www.perkinswill.com 1/10/2018 5:03:55 AM SHRC-Ma gna_CCC-2017_de tached.rvt ISSUED FOR TENDER NOV 2017 MAGNA CARDIAC REHABILITION CLINIC FIT OUT Copyright © 2016 Perkins+Will SHEET INDEX SHEET NUMBER SHEET NAME M-05 MECHANICAL SPECIFICATIONS G00-00 COVER SHEET A00-01 GENERAL NOTES, SYMBOLS, ABBREVIATIONS A00-01A SITE PLAN A01-01G CODE COMPLIANCE PLANS A05-01 DEMOLITION PLANS - LEVEL 01 A11-01 CARDIAC CLINIC FLOOR PLANS - LEVEL 01 A44-01 ENLARGED PLANS A52-01 DETAILS M-01 MECHANICAL SCHEDULES, LEGEND AND DRAWING LIST M-02 HVAC + HYDRONIC PLAN M-03 PLUMBING + FIRE PROTECTION PLAN M-04 MECHANICAL + FIRE PROTECTION DEMO PLAN E-01 CARDIAC CLINIC ELECTRICAL LEGEND E-02 CARDIAC CLINIC ELECTRICAL DEMOLITION PLANS E-03 CARDIAC CLINIC LIGHTING AND POWER PLANS E-04 CARDIAC CLINIC COMMUNICATIONS PLANS

Upload: others

Post on 17-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

www.perkinswill.com

1/10/2018 5:03:55 AM

SHRC-Ma gna_CCC-2017_detached.rvt

ISSUED FOR TENDER

NOV 2017

MAGNA CARDIAC REHABILITION CLINIC FIT OUT

Copyright © 2016 Perkins+Will

SHEET INDEX

SHEETNUMBER SHEET NAME

M-05 MECHANICAL SPECIFICATIONS

G00-00 COVER SHEET

A00-01 GENERAL NOTES, SYMBOLS, ABBREVIATIONS

A00-01A SITE PLAN

A01-01G CODE COMPLIANCE PLANS

A05-01 DEMOLITION PLANS - LEVEL 01

A11-01 CARDIAC CLINIC FLOOR PLANS - LEVEL 01

A44-01 ENLARGED PLANS

A52-01 DETAILS

M-01 MECHANICAL SCHEDULES, LEGEND AND DRAWING LIST

M-02 HVAC + HYDRONIC PLAN

M-03 PLUMBING + FIRE PROTECTION PLAN

M-04 MECHANICAL + FIRE PROTECTION DEMO PLAN

E-01 CARDIAC CLINIC ELECTRICAL LEGEND

E-02 CARDIAC CLINIC ELECTRICAL DEMOLITION PLANS

E-03 CARDIAC CLINIC LIGHTING AND POWER PLANS

E-04 CARDIAC CLINIC COMMUNICATIONS PLANS

Page 2: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

A1 START AT

UPPER LEFT

CORNER

NUMBERS=

HORIZONTAL

LETTERS =

VERTICAL

COLUMN HEAD TAG

A/C AIR CONDITION(ING)(ED)ACC ACCESSIBLE ACM ALUMINUM COMPOSITE MATERIALACP LARGE SCALE ACOUSTIC CEILING PANELACST ACOUSTIC(AL) ACT ACOUSTICAL PANEL CEILING SYSTEMAD AREA DRAIN ADJ ADJUSTABLE/ ADJACENT AFC ABOVE FINISHED COUNTER AFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADE AGGR AGGREGATE AHU AIR HANDLING UNIT ALT ALTERNATE ALUM PREFINISHED ALUMINUMANOD ANODIZE(D) APC ACOUSTICAL PANEL CEILINGAPPROX APPROXIMATE AR AREA RUGARGB ABUSE-RESISTANT GYPSUM BOARDARCH ARCHITECT(URAL), ARCHITECT AS ALUMINUM FRAMED DOORS AND STOREFRONT/SCREENSASPH ASPHALT ATC ACOUSTICAL TILE CEILINGAUTO AUTOMATIC AVB AIR/VAPOUR BARRIERAWCP ACOUSTIC WOOD CEILING PANELAWP LARGE SCALE ACOUSTIC WALL PANELAWT ACOUSTICAL WALL TREATMENT AWWP ACOUSTIC WOOD WALL PANELB/B BACK TO BACKBB BLACK BOARDBC BACK OF CURB BD BOARD BITUM BITUMINOUS BLDG BUILDING BM BEAM/ BENCHMARK BOT/ BOTTOM OF BSMT BASEMENT BUR BUILT-UP ROOFING C/W COMPLETED WITHCAB CABINET CB CATCH BASIN CCTV CLOSED CIRCUIT TELEVISIONCEM CEMENT CF/CI CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCF/OI CONTRACTOR FURNISHED, OWNER INSTALLEDCFM CUBIC FEET PER MINUTE CFMF COLD-FORMED METAL FRAMING CG STAINLESS STEEL CORNER GUARD CGS COMPOSITE GLASS SURFACING FABRICATIONCHK COAT HOOKSCI CAST IRON, CURB INLET CIP CAST-IN-PLACE CJ CONTROL JOINT CKB CHALKBOARDCL CENTER LINE CLG CEILING CLO CLOSET CLR CLEAR CM CENTIMETERCMT CERAMIC MOSAIC TILECMU CONCRETE MASONRY UNITCO CLEANOUT COL COLUMN CONC CONCRETE CONF CONFERENCECOORD COORDINATE CORR CORRIDOR

CP CARPETCPT CARPET TILES CQS COMPOSITE QUARTZ SURFACING FABRICATIONCRL CRASH RAILCT CERAMIC TILE CTR CENTER/CONTOUR CU CUBICCW COLD WATER PIPING/CHEMICAL WASTELINECWS CURTAIN WALL SYSTEMD DEEP, DEPTH, PENNY (NAIL)DBL DOUBLEDEG DEGREE DEMO DEMOLISH, DEMOLITION DEPT DEPARTMENT DF DRINKING FOUNTAIN DIA DIAMETER (EXTERIOR) DIAG DIAGONALDIFF DIFFUSER/ DIFFERENCE DIM DIMENSION DISP DISPENSER DIV DIVISION DL DEAD LOAD DR DOOR/ DRAIN DS DOWNSPOUTDW DISHWASHER DWG DRAWING DWS1 ALUMINUM DOME TACTILE WARNING SYSTEMDWS2 TACTILE WARNING TILINGDWS3 VISUAL WARNING TAPEE EAST EA EACH ECT ELECTRO CONDUCTIVE TILEEHD ELECTRIC HAND DRYEREIFS EXTERIOR INSULATION & FINISH SYSTEMEJ EXPANSION JOINTEL ELEVATION ELAST ELASTOMERIC ELEC ELECTRIC(AL) ELEV ELEVATOR EMER EMERGENCY EMER SHR EMERGENCY SHOWERENGR ENGINEER ENTR ENTRANCE EO ELECTRIC OUTLET EOS EDGE OF SLAB EP ELECTRICAL PANEL EQ EQUALEQUIP EQUIPMENTETC ET CETERAETR EXISTING TO REMAIN ETZ EPOXY TERRAZZO FLOORINGEW EACH WAY EWC ELECTRIC WATER COOLEREXH EXHAUST EXIST EXISTINGEXP EXPANSIONEXT EXTERIOR, EXTERNALF/F FACE TO FACE FAB FABRICFAB-BB BLACK OUT SHADE FABRICFAB-S SHADE FABRICFCO FLOOR CLEANOUTFD FLOOR DRAIN FDC FIRE DEPARTMENT CONNECTIONFE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINETFF FINISH FACE FH FIRE HYDRANT FHC FIRE HOSE CABINET FG ENTRANCE FLOOR GRILLESFILM GLAZING FILMFIN FINISH(ED)FF EL FINISHED FLOOR ELEVATION

FLR FLOORFLUOR FLUORESCENT FO FINISHED OPENING FOC FACE OF CURB FOF FACE OF FINISH FOM FACE OF MASONRY FOS FACE OF SLAB/ FACE OF STUDFP FIRE PROTECTION/FIREPROOFFRG FIRE RESISTIVE GLASSFRTW FIRE RETARDANT TREATED WOODFSS FOLDING SHOWER SEATS FT FOOT (FEET)/ FIRE TREATEDFTG FOOTING FURG FURRING FURN FURNISH, FURNITUREFUT FUTURE FV FIELD VERIFYGA GAGE GALV GALVANIZED GB GRAB BAR GBX FIRE RATED GYPSUM BOARD TYPE X GEN GENERAL GFRC GLASS FIBER REINFORCED ONCRETEGFRG GLASS FIBER REINFORCED GYPSUMGG1 STRUCTURAL GLASS GUARD WITH BASE SHOE ATTACHMENTGG2 STRUCTURAL GLASS GUARD WITH STANDOFF ATTACHMENTGL GLASS GL BLK GLASS BLOCK GL-LK GLASS LOCKERSGLU LAM GLUED LAMINATED WOODGR LN GRADE LINE GRFL GROUND FLOOR GSB GYPSUM SHEATHING BOARD GT GREASE TRAP GWB STANDARD GYPSUM BOARDGWT GLASS WALL TILESGYP PLAS GYPSUM PLASTERH HIGHHB HOSE BIBB HC HOLLOW CORE HDW HARDWARE HDWD HARDWOOD HM HOLLOW METALHMS HOLLOW METAL DOORS AND FRAMESHORIZ HORIZONTAL HPT HIGH POINT HS HEAT STRENGTHENED GLASSHSKPG HOUSEKEEPING HSLG HEAT STRENGTHENED LAMINATED SAFETY GLASSHSTG HEAT SOAKED TEMPERED GLASSHT HEIGHT HVAC HEATING, VENTILATION, AIR CONDITIONINGHW HOT WATERHWC HIGH IMPACT WALL PROTECTIONID INSIDE DIAMETER INCAND INCANDESCENT INSUL INSULATION INT INTERIOR INV INVERTJAN CLO JANITOR'S CLOSETKIT KITCHEN L LONG, LENGTH LAM LAMINATE(D) LAV LAVATORY LH LEFT HAND

LIB LIBRARYLIN LINOLEUM FLOORING LKR LOCKER LL LIVE LOAD LONG LONGITUDINAL LOC LOCATION LPT LOW POINT LQR LACQUER FINISHLT LIGHT LTPG LAMINATED TEMPERED SAFETY GLASSLVR LOUVER LVT LUXURY VINYL TILE

M METER MACH MACHINEMAINT MAINTENANCE MATL MATERIAL MAX MAXIMUM MB MARKER BOARDSMBWC MARKER BOARD WALL COVERINGMCP METAL CEILING PANELMDF MEDIUM DENSITY FIBREBOARDMECH MECHANICAL MEL MELAMINEMEMB MEMBRANE MEP MECHANICAL, ELECTRICAL, PLUMBING @ FIRE PROTECTIONMEZZ MEZZANINEMFR MANUFACTURER MG GLASS MARKER BOARDMGL MAGNETIC GLASS MARKER BOARDMH MANHOLE MHO MAGNETIC HOLD OPENMIN MINIMUM MISC MISCELLANEOUS MKR BD MARKER BOARD MM MILLIMETER MO MASONRY OPENING MTL METALMTL-LK METAL LOCKERSMTL-TP METAL TOILET PARTITIONS AND URINAL SCREENSMTLG METAL GRILLE PANELMWP METAL WALL PANELM1 UNFRAMED MIRRORSM2 TILTED MIRRORSN NORTH NIC NOT IN CONTRACT NO NUMBER NOM NOMINAL NTS NOT TO SCALEO/O OUT TO OUT OC ON CENTER OD OUTSIDE DIAMETER OF/CI OWNER FURNISHED, CONTRACTOR INSTALLEDOF/OI OWNER FURNISHED, OWNER INSTALLEDOFF OFFICE OPH OPPOSITE HAND OPNG OPENING OPP OPPOSITE ORD OVERFLOW ROOF DRAIN

PA PUBLIC ADDRESS PAR PARAPET, PARALLEL PCC PRE-CAST CONCRETEPCT PROCELAIN TILE PCTZ PRECAST EPOXY TERRAZZO FLOORINGPDO POWER DOOR OPERATORPERF PERFORATED PERP PERPENDICULAR PH-LK PHENOLIC LOCKERSPH-TP PHENOLIC TOILET PARTITIONS AND URINAL SCREENSPLAM PLASTIC LAMINATE PLAM-LK PLASTIC LAMINATE LOCKERSPLAM-TP PLASTIC LAMINATE TOILET PARTITIONS AND URINAL SCREENSPLAS PLASTER PLBG PLUMBING

PLYWD PLYWOOD PNT PAINT POL POLISHED PREFAB PREFABRICATE(D) PROJ PROJECT PROP PROPERTY PT PAINTINGPTD PAPER TOWELDISPENSER PTN PARTITION PVC POLYVINYL CHLORIDE PVG PAVING

QT QUARRY TILEQTY QUANTITY

R THERMAL RESISTANCE, RADIUS, RISERRB RUBBER BASE RC REINFORCED CONCRETE RCP REFLECTED CEILING PLAN RCPTN RECEPTION RD ROOF DRAIN REC RECESSED REF REFERENCE, REFRIGERATORREINF REINFORCE, REINFORCING REQ(D) REQUIRE, REQUIRED RESIL RESILIENT REV REVISION RF RESILIENT FLOORINGRFT RUBBER TREADS, RISERS AND LANDINGS RH RIGHT HAND RM ROOM RO ROUGH OPENING ROW RIGHT OF WAY RSF RESILIENT SHEET FLOORINGRSSF RESILIENT SAFETY SHEET FLOORINGRTF RUBBER TILE FLOOR RVL REVEALRWBB DUAL ROLLER WINDOW SHADES AND BLACKOUT BLINDS, MANUAL

OPERATEDRWBB-M DUAL ROLLER WINDOW SHADES AND BLACKOUT BLINDS, MOTORIZEDRWS ROLLER WINDOW SHADE, MANUAL OPERATEDRWS-M ROLLER WINDOW SHADE, MOTORIZED

S SOUTH SAN SANITARY SC SOLID CORE SCR SHOWER CURTAIN AND RODSCHED SCHEDULE SDT STATIC DISSIPATIVE TILESECT SECTION SF SQUARE FOOT(FEET)SF RUBBER SPORTS FLOORINGSFRM SPRAY APPLIED CEMENTITOUS FIRE RESISTIVE MATERIAL SGB GLASS-MAT, SILICONIZED GYPSUM BOARDSGL SINGLE SHR SHOWER SHT SHEET SIM SIMILAR SJ SLIP JOINT, SCORED JOINTSPEC SPECIFICATION SPG SWITCHABLE GLASSSPKR SPEAKER SQ SQUARE SS POLYMER BASED SOLID SURFACESSG STRUCTURAL SILICONE GLAZED CURTAIN WALL SST STAINLESS STEEL STA STATION

STC SOUND TRANSMISSION CLASSSTD STANDARD STL STEEL STN STONE TILESTOR STORAGE STS INTERIOR ALL-GLASS SCREENSSTS-WD WOOD ALL GLASS SCREENSSTRUCT STRUCTURAL SUSP SUSPENDED SV SHEET VINYL SVF CHEMICAL RESISTANT RESILIENT FLOORINGSYMM SYMMETRICAL

T TREAD T/ TOP OF TA TOILET ACCESSORY T&B TOP & BOTTOM T&G TONGUE & GROOVE TB TACKBOARDTEL TELEPHONE TEMP TEMPORARY TER TERRAZZOTHK THICK TI TENANT IMPROVEMENT TKBD TACKBOARDTO_ TOP OF _____ TOPO TOPOGRAPHY, TOPOGRAPHICTPG TEMPERED GLASSTRTD TREATED TS TUBE STEEL TV TELEVISION TYP TYPICAL

U HEAT TRANSFER COEFFICIENTUH UNIT HEATER UL UNDERWRITER'S LABORATORIESUNEX UNEXCAVATED UNFIN UNFINISHED UNO UNLESS NOTED OTHERWISEUTIL UTILITY

VB VINYL BASE VCT VINYL COMPOSITION TILE VENT VENTILATION VERT VERTICAL VEST VESTIBULE VIF VERIFY IN FIELD VNR VENEER VOL VOLUME VS VISION STRIPSVWC VINYL WALL COVERING

W WEST W/ WITH W/O WITHOUT WAP INTERIOR WOOD ACOUSTIC WALL PANELSWB WHITEBOARDWC WALL COVERINGWD NATURAL WOOD AND VENEER FINISHWD-LK WOOD VENEER LOCKERSWD-TP WOOD VENEER TOILET PARTITIONS AND URINAL SCREENSWG WALL GUARD WH WATER HEATER WI WROUGHT IRON WP MEMBRANE WATERPROOFINGWPG WIRED GLASSWSCT WAINSCOT WT WEIGHT WWF WELDED WIRE FABRIC WWM WELDED WIRE MESH

X BY

YD YARDYR YEAR

ZN ZINC

ABBREVIATIONS LEGENDNOTE 1: ABBREVIATIONS WHEN USED IN COMPOSITION MAY INCLUDE PERIODS FOR CLARIFICATION

NOTE 2: ABBREVIATIONS MAY BE DIFFERENT WHEN A PART OF A LEGEND

SYMBOLS

& ANDANGLE

@ ATX BY (LOWERCASE)

CENTER LINE[ CHANNELX° DEGREEØ DIAMETER

╩ DOUBLE ANGLE

# NUMBER, POUNDSPROPERTY LINE

± PLUS OR MINUSSQUARE FEETZEECOLUMN; TUBE

/ DIVIDED BY

COMPACTED FILL EARTH WORK

SAND

STEEL

STRUCTURAL CONCRETE

CONTINUOUS WOOD FRAMING

STRUCTURAL CLAY TILE

ALUMINUM/ORNAMENTAL METAL

CONCRETE MASONRY UNIT

BRICK, COMMON FACE

CUT STONE

TERRAZZO

ASPHALT

GRAVEL, POROUS FILL

GLASS

FINISH WOODWORK

RESILIENT FLOORING

GYPSUM WALLBOARD

PLASTIC LAMINATE

BLOCKING OR SHIM

WATERPROOFING/ DAMPROOFING/ AIR/ MOISTURE BARRIER

CARPETING (LARGE SCALE)

BATT INSULATION

RIGID INSULATION

PARTICLE BOARD

PLYWOOD

BOARD

ACOUSTICAL CEILING

SPRAY-ON FIREPROOFING OR INSULATION

UNDISTURBED SOIL

LIGHTWEIGHT CONCRETE

CAST STONE

BRICK, GLAZED

WOOD FLOORING

EXTERIOR SHEATHING

SOLID SURFACING

MATERIALS

WINDOW TYPE SYMBOL

INTERIOR GLAZING SYSTEM TAG (NUMERIC)

EXTERIOR GLAZING SYSTEM TAG (ALPHA)

LOUVER TYPEIDENTIFIER(ALPHA AND NUMERIC)

WALL/PARTITION TAG

FLOOR DRAIN

ROOF DRAIN AND OVERFLOW DRAIN

OVERFLOW DRAIN

ROOF DRAIN

GLAZING TAG

GLAZING DESIGNATION

ARCHITECTURAL WOODWORK

NO BOX INDICATES ARCHITECTURALWOODWORK REF AXX-XX FOR ARCHITECTURAL WOODWORK SECTIONS AND DETAILS

CABINET WIDTH

CABINET TYPE

EXISTING PARTITION / ITEM TO REMAIN

NEW PARTITION / ITEM

EXISTING TO BE REMOVED

COLUMN GRID DESIGNATION

NOTE TAGS

"NOTES BY NUMBER"

SPECIFICATION KEYNOTES

BUILDING SECTION TAG

SECTION

DESIGNATION

SHEET NUMBER

WALL / DETAIL SECTION TAGS

SECTION

DESIGNATION

SHEET NUMBER

SHEET NUMBERDETAIL DESIGNATION

ENLARGED PLAN TAG

PLAN OR DETAIL

DESIGNATION

SHEET NUMBER

EXTERIOR ELEVATION TAG

ELEVATION

DESIGNATION

SHEET NUMBER

INTERIOR ELEVATION TAG

SINGLE INTERIOR

ELEVATION TAG

ELEVATION

DESIGNATION

SHEET NUMBER

DOOR IDENTIFICATION TAG

DOOR DESIGNATOR

ROOM NUMBER (THAT DOOR

SWINGS INTO)

EQUIPMENT DESIGNATION

OWNER FURNISHED EQUIPMENT / ITEM

REF OWNER EQUIPMENT MANUAL

OWNER FURNISHED

EQUIPMENT/ ITEM

CONTRACTOR FURNISHED

EQUIPMENT/ ITEM

TOILET ACCESSORY TAG

X##

L1

A-XXXX

301A

FD

TA1

XXA-XXX

XXA-XXX

XXA-XXX

XXA-XXX

SIM

A-XXX

XX/A-XXX

A1

.610.

OUT OF SCOPE AREA

A

1

XXA-XXX

SYMBOLS LEGEND1. REFER TO COMPLETE SET OF ISSUED CONTRACT DOCUMENTS FOR APPLICABLE NOTES, ABBREVIATIONS, AND SYMBOLS.

2. DO NOT SCALE THE DRAWING. IF DIMENSIONS ARE IN QUESTION. OBTAIN CLARIFICATION FROM THE ARCHITECT BEFORE CONTINUING.

3. DIMENSIONS SHOWN ON THE FLOOR PLANS FOR NEW CONSTRUCTION ARE TO THE FACE OF FINISH OF INTERIOR WALLS, TO CENTER LINE OF COLUMNS AND TO FACE OF CONCRETE OR MASONRY WALLS, UNLESS OTHERWISE INDICATED. DIMENSIONS IN RENOVATED AREAS ARE FROM FINISH FACE OF EXISTING WALLS AND TO FINISH FACE OF NEW STUD WALLS, UNLESS OTHERWISE INDICATED.

4. FIELD MEASURE AND CONFIRM DIMENSIONS FOR OWNER PROVIDED EQUIPMENT AND FURNISHINGS. COORDINATE WITH THE OWNER ON DELIVERY AND INSTALLATION OF OF/CI EQUIPMENT. MINIMUM REQUIRED OPENINGS AND ACCESSIBLE ROUTES TO THE INSTALLATION AREA SHALL BE COORDINATED WITH THE SUPPLIER.

5. FINISH FLOOR ELEVATIONS ARE TO TOP OF CONCRETE SLAB UNLESS OTHERWISE NOTED.

6. COORDINATE EXACT SIZE AND PLACEMENT OF EQUIPMENT BASE AND HOUSEKEEPING PADS WITH EQUIPMENT TO BE PROVIDED.

7. WHERE NEW GYPSUM BOARD PARTITIONS ARE A CONTINUATION OF AN EXISTING PARTITION OR COLUMN ENCASEMENT, THE FACE OF THE NEW GYPSUM BOARDSHALL BE ALIGNED WITH THE FACE OF THE EXISTING SURFACE. WHERE A ONE HOUR PARTITION IS SHOWN AS A CONTINUATION OF A TWO-HOUR PARTITION OR COLUMN ENCASEMENT, THE FACE OF THE GYPSUM BOARD SHALL BE OFFSET AS REQUIRED TO PROVIDE FACE ALIGNMENT OFGYPSUM BOARD ON BOTH SIDES.

8. LEVEL FLOORS SO THAT THEY DO NOT EXCEED A ¼" VARIANCE IN A 10'-0" RADIUS.

9. PIPING LOCATED ABOVE GRADE AND INSIDE THE BUILDING SHALL BE CONCEALED IN FURRED SPACES WITH THE EXCEPTION OF PIPING IN STAIRWAYS, EQUIPMENT ROOMS AND POWERHOUSE. COORDINATE WITH OTHER TRADES TO PROVIDE FURRING FOR PIPING INSTALLED IN FINISHED AREAS.

10. ALL EXTERIOR STEEL HANDRAILS, GUARDRAILS, AND BOLLARDS SHALL BE GALVANIZED AND PAINTED UNLESS OTHERWISE NOTED.

11. PARTITION TYPES AND FIRE RESISTIVE RATINGS INDICATED ON A WALL ARE TO BE CONTINUOUS FOR THE LENGTH AND HEIGHT OF A PARTITION.

12. APPROVE FLOOR OUTLET LOCATIONS WITH ARCHITECT AND BUILDING MANAGEMENT PRIOR TO CORE DRILLING.

13. OPENINGS IN A RATED WALL, FLOOR, CEILING AND ROOF ASSEMBLIES SHALL BE SEALED WITH A FIRE RESISTANT JOINT SYSTEMS OR PROTECTED WITH A FIRE RATED CHASE.

14. EXIT SIGNS AND SMOKE DETECTORS LOCATED IN CEILINGS SHALL BE POSITIONED AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION.

15. WHERE MATERIALS ARE APPLIED TO, OR ARE IN DIRECT CONTACT WITH WORK INSTALLED BY ANOTHER SUBCONTRACTOR, COMMENCEMENT OF WORK IMPLIES ACCEPTANCE OF THE SUBSTRATE AS SUITABLE FOR THE APPLICATION INTENDED.

16. ISOLATE DISSIMILAR METALS TO PREVENT GALVANIC CORROSION.

17. SEALANTS EXPOSED TO VIEW SHALL BE CUSTOM COLOR AS SELECTED BY THE ARCHITECT.

18. COORDINATE LOCATION OF SEALANT AND COMPATIBILITY OF SEALANTS WITH ADJACENT WORK, INCLUDING MATERIALS AND OTHER CONTIGUOUS SEALANTS.

19. CAULK AT JUNCTURE OF INTERIOR FACES OF DOOR FRAMES, VIEW WINDOW FRAMES, EXTERIOR WINDOW FRAMES, AND CABINET WORK WITH ADJACENT MATERIALS. MAINTAIN THE FIRE RATING OF CONSTRUCTION AROUND CABINETS, PANELS, AND BOXES RECESSED IN FIRE RATED WALL, FLOOR, AND CEILING ASSEMBLIES.

20. ACCESSORIES SUCH AS GRAB BARS, TOWEL BARS, PAPER DISPENSERS AND SOAP DISHES INSTALLED WITHIN 610MM OF A URINAL, WATER CLOSET, SINK OR LAVATORY SHALL BE MOISTURE SEALED.

21. DO NOT HANG (SUPPORT) ANY ITEMS FROM METAL ROOF DECK. IT IS ACCEPTABLE TO ATTACH, I.E. CEILING SYSTEM WIRE HANGERS FROM JOISTS AND/ OR BEAMS. IF NO JOIST OR BEAM, PROVIDE A STEEL STRIP.

GENERAL PROJECT NOTES

0 1.2

A

X

X X

X

X

GL-X

KEYNOTE TAG

00 00 00.A1 TEXT

SPECIFICATION SECTION

NOTE DESCRIPTOR

ALPHA-NUMERIC SUFFIX (NOT REFECENED IN

SPECIFICATION)

WALL CONSTRUCTION KEY

FLOOR MATERIAL TRANSITION

RECESSED FLOOR JUNCTION BOX

PL

CL

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10/2018 5:04:17 AM

SHRC-Ma gna_CCC-2017_detached.rvt

A00-01

GENERAL NOTES,SYMBOLS,

ABBREVIATIONS

351702.000

BC

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

15 Foundry StreetDundas, OntarioCanada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

SHEET INDEX

SHEETNUMBER SHEET NAME

M-05 MECHANICAL SPECIFICATIONS

G00-00 COVER SHEET

A00-01 GENERAL NOTES, SYMBOLS, ABBREVIATIONS

A00-01A SITE PLAN

A01-01G CODE COMPLIANCE PLANS

A05-01 DEMOLITION PLANS - LEVEL 01

A11-01 CARDIAC CLINIC FLOOR PLANS - LEVEL 01

A44-01 ENLARGED PLANS

A52-01 DETAILS

M-01 MECHANICAL SCHEDULES, LEGEND AND DRAWING LIST

M-02 HVAC + HYDRONIC PLAN

M-03 PLUMBING + FIRE PROTECTION PLAN

M-04 MECHANICAL + FIRE PROTECTION DEMO PLAN

E-01 CARDIAC CLINIC ELECTRICAL LEGEND

E-02 CARDIAC CLINIC ELECTRICAL DEMOLITION PLANS

E-03 CARDIAC CLINIC LIGHTING AND POWER PLANS

E-04 CARDIAC CLINIC COMMUNICATIONS PLANS

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017

Page 3: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

13

A9.6

11

A9.6

T

TYPSTALL

TYPSTALL

GARBAGESTORAGE

FIREROUTE

CONCPAD

LOW STONEWALL

LOW STONEWALL

RECEIVINGAREA

FUTUREPARKING

FUTUREPARKING

POLE MOUNTEDSWITCHGEAR

9000 SIDESETBACK

10000REAR

9000 SIDESETBACK

9000 SIDESETBACK

10700 FRONTSETBACK

10700 FRONTSETBACK

252.15+FIN. FIRST FLOOR

GEODETIC ELEVATION

SC

CANOPYOVERHEAD

CANOPYOVERHEAD

CANOPYOVERHEAD

LAY-BY

LAY-BY

BUS

LAY-BY

BUSPARKING

ONEWAY

ONE

WAY

ONE

WAY

ONE

WAY

FH

FH

FH

FH

FH

CURBCUT

ANNUNCIATORPANEL

AREAWAY

MAINTENANCESTRIP

CONC.PAD

CHLCO2

BBBB

BB

BB

B

B

43280

3600

TYP.

6340

135615

133875

13385

104590 8000 120980

16800 18000 180002600

18000 6000 6000 8015

5500

6700TYPAISLE

2600

R9000

R9000

R9000

6700

2710

18000

18000

18000

18000

18000

7275

2710

100595

32135

R9000R9000

R9000

R9000

6700

3000

54600

4750

6700

2350

11665

2600

6700

TYP

AISLE

5500

5500

R9000

6700

2695

39000

36400

31200

91220 6700

3600

72800 5835 6700 6225 62800 32445

R9000 R7300

R9000

R9000

7000

10450

15830

10000

12650

465

23700 13820 33620 29220 6000 1245+/-

10200 6000

6000

6000 5500 6700 5500 8410

8080

17410

6900

3230

57200

3230

6000

3200

16290

R9000

74203210

6000

R9000 R9000

4600

18000

17850

R16000

3660

R3020

10900

11365

TO FACE OF

FOUNDATION WALL

48915TO FACE OF

FOUNDATION WALL

488805910

MULOCK DRIVE

CO

LLE

GE

MA

NO

R

SITE AREA: 77,845 s.m BLDG. FOOTPRINT: 14,865 s.mLOT COVERAGE: 19.1%PERMITTED LOT COVERAGE: 20%

FIRST FLOOR GFA: 12,666 s.m

SECOND FLOOR GFA: 6,318 s.mMEZZANINE LEVEL GFA: 1,083 s.m

BLDG. TOTAL GFA: 20,067 s.m

BLDG. HEIGHT 9.3 m EAST SIDE13.3 m WEST SIDE

SITE PLAN STATISTICS

PARKING:

16 ACRE SITE: 516 SPACESADDITIONAL 3 ACRES: 302 SPACES

PARKING STALL SIZE: 2.6m x 5.5m MIN.

ACCESSIBLE STALL: 3.6m x 5.5m MIN.

ZONING INFORMATION

SETBACKS 10.7 m FRONT9.0 m SIDE10.0 m REAR

BUILDING CLASSIFICATION:

FIRST FLOOR GROUP A, DIVISION 3, 3.2.2.29., ANY HEIGHT, ANY AREA, SPRINKLERED

SECOND FLOOR: GROUP A, DIVISION 2, 3.2.2.24., UP TO 6 STOREYS, ANY AREA, SPRINKLERED

GROUP A, DIVISION 3, 3.2.2,29., ANY HEIGHT, ANY AREA, SPRINKLERED

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10/2018 5:04:24 AM

SHRC-M

a gna_C

CC-2017_detached.rvt

A00-01A

SITE PLAN

351702.000

Approver

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

15 Foundry StreetDundas, OntarioCanada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

1 : 10001 SITE PLAN

OVERALL MAP

VICINITY MAP

SITE MAP

SITE

SITE

SITE

AREA OF RENOVATION

NORTH

OTN/Multipurpose

Room 3

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017

NOT TO SCALE2 KEY PLAN

NORTHNORTHNORTH

Page 4: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

Firm Name: PERKINS+WILL CANADACertificate of Practice: Bob CurriePerkins+Will Canada15 Foundry StreetDundas, Ontario L9H 2V6The certificate of Practice Number of the holder is the holder's BCDN.

Name of Project:MAGNA CENTRE CARDIAC CLINIC RENOVATIONSLocation:800 Mulock DriveNewMarket, OntarioL3Y 9C1, Canada

Ontario Building Code Data Matrix Parts 3 & 11Item OBC Reference

Project Description:

__ New Addition

__ Change of Use X Alteration

Part 3 Part 113.2.2.383.8.3.12

1

Major Occupancy(s): Group A, Division 2 - Gymnasia 2

Building Area (m²): Existing:14,865m² | New:Unchanged | Total: Unchanged3

3.2.2.24 N/A

N/A

5 Number of Storeys: 2 Above Grade: 2 Below Grade: 0 N/A6 Number of Streets/Fire Fighter Access: 1 N/A7 Building Classification:

Group A, Division 2 - Gymnasia, Up to 6 stories, Any Area, SprinkleredSubsidiary Occupancy: Group D (Offices)

3.2.1.53.2.2.20 - 3.2.2.833.2.2.51

N/A

8 Sprinkler System Proposed

X entire building__ basement only__ in lieu of roof rating__ not required

3.2.2.173.2.2.20 - 3.2.2.83

11.3.3.211.5.1.1

9 Standpipe required Yes X No 3.2.9 N/A10 Fire Alarm required 3.2.4 N/A X Yes __ No11 Water Service/Supply is Adequate 3.2.5.7 N/A X Yes __ No

High Building12 3.2.6 N/A _ Yes X NoPermitted Construction

133.2.2.20 - 3.2.2.83 N/A

Actual Construction__ Combustible X Non-Combustible __ Both__ Combustible X Non-Combustible __ Both

Mezzanine Area m² 0 m² N/A

Occupant load based on15 3.1.17.13.2.2.243.2.2.25

N/A m²/person X design of building

unchanged

Barrier-free Design16 3.8 N/AX Yes __ No (Explain)

Hazardous Substances17 3.3.1.2 & 3.3.1.19 N/A__Yes X No (Explain) No dangerous goods use.

RequiredFire

ResistanceRating

18 3.2.2.38 & 3.2.1.4N/AHazardous Assemblies

FRR (Hours)Floor Assemblies 2 Hours

Listed Design No.or Description (SG-2)

non-combustiblenon-combustible

N/A

OBC CODE MATRIX

The architect noted above has exercised responsible control with respect to design activities. The

architect's seal number is the architect's BCDN.

Magna Cardiac Rehabiliation Clinic

non-combustible

Mezzanines 1 HoursFRR of Supporting Members

Loadbearing Elements-At least equal to the required rating for the supported assembly

Roof Assemblies N/A Hours

N/A

11.1.2.111.3.1.111.3.3.2

11.3.4

Gross Area (m²): Existing:20,067m² | New: Unchanged | Total: Unchanged41.1.3.21.1.3.23.2.2.24 | 1.1.3.23.2.2.10 | 3.2.5

TOTAL AREA OF RENOVATION: +/-308 m2

14

non-combustibleWalls N/A Hours

non-combustibleColumns 2 Hours

AREA NOT IN SCOPE OF WORK

T

U

V

W

X

Y

00 01 02

Z

X2HR X2HRX2HR X2HRX2HR X2HR

X2H

RX

2HR

X2HR X2HR X2HR X2HRX2HR X2HR

X2H

RX

2HR

X2H

RX

2HR

X2H

RX

2HR

X2H

RX

2HR

X2H

RX

2HR

X1HRX1HRX1HRX1HR X1HRX1HR

X1H

RX

1HR

X1H

R

X1HRX1HR X1HRX1HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

0HR

TOTAL DISTANCE

43131mm

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10/2018 5:04:32 AM

SHRC-Ma gna_C

CC-2017_detached.rvt

A01-01G

CODE COMPLIANCEPLANS

351702.000

Approver

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

15 Foundry StreetDundas, OntarioCanada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

1 : 1002 LEVEL 01 - CARDIAC CLINIC CODE COMPLIANCE DRAWING

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017

Page 5: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

T

U

V

W

X

Y

00 01 02

Z

T

U

V

W

X

Y

00 01 02

Z

DEMOLITION LEGEND

EXISTING PARTITION /

ITEM TO REMAIN

EXISTING TO BE REMOVED

OUT OF SCOPE AREA

WALL CONSTRUCTION KEY

NOTE:

THIS DRAWING TO BE READ IN CONJUNCTION WITH DEMOLITION

DRAWINGS FOR ALL OTHER DISCIPLINES FOR COMPLETE

SCOPE

1..

EXISTING RUBBER SPORTS FLOORING TO REMAIN

ONLY REMOVE FLOORING TO SLAB BELOW IN AREAS INDICATED

FOR ERECTION OF NEW PARTITION WALLS.

PATCH AND MAKE GOOD FLOORING TO MATCH EXISTING

FLOORING.

2.

REMOVE ANY PRE-EXISTING ADHESIVE RESIDUE/STAINS FROM

EXISTING RUBBER SPORTS FLOORING.

FLOORING TILES WITH STAINS/RESIDUE THAT CANNOT BE

REMOVED ARE TO BE PATCHED WITH FLOORING TO MATCH

EXISTING FLOORING.

3.

REMOVE PRE-EXISTING SOUND PROOFING TILES FROM CEILING.

REMOVE ANY LEFTOVER RESIDUE.

4.

REMOVE AND DISPOSE OF EXISTING FLOURESCENT LIGHT

FIXTURES ACCORDING TO DISPOSAL REQUIREMENTS OF

AUTHORITIES HAVING JURISDICTION

5.

REMOVE AND DISPOSE OF EXISTING CEILING FANS ACCORDING

TO DISPOSAL REQUIREMENTS OF AUTHORITIES HAVING

JURISDICTION

6.

REPLACE ANY PRE-EXISTING DAMAGED WALL BASE WITH BASE

TO MATCH EXISTING.

SHEET NOTES

EXISTING T-BAR CIELING GRID TO REMAIN.

NEW ACOUSTIC CEILING TILES; NEW LIGHT

FIXTURES

DM 01

DEMOLITION NOTES

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10

/201

8 5:

04:3

7 A

MS

HR

C-M

a gna

_CC

C-2

017_

deta

ched

.rvt

A05-01

DEMOLITION PLANS -LEVEL 01

351702.000

Approver

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

1 : 1001 LEVEL 01 - CARDIAC REHAB CLINIC - DEMO PLAN

15 Foundry StreetDundas, Ontario

Canada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

1 : 1002 LEVEL 01 - CARDIAC REHAB CLINIC - DEMO RCP

DM 01

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017

Page 6: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

T

U

V

W

X

Y

00 01 02

+/- 12328

+/- 5550

+/- 3566

+/- 3149

+/- 2953

4021

+/- 2275

+/- 542431023102

9722

+/- 3035

+/- 6000

+/- 4014

2698

790

EQ.

EQ.

EQ.

Z +/- 6307

+/- 3383

3563

+/- 6002

5433 1200 5695

+/- 4606

2060

2037

NOTE 01

T

U

V

W

X

Y

00 01 02

NOTE 03

Z

AP1

NOTE 02

NOTE 06

AP2

NOTE 05

NOTE 04

NOTE 07

1.

ALL DIMS ARE TO FACE OF FINISH GWB UNO.

2.

ALL PENETRATIONS SHALL BE SEALED WITH FIRE RESISITIVE

MATERIALS AS APPROVED BY AUTHORITIES HAVING

JURISDICTION

3.

ALL CONSTRUCTION IS TO BE IN COMPLIANCE W/ ALL

GOVERNING CODES AND AUTHORITIES HAVING JURISDICTION

4.

NEW FULL HEIGHT PARTITIONS

TO U/S SLAB INDICATED WITH

DASH DOT DOT DASH LINE:

5.

NEW PARTITIONS C/W SOUND BATT

INSULATION INDICATED

WITH CROSS HATCH:

SHEET NOTES

PROVIDE BRACKETS FOR CEILING MOUNTED

PROJECTOR (REF. ELEC FOR COORDINATION)

NEW TELE-POWER POLES MOUNTED TO U/S SLAB

(REF SHEET E-01)

REPLACE EXISTING ACOUSTIC CEILING TILES WITH

NEW ACOUSTIC CEILING TILES. EXISTING ATC GRID

TO REMAIN

NEW ACOUSTIC CEILING TILES @ 8' AFF

PROVIDE BRACKETS FOR WALL MOUNTED WIRELESS

ACCESS POINT DEVICE

PROVIDE BRACKETS FOR CEILING MOUNTED

WIRELESS ACCESS POINT DEVICE

CURTAIN TRACK + MOUNTING HARDWARE (SEE

A44-01)

NOTE 01

NOTE 02

NOTE 03

PLAN + RCP NOTES

NOTE 04

NOTE 05

NOTE 06

NOTE 07

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10/2018 5:04:42 AM

SHRC-Ma gna_CCC-2017_detached.rvt

A11-01

CARDIAC CLINICFLOOR PLANS - LEVEL

01

351702.000

Approver

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

1 : 1001 LEVEL 01 - CARDIAC REHAB CENTRE - FLOOR PLANS

15 Foundry StreetDundas, OntarioCanada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

1 : 1002 LEVEL 01 - CARDIAC REHAB CENTRE - RCP

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017

Page 7: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

7.83 m²

MECHANICALA252

12.66 m²

OFFICE/STORAGE/RENTALA253

19.43 m²

WAITING AREAA254

9.12 m²

OFFICE 2A255

9.00 m²

OFFICE 1A256 16.46 m²

MANAGER'S OFFICEA257

13.35 m²

TREATMENT ROOM3A258

13.26 m²

TREATMENT ROOM2A259

13.48 m²

TREATMENT ROOM1A260

9.13 m²

DR'S OFFICEA293

32.99 m²

CLASSROOMA262

20.18 m²

FILING CABINETSA263

2.49 m²

I.T.A295

20.45 m²

EXERCISE THERAPYAREAA265

13.84 m²

STAFF AREAA266

17.25 m²

CORRIDORA267

37.63 m²

EXERCISE AREAA268

31.92 m²

RECEPTION AREAA269

DEBIT

MACHINE

PRINTER / FAX

WHITEBOARD

NU STEP

PRINTER/ FAX

NOTE 01

MICROWAVE

1' - 3 3/4"

+/- 400

3' - 1 3/8"

+/- 950

2' - 11"

+/- 890

NOTE 02

VOIP

VOIP

VOIP VOIP VOIP

VOIPVOIPVOIP

VOIP

VOIP

VOIP

VOIP

VOIPVOIPVOIP

VOIP

3' - 3 1/4"

+/- 995

7' - 2"

+/- 2184

NOTE 05

COW STATION

NOTE 06NOTE 07

BOOKCASE

F. CABINET

F. CABINET

MOBILE CABINETS

F. CABINET

BOOKCASE

F. CABINET F. CABINET F. CABINET F. CABINET

OTN +MONITOR

VOIP

F. CABINET

WEIGHT

RACK

COAT RACK

TREADMILL

TREADMILL

COW STATION

TREADMILL

COW STATION

COW STATION

SCALE

SCALE

COW STATION

COW STATION

SCALE

STRETCHER

BIO SCALEWATER COOLER

SUPPLYCART

PAMPHLETAREA

T

U

V

W

X

Y

00 01 02

3' - 10 1/8"

+/- 1170

MOBILESTAND

STORAGEUNIT

F. CABINET

F. CABINETF. CABINETSTORAGE

NOTE 08

EQ.

EQ.

LOCKER

4' - 5 1/2"

+/- 1360

3' - 11 1/4"

+/- 1200

4' - 2 3/8"

+/- 1280

BIKE

5' - 10 7/8"

+/- 1800

PAMPHLETS

VOIP

BIKE

BIKE

COAT RACK

NOTE 03

NOTE 04

LOCKER

LOCKER

LOCKER

NOTE 06

NOTE 05

NOTE 04

NOTE 09

NOTE 10

A293

A257A256A255

A253

A252

A263

A295

NOTE 04

NOTE 03

NOTE 03

REFRIDGERATOR NOTE 11

Z

NOTE 12

A272

19' - 1 7/8"

5840

TV c/w STAND

NOTE 10

17' - 7 1/2"

5371

NOTE 06

13' - 10 3/8"

4226

DRAWING NOTES

1.

UNO, ALL NEW PARTITIONS @ 8' AFF

UNO, ASSEMBLIES TO BE:

16mm GBX CLADDING, 1 LAYER EA. SIDE

38.1 X 88.9 MM LIGHT GAUGE STEEL STUDS

2.

ALL FURNITURE AND EQUIPMENT NIC. :OWNER SUPPLIED AND

INSTALLED UNO.

3.

PROVIDE FIRESTOPPING AT ALL NEW PENETRATIONS AND

OPENINGS IN ALL FIRE SEPARATIONS

4.

INSTALL RUBBER WALL BASE (ASTM F-1861 - STANDARD

SPECIFICATION FOR RESILIENT WALL BASE) ON ALL NEW WALLS

5.

PAINT NEW AND EXISTING PARTITION WALLS. FINISH COLORS:

PNT: DULUX - WHITE ON WHITE, COLOR #: 30GY 88/014

PNT-1: DULUX- SHADED ICE - COLOR #: 30 GG 72/008 A0161 (Ref.

MPI: INT 5.3)

6.

NEW FULL HEIGHT PARTITIONS

TO U/S SLAB INDICATED WITH

LINE DASH DOT DOT DASH:

7.

NEW PARTITIONS C/W SOUND BATT

INSULATION INDICATED WITH

90 DEGREE CROSS HATCH:

8.

OUT OF SCOPE AREA:

SHEET NOTES

NEW FURRING TO U/S OF SLAB TO COVER EXISTING MIRROR

16mm GBX CLADDING, 1 LAYER GWB ON OUTWARD FACING

SIDE; 38.1 X 88.9 MM LIGHT GAUGE STEEL STUDS

EXISTING WINDOW, FRAME AND INFILL.

REMOVE EXISTING GBX AND EXTEND WALL ASSEMBLY TO U/S

OF SLAB TO INSTALL SOUND BATT INSULATION. FINISH AND

MAKE GOOD GBX ON EACH SIDE.

NEW SILENT GLISS 6100 TRACK SYSTEM FOR TREATMENT

ROOMS 1-3 AT 8' AFF. SUSPENDED FROM U/S SLAB WITH

SILENT GLISS V-HANGERS. CURTAINS TO IN 5-6' SECTIONS.

MOUNT CURTAINS AT 8' AFF. CURTAINS TO BE 7' LONG AND

MAINTAIN 1' CLEARANCE FROM SLAB. COORDINATE CURTAIN

TRACK SYSTEM LOCATION WITH MECHANICAL/ELECTRICAL

SYSTEMS ABOVE. SLAB TO SLAB HEIGHT AT +/- 3350.

CURTAIN FABRIC - ANTI-MICROBIAL: COL 410 - COLORAMA 2

BIOACTIVE - PLAIN TREVIRA CS FABRIC W/ CANULC-S109 FIRE

RATING

NEW PARTITIONS C/W SOUND BATT INSULATION FOR OFFICE

#1, #2. TERMINATE AT ATC.

ASSEMBLY: 16mm GBX CLADDING, 1 LAYER EA. SIDE, SOUND

BATT INSULATION

38.1 X 88.9 MM LIGHT GAUGE STEEL STUDS

NEW PARTITIONS C/W SOUND BATT INSULATION FOR

MANAGERS OFFICE TO U/S OF EXISTING CEILING. ALIGN WITH

FACE OF EXISTING BULKHEAD

ASSEMBLY: 16mm GBX CLADDING, 1 LAYER EA. SIDE, SOUND

BATT INSULATION

38.1 X 88.9 MM LIGHT GAUGE STEEL STUDS

INSTALL CONTINUOUS SOLID OAK CHAIR RAIL (50 X 250) AT

HEIGHT 800 AFF. CHAMFER EXPOSED EDGES. CONCEAL

FASTNERS, CLEAR COAT FINISH

NEW TELE-POWER DROP POLES SERVICING TREADMILLS AND

NU-STEP MACHINE. MOUNTED TO U/S SLAB C/W 90 X 300 X 6

PLATES MOUNTED TO TOP AND BOTTOM OF SLAB.

I.T. CLOSET REAR WALL TO U/S OF SLAB TO HOST

ELECTRICAL SERVICES (REF. to ELECTRICAL)

STIFFEN STUDS TO ENSURE CARRYING CAPACITY OF 70LBS

FOR WALL MOUNTED I.T. CABINET

OTHER ENCLOSING WALL HEIGHT FOR I.T. CLOSET AT 8' TYP.

2x FULL LOUVRED BIFOLD DOOR. INSTALL KNOB ON EA.

DOOR. MANUFACTURER: MASONITE OR EQUIV.

W 1829 X H 2032. STILE WIDTH: 4-3/8"

PROVIDE MOUNTING BRACKET FOR OWNER SUPPLIED

WHITEBOARD MOUNTED ON CL OF WALL.

B.O. WHITEBOARD AT 915 AFF

HSS POST (152.4 X 76.2) TO U/S SLAB FOR LATERAL SUPPORT

OF ADJACENT FREE STANDING PARTITION WALL

FORM OPENING IN EXISTING WALL TO INSTALL NEW DOOR

C/W PANIC HARDWARE AND CLOSER.

BREAK OUT COSTS AS SEPERATE PRICE ITEM.

EXISTING DOOR LOCK HARDWARE TO BE REMOVED AND

REPLACED WITH MECHANISM NOT REQUIRING KEYS OR

SPECIAL DEVICES FOR OPENING.

INSTALL PANIC HARDWARE AND DOOR CLOSER

BREAK OUT COSTS AS SEPARATE PRICE ITEM

NOTE 01

NOTE 02

NOTE 03

NOTE 04

NOTE 05

NOTE 06

NOTE 07

NOTE 08

NOTE 09

FL N F

DOOR ELEVATIONS

NOTE 10

NOTE 11

NOTE 12

FULL LOUVERED NARROW LITE FLUSH

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10/2018 5:04:51 AM

SHRC-Ma gna_CCC-2017_detached.rvt

A44-01

ENLARGED PLANS

351702.000

Approver

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

15 Foundry StreetDundas, OntarioCanada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

1 : 501 LEVEL 01 - CARDIAC REHAB CLINIC ENLARGED FLOOR PLANS

DOOR SCHEDULE

Mark Width Height Thickness Type Material Finish Glazing Frame Material Frame Types Fire Rating Comments

A253 965 2150 44 N HM PNT-1 High Impact HM KD

A257 965 2150 44 N HM PNT-1 High Impact HM KD N/A Requires Lock

A252 965 2150 44 F HM PNT-1 HM KD N/A

A255 965 2150 44 N HM PNT-1 High Impact HM KD N/A

A256 965 2150 44 N HM PNT-1 High Impact HM KD N/A

A293 965 2150 44 N HM PNT-1 High Impact HM KD N/A

A295 1829 2032 29 FL SCWD N/A N/A N/A See NOTE 08

A263 1200 2150 44 N HM PNT-1 High Impact HM KD N/A Requires Lock

A272 965 2150 44 F HM PNT-1 HM KD 45 min. Exit Door c/w Panic HW and Closer

ROOM FINISH SCHEDULE

Number Name Ceiling Finish Room Height Wall Finish Base Finish Floor Finish Comments

A252 MECHANICAL EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See NOTE 02

A253 OFFICE/STORAGE/RENTAL EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A254 WAITING AREA EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A255 OFFICE 2 ATC 2440 PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A256 OFFICE 1 ATC 2440 PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A257 MANAGER'S OFFICE EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A258 TREATMENT ROOM 3 EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A259 TREATMENT ROOM 2 EXIST. EXIST. EXIST. EXIST. EXIST.

A260 TREATMENT ROOM 1 EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A293 DR'S OFFICE EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See NOTE 02, See Sheet Note 5

A262 CLASSROOM EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A263 FILING CABINETS EXIST. EXIST. PNT COVE EXIST. See Sheet Note 5

A295 I.T. EXIST. EXIST. PNT COVE EXIST. See NOTE 08, See Sheet Note 5

A265 EXERCISE THERAPY AREA EXIST. EXIST. PNT COVE EXIST. See Sheet Note 5

A266 STAFF AREA EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

A267 CORRIDOR EXIST. EXIST. PNT COVE EXIST. See Sheet Note 5

A268 EXERCISE AREA EXIST. EXIST. PNT COVE EXIST. See Sheet Note 5

A269 RECEPTION AREA EXIST. EXIST. PNT, EXIST. COVE, EXIST. EXIST. See Sheet Note 5

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017

Page 8: MAGNA CARDIAC REHABILITION CLINIC FIT OUT ISSUED FOR … · 2018. 1. 13. · vs vision strips vwc vinyl wall covering w west w/ with w/o without wap interior wood acoustic wall panels

PARTITION INTERSECTION

STEEL STUD (SIZED PER PARTITION TYPE)

GYPSUM BOARD

ACOUSTICAL SEALANT

BATT INSULATION

JOINT REINFORCEMENT

16" MAX

16" MAX

STEEL STUD(SIZED PER PARTITION TYPE)

CONTROL JOINT

FIBER GLASS PACKING (3#-6# DENSITY)

PARTITION-WALLINTERSECTION

ACOUSTICAL SEALANT

STEEL STUD (SIZED PER PARTITION TYPE)

BATT INSULATION

GYPSUM BOARD

ACOUSTICAL SEALANT

BATT INSULATION

ACOUSTICAL SEALANT

SLIP TRACK WITH 1" EXPANSION AT STRUCTURE

SCHEDULED CEILING

SOUND ATTENUATION BATTSSTEEL STUDS

GYP BD EXTENDS TO 6"ABOVE FINISHED CEILING

LINE OF STRUCTURE

SOUND ATTENUATION BATTS

STEEL STUD RUNNER

JOINT COMPOUND @ EA SIDE(USE ACOUSTICAL SEALANT IFWALL IS NOT RATED) REF 14/A812FOR SOUND ISOLATED CONSTRUCTION@ TWO HOUR RATED WALL

FLOOR

WALL BASE

DUCT.

GYPSUM BOARD

ACOUSTICAL SEALANT (AROUND PERIMETER)

SHEET METALENCLOSURE

SOUND ATTENUATIONBATTS

STEEL STUDS

MAX

6"1/2" MIN GYP BD PENETRATION

2"5/8"

UNO

4" TYP

SCHEDULED PARTITION

LINE OF ADJACENTPARTITION (DASHED)

5/8" GYP BD

DOUBLE MTL STUD

JOINT SEALANT BOTHSIDES

HM FRAME

JAMB ANCHORS - 3PER JAMB MIN

SCHEDULED DOOR

DOOR WIDTH

AS SCHED

VARIES

1/2"

1/2" MIN GYP BD PENETRATION

1/2"

2"5/8"

SCHEDULED PARTITION

DOUBLE 6" MTL STUDBOX HEADER

JOINT SEALANT BOTH SIDES

MTL TRACK RUNNER

HM FRAME

SCHEDULED DOOR

VARIES

6" MAX

UNO

4"

LINE OF ADJACENTPARTITION

SCHEDULED PARTITION

DOUBLE MTL STUD

JOINT SEALANT (BOTH SIDES)

HM FRAME

JAMB ANCHORS -3 PER JAMB MIN

1/2"

0'

2"

1/2" MIN GYP BDPENETRATION

VARIES

14 23

A

C

B

14 23

A

C

B

SHEET NUMBER

TITLE

Approved

Checked

Drawn

Job Number

ISSUE CHART

CONSULTANTS

KEYPLAN

PROJECT

STRUCTURAL

CIVIL

MEP

LANDSCAPING

EP

BC

1/10/2018 5:04:56 AM

SHRC-Ma gna_CCC-2017_detached.rvt

A52-01

DETAILS

351702.000

Approver

MAGNA CARDIACREHABILITION CLINIC

FIT OUT

Copyright © 2016 Perkins+Will

800 MULOCK DRIVENEWMARKET, ONTARIO

L3Y 9C1, CANADA

TOWN OF NEWMARKET

MCW Consultants LTD.

15 Foundry StreetDundas, OntarioCanada L9H 2V6t 905.628.1500f 905.628.6300

www.perkinswill.com

1 : 804 ACOUSTICAL PARTITION PLAN DETAILS 1 : 805 PARTITION HEAD SECTION 1 : 807 PARTITION FLOOR SECTION1 : 806 ACOUSTICAL PARTITION SECTION

1 : 401 JAMB DETAIL 1 : 402 HEAD DETAIL 1 : 403 JAMB / HEAD DETAIL

MARK ISSUE DATE

2 ISSUED FOR PERMIT 11/10/2017

3 ISSUED FOR TENDER 11/28/2017