  • Copyright 2002, OTIS GmbH & Co. OHG Berlin

    OTISCentral & East Europe

    Area

    PRODUCTADMINISTRATION

    FIELD COMPONENT MANUAL

    Software Data

    MCS - RCB IIInstallation Parameters - MCS 311 / 321 / 411/ 413

    Part: 4 - AA3No.: GCA21270A VIIIaVintage: 01 / 10Page: 1 / 34D1: 25-Oct-2002

    Date: 14-Oct-2002SCN: GAE30075JAA

    MCS - RCB II

    Software - Installation Parameters MCS 311 / 321 / 411 / 413

    Copyright 2002, OTIS GmbH & Co. OHG BerlinNo part of this document may be copied or reproduced in any form or by any means without the prior written

    consent of OTIS GmbH & Co, OHG.

    Authorization Date D1: 25-Oct-2002

    Running on PCB: GCA 21270 A2 or higher

    Software Version: GAE30075JAA

    Document Revision :

    Date SCN Author Comment24-Jan-1994 GAC 30075 BAA Botta Original Document30-Jun-1995 GAE 30075 EAA Szekeres Major revision of document20-Jan-1996 GAE 30075 FAA Hildebrand Revision, Separation of MCS 311 /411

    and MCS 32125-Sep-1996 GAE 30075 GAA Szekeres update for GAA release31-Jul-1997 GAE 30075 HAA Szekeres update for HAA release16-Feb-1998 GAE 30075 HAB Dridi. Update for HAB release25-May-2000 GAE 30075 HAC Seelmann Enable ACG Type 2 added14-Oct-2002 GAE 30075 JAA Seelmann Revision for release

  • Copyright 2002, OTIS GmbH & Co. OHG Berlin

    OTISCentral & East Europe

    Area

    PRODUCTADMINISTRATION

    FIELD COMPONENT MANUAL

    Software Data

    MCS - RCB IIInstallation Parameters - MCS 311 / 321 / 411/ 413

    Part: 4 - AA3No.: GCA21270A VIIIaVintage: 01 / 10Page: 2 / 34D1: 25-Oct-2002

    Date: 14-Oct-2002SCN: GAE30075JAA

    Table of Contents

    1 SYSTEM < M - 1 - 3 - 1 - 1 >.................................................................. 3

    2 DOOR < M - 1 - 3 - 1 - 2 >....................................................................... 7

    3 DRIVE/FIELD < M - 1 - 3 - 1 - 3 > .......................................................... 9

    4 GROUP < M - 1 - 3 - 1 - 4 > ................................................................. 10

    5 DISPATCHING < M - 1 - 3 - 1 - 5 >....................................................... 18

    6 EMERGENCY < M - 1 - 3 - 1 - 6 > ....................................................... 21

    7 SECURITY < M - 1 - 3 - 1 - 7 > ............................................................. 28

    8 SIGNAL DEV < M - 1 - 3 - 1 - 8 >......................................................... 31

    9 DEBUG/TEST < M - 1 - 3 - 1 - 9 > ....................................................... 34

    Note:Shaded Variables are depending of the Controller Type or some

    other parameters.These are only displayed if the related condition is met. !!!!

  • Copyright 2002, OTIS GmbH & Co. OHG Berlin

    OTISCentral & East Europe

    Area

    PRODUCTADMINISTRATION

    FIELD COMPONENT MANUAL

    Software Data

    MCS - RCB IIInstallation Parameters - MCS 311 / 321 / 411/ 413

    Part: 4 - AA3No.: GCA21270A VIIIaVintage: 01 / 10Page: 3 / 34D1: 25-Oct-2002

    Date: 14-Oct-2002SCN: GAE30075JAA

    1 SYSTEM < M - 1 - 3 - 1 - 1 >

    1. System setupsSymbol Default Definition DSPRCB Identifier 1 Car ID in the Group,

    1...8Controller Type 0 0: MCS 311/411/421 1: MCS 321 NEL TDis UHB0 Mapping 0 MCS321 assigns UHB0 to DHB0 input.

    0: standard 321 mapping1: modernization, leave UHB0 = UHB0 input** no effect when controller type 0

    Operation Type 0 0: FCL Full Collective Operation1: DCL Down Collective Operation2: SAPB Single Auto Push Button3: SAPB wit Car Coming Light4: FCL Both Directions are deleted5: FCL Single Button FCL

    T

    Enable DCL BSM 0 MCS321 Enable BSM during DCL0: Disabled 1: Enabled

    D

    Reverse HC Tout 0 Timeout, in which a hall call in the opposite direction isnot accepted (same riser only): 0 50 valid, time is 100 ms steps

    Bottom Position 0 Bottom Position for car0...99 valid

    Lobby Position 1 Lobby Position for group0...99 valid

    Car Top Position 53 Top position for car0...99 valid

    Group Top Pos 53 Top position for group0...99 valid

    Cafeteria Pos 255 Cafeteria position0...99 or 255 disabled

    Expr. zone 1 bot 255 Bottom of Express Zone 10...99 or 255 disabled

    T

    Expr. zone 1 top 255 Top of Express Zone 10...99 or 255 disabled

    D

    Expr. zone 2 bot 255 Bottom of Express Zone 20...99 or 255 disabled

    D

    Expr. zone 2 top 255 Top of Express Zone 20...99 or 255 disabled

    D

    Expr. zone 3 bot 255 Bottom of Express Zone 30...99 or 255 disabled

    D

    Expr. zone 3 top 255 Top of Express Zone 30...99 or 255 disabled

    D

  • Copyright 2002, OTIS GmbH & Co. OHG Berlin

    OTISCentral & East Europe

    Area

    PRODUCTADMINISTRATION

    FIELD COMPONENT MANUAL

    Software Data

    MCS - RCB IIInstallation Parameters - MCS 311 / 321 / 411/ 413

    Part: 4 - AA3No.: GCA21270A VIIIaVintage: 01 / 10Page: 4 / 34D1: 25-Oct-2002

    Date: 14-Oct-2002SCN: GAE30075JAA

    1. System setupsSymbol Default Definition DSPANS Call Limit 3 Anti Nuisance Call Limit

    0: disabled,1..255 car calls needed to trigger ANS

    ATT Type 0 Attendant Operation Type0: Start on DCB when demand exists (ATT-1)1: Start on ATTU/ATTD (ATT-3)2: Start on DCB3: same as 0 with annunciator4: same as 1 with annunciator5: same as 2 with annunciator

    CTL Type 0 Car to Landing Operation0: ETO 1: NAO

    CTL Position 255 Car to landing position0...99 or 255 disabled

    CTL Default Door 0 Door State at CTL Position0: both open1: front opened2: rear opened

    DCP Time 50 Delayed Car Protection Timeout20...255 seconds

    ESB enable 0 Emergency Stop Button with memory0: disabled1: not closed door will reopen2: door will always open

    ISC Type 0 Independent Service starts with:0: continuous pressure on CCB1: continuous pressure on DCB2: ISU / ISD3: not used4: continuous pressure CCB or DCB5: momentary pressure on CCB

    ISC Timeout 0 Timeout to close the doors in ISC in case of FPD1255 sec.

    ISC while EPO 0 ISC allowed on Emergency Power0: disabled, shutdown after

    EPO-NAV Timeout1: enabled, no shutdown

    ISC2 Type 0 Independent Service (via ISS2/RISS2) starts with:0: continuous pressure on CCB1: continuous pressure on DCB2: ISU / ISD3: not used4: continuous pressure CCB or DCB5: momentary pressure on CCB

  • Copyright 2002, OTIS GmbH & Co. OHG Berlin

    OTISCentral & East Europe

    Area

    PRODUCTADMINISTRATION

    FIELD COMPONENT MANUAL

    Software Data

    MCS - RCB IIInstallation Parameters - MCS 311 / 321 / 411/ 413

    Part: 4 - AA3No.: GCA21270A VIIIaVintage: 01 / 10Page: 5 / 34D1: 25-Oct-2002

    Date: 14-Oct-2002SCN: GAE30075JAA

    1. System setupsSymbol Default Definition DSPLight Relay Time 20 Light Relay Time

    1...255 secondsPerf Monitor Int 10 CPU Monitoring Interval (For Engineering use)

    0...255 secondsCar Calls Behind 0 Car Calls behind a moving cars position

    0: Car Calls are enabled1: Car Calls are disabled

    SaveCalls in OLD 0 Save Car calls if car goes in overload mode0: calls are deleted1: calls are saved

    OCSS-MCSS ICD 0 For LMCSS (only 2 byte messages)0: GBA30085 AAA (V3.3)1: GBA30085 BAA (V4.0)2: GBA30085 CAA (V4.1)3: GBA30085 EAA or higher (V4.2)

    For MCSS (2 byte and 4 byte messages*)0: AAA 30045 AAF or higher (2 bytes) MCSS does not support loadweighing From OCSS or alternate door profiles

    100: AAA30045AAF (4 bytes)101: AAA30045AAH (4 bytes)102: AAA30045AAI or higher (4 bytes)* 4 bytes only used for double deck, fuzzy logic, orspecial Japanese features

    Note: MCSS with alternate door profiles requiresA1130045AAKE or higher

    Safety Note: Units with EFO, EFS, EPO, EQO has tobe equipped with- GBA30085HAA01 or higher- AAA30045AAI or higher

    OCSS-EMS ICD 0 When EMS is configured for version 3.3, 4.0, 4.1 ICDlevel it needs load weight and actual position in statusmessages. When the ICD setups of OCSS and EMSdo not match the cars jump on the EMS display andload weight is not shown correctly.

    0: EMS is at ICD Level 3.3, 4.0, 4.11: EMS is configured for 4.2

    Load weighing 0 Load weighing inputs connected to0: DISS (E411)1: OCSS (MCS311/SPEC90)

  • Copyright 2002, OTIS GmbH & Co. OHG Berlin

    OTISCentral & East Europe

    Area

    PRODUCTADMINISTRATION

    FIELD COMPONENT MANUAL

    Software Data

    MCS - RCB IIInstallation Parameters - MCS 311 / 321 / 411/ 413

    Part: 4 - AA3No.: GCA21270A VIIIaVintage: 01 / 10Page: 6 / 34D1: 25-Oct-2002

    Date: 14-Oct-2002SCN: GAE30075JAA

    1. System setupsSymbol Default Definition DSPInverted Rise 0 Activation of Inverted Rise

    (Lobby near Top Position)0: disabled 1: enabled

    Number of rings 2 Number of rings to transmit on1: One ring 2: Both

    Test Ring Port 0 OCSS sends ring messages only on selected ring portfor test.

    0: Normal ring communication1: Ring 1 port for test2: Ring 2 port for test

    Startup Time 0 Time the car waits before moving after returning tonormal power from emergency power.

    0..12 : 12 second delay13...255 seconds in addition to 5 sec. default

    Hall Button Type 1 Hall Button Type1: Mechanical 2:Touch Tube

    Car Button Type 1 Car Button Type1: Mechanical 2: Touch Tube

    Enable Moderniz 0 Enable Modernization Overlays enable reset of car calltouch tubes

    0: disabled1: Reset Car Button output is activated whenever touch tubes need to be reset

    Double COP 0 Double COP0: disable 1: enabled

    CB to ECB copy 0 Copying of Car TTL Lights:0: no copying1: CB TTL copied t