CRB ANIMAL AREA RENOVATION -ACTIVATION PACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MD ANDERSON CANCER CENTER
ArchitectPerkins + Will1001 McKinney, Ste1300Houston, TX 77022P: 713.366.4000F: 713.528.3339
MEP EngineerShah Smith & Associates2825 Wilcrest, Suite 350Houston, TX 77042P: 713.780.7563F: 713.780.9209
MDACC PROJECT NO. 12-0545.1
INDEX OF DRAWINGS - ACTIVATION PACKAGE
SHEETNUMBER SHEET NAME
ACTIVATION PACKAGE - ISSUED FORBIDDING AND CONSTRUCTION
04-Architectural - ACTIVATION PACKAGE
000 COVER SHEET ●
A04-01 FLOOR PLANS - BASEMENT LEVEL AREA A, BA & CA ●
A00-50 DOOR SCHEDULE AND DETAILS ●
07-Mechanical
M11-01 MECHANICAL LEGENDS, GENERAL NOTES AND SCHEDULES ●
M11-02 ENLARGED BASEMENT LEVEL AREA A-C ●
M11-03 ENLARGED BASEMENT LEVEL PIPING AREA A-C ●
M11-04 MECHANICAL CONTROLS ●
M11-05 MECHANICAL DETAILS ●
10-Electrical
E00-03 ELECTRICAL LEGEND SYMBOLS AND ABBREVIATIONS ●
E03-15 POWER PLAN - BASEMENT LEVEL B-A ●
E07-07 PANEL SCHEDULES ●
48"
48"
1 2
A
B
C
D
F
4 5 6 7
8 9 10 11
PROCEDURETB.3917A
PROC./HOLDINGTB.3911
PROC./HOLDINGTB.3907
STORAGETB.3885
CHANGINGROOMTB.3887
JANITORTB.3904
PROC./HOLD.TB.3906
ANIMALHOLDINGTB.3876
ANIMALHOLDINGTB.4271
I.P.CLINICTB.4262
O.R.PREPTB.4258
O.R.PREPTB.4250
PRO./HOLD.TB.3933
PROCEDURE/HOLDINGTB.3935
PROCEDURE/HOLDINGTB.3947
PROCEDURE/HOLDINGTB.3934
PROCEDURE/HOLDINGTB.3938
PROCEDURE/HOLDINGTB.3942
PROCEDURE/HOLDINGTB.4024
ANIMALHOLDING/BEHAVIORAL
TB.3927A
PROC./HOLDINGTB.3893
CLINICAL RESEARCHBUILDING
F.4
E.8
B.4
5.8
CHANGINGROOMTB.3874
QUARANTINETB.3891
3900
3891
3876
3942
4024
PROCEDURETB.3876A
3929
PROCEDURE/HOLDINGTB.4020
PROCEDURETB.4271A
PROC./HOLD.TB.3922
3938
3922
3933
4020 4271
3946
3947
3907 3893
4271A
CORRIDORTB.3929
CORRIDORTB.4228
CORRIDORTB.3846
CORRIDORSB.8470
CORRIDORTB.3953
CORRIDORTB.3900
3935
3939
39113919
PROC./HOLD.TB.3908
VESTIBULETB.3927
PROC./BEHAVIORAL
TB.3927B
3934
3953A
TB.3915
TB.3930
TB.3918 TB.3914TB.4025A
TB.4025
TB.3951 TB.4008
TB.4012
TB.4016
TB.4013
TB.4009 TB.4037 TB.4041 TB.4045A TB.4049 TB.4055D TB.4055E TB.4055C TB.4059A
TB.4246 TB.4242
TB.4255 TB.4247 TB.4241
TB.3872 TB.3868 TB.3868A TB.3860A TB.3860 TB.3856
TB.3863
TB.3857A
TB.3857
TB.3853
TB.3851
TB.3954
ANIMALHOLDINGTB.3919
PROCEDURETB.3919A
ANIMALHOLDINGTB.3917
3927A
3927B
3917
JANITORTB.3926
PROCEDURE/HOLDINGTB.3946
PROCEDURE/HOLDINGTB.3939
3908
WRITE-UPSTATIONTB.3902
TB.3950
CORRIDORTB.4101
3923
CR
WP
TB.3985 TB.3989
TB.3955
TB.3959
TB.3982 TB.3986 TB.3990 TB.4030
TB.4001
TB.4005
1
1
111 1
1
1
1
1
1
1
2
A00-50
1
A00-50
5
WP
WP
3
4
4
4
4
4
4
4
4
4
4
4
4
4 4 4
1
FLOOR PLAN KEYNOTED NOTES FLOOR PLAN LEGEND
EXISTING PARTITION
NOT IN SCOPE
DOOR TAG, RE:A00-5038
10EXISTING CMU PARTITION
EXISTING CONCRETEPARTITION
WP
CR EXISTING CARD READER
WAVE PLATE
1 REMOVE/COVER THE NOW OBSOLETE ROOM STAT REPORTING PANELS. INSTALL METAL CUSTOMBLANK-OFF IN CMU WALLS. PAINT COLOR IS TO MATCH EXISTING PANEL COLOR.
2DEMO EXISTING 90 MIN RATED FLUSH DOORS. DOOR FRAME IS TO REMAIN IN PLACE FOR NEWDOORS. A NEW PAIR OF 90 MIN RATED DOORS THAT INCLUDE DOOR LITES WILL REPLACE THE OLDDOORS. REUSE EXISTING DOOR HARWARE. DOORS ARE TO BE PAINTED TO MATCH EXISTING DOORPAINT COLOR.
3 CHANGE EXISTING CARD READER TO A WAVE PLATE. RE: HARDWARE GROUP NO. 04
WP EXISTING WAVE PLATE
EXISTING ROOM STATREPORTING PANELS4 PLUMBING CONNECTIONS OF THE CASEWORK MOBILE SINKS TO THE UTILITY WALL BOXES NEED TO BE
EXECUTED.
C
14
MICROSURGERYTRAININGTB.4233
4
CORRIDORSB.8470
AIRLOCKSB.8460A
AUTOCLAVEROOMSB.8468
4
KEY PLAN
A B
C D
A-A A-B B-A
A-C A-D
C-A
01/2"
1"2"
Sheet
Title
Approved
Checked
Drawn
Job Number
Date
Sheet Information
Copyright © 2017 Perkins+Will
Revisions
MEP Engineer
Shah Smith & Associates
2825 Wilcrest, Suite 350Houston, TX 77042
t 713.780.7563
f 713.780.9209
15 234
A
D
B
C
15 234
A
D
B
C
MDACC Project# 12-0545.1
4/1
8/2
017 3
:19
:27 P
M
c:\te
mp\ 1
8510
8.0
00_
CR
B V
ivarium
Reno
va
tion_
activation
package_rf
_fe
rnandez.r
vt
A04-01
FLOOR PLANS -BASEMENT LEVELAREA A, BA & CA
DR
RF
185108.000
April 18, 2017
DR
CRB ANIMAL AREARENOVATION -
ACTIVATIONPACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER
ISS
UE
D F
OR
BID
DIN
G A
ND
CO
NS
TR
UC
TIO
N A
pri
l 18, 2017
1001 McKinneySuite 1300
Houston, TX 77002t 713.366.4000f 713.528.3339
www.perkinswill.com
1/8" = 1'-0"1 FLOOR PLAN - CRB BASEMENT LEVEL -A
NORTHTRUE NORTH
3/16" = 1'-0"2 MICROSURGERY ROOM - AREA BA
3/16" = 1'-0"3 AUTOCLAVE - AREA CA
NO ISSUE DATE
LAB-TRAC AIR TERMINAL CONTROL MODES
MARK
GE-BR-B-22
SD-BR-B-22
LAB-TRAC SCHEDULE GENERAL NOTES (APPLY TO ALL ROOMS/EQUIPMENT):
A.
B.
C.
D.
E.
F.
G.
H.
ROOM
SERVED
LARGE ANIMAL HOLDING TB.3950
POSITIVE (+) OFFSET INDICATES FLOW LEAVING LAB/AREA. REFER TO AIR BALANCE DIAGRAM FOR ADDITIONAL INFORMATION.
ALL TERMINALS SHALL BE PROVIDED WITH VAV CONTROL CAPABILITY DESPITE THE CONTROL MODES REQUIRED AS PART OF THIS PROJECT.
ROOM OFFSET APPLIES TO NORMAL OPERATING MODES ONLY.
"-" INDICATES MODE DOES NOT AFFECT ZONE/VALVES. "*" INDICATES FAIL TO LAST POSITION
"MODE 1" AND "MODE 2" ARE CONTROL MODES FOR PHEONIX. MATCH CONTROL MODES TO EXISTING VIVARIUM CONTROL SCHEME.
"SHED 1" SHALL BE WHEN VIVARIUM IS ON STANDBY POWER. THIS SHALL BE THE SAME AS NORMAL OPERATING MODE.
"LOSS OF POWER" SHALL BE LOSS OF ALL POWER (NORMAL AND STANDBY). ALL VALVES SHALL FAIL TO LAST POSITION.
CONTRACTOR SHALL TAB THE PROJECT AT THE NORMAL "MODE 1" SETTING. ADJUST DIFFUSER CFM AS REQUIRED. THIMBLE CONNECTIONS SHALL REMAIN AS SHOWN.
ROOM
CFM
OFFSET
100
ANIMAL HOLDING AND PROCEDURE ROOMS
15 ACH
POSITIVE
15 ACH
NEGATIVE
790
690
10 ACH
POSITIVE
10 ACH
NEGATIVE
525
425
UNOCCUPIED ("MODE 2")
4 ACH
POSITIVE
110
210
OTHER: CONSTANT
CFM
-
-
NORMAL ("MODE 1")
790
690
SHED 1
CFM
790
690
LOSS OF POWER
CFM
*
*
REMARKS
GE
NE
RA
L N
OT
ES
THESE GENERAL NOTES APPLY TO ALL MECHANICAL DRAWINGS.
IN ANY CASE WHERE A PIPE OR DUCT SHOWN ON A PLAN SHEETDIFFERS FROM THAT SHOWN IN A SCHEMATIC OR DETAIL. USETHE LARGER OF THE TWO SIZES SHOWN.
PIPING SHOWN ON EACH PLAN IS RUN ABOVE THE CEILING ONTHE FLOOR WHERE IT IS SHOWN UNLESS OTHERWISE NOTED.
ALL ELEVATIONS INDICATED IN THIS WAY (8'-0") ARE THEELEVATIONS FROM THE FINISHED FLOOR DIRECTLY BELOW TO THEBOTTOM OF THE BARE PIPE OR DUCT.
MOUNT TEMPERATURE AND HUMIDITY SENSORS 44 INCHES ABOVEFINISHED FLOOR AND CENTERED ABOVE THE LIGHT SWITCHESWHERE BOTH OCCUR IN THE SAME LOCATION. UNLESSOTHERWISE NOTED.
PROVIDE FIRE DAMPER, ACCESS DOOR IN ALL DUCTWORKPIERCING FLOORS, AND 2 HOUR FIRE RATED WALLS.
COORDINATE LOCATION OF CEILING DIFFUSERS AND GRILLES WITHLIGHTING. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS.
DUCT RUN-OUTS TO DIFFUSERS SHALL BE THE SAME SIZE ASDIFFUSER NECK SIZE.
SUPPLY DUCT BRANCH TO TERMINAL BOXES SHALL BE SAMESIZE AS BOX INLET SIZE UNLESS OTHERWISE NOTED. REFER TOM09-02.
DUCT SIZE SHOWN ARE NET FREE AIR PASSAGE DIMENSIONS.DUCTS ARE NOT LINED, BUT ARE EXTERNALLY INSULATED.
PROVIDE AIR VENTS AT HIGH POINT OF ALL WATER SYSTEM.
COORDINATE INSTALLATION OF EQUIPMENT AND PIPING WITHELECTRICAL CONTRACTOR TO INSURE NEC CLEARANCE IN FRONTOF ALL ELECTRICAL PANELS.
ARRANGE PIPING CONNECTIONS TO ALL EQUIPMENT TO ALLOWEASY REMOVAL OF EQUIPMENT, COILS, FANS, MOTORS, FILTERS,ACCESS PANELS, ETC. PROVIDE UNIONS, FLANGES AND VALVESAT CONNECTIONS.
REFER TO ARCHITECTS DRAWINGS FOR EXACT LOCATION AND SIZEOF LOUVERS. BLANKOFF AREA OF LOUVERS NOT USED FOROUTSIDE AIR OR EXHAUST.
FVV-1-10[5000]
TERMINAL BOX NOMENCLATURE
TERMINAL BOXTYPE
TERMINAL BOXFLOOR LOCATION
MAXIMUM CFM
BOX NUMBER
LE
GE
ND
DIS
RE
GA
RD
LE
GE
ND
IT
EM
S N
OT
IN
DIC
AT
ED
ON
DR
AW
ING
S
SYMBOL DESCRIPTIONABBREV.
FD/FSD
DESCRIPTIONABBREV.SYMBOL
MVD
VD
SA/OA
RA
EA/REA
D OR DD
OR
10
1
CARBON DIOXIDE SENSOR
N.O.
HUMIDITY SENSOR
DIFFERENTIAL PRESSURE SENSOR
MOTOR STARTER
NORMALLY CLOSED
NORMALLY OPEN
N.C.
VARIABLE FREQUENCY DRIVE
FREEZE STAT
FILTER GAUGE
DIFFERENTIAL PRESSURE SWITCH
AIRFLOW MEASURING STATION
ELECTRICAL SIGNAL
DAMPER OR VALVE ACTUATOR
HIGH PRESSURE SHUT OFF SWITCH
AFMS
NEW WORK
EXISTING WORK
FIRE/FIRE SMOKE DAMPER
RETURN AIR DUCT
SUPPLY/OUTSIDE AIR DUCT
EXHAUST/RELIEF AIR DUCT
ACCESS DOOR
MOTORIZED VOLUME DAMPER
VOLUME DAMPER
SUPPLY AIR DIRECTION
OFFSET AIR QUANTITY (CFM)/EXHAUST/RETURN DIRECTION
TEMPERATURE SENSOR
THERMOSTAT
HUMIDISTAT
SMOKE DUCT DETECTOR
SMOKE DETECTOR
STATIC PRESSURE SENSOR
KEYED NOTE
REVISION TRIANGLE
DENOTES RECTANGULAR DUCTWORK
DENOTES OVAL DUCTWORK
DENOTES ROUND DUCTWORK/PIPING12"
70/22
70/22 O.
VARIABLE FREQUENCY DRIVE
ABOVE FINISHED FLOOR
BOTTOM OF DUCT
AFF
VFD
BOD
FLAT OVAL
(E)/EXIST.
FO
EXISTING
BOP BOTTOM OF PIPE
CAV CONSTANT AIR VOLUME
VARIABLE AIR VOLUMEVAV
C/C COOLING COIL
HEATING COILH/C
CFM CUBIC FEET PER MINUTE
EXHAUST FANEF
EXH EXHAUST
FAN COIL UNITFCU
GPM GALLONS PER MINUTE
NOT TO SCALENTS
SAD SOUND ATTENUATING DEVICE
AFMS AIR FLOW MEASURING STATION
VTR VENT THRU ROOF
DDC DIRECT DIGITAL CONTROL
AIR HANDLING UNITAHU
COMPRESSED AIR
CHS
CWS
CWR
HWS
CHR
CHILLED WATER SUPPLYCHS
CONDENSING WATER RETURN
CONDENSING WATER SUPPLY
CHILLED WATER RETURN
HOT WATER SUPPLY
CWS
CWR
HWS
CHR
THREE-WAY CONTROL VALVE
TWO-WAY CONTROL VALVE
BUTTERFLY VALVE
SOLENOID VALVE
VENTURI FLOW TUBE
THERMOMETER WELL
PLUG VALVE
GAGE COCK
VALVE BOX
CHECK VALVE
GLOBE VALVE
GATE VALVE
BALL VALVE
PRESSURE RELIEF VALVE
# OF STEAM RETURN
# OF STEAM SUPPLY
PRESSURE REDUCING VALVE
HOT WATER RETURN
PRV
STRAINER
ANCHOR
FLEXIBLE JOINT
GAGE
REDUCER
UNION
THERMOMETER
RV
HWR
A
#R
#S
HWR
#S
#R
A
PCR PCR PUMP CONDENSATE RETURN
CR CR CONDENSATE RETURN
HP
DP
VFD
FS
G
P
HS
CO2
S
TS
SP
H HS
T
ES
TEMPORARY WORK
MECHANICAL SYSTEMS INFORMATION
SYSTEMS DESCRIPTION
DESIGN CONDITIONS (FOR HEATING AND COOLING LOAD CALC.)
SUPPLY
EXISTING 100% OUTSIDE ARE HANDLERS WITH AND HUMIDITY CONTROL.
ALL LAB AND ANIMAL SUPPORT AREAS WILL HAVE PHOENIX LAB-TRAC AIRVALVES WITH HEATING HOT WATER COIL FOR EACH ROOM
NEW WORK WILL TIE INTO EXISTING HIGH PLUME DILUTION EXHAUST FANS WITH REDUNDANT CAPACITY.
PHOENIX LAB-TRAC AIR VALVES WILL BE PROVIDED FOR EACH ROOM. ANIMAL HOLDING/PROCEDUREROOMS WILL BE PROVIDED WITH ONE EXHAUST VALVE.
SUMMER OUTSIDE (DEG. F DB/WB)
WINTER OUTSIDE (DEG F)
SUMMER INSIDE:
ANIMAL HOLDING, PROCEDURE
FRESH (OUTSIDE) AIR (OWNER REQ)
96.0 F / 80 F
20.0 F DB
70 F DB / 15 ACH
EXHAUST
WINTER INSIDE (OCCUPIED SPACES) 70 F DB
SMALL ANIMAL VIVARIUM WITH IVCS, OCCUPIED, OPERATION (MINIMUM) 10 AIR CHANGES/HR
SMALL ANIMAL VIVARIUM WITH IVCS, OCCUPIED, DESIGN (MINIMUM) 15 AIR CHANGES/HR
LARGE ANIMAL VIVARIUM, OCCUPIED, DESIGN, OPERATION (MINIMUM) 15 AIR CHANGES/HR
GENERAL NOTES
REFER TO CONTROL MODE SCHEDULES (M-003, AND M-004) FOR FURTHER OPERATING MODE REQUIREMENTS INCLUDING ROOM OFFSETSETPOINTS. ALL PHEONIX AIR VALVES SHALL BE SIZED TO OPERATE AT ALL MODES.
REFER TO SPECIFICATIONS FOR MATERIAL REQUIREMENTS.
MAX. SP. IS THE MAXIMUM ALLOWABLE STATIC PRESSURE LOSS THROUGH THE AIR VALVE AND COIL AT SCHEDULED MAXIMUM COIL CFM.
DIVISION 26 WILL PROVIDE 120/1PH POWER AT EACH PHEONIX LAB ROOM CONTROLLER (LRC) CONTROL PANEL. LRC IN SEPARATE PANELENCLOSURE SHALL BE LOCATED ADJACENT TO LS TERMINAL UNIT. DIVISION 23 TO PROVIDE TRANSFORMER AS REQUIRED FOR CONTROLSPOWER. PROVIDE CONTROL POWER TO EACH AIR VALVE AS REQUIRED FROM THE LAB ROOM CONTROLLER.
ALL AIR VALVES SHALL BE MEDIUM PRESSURE AIR VALVES.
A.
B.
C.
D.
E.
01/
2"1"
2"
TA
S
E OF TEXAS
P RE
ENI
GNELANOISS
FO
R
EL IC E N S E D
T
JON HARPER
115708
Tx. Registration # F-2113
Sheet
Title
Approved
Checked
Drawn
Job Number
Date
Sheet Information
Copyright © 2015 Perkins+Will
Revisions
15 234
A
D
B
C
15 234
A
D
B
C
185108.000
MEP Engineer
Shah Smith & Associates
2825 Wilcrest, Suite 350Houston, TX 77042
t 713.780.7563
f 713.780.9209
MDACC Project# 12-0545.1
4/1
8/2
017 1
1:2
1:1
5 A
MC
:\E
ds_cad\P
roje
cts
\Revit_2015\1
111-0
42-0
1_M
echanic
al_
R15_E
Str
iblin
g.r
vt
4/1
8/2
017 1
1:2
1:1
5 A
M
C:\E
ds_cad
\Pro
jects
\Revit_20
15\1
11
1-0
42-0
1_
Mecha
nic
al _
R15_E
Str
iblin
g. r
vt
M11-01
MECHANICALLEGENDS,
GENERAL NOTESAND SCHEDULES
J. HARPER
E. STRIB
April 18, 2017
J. HARPER
ISS
UE
D F
OR
BID
DIN
G A
ND
CO
NS
TR
UC
TIO
N A
pri
l 18, 2017
CRB ANIMAL AREARENOVATION -
ACTIVATIONPACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER
1001 McKinneySuite 1300
Houston, TX 77002t 713.366.4000f 713.528.3339
www.perkinswill.com
MECHANICAL SHEET LIST - ACTIVATION PACKAGESheet
Number Sheet Name
M11-01 MECHANICAL LEGENDS, GENERAL NOTES AND SCHEDULES
M11-02 ENLARGED BASEMENT LEVEL AREA A-C
M11-03 ENLARGED BASEMENT LEVEL PIPING AREA A-C
M11-04 MECHANICAL CONTROLS
M11-05 MECHANICAL DETAILS
Grand total: 5
LAB TRAC SUPPLY AIR TERMINAL BOX SCHEDULE (HEATING WATER) AP
MARK LAB SERVED
CFM RoomOffsetCFM
VALVESIZE
MAXS.P. IN.
WG
HOT WATER COIL
REMARKSMAX MIN CFMEAT(F)
LAT(F) MBH
ENTERINGWATER (F) GPM
MINROWS
GE-BR-B-22 LG ANIMAL HOLDING TB.3950 790 790 100 12 0.6 OWNER FURNISHED CONTRACTOR INSTALLED
SD-BR-B-22 LG ANIMAL HOLDING TB.3950 690 690 100 12 0.7 690 55 80 18.5 130 1.9 2 OWNER FURNISHED CONTRACTOR INSTALLED
NO ISSUE DATE
04-18-2017
1 2
1
LG ANIMAL HOLDING
TB.3950
[790]GE-BR-B-22
DP
[690]SD-BR-B-22
1
KEYED NOTES
REPLACE EXISTING AIR TERMINAL WITH NEWUNIT AS SCHEDULED. MATCH EXISTINGTEMPERATURE SENSOR LOCATION. VALVES AREOWNER FURNISHED CONTRATOR INSTALLED.
1
GENERAL NOTES
A. REFER TO DETAIL SHEET M11-05 FORTERMINAL BOX INSTALLATION.
B. CONTRACTOR SHALL PROVIDE CLEARANCEIN FRONT AND AT SIDES OF TERMINAL BOX UNITCONTROL PANEL AND J-BOX AS REQUIRED BYN.E.C. (36 INCHES).
C. PROVIDE DUCTWORK TRANSITIONS ASREQUIRED AT TERMINAL BOX INLET ANDDISCHARGE CONNECTIONS.
D. INSULATE EXTERIOR OF ALL SUPPLY AIRDUCTWORK AND THE TOP OF ALL SUPPLY AIRDIFFUSERS.
E. PROVIDE YOUNG REGULATORS FOR ALLDAMPERS LOCATED ABOVE INACCESSIBLECEILINGS AND NOT WITHIN THE INTERSTITIALSPACE. YOUNG REGULATORS SHALL BEPROVIDED WITH SOLID SHAFT CONNECTION;CABLE CONNECTION TO REGULATOR WILL NOT BEACCEPTED.
F. ALL AIR VALVES SHALL BE LOCATED TOALLOW FOR ACCESS TO THE CONTROLS PANELAND THE ACTUATOR.
G. CONNECT TEMP SENSOR TO LABCONTROLLER ASSOCIATED WITH EACH SPACE.REFER TO SCHEDULE FOR ASSOCIATED AIRTERMINALS.
H. PIPING AND DUCTWORK ARE NOTPERMITTED IN ELECTRICAL ROOMS, ELEVATORMACHINE ROOMS AND COMMUNICATION ROOMS.
I. EXISTING MEP DRAWINGS ARE TAKEN FROMAS-BUILT DOCUMENTS. DOCUMENTS AREGENERALLY CORRECT, HOWEVER, REVISIONSDUE TO MAINTENANCE AND MINOR RENOVATIONSHAVE OCCURRED AND MAY NOT BE REFLECTEDON THE PLANS. CONTRACTOR TO FIELD VERIFYEXISTING MEP EQUIPMENT AS REQUIRED TOACCOMPLISH WORK.
J. CONNECT NEW HOT WATER COILS TOEXISTING HOT WATER BRANCHES IN INTERSTITIALSPACE. HW PIPE TO BE 3/4" UNLESS OTHERWISENOTED.
01/
2"1"
2"
TN
0'
TA
S
E OF TEXAS
P RE
ENI
GNELANOISS
FO
R
EL IC E N S E D
T
JON HARPER
115708
Tx. Registration # F-2113
1/4" = 1'-0"
4' 8'
KEY PLAN
Sheet
Title
Approved
Checked
Drawn
Job Number
Date
Sheet Information
Copyright © 2015 Perkins+Will
Revisions
15 234
A
D
B
C
15 234
A
D
B
C
185108.000
MEP Engineer
Shah Smith & Associates
2825 Wilcrest, Suite 350Houston, TX 77042
t 713.780.7563
f 713.780.9209
MDACC Project# 12-0545.1
4/1
8/2
017 1
0:3
7:1
4 A
MC
:\E
ds_cad\P
roje
cts
\Revit_2015\1
111-0
42-0
1_M
echanic
al_
R15_E
Str
iblin
g.r
vt
4/1
8/2
017 1
0:3
7:1
4 A
M
C:\E
ds_cad
\Pro
jects
\Revit_20
15\1
11
1-0
42-0
1_
Mecha
nic
al _
R15_E
Str
iblin
g. r
vt
M11-02
ENLARGEDBASEMENT LEVEL
AREA A-C
J. HARPER
E. STRIB
April 18, 2017
J. HARPER
ISS
UE
D F
OR
BID
DIN
G A
ND
CO
NS
TR
UC
TIO
N A
pri
l 18, 2017
CRB ANIMAL AREARENOVATION -
ACTIVATIONPACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER
A-C
1001 McKinneySuite 1300
Houston, TX 77002t 713.366.4000f 713.528.3339
www.perkinswill.com
1/4" = 1'-0"1
ENLARGED BASEMENT LEVEL -AREA A-C
NO ISSUE DATE
04-18-2017
PIPING GENERAL NOTES
A. REFER TO DETAIL SHEET M11-05 FOR 2-WAY CONTROL VALVE CONNECTION PIPING.
B. INSULATE ALL HOT WATER PIPING.
C. INSULATE HOT WATER COIL CASING ATEACH TERMINAL UNIT.
D. PIPING IS NOT PERMITTED ABOVEELECTRICAL AND TELECOMMUNICATIONSROOMS.
C. COORDINATE PIPING WITH CABLE TRAYINSTALLATION IN ALL SPACES. PIPING SHALLNOT INTERFERE WITH ACCESS TO CABLETRAY.
D. PROVIDE REDUCERS IN PIPING AT COILCONNECTIONS AS REQUIRED. TYPICAL AT ALLTERMINAL UNITS.
E. RUN OUTS TO TERMINAL UNITS ARE 3/4"UNLESS OTHERWISE NOTED.
F. CONTRACTOR TO PROVIDECOORDINATION DRAWINGS FOR ABOVECEILING AND INTERSTITIAL INSTALLATIONS OFDUCTWORK, FIRE PROTECTION PIPING,PLUMBING, ELECTRICAL, AND DATA.
G. COORDINATE ROOF, FLOOR, AND WALLPENETRATIONS AND CHASE DIMENSIONS WITHARCHITECTURAL AND STRUCTURAL.
KEYED NOTES
REPLACE PIPING FROM EXISTING ISOLATIONVALVES TO COIL.
1
1 2
PROCEDURE/ HOLDING
TB.3946
LG ANIMAL HOLDING
TB.3950 (1.9)SD-BR-B-22
GE-BR-B-221
01/
2"1"
2"
TN
0'
TA
S
E OF TEXAS
P RE
ENI
GNELANOISS
FO
R
EL IC E N S E D
T
JON HARPER
115708
Tx. Registration # F-2113
1/4" = 1'-0"
4' 8'
KEY PLAN
Sheet
Title
Approved
Checked
Drawn
Job Number
Date
Sheet Information
Copyright © 2015 Perkins+Will
Revisions
15 234
A
D
B
C
15 234
A
D
B
C
185108.000
MEP Engineer
Shah Smith & Associates
2825 Wilcrest, Suite 350Houston, TX 77042
t 713.780.7563
f 713.780.9209
MDACC Project# 12-0545.1
4/1
8/2
017 1
0:3
7:2
1 A
MC
:\E
ds_cad\P
roje
cts
\Revit_2015\1
111-0
42-0
1_M
echanic
al_
R15_E
Str
iblin
g.r
vt
4/1
8/2
017 1
0:3
7:2
1 A
M
C:\E
ds_cad
\Pro
jects
\Revit_20
15\1
11
1-0
42-0
1_
Mecha
nic
al _
R15_E
Str
iblin
g. r
vt
M11-03
ENLARGEDBASEMENT LEVELPIPING AREA A-C
J. HARPER
E. STRIB
April 18, 2017
J. HARPER
ISS
UE
D F
OR
BID
DIN
G A
ND
CO
NS
TR
UC
TIO
N A
pri
l 18, 2017
CRB ANIMAL AREARENOVATION -
ACTIVATIONPACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER
A-C
1001 McKinneySuite 1300
Houston, TX 77002t 713.366.4000f 713.528.3339
www.perkinswill.com
1/4" = 1'-0"1
ENLARGED BASEMENT LEVELPIPING - AREA A-C
NO ISSUE DATE
04-18-2017
C
H
V-X
PXLS-Y-X PXGE-Y-X
TTE-X
SEQUENCE OF OPERATIONINSTALLATION NOTES: indicated by
1. Point summary states points required and do not excludepoints listed/specified elsewhere in the construction documents.
2. All safeties shall be hard-wired. Software interlocks are notacceptable. BAS shall monitor status of safeties as shown.Provide all safeties necessary to protect the equipment fromphysical damage.
3. BAS point names and new and/or modified graphics shall beapproved by owner prior to implementation.
4. Any removal and/or interruption of existing BAS shall bescheduled and coordinated with owner prior to starting.
5. BAS contractor to coordinate with owner for verification ofBAS devices prior to commissioning. Coordinate commissioningwith owner.
6. BAS contractor is responsible for demolition of all physicaldevices and deletion of points and programming from thedatabase.
7. All new or relocated wiring shall have typed relocation tags.Hand written tags are not acceptable.
8. A copy of the final as-built control termination drawing andrelated riser diagram layout shall reside inside of all buildingcontrollers panel enclosures.
9. Mount lab zone controller adjacent to supply valve. Mount onunistrut on hand rail in interstitial or wall mount as appropriate foraccess.
10. All valves shall fail to last position.
11. Coordinate all required points to be monitored by EdstromSystem. This shall be a minimum differential pressure,temperature, and humidity.
POINT DESCRIPTORPOINT NAME
POINT TYPE
DI AI DO AO VP
TYPICAL POINTS LIST
REMARKS
:GEF GENERAL EXHAUST FLOW X
:RT ROOM (ZONE) TEMP XACTUAL ZONE TEMP SET POINT X ACTUAL PHOENIX ZONE TEMP SET POINT FEEDBACK TO SIEMENS
:TSF TOTAL SUP FLOW X SUM OF ALL SUPPLIES:TEF TOTAL EXH FLOW X SUM OF ALL GENERAL
TOTALS 6 10 1 12
:OCC 15 OCC SUPPLY FLOW 15ACH SET POINT XREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TO PHOENIX;SIEMENS SUPERVISORY CONTROL
:UnocMnSAF UNOCC SUPPLY FLOW MIN SET POINT XCFM (RELATED T0 4 ACH); AO FROM SIEMENS TO PHOENIX;SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)
:OccStpt OCC/UNOCC COMMAND SET POINT X SIEMENS SUPERVISORY CONTROL
Control Qty ProductNumber Manufacturer Document DescriptionDevice Number
Field Mounted Devices
BILL OF MATERIAL
PXGE-Y-X 1 EXHAUST AIR VALVE
PXLS-Y-X SUPPLY AIR VALVE WITH REHEAT
TTE-X ROOM (ZONE) TEMPERATURE SENSOR
RTR-X ROUTER/POWER PANEL
V-X SEE CONTROL VALVE SUBMITTAL
NOTES: Y = ROOM NUMBER; X = NUMBER
:OccSta OCC/UNOCC COMMAND STATUS X
OCC COOLING ZONE TEMP SET POINT XOCC HEATING ZONE TEMP SET POINT XUNOCC COOLING ZONE TEMP SET POINT XUNOCC HEATING ZONE TEMP SET POINT X
:SAF SUPPLY AIRFLOW X:SPA STATIC PRESSURE ALARM X:JAM JAM ALARM X:RVA HCLO REHEAT VALVE HEATING COIL LOOPOUT X AI TO SIEMENS FROM PHOENIX
:ROStpt ZONE AIRFLOW OFFSET SET POINT X SIEMENS SUPERVISORY CONTROL:RO ZONE AIRFLOW OFFSET X
NOTE: DI AND AI ARE CONTROL POINTS THAT PHOENIX SENDS VALUES TO SIEMENS. DO AND AO ARE CONTROL POINTS THATSIEMENS SENDS VALUES TO PHOENIX.
The laboratory zone consists of a building automation system that controls venturi-type air valves (supply and general exhaust), and reheat coil valve actuator.
OCCUPIED/UNOCCUPIED MODES:Enable mutiple occupied and unoccupied mode capabilities. SIEMENS shall sendan occupancy mode signal (adjustable) to Phoenix. SIEMENS shall receive fromPhoenix the status of occupancy mode.
SIEMENS shall send signal (adjustable) for minimum occupied supply air flow setpoint to Phoenix system. SIEMENS shall send signal (adjustable) for minimumunoccupied supply air flow set point to Phoenix system.
ZONE AIR CHANGE PER HOUR RATE CONTROL:The Lab Zone Controller (LZC) receives the general exhaust CFM value from thegeneral exhaust air valve(s). The LZC total zone exhaust CFM is the zone generalexhaust CFM. Using a proportional, integral, and derivative (PID) closed loopcontrol algorithm, the LZC modulates the zone supply and general exhaust airvalves to ensure that the zone does not go below the minimum required zone airchanges per hour (ACH) rate (occupied and unoccupied).
ZONE PRESSURIZATION CONTROL:The total exhaust air volume and the total supply air volume for the zone ismonitored and controlled to maintain a negative or positive zone airflow offset setpoint (" refer to M-400 series") relative to the exhaust air flow. SIEMENS shallsend the ZONE AIRFLOW OFFSET CFM set point (adjustable) to Phoenix to use.SIEMENS shall receive from Phoenix the actual monitored zone airflow CFMoffset.
The LZC calculates the required ZONE SUPPLY AIR CFM necessary bysubtracting the zone airflow offset CFM set point from the total zone exhaustCFM. The LZC modulates the ZONE SUPPLY AIR CFM using the supply airvalve to ensure that the zone airflow offset CFM (flow tracking differential CFM) isalways maintained by a proportional, integral, and derivative (PID) closed loopcontrol algorithm.
ZONE TEMPERATURE CONTROL:The LZC measures the temperature in the zone by means of the ZONETEMPERATURE SENSOR and maintains the zone temperature at the set point byadjusting the supply airflow and modulating the NORMALLY CLOSED (N.C.)HEATING VALVE using a proportional, integral, and derivative (PID) closed loopcontrol algorithm.
If the ZONE SUPPLY AIR is at its minimum limit, the zone has general exhaust airvalve(s), and the zone requires increased cooling beyond the amount of ZONESUPPLY AIR CFM necessary to maintain the required ZONE AIRFLOW OFFSET, theLZC increases the ZONE SUPPLY AIR CFM as well as the ZONE GENERALEXHAUST CFM to maintain the zone temperature set point and the ZONE AIRFLOWOFFSET.
Occupied Mode-SIEMENS shall send zone temperature occupied cooling set point (adjustable) andzone temperature occupied heating set point (adjustable) to Phoenix system formaintaining zone temperature set point during occupied mode.
Unoccupied Mode-SIEMENS shall send zone temperature unoccupied cooling set point (adjustable) andzone temperature unoccupied heating set point (adjustable) to Phoenix system formaintaining zone temperature band during unoccupied mode.
CONTROL PRIORITY:A priority structure applies to the above control applications to ensure that safety ismaintained as the highest control priority when HVAC systems or individualcomponents cannot meet all demands placed upon the system.
1. ZONE PRESSURIZATION is first highest priority.2. ZONE MINIMUM AIR CHANGE PER HOUR RATE is the second level of priority.3. ZONE TEMPERATURE CONTROL is the third level of priority.
NCHWS
HWR
1
:ActRTStpt:CSP:HSP:UnoccCSP:UnoccHSP
1
1
1
1
X
X
ROOM DIFFERENTIAL PRESSURE X:DIFF PRESSUREPROVIDE ALARMS FOR HIGH AND LOW DIFFERENTIAL PRESSURE. PROVIDE ONROOMS SHOWN ON M-400 SERIES. DIFFERNTIAL PRESSURE SHALL DISPLAY IN THEDDC, NOT A MONITOR IN THE ROOM/PLENUM.
MONITOR ROOM RELATIVE HUMIDITY X:RHANIMAL HOLDING, PROCEDURE ROOM, CLINIC, GEM ROOMS, ASSOCIATED CORRIDORSONLY. MONITOR ONLY. NO CONTROL ASSOCIATED.
:OCC 10 OCC SUPPLY FLOW 10ACH SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)
:OCC SANITIZE OCC SUPPLY FLOW SANITIZE SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)
X
X:OCC SHED 1 OCC SUPPLY FLOW SHED 1 SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)
X:OCC SHED 2 OCC SUPPLY FLOW SHED 2 SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)
X:OCC EMER OCC SUPPLY FLOW EMER SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)
HMT-X
FOR ROOMS WITH A HUMIDITYSENSOR AND A TEMPERATURESENSOR (SHOULD BE A SINGLE UNIT)
RTR-X
OUT
IN
120V POWERBY DIV 26
TO BAS
FOR ROOMS WITH ONLY ATEMPERATURE SENSOR.
DP
FOR ROOMS INDICATED.RE: FLOORPLANS
HMT-X COMBINATION TS AND HS1
DP-XDIFFERENTIAL PRESSURE SENSOR AND ASSOCIATEDSENSING PROBES/COVER PLATES
1
* (NOTE: 1 PER VALVE)* (NOTE: 1 PER VALVE)
CALCULATED ACH X:ACH CALCULATED ACH BASED ON MEASURED AIRFLOW
01/
2"1"
2"
TA
S
E OF TEXAS
P RE
ENI
GNELANOISS
FO
R
EL IC E N S E D
T
JON HARPER
115708
Tx. Registration # F-2113
Sheet
Title
Approved
Checked
Drawn
Job Number
Date
Sheet Information
Copyright © 2015 Perkins+Will
Revisions
15 234
A
D
B
C
15 234
A
D
B
C
185108.000
MEP Engineer
Shah Smith & Associates
2825 Wilcrest, Suite 350Houston, TX 77042
t 713.780.7563
f 713.780.9209
MDACC Project# 12-0545.1
4/1
8/2
017 1
0:3
7:2
7 A
MC
:\E
ds_cad\P
roje
cts
\Revit_2015\1
111-0
42-0
1_M
echanic
al_
R15_E
Str
iblin
g.r
vt
4/1
8/2
017 1
0:3
7:2
7 A
M
C:\E
ds_cad
\Pro
jects
\Revit_20
15\1
11
1-0
42-0
1_
Mecha
nic
al _
R15_E
Str
iblin
g. r
vt
M11-04
MECHANICALCONTROLS
J. HARPER
E. STRIB
April 18, 2017
J. HARPER
ISS
UE
D F
OR
BID
DIN
G A
ND
CO
NS
TR
UC
TIO
N A
pri
l 18, 2017
CRB ANIMAL AREARENOVATION -
ACTIVATIONPACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER
1001 McKinneySuite 1300
Houston, TX 77002t 713.366.4000f 713.528.3339
www.perkinswill.com
NO ISSUE DATE
NO SCALE1
LAB ZONE (ROOM) CONTROLWITHOUT HOOD
04-18-2017
THERMOMETER (TYPICAL)
PRESSURE GAUGE (TYPICAL)
REDUCER (TYPICAL)
SUPPLY
STRAINER WITH BALL VALVE AND CAPPEDHOSE ADAPTER
2-WAY MODULATINGCONTROL VALVE
RETURN
AIR
3/4" BALL VALVE WITH CAPPEDHOSE ADAPTE
BALANCING VALVE(MEMORY STOPS)
3/4" AUTO AIRVENT PIPED TOF.D. (NOTE 4)
PRESSURE/TEMPERATURETEST PORT (TYPICAL )BUTTERFLY VALVE
WHERE PIPE SIZE IS 2" OR SMALLER, PROVIDE BALL VALVE IN LIEU OF BUTTERFLY VALVE.
INSTALL UNIONS OR FLANGES IN PIPE LOCATIONS OUT OF WAY TO PERMIT COIL REMOVAL.
FOR TERMINAL AND FAN COIL UNITS PIPING PROVIDE PRESSURE/TEMPERATURE TEST
PLUGS ONLY. PRESSURE GAUGES AND THERMOMETERS NOT REQUIRED.
PROVIDE MANUAL AIR VENT AT TERMINAL UNITS.
PROVIDE REDUCERS AT TERMINAL UNIT COIL CONN. AS REQUIRED.
CONNECT COILS IN COUNTER FLOW ARRANGEMENT.
PROVIDE UNIONS OR FLANGES IMMEDIATELY UPSTREAM AND DOWNSTREAM OFCONTROL VALVE.
3/4" BALL VALVE WITH CAPPED HOSE ADAPTOR CAN BE OMITTED IF STRAINER IS AT LOWPART OF PIPING.
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
ACID RESISTANTGASKET MATERIAL(TYPICAL)
316L STAINLESSSTEEL FLANGE(TYPICAL)
TRANSITIONAS REQUIRED
ALL THREAD ROD(SUPPORT FROMSTRUCTURE)
1.
2.
3.
4.
PROVIDE PIPE TYPE GASKET EQUAL TOSEALEX BY THERMOSEAL INC.
SUPPORT ARE VALVE INDEPENDENT OFATTACHED DUCTWORK.
PROVIDE 24" ACCESS TO CONTROL PANEL.
BASED ON PHOENIX VALVES.
NOTES:
STAINLESS STEEL EZJOINT CONNECTORBY UNION MADEPRODUCT FORROUND FLANGECONNECTIONS
18" ADD TRANSITION ASREQUIRED FOR DUAL,TRIPLE AND QUADCONNECTIONS.
LAB/GENERALEXHAUST VALVE
TRANSITION ASREQUIRED
DUCT INSULATION
WRAP VAPOR BARRIERAROUND DUCTBOARDAND SEAL VAPORTIGHT
DUCTBOARD INSULATION
DUCT
VAPOR BARRIER3" MIN.
SHEETMETALDUCTWORK
UNISTRUT SUPPORT
SEE DETAIL "A" DUCTBOARD INSULATIONWITH VAPOR BARRIER
INSULATION INACCORDANCE WITHSPECIFICATIONS
THREADED ROD
DETAIL "A"
2" MIN.
DUCT INSULATION SHIELD
15-DEG.MAX
30-DEG.MAX
A x B A x B
A x
B
TWO-SIDEDTRANSITION
ONE-SIDEDTRANSITION
REDUCE DUCTSIZE IN ONEDIMENSIONONLY, IFPOSSIBLE.
NOTE: 1. FLAT ON ONE SIDE AND/OR FLAT ON BOTTOM PREFERRED.
A x
B
ACCESS DOOR
ACCESS DOOR
HEATING COILS MAY BE DIRECTLY CONNECTEDTO DUCT.INSULATE COIL U-BENDS.PROVIDE EXTENSION HANDLES FORACCESS DOOR CLOSERS.
HEATING COILS
FLOW
30-DEG. MAX
45-DEG. MAX
FLOWA.D.
NOTE:
1.
2.3.
1'-0" MAXLENGTHFLEX DUCTCONNECTION
ACCESS DOOR
MAX 15 DEG. ANGLEUPSTREAM OF COIL
MAXIMUM 30 DEG. ANGLEDOWNSTREAM OF COIL
HEATING COIL
LOW PRESSUREDUCTWORK(SIZE PER PLAN)
1.
2.
3.
4.
REFER COIL PIPING DETAILS.
INSULATE HEATING COIL AND TUBE ENDS SAMEAS ADJACENT DUCTWORK.
SUPPORT LAB SUPPLY VALVE INDEPENDENTLYFROM DUCTWORK.
BASED ON PHOENIX VALVES.
NOTES:
LAB SUPPLY VALVE
36" ACCESS TOCONTROL PANEL
01/
2"1"
2"
TA
S
E OF TEXAS
P RE
ENI
GNELANOISS
FO
R
EL IC E N S E D
T
JON HARPER
115708
Tx. Registration # F-2113
Sheet
Title
Approved
Checked
Drawn
Job Number
Date
Sheet Information
Copyright © 2015 Perkins+Will
Revisions
15 234
A
D
B
C
15 234
A
D
B
C
185108.000
MEP Engineer
Shah Smith & Associates
2825 Wilcrest, Suite 350Houston, TX 77042
t 713.780.7563
f 713.780.9209
MDACC Project# 12-0545.1
4/1
8/2
017 1
0:3
7:3
4 A
MC
:\E
ds_cad\P
roje
cts
\Revit_2015\1
111-0
42-0
1_M
echanic
al_
R15_E
Str
iblin
g.r
vt
4/1
8/2
017 1
0:3
7:3
4 A
M
C:\E
ds_cad
\Pro
jects
\Revit_20
15\1
11
1-0
42-0
1_
Mecha
nic
al _
R15_E
Str
iblin
g. r
vt
M11-05
MECHANICALDETAILS
J. HARPER
E. STRIB
April 18, 2017
J. HARPER
ISS
UE
D F
OR
BID
DIN
G A
ND
CO
NS
TR
UC
TIO
N A
pri
l 18, 2017
CRB ANIMAL AREARENOVATION -
ACTIVATIONPACKAGE
1515 Holcombe Blvd.Houston, TX 77030
UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER
1001 McKinneySuite 1300
Houston, TX 77002t 713.366.4000f 713.528.3339
www.perkinswill.com
NO ISSUE DATE
NO SCALE1
2-WAY CONTROL VALVE COILCONNECTION DETAIL
NO SCALE3
LAB AND GENERAL EXHAUSTVALVE CONNECTION DETAIL
NO SCALE4
RECTANGULAR DUCT SUPPORTEDBY UNISTRUT DETAIL
NO SCALE5
TYPICAL ONE & TWO SIDEDRECTANGULAR DUCT TRANSITIONDETAIL
NO SCALE6
REMOTE HEATING COIL DUCTINSTALLATION DETAIL
NO SCALE2
PHOENIX LAB SUPPLY VALVECONNECTION DETAIL_AP
04-18-2017