3/h)H3.04 15 150 540
H3.05 13 130 468
H3.06 6 60 216
H3.07 4 40 144
H3.08 4 40 144
H3.09 5 50 180
H3.10 7 70 252
Polica Nacional:
Zona Ocupacin Qv(l/s) Qv(m3/h)H3.22 1 10 36
H3.23 1 10 36
H3.24 1 10 36
H3.25 1 10 36
H3.26 2 20 72
H3.27 1 10 36
H3.28 1 10 36
H3.29 1 10 36
H3.30 2 20 72
H3.31 3 30 108
H3.32 8 80 288
H3.33 5 50 180
H3.34 2 20 72
H3.35 3 30 108
H3.36 2 20 72
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
47/271
MEMORIA 47
1.2.3 CLCULO DE EQUIPOS.
En funcin de las necesidades frigorficas y calorficas de cada local estimaremos el
empleo de Fan-Coils o de climatizadores para conseguir las condiciones de confort
de nuestro local. De este modo las habitaciones con cargas menores como puedas ser
oficinas de pequea superficie se han empleado Fan-Coils, mientras que para zonas
de gran superficie se han empleado climatizadores.
1.2.3.1 CLCULO DE CLIMATIZADORES.
Clculo para verano:
Caudal de impulsin.
En primer lugar para poder conocer las condiciones del punto de impulsin que
requiere nuestro local es necesario calcular el factor de carga sensible de nuestro
local mediante la siguiente frmula:
LS
S
CC
CFCS
+=
Conocido este factor y haciendo uso del diagrama psicromtrico, se traza la recta que
une el factor de carga sensible con las condiciones de confort de nuestro local, es
decir 24 C y 50% de humedad relativa para verano.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
48/271
MEMORIA 48
El punto de impulsin de nuestro local de encuentra en esta recta. En primer lugar
podramos considerar el punto de impulsin como la interseccin de la recta de carga
con las condiciones de saturacin, pero en nuestro caso, para la mayor parte de los
climatizadores se obtenan valores del punto de impulsin inferiores a 13 C, esto
puede suponer temperaturas muy bajas en el agua de refrigeracin de la batera de
fro. Temperaturas tan bajas pueden suponer el empleo de glicol, lo que encarecera
nuestra instalacin.
Por esta razn para nuestro clculo se ha partido, como hiptesis, de considerar una
temperatura de impulsin que est entre 13,5 C y 14,5 C. Para la temperatura seca
fijada y con la recta de carga podemos obtener las condiciones del punto de
impulsin:
Ts: Temperatura seca (C).
HR: Humedad relativa (%).
H: Humedad especfica (g/kg de aire).
De este modo el valor del caudal de impulsin ser:
)(01,3
)(23,1
ihiL
ihiS
HHQC
TTQC
=
=
Despejando de una de las frmulas obtenemos el valor del caudal de impulsin:
)(23,1
)()/(
ih
S
iTT
WCslQ
=
Punto de salida de la batera.
Se ha considerado un recalentamiento de 1,5 C, por lo que la temperatura a la salida
de la batera (TSB) sera:
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
49/271
MEMORIA 49
5,1= iSB TT
De este modo y con la misma humedad especfica que la del punto de impulsin
podemos conocer las condiciones a la salida de la batera:
Ts: Temperatura seca (C).
HR: Humedad relativa (%).
H: Humedad especfica (g/kg de aire).
Balance de caudales.
Conocido el caudal de ventilacin (Qv) y el valor del caudal de impulsin (Qi), el
caudal de retorno (Qr) a la habitacin se obtiene como:
vir QQQ =
El caudal de extraccin se ha calculado mediante la siguiente expresin:
6,3
)(6,0)/(
3mV
slQ localExtraccin =
Punto de mezcla.
El aire impulsado a los locales ser resultado de la mezcla de aire que retornamos a
nuestro local y el aire de ventilacin.
Las condiciones de temperatura del aire sern diferentes, por un lado el caudal que
retornamos de nuestro local estar a la temperatura de dicho local, considerando que
tenemos un recalentamiento del aire en el ventilador de retorno de 1C, el punto de
retorno ser de 25 C.
Mientras que las condiciones del caudal de ventilacin sern las del exterior
consideradas.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
50/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
51/271
MEMORIA 51
Condiciones de impulsin.
Conocida la carga de invierno para nuestro local y con las condiciones de confort de
invierno, 22C y humedad relativa del 50%, podemos obtener el valor de la
temperatura de impulsin.
)(23,1hiiT TTQC =
Despejando de la formula obtenemos la temperatura de impulsin:
h
i
Ti T
QCT +
=23,1
Punto de mezcla.
El aire impulsado para invierno es, como en verano, la suma de los caudales de
retorno y ventilacin.
Para este caso el caudal de retorno se considera a la temperatura de nuestro local, es
decir 22 C. Mientras que las condiciones del caudal de ventilacin sern las del
exterior consideradas.
El punto de mezcla se obtendr despejando de las siguientes ecuaciones:
extvhrmi
extvhrmi
HQHQHQ
TQTQTQ
+=
+=
Humectacin con vapor.
En el caso de que la humedad relativa del punto de impulsin fuera inferior a un
40%, sera necesario aadir vapor al aire.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
52/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
53/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
54/271
MEMORIA 54
Climatizadores para zona de equipaje:
Para esta zona se utilizarn cuatro climatizadores iguales ya que se han
dimensionado las zonas para que la carga a combatir sea la misma.
Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
1.1 27,9 12,84 13 9,2 14,5 9,2
Climatizadores para aduana:
Tenemos dos zonas de aduanas pero slo utilizaremos un climatizador ya que en la
otra zona dispondremos de un Fan-Coil para combatir la carga.
Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
H2.02 27,14 12,13 13 9,45 14,5 9,45
Climatizador para la zona VIP:
Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)H1.28/29-
VIP 25,79 10,88 13 9,62 14,5 9,62
Climatizador para la sala de prensa:
Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
H1.30 26,79 11,8 13 9,56 14,5 9,56
Climatizador para la zona de trnsito:
Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
55/271
MEMORIA 55
Trnsito 27,3 12,27 13 9,4 14,5 9,4
Climatizador para sala de equipaje:
Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
H2.2 28,84 13,71 13 8,9 14,5 8,9
Para el clculo de calefaccin, el punto de impulsin y el de salida de batera se
consideran el mismo. El recalentamiento del aire que se produce en el ventilador de
impulsin se considera una ganancia y por seguridad no se tiene en cuenta. En las
siguientes tablas resumimos para cada zona los valores del punto de impulsin y del
punto de mezcla obtenidos con las expresiones indicadas en este apartado.
Climatizadores para grandes estancias:
Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
H1.16 17,37 7,85 28,76 7,85
H1.37 16,64 7,69 28,8 7,69
H3.01 14,85 7,24 28,34 7,24
H3.02 14,87 7,24 28,34 7,24
Climatizadores para zonas comerciales:
Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
H1.31 16,65 7,69 28,76 7,69
H1.36 16,63 7,68 28,79 7,68
H2.01 14,81 7,23 28,3 7,23
H2.20 16,47 7,62 28,56 7,62
H2.26 15,85 7,47 28,37 7,47
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
56/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
57/271
MEMORIA 57
Climatizador para la zona de trnsito:
Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
Trnsito 16,51 7,63 28,36 7,63
Climatizador para sala de equipaje:
Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)
H2.22 12,81 6,7 27,48 6,7
Balance de caudales.
El balance de caudales obtenido para cada uno de los locales se expresa en las
siguientes tablas. El caudal de extraccin ser el caudal que retornamos desde el
local al climatizador, el caudal de retorno es aquel que extrado del local mezclamos
con el aire exterior y una vez tratado volvemos a impulsar de nuevo al local, el
caudal de expulsin es el aire que retornamos del local y expulsamos al exterior, el
caudal de ventilacin es el calculado en el apartado 1.2.2 y el caudal de impulsin se
ha calculado segn lo indicado en este apartado.
Grandes estancias:
Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)
H1.16 817 752 66 200 952
H1.37 3787 3476 312 930 4406
H3.01 2963 2449 514 960 3409
H3.02 2846 2356 491 920 3276
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
58/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
59/271
MEMORIA 59
Zona VIP:
Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)
H1.28/29 5239 4986 253 470 5456
Sala de prensa:
Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)
H1.30 2869 2653 217 640 3293
Zona de trnsito:
Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)
Trnsito 4305 3726 579 1240 4966
Sala de equipaje:
Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)
H2.22 914 600 315 430 1030
Potencia de refrigeracin.
En las siguientes tablas mostramos los valores de potencia sensible, potencia latente
y la total, que ser el resultado de las suma de ambas potencias. En la ltima columna
se expresa el caudal de agua necesario en la batera de fro.
Grandes estancias:
Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)
H1.16 16313 6923 23236 0,791
H1.37 75558 33051 108609 3,695
H3.01 61181 58758 119939 3,212
H3.02 58758 31844 90602 3,082
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
60/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
61/271
MEMORIA 61
Zona VIP:
Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)
H1.28/29 85858 20551 106409 3,62
Sala de prensa:
Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)
H1.30 55845 22152 77997 2,653
Zona de trnsito:
Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)
Trnsito 87333 42919 130252 4,431
Sala de equipaje:
Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)
H2.22-equipaje 20060 14883 34943 1,189
Potencia de calefaccin.
Los valores obtenidos para la potencia necesaria en la batera de calor se resumen en
las siguientes tablas para cada una de las zonas, en la ltima columna se indica el
caudal de agua necesario en la batera de calefaccin.
Grandes estancias:
Zona P.Total(W) Q.agua(l/s)
H1.16 13329 0,159
H1.37 65884 0,785
H3.01 56580 0,674H3.02 54295 0,647
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
62/271
MEMORIA 62
Zonas comerciales:
Zona P.Total(W) Q.agua(l/s)
H1.31 31117 0,371
H1.36 26177 0,312
H2.26 66688 0,794
H2.01 20513 0,245
H2.20 49113 0,585
Vestbulo de entrada:
Zona P.Total(W) Q.agua(l/s)
Vestbulo1.1 73809 0,879
Vestibulo 3.1 74237 0,884
Vestibulo 2.1 160769 1,914
Vestibulo 2.2 195486 2,328
Sala de tripulaciones:
Zona P.Total(W) Q.agua(l/s)
H1.23 22322 0,266
Zona de equipaje:
Zona P.Total(W) Q.agua(l/s)
Sector 1.1 227945 2,71
Aduana:
Zona P.Total(W) Q.agua(l/s)
H2.02 22322 0,266
Zona VIP:
Zona P.Total(W) Q.agua(l/s)
H1.28/29 65605 0,782
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
63/271
MEMORIA 63
Sala de prensa:
Zona P.Total(W) Q.agua(l/s)
H1.30 48582 0,579
Zona de trnsito:
Zona P.Total(W) Q.agua(l/s)
Trnsito 72396 0,862
Sala de equipaje:
Zona P.Total(W) Q.agua(l/s)
H2.22 18579 0,222
1.2.3.2 CLCULO DE CLIMATIZADORES DE AIRE PRIMARIO.
Para aquellas zonas de oficinas y comerciales en las que vamos a emplear Fan Coil
ser necesario contar con un equipo que pueda aportar el aire de ventilacin
necesario para el local. En aquellos locales en los que hemos puesto unidades
horizontales con mueble y que tienen amplias ventanas que dan al interior de las
grandes zonas del hall de entrada y zona de equipajes, no ser necesario impulsar aire
de ventilacin. Se han calculado cinco climatizadores que impulsarn el aire a todos
los locales en los que se han empleado unidades verticales ocultas de Fan Coils.
Estos climatizadores no tendrn ventilador de retorno, todo el aire que se extraiga del
local ser por tanto expulsado al exterior. A continuacin exponemos como se ha
realizado el clculo de estos equipos.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
64/271
MEMORIA 64
Potencia de refrigeracin:
En este caso no tenemos punto de mezcla ya que hemos eliminado el ventilador de
retorno y todo el aire que impulsamos a la habitacin procede del exterior. El punto
por tanto antes de entrar a la batera de fro ser de 34 C, es decir las condiciones
externas que tenemos para verano en Madrid. Como queremos que la temperatura del
punto de impulsin sea para todo el ao de 22 C, la temperatura a la salida en la
batera de fro ser de 20,5 C, considerando un incremento de temperatura de 1,5 C
en el ventilador de impulsin.
El caudal que tenemos que considerar es el de ventilacin calculado en el apartado
1.2.2 y ser el resultado de la suma de todos los caudales de ventilacin de los
locales que vamos a tratar con el mismo climatizador.
La potencia latente ser nula ya que si miramos en el diagrama psicromtrico, al
movernos desde las condiciones exteriores hasta 22 C no le da tiempo a condensar al
aire.
La potencia se obtiene de la siguiente expresin:
LST
L
VS
PPP
P
QP
+=
=
=
0
)5,12236(23,1
Para el clculo del caudal de agua necesario en la batera de fro del climatizador de
aire exterior se considerar la potencia total de refrigeracin. La temperatura de
entrada del agua (Te) ser de 7 C, mientras que la temperatura de salida del agua
(Ts) ser de 14 C. El caudal se obtiene despejando de la siguiente expresin:
)()/(2,4)( TeTsslQkWPT =
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
65/271
MEMORIA 65
Potencia de calefaccin:
Para el clculo de la potencia necesaria para la batera de calor tampoco existe punto
de mezcla, ya que no retornamos el aire de la habitacin. Por tanto la temperatura
antes de la entrada a la batera es la del exterior, que para Madrid en invierno son -3
C. la temperatura de impulsin ser de nuevo 22 C y coincidir con la temperatura
a la salida de la batera, ya que el incremento de temperatura que se produce en el
ventilador favorece a combatir la carga y no se considera por seguridad.
Los caudales de ventilacin ser la suma de todos los caudales de ventilacin de los
locales a tratar con el mismo climatizador.
La potencia se obtiene de la siguiente expresin:
)022(23,1 = VQP
Para el clculo del caudal de agua necesario en la batera de calor del climatizador de
aire exterior se considerar la potencia de calefaccin. La temperatura de entrada del
agua (Te) ser de 85 C, mientras que la temperatura de salida del agua (Ts) ser de
65 C. El caudal se obtiene despejando de la siguiente expresin:
)()/(2,4)( TsTeslQkWP =
Resultados.
Para el balance de caudales, al no considerar ventilador de retorno el caudal de
retorno ser nulo. Sin embargo si ser necesario disponer de un ventilador que ir
separado del climatizador y que servir para realizar la extraccin de aire del local, el
caudal de extraccin ser un 80 por ciento del caudal de ventilacin. Para este caso
los caudales de ventilacin y de impulsin son el mismo. A continuacin exponemos
una tabla con los resultados:
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
66/271
MEMORIA 66
Equipo Extraccin(l/s) Retorno(l/s)
Expulsin(l/s)
Ventilacin(l/s)
Impulsin(l/s)
Equipo 0.1 640 0 640 800 800Equipo 0.2 1376 0 1376 1720 1720
Equipo 0.3 1288 0 1288 1610 1610
Equipo 0.4 896 0 896 1120 1120
La potencia que necesitamos para la batera de fro y el caudal de agua necesario para
la misma se expone en la siguiente tabla:
Equipo P.Sensible(W) P.Latente(W) P.Total(W)Equipo 0.1 10332 0 10332
Equipo 0.2 22214 0 22214
Equipo 0.3 20794 0 20794
Equipo 0.4 14465 0 14465
La potencia necesaria para la batera de calor y el caudal de agua necesaria para la
misma se expone en la siguiente tabla:
Equipo P.Total(W) Q.Agua(l/s)Equipo 0.4 30308 0,361
Equipo 0.1 21648 0,258
Equipo 0.2 46544 0,555
Equipo 0.3 43567 0,519
1.2.3.3 CLCULO DE FAN COILS.
Las oficinas y zonas comerciales del aeropuerto en la que no se ha empleado un
climatizador ser necesario la utilizacin de Fan-Coil para combatir la carga del
local.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
67/271
MEMORIA 67
Seleccin de los equipos:
Para realizar su seleccin se ha comprobado que los modelos elegidos pueden
cumplir con las necesidades tanto de verano como de invierno que requiere nuestro
local.
En algunas oficinas, que situados en el interior del aeropuerto, es decir que sus muros
no dan al exterior, la carga de invierno se ha considerado despreciable. En funcin de
que consideremos o no la carga de invierno los modelos sern de cuatro tubos o de
dos tubos.
Para pequeas oficinas, en su mayora ocupadas por una nica persona, se han
dispuesto unidades verticales con mueble, mientras que en oficinas ms grandes y
locales comerciales se han empleado unidades horizontales ocultas.
Los modelos seleccionados de catlogo han sido los siguientes:
42N 16-25-33-43-50
42JW 005-009-016
Las unidades verticales con mueble y parte de las unidades horizontales ocultas
pertenecen al modelo 42N, cuya capacidad frigorfica y calorfica nominal ser
menor que para los modelos 42JW. Todos las unidades del modelo 42JW ser
unidades horizontales ocultas.
Para los modelos 42N las capacidades frigorficas y calorficas sern las siguientes:
Capacidad frigorfica nominal 1,4 7,3 kW
Capacidad calorfica nominal 2,0 9,8 kW
Para los modelos 42JW las capacidades frigorficas y calorficas sern las siguientes:
Capacidad frigorfica nominal 3 16 kW
Capacidad calorfica nominal 4 18,5 kW
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
68/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
69/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
70/271
MEMORIA 70
Polica Nacional:
Zona modelo Fan-Coil
H3.22 42N 25 Unidad vertical con mueble(4tubos)H3.23 42N 25 Unidad vertical con mueble(4tubos)H3.24 42N 25 Unidad vertical con mueble(4tubos)H3.25 42N 25 Unidad vertical con mueble(4tubos)H3.26 42N 25 Unidad vertical con mueble(4tubos)H3.27 42N 25 Unidad vertical con mueble(4tubos)H3.28 42N 25 Unidad vertical con mueble(4tubos)H3.29 42N 25 Unidad vertical con mueble(4tubos)H3.30 42N 25 Unidad vertical con mueble(4tubos)H3.31 42N 33 Unidad vertical con mueble(4tubos)H3.32 42JW 009 unidad horizontal oculta(4tubos)H3.33 42N 43 unidad horizontal oculta(4tubos)H3.34 42N 25 Unidad vertical con mueble(4tubos)H3.35 42N 33 Unidad vertical con mueble(4tubos)H3.36 42N 25 Unidad vertical con mueble(4tubos)
Caractersticas de los Fan-Coils:
Los equipos se han seleccionado un ventilador centrfugo y que trabaja a velocidad
media. Para el modo de refrigeracin la temperatura de entrada del agua ser de 7 C
y para calefaccin de 50 C, en ambos casos el incremento de temperatura ser de 5
C. En ningn caso ser necesario el empleo de glicol en la instalacin.
Para el clculo del caudal de agua necesario en las bateras de fro y de calor de los
equipos se considerar la potencia total frigorfica y la potencia de calefaccin. La
temperatura de entrada del agua (Te) ser de 7 C en verano y 50 en invierno,
mientras que la temperatura de salida del agua (Ts) ser de 12 C en verano y 45 en
invierno. Los caudales para verano e invierno se obtienen despejando de las
siguientes expresiones:
)()/(2,4)(
)()/(2,4)(
TsTeslQkWPInvierno
TeTsslQkWPVerano
=
=
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
71/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
72/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
73/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
74/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
75/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
76/271
MEMORIA 76
H1.17 ADLQ 4 400 400 5H1.20 ADLQ 4 400 400 5
H1.26 ADLQ 4 400 400 5H1.32 ADLQ 4 400 400 5H1.33 ADLQ 4 400 400 5H1.34 ADLQ 4 400 400 5H1.35 ADLQ 2 400 400 5H2.03 ADLQ 4 400 400 5H2.04 ADLQ 4 400 400 5H2.05 ADLQ 2 400 400 5H2.12 ADLQ 2 400 400 5H2.17 ADLQ 2 400 400 5H2.18 ADLQ 4 400 400 5
H2.19-aduana ADLQ 4 600 500 12H2.21 ADLQ 4 400 400 5H2.25 ADLQ 4 400 400 5H3.03 ADLQ 4 400 400 5
H3.04-policia ADLQ 6 400 400 5H3.05-policia ADLQ 4 600 500 12H3.06-policia ADLQ 4 400 400 5H3.09-policia ADLQ 4 400 400 5H3.10-policia ADLQ 4 400 400 5
H3.11 ADLQ 2 400 400 5H3.13 ADLQ 4 400 400 5H3.16 ADLQ 4 400 400 5H3.18 ADLQ 4 400 400 5H3.20 ADLQ 4 400 400 5H3.21 ADLQ 4 400 400 5
H3.32-policianacional ADLQ 4 400 400 5
H3.33-policianacional ADLQ 2 400 400 5H3.45 ADLQ 4 400 400 5H3.46 ADLQ 4 400 400 5H3.47 ADLQ 6 400 400 5H3.48 ADLQ 4 600 500 12
H3.50-handling ADLQ 4 400 400 5H3.51 ADLQ 6 400 400 5H3.52 ADLQ 4 400 400 5H3.55 ADLQ 2 400 400 5H3.56 ADLQ 4 400 400 5H3.57 ADLQ 6 400 400 5
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
77/271
MEMORIA 77
1.2.3.5 CONDUCTOS DE IMPULSIN.
Los conductos de impulsin son los que van llevar el aire desde el climatizador hasta
el local. El conducto lleva el caudal de impulsin calculado para cada climatizador
en el apartado 1.2.3.1, en el caso de los climatizadores de aire primario el caudal de
impulsin ser el mismo que el caudal de ventilacin y se han calculado en el
apartado 1.2.3.2.
Los conductos se han diseado mediante tablas, para las que conocido el caudal de
impulsin podemos conocer la velocidad, la prdida de carga por metro lineal en el
conducto y el dimetro del conducto. Se han diseado para que trabajen a media
velocidad y teniendo en cuenta que la velocidad nunca sea superior a 10 m/s y para
que la prdida de carga por metro lineal de conducto no sea superior a 1,2 Pa/m. Una
vez que tenemos el dimetro del conducto, hemos empleado otra tabla para el clculo
del conducto rectangular equivalente.
Para el clculo de la prdida de carga en el conducto que nos permita disear el
ventilador empleado en el climatizador, hemos empleado un programa de clculo en
Excel. La prdida de carga se calcula para el tramo ms desfavorable, que ser aquel
que termine en el punto ms alejado del climatizador.
En las siguientes tablas damos los valores de caudal, seccin rectangular del
conducto, dimetro equivalente, longitud del tramo, velocidad, prdida de carga por
metro lineal y el sumatoria de la prdida de carga dada por el programa de clculo en
Excel, que considera la prdida que se produce en los codos y por metro lineal de
conducto.
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
78/271
MEMORIA 78
Conducto impulsin 001:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
45123 12534 1500 900 6,29 9,29 0,61 56,89
40122 11145 1300 900 6,29 9,53 0,69 61,19
35122 9756 1300 800 6,29 9,39 0,73 65,74
30122 8367 1100 800 6,29 9,51 0,81 70,8
25121 6978 1100 700 6,29 9,07 0,81 75,88
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,81
5120 1422 500 400 6,29 7,11 1,13 100,91119 33 350 300 3,23 0,32 0,01 100,95
Perdida de carga en el difusor 5
Total 106
Conducto impulsin 002:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
45123 12534 1500 900 6,29 9,29 0,61 56,89
40122 11145 1300 900 6,29 9,53 0,69 61,19
35122 9756 1300 800 6,29 9,39 0,73 65,74
30122 8367 1100 800 6,29 9,51 0,81 70,8
25121 6978 1100 700 6,29 9,07 0,81 75,88
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,81
5120 1422 500 400 6,29 7,11 1,13 100,91
119 33 350 300 3,23 0,32 0,01 100,95
Perdida de carga en el difusor 5
Total 106
Conducto impulsin 003:
Seccin
Q(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
79/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
80/271
MEMORIA 80
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,815120 1422 500 400 6,29 7,11 1,13 100,91
119 33 350 300 3,23 0,32 0,01 100,95
Perdida de carga en el difusor 5
Total 106
Conducto impulsin 006:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
45123 12534 1500 900 6,29 9,29 0,61 56,89
40122 11145 1300 900 6,29 9,53 0,69 61,19
35122 9756 1300 800 6,29 9,39 0,73 65,74
30122 8367 1100 800 6,29 9,51 0,81 70,8
25121 6978 1100 700 6,29 9,07 0,81 75,88
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,81
5120 1422 500 400 6,29 7,11 1,13 100,91
119 33 350 300 3,23 0,32 0,01 100,95
Perdida de carga en el difusor 5
Total 106
Conducto impulsin 007:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
45123 12534 1500 900 6,29 9,29 0,61 56,89
40122 11145 1300 900 6,29 9,53 0,69 61,19
35122 9756 1300 800 6,29 9,39 0,73 65,74
30122 8367 1100 800 6,29 9,51 0,81 70,8
25121 6978 1100 700 6,29 9,07 0,81 75,88
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,81
5120 1422 500 400 6,29 7,11 1,13 100,91119 33 350 300 3,23 0,32 0,01 100,95
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
81/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
82/271
MEMORIA 82
Perdida de carga en el difusor 5
Total 106
Conducto impulsin 010:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
45123 12534 1500 900 6,29 9,29 0,61 56,89
40122 11145 1300 900 6,29 9,53 0,69 61,19
35122 9756 1300 800 6,29 9,39 0,73 65,74
30122 8367 1100 800 6,29 9,51 0,81 70,8
25121 6978 1100 700 6,29 9,07 0,81 75,88
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,81
5120 1422 500 400 6,29 7,11 1,13 100,91
119 33 350 300 3,23 0,32 0,01 100,95
Perdida de carga en el difusor 5
Total 106
Conducto impulsin 011:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06
45123 12534 1500 900 6,29 9,29 0,61 56,89
40122 11145 1300 900 6,29 9,53 0,69 61,19
35122 9756 1300 800 6,29 9,39 0,73 65,7430122 8367 1100 800 6,29 9,51 0,81 70,8
25121 6978 1100 700 6,29 9,07 0,81 75,88
20121 5589 1000 600 6,29 9,32 1 82,16
15120 4200 800 600 6,29 8,75 0,99 88,37
10120 2811 750 500 6,29 7,5 0,87 93,81
5120 1422 500 400 6,29 7,11 1,13 100,91
119 33 350 300 3,23 0,32 0,01 100,95
Perdida de carga en el difusor 5
Total 106
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
83/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
84/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
85/271
MEMORIA 85
20121 5589 1000 600 5,95 9,32 1 80,3
15120 4200 800 600 5,95 8,75 0,99 86,18
10120 2811 750 500 5,95 7,5 0,87 91,325120 1422 500 400 5,95 7,11 1,13 98,04
119 33 350 300 7,43 0,32 0,01 98,11
Perdida de carga en el difusor 5
Total 104
Conducto impulsin 017:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 9,5 9,29 0,57 52,78
45123 12534 1500 900 5,95 9,29 0,61 56,4
40122 11145 1300 900 5,95 9,53 0,69 60,47
35122 9756 1300 800 5,95 9,39 0,73 64,77
30122 8367 1100 800 5,95 9,51 0,81 69,56
25121 6978 1100 700 5,95 9,07 0,81 74,37
20121 5589 1000 600 5,95 9,32 1 80,3
15120 4200 800 600 5,95 8,75 0,99 86,18
10120 2811 750 500 5,95 7,5 0,87 91,32
5120 1422 500 400 5,95 7,11 1,13 98,04
119 33 350 300 7,43 0,32 0,01 98,11
Perdida de carga en el difusor 5
Total 104
Conducto impulsin 018:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)
50123 13923 1500 1000 9,5 9,29 0,57 52,7845123 12534 1500 900 5,95 9,29 0,61 56,4
40122 11145 1300 900 5,95 9,53 0,69 60,47
35122 9756 1300 800 5,95 9,39 0,73 64,77
30122 8367 1100 800 5,95 9,51 0,81 69,56
25121 6978 1100 700 5,95 9,07 0,81 74,37
20121 5589 1000 600 5,95 9,32 1 80,3
15120 4200 800 600 5,95 8,75 0,99 86,18
10120 2811 750 500 5,95 7,5 0,87 91,32
5120 1422 500 400 5,95 7,11 1,13 98,04
119 33 350 300 7,43 0,32 0,01 98,11
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
86/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
87/271
MEMORIA 87
Conducto impulsin 021:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)
3428 952 500 350 6,85 5,44 0,75 21,42
2427 674 400 350 6,85 4,82 0,68 26,03
1430 397 350 300 6,85 3,79 0,52 29,54
429 119 300 200 5,95 1,99 0,23 30,9
Perdida de carga en el difusor 9
Total 40
Conducto impulsin 022:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)
5566 1546 500 350 8,23 8,84 1,98 59,22
4565 1268 450 350 5,53 8,06 1,79 69,07
3564 990 450 300 5,53 7,34 1,74 78,65
2564 712 400 250 5,53 7,12 2,3 91,33
1563 434 400 200 5,53 5,43 7,84 134,66
562 156 300 200 5,53 2,6 2 145,7262 17 250 200 3,7 0,34 0,04 145,89
Perdida de carga en el difusor 5
Total 151
Conducto impulsin 023:
Seccin
Q(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)19642 5456 900 650 34,32 9,33 1 129,81
15646 4346 800 600 2,24 9,06 1,06 154,73
11650 3236 700 500 5,8 9,25 1,34 162,46
7654 2126 600 400 5,8 8,86 1,56 171,5
3658 1016 500 300 5,8 6,78 1,27 178,85
1660 461 400 250 6,73 4,61 0,79 189,99
Perdida de carga en el difusor 24
Total 214
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
88/271
MEMORIA 88
Conducto impulsin 024:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)11852 3292 750 500 3,11 8,78 1,17 46,05
7852 2181 650 450 5,88 7,46 1 67,18
3852 1070 500 350 5,88 6,12 0,94 72,67
1854 515 400 250 6,73 5,15 0,97 79,18
Perdida de carga en el difusor 31
Total 111
Conducto impulsin 025:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)
7521 2089 700 400 3,31 7,47 1,05 34,11
5922 1645 600 400 4,33 6,86 0,96 38,26
4324 1201 550 350 4,33 6,24 0,93 42,26
2726 757 500 350 4,33 4,33 0,49 44,38
1127 313 450 300 4,33 2,32 0,19 45,17
328 91 400 250 4,85 0,91 0,05 45,6
Perdida de carga en el difusor 5
Total 51
Conducto impulsin 026:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)
6304 1751 600 400 2,85 7,3 1,08 32,385303 1473 550 400 4,29 6,7 0,96 36,49
4302 1195 500 350 4,29 6,83 1,15 41,41
3302 917 450 350 4,29 5,83 0,9 45,26
2301 639 400 300 4,29 5,33 0,91 49,13
1300 361 400 250 1,79 3,61 0,51 50,03
299 83 300 200 3,7 1,39 0,12 50,99
Perdida de carga en el difusor 5
Total 56
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
89/271
MEMORIA 89
Conducto impulsin 027:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)20344 5651 900 650 10 9,66 1,21 63,38
16240 4511 900 550 12,58 9,12 1,21 78,53
12136 3371 800 500 12,58 8,43 1,17 93,25
8032 2231 700 450 12,58 7,09 0,96 105,27
3928 1091 500 400 12,6 5,46 0,73 114,46
1876 521 400 250 3,3 5,21 1,05 125,37
Perdida de carga en el difusor 31
Total 157
Conducto impulsin 028:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)15862 4406 700 650 7,11 9,69 1,23 60,3
6250 1736 500 450 19,51 7,72 1,22 100,45
3046 846 450 300 7,12 6,27 1,16 108,65
1444 401 400 250 2,87 4,01 0,61 114,82
Perdida de carga en el difusor 24
Total 139
Conducto impulsin 029:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)
33974 9437 1200 800 9 9,84 0,83 60,5830568 8491 1100 800 6,29 9,65 0,83 65,79
27162 7545 1100 750 6,29 9,15 0,79 70,71
23757 6599 1100 650 6,29 9,23 0,89 76,27
20351 5653 900 700 6,29 8,98 0,88 81,78
16946 4707 800 650 6,29 9,06 1 88,05
13540 3761 750 550 6,29 9,12 1,18 95,42
10134 2815 650 550 6,29 7,88 0,96 101,45
6729 1869 600 450 6,29 6,93 0,9 107,1
3323 923 500 300 6,29 6,16 1,06 113,75
1620 450 450 200 3,66 5 1,05 124,45
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
90/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
91/271
MEMORIA 91
Perdida de carga en el difusor 24
Total 112
Conducto impulsin 033:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)11884 3301 700 550 27,09 8,58 1,09 150,68
9479 2633 700 500 3,68 7,53 0,91 154
7074 1965 650 400 10,83 7,56 1,07 165,54
4670 1297 600 350 10,83 6,18 0,84 174,53
2265 629 500 350 10,83 3,6 0,32 177,94
1062 295 400 200 2,87 3,69 0,56 183,28
Perdida de carga en el difusor 12
Total 196
Conducto impulsin 034:
SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)44000 12222 1400 900 9 9,7 0,69 57,94
39600 11000 1300 850 6,29 9,96 0,78 62,81
35201 9778 1200 850 6,29 9,59 0,75 67,53
30802 8556 1100 800 6,29 9,73 0,84 72,81
26403 7334 1000 750 6,29 9,78 0,94 78,6722004 6112 900 700 6,29 9,71 1,02 85,06
17604 4890 850 650 6,29 8,86 0,93 90,88
13205 3668 800 600 6,29 7,65 0,77 95,69
8806 2446 750 500 6,29 6,53 5,03 127,3
4407 1224 600 400 6,29 5,1 3,85 151,46
8 2 400 200 3,13 0,03 0,01 151,46
Perdida de carga en el difusor 5
Total 157
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
92/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
93/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
94/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
95/271
MEMORIA 95
2268 630 450 300 33,17 4,67 0,6 112,35
1440 400 400 250 19,5 4 0,52 126,79
540 150 250 150 17,74 4 0,85 146,23324 90 200 150 47,5 3 0,53 178,45
144 40 200 125 4,45 1,6 0,17 179,19
72 20 150 125 5,98 1,07 0,09 180,01
Conducto impulsin equipo 0.4:
Seccin
Q(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)4752 1320 500 350 11,45 7,55 1,39 31,52
4464 1240 500 350 6,62 7,09 1,24 39,66
4356 1210 500 350 3,34 6,92 1,18 43,59
3600 1000 450 350 31,55 6,35 1,06 88,04
3456 960 450 350 5,72 6,1 0,98 93,64
3312 920 450 350 6,32 5,85 0,91 99,35
3060 850 450 350 25,06 5,4 0,78 118,89
2988 830 450 300 44,27 6,15 1,12 178,47
2592 720 450 300 24,52 5,34 0,86 207,17
1584 440 350 250 15,53 5,03 0,99 222,51
1332 370 300 250 2,59 4,94 1,04 231,891116 310 300 250 48,35 4,14 0,75 282,05
900 250 300 250 5,33 3,34 0,5 284,7
828 230 300 200 5,49 3,84 0,76 292,89
1.2.3.6 REJILLAS DE RETORNO.
El modelo de rejillas seleccionadas para extraer el aire del local son la serie AT, con
un rango de caudales de 100 a 6000 m3/h. La colocacin de las rejillas se har de
forma que el conducto de retorno tenga la menor perdida de carga posible, las rejillas
no tendrn que estar distribuidas de forma simtrica en el local.
Para cada local cuya carga se combate con un climatizador se han seleccionado un
nmero de rejillas en funcin del caudal de extraccin, las rejillas seleccionadas para
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
96/271
MEMORIA 96
la extraccin del aire con sus caractersticas, tamao, caudal de aire, prdida de carga
y nivel de potencia sonora se indican en la siguiente tabla.
Zona Modelo n Rejillas Q(m3/h) H L P(A)
H1.16 AT 3 1000 325 525 4
H1.37 AT 7 2000 325 825 6
H3.01 AT 5 2200 325 825 8
H3.02 AT 5 2200 325 825 8
Trnsito AT 10 1600 325 625 7
H1.31 AT 5 1400 325 625 5
H1.36 AT 5 1200 325 525 6
H2.26 AT 5 2800 425 625 10
H2.01 AT 4 1000 325 525 4
H2.20- AT 5 2200 325 825 8
H2.02 AT 5 1000 325 525 4H2.22 AT 3 1100 325 525 5
H1.23 AT 5 1000 325 525 4
Vestbulo1.1 AT 10 2000 325 825 6
Vestibulo 3.1 AT 7 2000 325 825 6
Vestibulo 2.1 AT 20 1600 325 625 7
Vestibulo 2.2 AT 20 2000 325 825 6
H1.28/29 AT 10 2000 325 825 6
H1.30 AT 10 1100 325 525 5
Sector 1.1 AT 20 2250 425 625 8
Sector 1.2 AT 20 2250 425 625 8
Sector 1.3 AT 20 2250 425 625 8
Sector 1.4 AT 20 2250 425 625 8
En los locales que estn climatizados por Fan Coil hemos colocado una rejilla en el
falso techo, lo ms cerca posible del equipo, para que el Fan Coil pueda tomar el aire
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
97/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
98/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
99/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
100/271
MEMORIA 100
4335 1204 500 400 488 6,44 0,84 0,84 158,17
2085 579 300 300 328 6,86 1,53 1,53 176,02
Perdida de carga en la rejilla de retorno (Pa) 5
Total 181
Conducto retorno 002:
SeccinQ(m3/h) Q(l/s) A B (m) L(m) V(m/s) P/m(Pa/m) P(Pa)44835 12454 1400 900 1.220 4,35 10,66 0,72 65,6
22335 6204 1200 650 954 10,43 8,68 0,66 93,14
20085 5579 1100 600 878 9,87 9,22 0,81 101,12
17835 4954 1100 600 878 10,59 8,19 0,65 107,95
15585 4329 1000 500 762 9,55 9,5 1,02 117,64
13335 3704 800 500 687 9,52 10 1,27 129,71
11085 3079 800 500 687 8,27 8,31 0,9 137,09
8835 2454 600 500 598 8,92 8,74 1,17 147,45
6585 1829 600 450 567 7,25 0,87 0,87 152,91
4335 1204 500 400 488 6,44 0,84 0,84 158,17
2085 579 300 300 328 6,86 1,53 1,53 176,02
Perdida de carga en la rejilla de retorno (Pa) 5
Total 181
Conducto retorno 003:
SeccinQ(m3/h) Q(l/s) A B (m) L(m) V(m/s) P/m(Pa/m) P(Pa)44835 12454 1400 900 1.220 4,35 10,66 0,72 65,6
22335 6204 1200 650 954 10,43 8,68 0,66 93,1420085 5579 1100 600 878 9,87 9,22 0,81 101,12
17835 4954 1100 600 878 10,59 8,19 0,65 107,95
15585 4329 1000 500 762 9,55 9,5 1,02 117,64
13335 3704 800 500 687 9,52 10 1,27 129,71
11085 3079 800 500 687 8,27 8,31 0,9 137,09
8835 2454 600 500 598 8,92 8,74 1,17 147,45
6585 1829 600 450 567 7,25 0,87 0,87 152,91
4335 1204 500 400 488 6,44 0,84 0,84 158,17
2085 579 300 300 328 6,86 1,53 1,53 176,02
Perdida de carga en la rejilla de retorno (Pa) 5
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
101/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
102/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
103/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
104/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
105/271
-
7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL
106/271
MEMORIA 106
Perdida de carga en la rejilla de retorno (Pa) 5
Total 181
Conducto retorno 015:
SeccinQ(m3/h) Q(l/s) A B (m) L(m) V(m/s) P/m(Pa/m) P(Pa)44835 12454 1400 900 1.220 4,35 10,66 0,72 6