lv switch gear assemblies
TRANSCRIPT
-
8/3/2019 LV Switch Gear Assemblies
1/24
Type-tested
low voltage switchgear
assembliesup to 7300 A
Product informationas at: 6/2005
Industrial Electrical Power Distribution Systems
NEW! SAS low voltage switchgear assemblieswith HENCONNECT plug-in technology
for power functional units
-
8/3/2019 LV Switch Gear Assemblies
2/242
Type-tested quality
The market lead which we and our partners are able to command
tests on a solid foundation of a consistently high standard of quality.
Hensel meets the highest demands of ISO 9001 with all its operating
areas.
It is both a requirement and a promise to do everythingnot only to ensure the high level of quality of our products
in the future but also to extend it.
It can be taken for granted that we are working on the
continued optimisation of operating processes
on all levels.
Your competent partner
Temperature rise test IPH in Berlin
2
Lennestadt-Altenhundern factory
Grimma factory
Competencein low voltage switchgear assemblies
Hensel has been producing high quality low voltage switchgear
assemblies for industry, commerce and functional buildings
for more than 40 years.
Innovative systems made from insulating material and sheet steel have made
us into a leading supplier in the distribution of electrical energy.
Our switchgear manufacturing plants in Lennestadt and Grimma offer a high
level of flexibility and guarantee a reliable standard of quality.
Contents
System overview and technical data
Mi 1000
SV 250
MC 630
SAS 600/600i
SAS 2000/2000i
SAS 5000
SAS low voltage switchgear assemblies with
HENCONNECT plug-in technology for power functional units
SMC 7000
References
Pages 4 - 5
Page 6
Page 7
Page 8
Page 9
Pages 10
Page 11
Pages 12 - 17
Page 18
Pages 19 - 24
NEW!
-
8/3/2019 LV Switch Gear Assemblies
3/243
Type-tested switchgear assemblies
Technical features:
Rated current: up to 7300 A
Rated voltage: 690 V AC
Rated peak withstand current: up to IPK = 330 kA
Network systems: TN, TT, IT
Protection class: II totally insulated up to 2500 A
I with protective conductor up to 7300 A
Degree of protection: IP 30 to IP 65
During the development stage,
we place particular value on a
simple and time-saving installation
of the switchgear assembly on siteas well as sufficiently large
wiring compartments.
Our servicesOur understanding of partner-based co-operation extends
beyond the supply of products.
We are pleased to advise you on the creation of concepts for the
distribution of electrical energy.
- Calculations within the network (short-circuit currents, selectivity etc.)
can be offered by us if required
- Configuration of the low voltage switchgear assemblies
according to your ideas and local conditions
- Factory inspections and customer acceptance tests after consultation
Your competent partner
-
8/3/2019 LV Switch Gear Assemblies
4/244
Mi 1000 SV 250 MC 630
Protection class II (totally insulated) II (totally insulated) I (earthed)
Material Insulating material Sheet steel Sheet steel
Type of assembly Box-type Single cabinet Modular cabinet
Colour RAL 7032, slate grey IP 41/43 = RAL 9016,
traffic whiteIP 54 = RAL 9002,
greyish white
RAL 7032, slate grey
Operating and ambient conditions
For indoor use x x x
For outdoor use with protection against
ambient conditions
Ambient temperature
Average value over 24 hours + 35 C + 35 C + 35 C
Maximum value + 40 C + 40 C + 40 C
Minimum value - 5 C - 5 C - 5 C
Relative humidity 50% at 40C 50% at 40C 50% at 40C
short-time 100% at 25C 100% at 25C 100% at 25C
Dimensions
Width mm in 300 mm grid 300, 550, 800, 1050,
1300*(*wall-mounted cabinet only)
350, 600
Height (wall-mounted cabinet/wall-mounted distribution board) mm in 300 mm grid 650, 800, 950, 1100,
1250, 1400
650, 850, 1050
Height (floor-mounted cabinet with base) mm in 300 mm grid 1980
Height (floor-mounted cabinet without base) mm in 300 mm grid 1850 1400, 1750
Depth mm 170, 214, 255, 299
+ mounting frame =
62,5
IP 41 = 160 (up to 63
A),
IP 41 = 210,
IP 54 = 225
250
+ mounting frame =
62,5
Combinable In all directions No Laterally and at the top
Busbars Rated current [Ie] / Rated peak withstand current [IPK] / Rated short-time withstand current [ICW]
250 A (IPK 30 kA/ICW 15 KA) 250 A (IPK 30 kA/ICW 15 KA) 250 A (IPK 30 kA/ICW 15 KA)
400 A (IPK 30 kA/ICW 15 KA) 400 A (IPK 30 kA/ICW 15 KA)
630 A (IPK 45 kA/ICW 21 KA) 630 A (IPK 45 kA/ICW 21 KA)1000 A (IPK 75 kA/ICW 36 KA)
N/PEN conductor
EMC compliant in the area of phase conductors Standard Standard Standard
Same current carrying capacity as phase conductors Standard Standard Standard
Higher current carrying capacity than phase conductors
Circuit-breaker 160-630 A
Fixed part x x x
Removable part
Withdrawable part
Circuit-breaker 800 A up to maximum rated current
Fixed part
Withdrawable part
Switch-disconnector with strip type HRC fuse
Removable part
Voltage values
Rated operating voltage [Ue] AC 690 V AC 400 V AC 690 V
Rated insulation voltage [Ui] AC 690 V AC 400 V AC 690 V
Degree of pollution 3 3 3
Overvoltage category III III III
Standards and regulations
IEC 60 439-1/EN 60 439-1 Type-tested low voltage switchgear and control-
gear assembly (TTA)
x x x
IEC 439-3/EN 60 439-3 Type-tested low voltage switchgear and controlgear
assembly to which unskilled persons have access for their operation
x x x
IEC 60 439-1/EN 60 439-1 supplement 1 Personal protection in the eventof internal arcing currents
IEC 60 529 Degrees of protection provided by enclosure (IP-Code) x x x
DIN 43 880 Built-in equipment for electrical installations; overall dimensi-
ons and related mounting dimensions
x x x
IEC 999/EN 60 999 Screw-type and screwless-type clamping units for
electrical copper conductors
x x x
DIN EN 0100 Part 534 Tested lightning conductors x x x
System overview and technical data
-
8/3/2019 LV Switch Gear Assemblies
5/245
SAS 600 SAS 600i SAS 2000 SAS 2000i SAS 5000 SMC 7000
I (earthed) II (totally insulated) I (earthed) II (totally insulated) I (earthed) I (earthed)
Sheet steel Sheet steel Sheet steel Sheet steel
Cabinet system Cabinet system Cabinet system Cabinet system
RAL 7032, slate grey RAL 7032, slate grey RAL 7032, slate grey RAL 7032, slate grey
x x x x
+ 35 C + 35 C + 35 C + 35 C
+ 40 C + 40 C + 40 C + 40 C
- 5 C - 5 C - 5 C - 5 C
50% at 40C 50% at 40C 50% at 40C 50% at 40C
100% at 25C 100% at 25C 100% at 25C 100% at 25C
350, 600, 850, 1100 400, 600, 650, 850, 1000 400, 600, 650,
850, 1000
250, 350, 450, 650
1000*, 1100*, 1150(*in case of combination)
2200 2200 2200 2200/2350
2050 2050 2050
275 500 750, 1250*, 1500*(*in case of combination)
600, 1000*, 1200*,
1400*(*in case of combination)
Laterally Laterally Laterally Laterally
250 A (IPK 30 kA/ICW 15 KA) 250 A (IPK 30 kA/ICW 15 KA) 2000 A (IPK 130 kA/ICW 59 KA) 1900 A (IPK 110 kA/ICW 50 KA)
400 A (IPK 30 kA/ICW 15 KA) 400 A (IPK 30 kA/ICW 15 KA) 2500 A (IPK 130 kA/ICW 59 KA) 2500 A (IPK 176 kA/ICW 80 KA)
630 A (IPK 45 kA/ICW 21 KA) 630 A (IPK 45 kA/ICW 21 KA) 2500 A (IPK 160 kA/ICW 72 KA) 3200 A ( IPK 220 kA/ICW 100 KA)1000 A (IPK 75 kA/ICW 36 KA) 3200 A (IPK 160 kA/ICW 72 KA) 4000 A ( IPK 220 kA/ICW 100 KA)
1250 A (IPK 100 kA/ICW 45 KA) 4000 A (IPK 220 kA/ICW 100 KA) 4500 A (IPK 220 kA/ICW 100 KA)
1600 A (IPK 130 kA/ICW 59 KA) 5000 A (IPK 220 kA/ICW 100 KA) 5800 A (IPK 220 kA/ICW 100 KA)
2000 A (IPK 130 kA/ICW 59 KA) 7300 A (IPK 330 kA/ICW 150 KA)
2500 A (IPK 130 kA/ICW 59 KA)
Standard Option Option Standard
Standard Option Option Standard
Option Option Option
x x x x
x x x
x x x
x x
x x x
x x x
AC 690 V AC 690 V AC 690 V AC 690 V
AC 690 V AC 1000 V AC 1000 V AC 1000 V
3 3 3 3
III III III IV
x x x x
x
x x
x x x x
x x x x
x x x x
x x x x
-
8/3/2019 LV Switch Gear Assemblies
6/24
Mi 1000
up to 1000 A, degree of protection IP 65
Wall fixing with fastening tags. Wall fixing with mounting rai ls Wall fixing with stable mounting
frame
System benefits:
As standard with N conductor:
- with the same current carrying capacity as
the phase conductors
- EMC-compliant in the area of the phase
conductors
Also available as preassembled or partially
extended. The degree of expansion can be
agreed.
Mi-Distribution boards are also offered as
combinable type-tested boxes for self
assembly.
Incoming supply up to
1000 A with integrated
current and voltage
measurement
Easily accessible and
sufficient wiring compart-
ment even for parallel
cables. The separable
flange makes it easier to
insert the cable
Protection cover with
captive labelling strips
Box lid with quick-release
lock can be operated
manually or with a tool,
depending on the inte-
grated function
Assembled, insulation-enclosed, totally insulated, low voltage switchgear assembly in
a box-type assembly as a type-tested switchgear and controlgear assembly TTA in
accordance with IEC 60 439 -1/EN 60 439 -1, for surface mounting on walls, floor-
mounted distribution board or floor-mounted distribution board with covering,
degree of protection IP 65.
Box-type system consisting of combinable boxes of the same design, grid spacing
300 x 300 mm which can be extended in all directions.
- Standardised and type-tested modules enable the creation of all circuit variants of
a modern and reliable energy supply
- Generous wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
Built-in devices:Main busbar system:
As standard
- EMC-compliant, with N/PEN conductor in the area of the phase conductors
- N/PEN conductor with the same current carrying capacity as the phase conductors
Fixed-mounted switchgear:- Circuit-breaker 100-1000 A
- Switch-disconnector 100-1000 A
- Fuse switch-disconnector HRC 00 (160 A) - HRC 3 (630 A)
- DIN rail equipment in accordance with DIN 43 880
- KWH meter mounting boards
Bus-mounted switchgear:
- Fuse switch-disconnector HRC 00 (160 A), HRC 1 (250 A)
- Screw-in fuse bases D02, DII, DIII
Reactive current compensation:
- Fixed part
Connection:
- Cable from top and/or bottom
Areas of application:Main distribution board or subdistribution board
For the reliable supply of energy particularly in a harsh industrial environment with a
high volume of dust and high degree of humidity
- of industrial, commercial and trade buildings
- of railway companies, particularly in technical areas of all commercial departments
- Suitable for the protected outdoor use.
6
-
8/3/2019 LV Switch Gear Assemblies
7/247
SV 250
up to 250 A, degree of protection IP 41/54
Assembled, totally insulated, low voltage switchgear assembly as a type-tested switch-
gear and controlgear assembly TTA in accordance with IEC 60 439/EN 60 439 -1, in
cabinet form as a wall-mounted or floor-mounted distribution board,
degree of protection IP 41/54.
- Standardised and type-tested modules enable the creation of all circuit variants of amodern and reliable energy supply
- Generous wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
Built-in devices:Main busbar system:
As standard
- EMC-compliant, with N/PEN conductor in the area of the phase conductors
- N/PEN conductor with the same current carrying capacity as the phase conductors
Fixed-mounted switchgear:
- Circuit-breaker 100-250 A
- Switch-disconnector 100-250 A
- Fuse switch-disconnector HRC 00 (160 A) - HRC 1 (250 A)
- DIN rail equipment in accordance with DIN 43 880
- KWH meter mounting boards
Bus-mounted switchgear:
- Fuse switch-disconnector HRC 00 (160 A)
- Screw-in fuse bases D02, DII, DIII
Connection:
- Cable from top and/or bottom
Areas of application:Subdistribution board for the reliable supply of energy
- of industrial and commercial buildings
- of administration buildings and hospitals
Circuit-breaker board for DIN rail
equipment in accordance with
DIN 43 880
Termination panel with modular
terminal blocks
Fuse bases D02 on busbar 250 A
Incoming circuit-breaker and fuse
switch-disconnector HRC 1 wired
onto busbar system
Fuse switch-disconnector HRC 00
bus-mounted onto busbar system
250 A
Empty panel with mounting plate,
height adjustable
System benefits:
As standard with N conductor:
- with the same current carrying capacity as the
phase conductors- EMC-compliant in the area of the phase
conductors
-
8/3/2019 LV Switch Gear Assemblies
8/24
MC 630
up to 630 A, degree of protection IP 55
Assembled, metal-enclosed, low voltage switchgear assembly in modular cabinet form
as a type-tested switchgear and controlgear assembly TTA in accordance with
IEC 60 439/ EN 60 439 -1, as a wall-mounted or floor-mounted cabinet,
degree of protection IP 55.
Cabinet system consisting of extendable, individual panels of the same design inwidths of 350 and 600 mm, extendable on both sides and at the top and bottom.
- Standardised and type-tested modules enable the creation of all circuit variants of a
modern and reliable energy supply
- Generous wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
Built-in devices:Main busbar system:
As standard
- EMC-compliant, with N/PEN conductor in the area of the phase conductors
- N/PEN conductor with the same current carrying capacity as the phase conductors
Fixed-mounted switchgear- Circuit-breaker 160-630 A
- Switch-disconnector 160-630 A
- Fuse switch-disconnector HRC 00 (160 A) - HRC 3 (630 A)
- DIN rail equipment in accordance with DIN 43 880
- KWH meter mounting boards
Bus-mounted switchgear:
- Fuse switch-disconnector HRC 00 (160 A)
- Fuse switch-disconnector in strip type HRC 00 (160 A)
- Screw-type fuse bases D02 D02, DII, DIII
Reactive current compensation:
- Fixed part
Connection:
- Cable from top and/or bottom
Areas of application:Main distribution board or subdistribution board for the reliable supply of energy
particularly in a harsh industrial environment
- of industrial, commercial and trade buildings
- of railway companies, particularly in technical areas of all commercial departments
Due to the modular design, can be adapted to any local conditions without special components
System benefits:
Modular system can be extended in all
directions
Also available as preassembled or partially
extended. The degree of expansion can be
agreed.
MC 630 are also offered as a kit system for
self assembly.
Comprehensive range of accessories for fixing onto the unit
Wall-mounted Wall-mounted Floor-mounted Floor-mounted
distribution board distribution board distribution board distribution board,
with covering back to back
8
-
8/3/2019 LV Switch Gear Assemblies
9/249
SAS 600 / SAS 600i
up to 630 A, degree of protection IP 30/40/54
System benefits:
As standard with N conductor:
- with the same current carrying capacity as
the phase conductors
- EMC-compliant in the area of the phase
conductors
Also available as preassembled or partially
extended.
Door panels
Sufficient wiring compart-
ment in the incoming
panel
Cabinet base enables
transport with a fork-lift
truck
Fixing parts available for
floor-mounting
Door panel for totally insulated location of
built-in equipment for doors
Cabinet labelling
Areas can be identified
using different colours
Lifting eyes with dual function
1. Assembly of the cabinet panels externally
using centring elements2. Crane transport
Assembled, metal-enclosed (totally insulated) low voltage switchgear assembly in
cabinet form as a free-standing unit as a type-tested switchgear and controlgear
assembly TTA in accordance with IEC 60 439/ EN 60 439 -1,
degree of protection IP 30/40/54.
Cabinet system consisting of extendable, individual panels of the same design in widthsof 350, 600, 850 and 1100 mm
- Standardised and type-tested modules enable the creation of all circuit variants of a
modern and reliable energy supply
- Generous wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
- Totally insulated switchgear assemblies up to a rated busbar current of 630 A
Built-in devices:Main busbar system:
As standard
- EMC-compliant, with N/PEN conductor in the area of the phase conductors
- N/PEN conductor with the same current carrying capacity as the phase conductors
Fixed-mounted switchgear:
- Circuit-breaker 100-630 A
- Switch-disconnector 100-630 A
- Fuse switch-disconnector HRC 00 (160 A) - HRC 3 (630 A)
- DIN rail equipment in accordance with DIN 43 880
- KWH meter mounting boards
Bus-mounted switchgear:
- Fuse switch-disconnector HRC 00 (160 A) and HRC 1 (250 A)
- Fuse switch-disconnector in strip type HRC 00 (160 A)
- Screw-type fuse bases D02, DII, DIII
Reactive current compensation:
- Fixed part
Cablinet for 90 extension, 350 x 350 mm: Connection:- with turn around of the busbars - Cable from top and/or bottom
Areas of application:Main distribution board or subdistribution board
for the reliable supply of energy
- of industrial, commercial and trade buildings
- of railway companies, particulary in technical areas of all commercial departments
- of administration buildings, hospitals, exhibition halls etc.
-
8/3/2019 LV Switch Gear Assemblies
10/24
Sufficient wiring compartment in
the incoming panel
Cabinet base enables transport
with a fork-lift truck
Elements available for false floor-
mounting without bore holes
SAS 2000 / SAS 2000i
up to 2500 A, degree of protection IP 30/40/54
Assembled, metal-enclosed (totally insulated) low voltage switchgear assembly in cabi-
net form as a free-standing unit as a type-tested switchgear and controlgear assembly
TTA in accordance with IEC 60 439/EN 60 439 -1, degree of protection IP 30/40/54.
Cabinet system consisting of extendable, individual panels of the same design in widths
of 400, 600, 650, 850 and 1000 mm- Standardised and type-tested modules enable the creation of all circuit variants of a
modern and reliable energy supply
- Generous wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
- Totally insulated switchgear up to a rated busbar current of 2500 A
Built-in devices:Main busbar system:
- EMC-compliant, with N/PEN conductor in the area of the phase conductors
(if required)
- N/PEN conductor with the same current carrying capacity as the phase conductors
or higher (if required)
Circuit-breaker 160-630 A: Circuit-breaker 800-2500 A:- Plug-in - Withdrawable part
technology - Fixed part
- Withdrawable part
- Fixed part
Switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:
- Plug-in technology
Fuse switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:
- Fixed part
Reactive current compensation:
- Fixed part linked to the main busbar via group back-up fuse
Cabinet for 90 extension, Connection:
600 x 600 mm: - cable from top and/or bottom
- with turn around of the busbars - with busbar trunking system
from top or bottom
Areas of application:Main distribution board or subdistribution board
for the reliable supply of energy
- of industrial, commercial and trade buildings
- of railway companies, particulary in technical areas of all commercial departments
- of administration buildings, hospitals, exhibition halls etc.System benefits:
If required with N conductor:
- with the same current carrying capacity as
the phase conductors or higher
- EMC-compliant in the area of the phase
conductors
Cabinet labelling
Areas can be identified using different colours
Lifting eyes with
dual function
1. Crane transport
2. Assembly of the
cabinet panels externally
using centring elements
Cabinets with 90 extension enable
installation even in small-sized
rooms
10
newwith HENCONNECT plug-in technology
for power functional units
-
8/3/2019 LV Switch Gear Assemblies
11/2411
SAS 5000
up to 5000 A, degree of protection IP 30
Sufficient wiring compartment in
the incoming panel
System benefits:
If required with N conductor:
- with the same current carrying capacity as
the phase conductors or higher
- EMC-compliant in the area of the phase
conductors (option, following agreement)
Busbar system
The busbar system lies in the rear part of the
cabinet.
The busbar system can change in heights of
cabinets in the course of the installation which
simplifies the use of bus-couplers.
Depending on the design up to form 4a can be
used.
Assembled, metal-enclosed, low voltage switchgear assembly in cabinet form as a
free-standing unit as a type-tested switchgear and controlgear assembly TTA in
accordance with IEC 60 439/EN 60 439 -1, degree of protection IP 30.
Cabinet system consisting of extendable, individual panels of the same design in widths
of 400, 600, 650, 850 and 1000 mm- Standardised and type-tested modules enable the creation of all circuit variants of
a modern and reliable energy supply
- Generous wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
Built-in devices:Main busbar system:
- EMC-compliant, with N/PEN conductor in the area of the phase conductors (if required)
- N/PEN conductor with the same current carrying capacity as the phase conductors
(if required)
Circuit-breaker 160-630 A: Circuit-breaker 800-5000 A:
- Plug-in technology - Withdrawable part
- Fixed part
- Withdrawable part
- Fixed part
Switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:
- Plug-in technology
Fuse switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:
- Fixed part
Reactive current compensation:
- Plug-in technology (via distribution busbar)
Cabinet for 90 extension, 850 x 850 mm:
- with turn around of the busbars
Connection:
- cable from top or bottom
- with busbar from top or bottom
Areas of application:Main distribution board
for the reliable supply of energy
- of industrial, commercial and trade buildings
- of railway companies, particulary in technical areas of all commercial departments
- of administration buildings, hospitals, exhibition halls etc.
Access from
one side
Back-to-back
with a central
busbar system
Back-to-back with
two separate central
busbar systems
Cabinets with
90 extension
including busbars
In assemblies
with several trans-
formers, a busbar
link can be set up
with a 250 mm
deep cabinet
Plan view:
Space for busbars
wiring space
Space for equipment
newwith HENCONNECT plug-in technology
for power functional units
-
8/3/2019 LV Switch Gear Assemblies
12/24
SMC 7000
up to 7300 A, degree of protection IP 31
System benefits:
If required with N conductor:
With the same current carrying capacity as the
phase conductors,
EMC-compliant in the area of the phase con-
ductors.
Outgoing feeder cabinet with switch-
disconnector with strip type HRC
fuse, sizes HRC 00 - HRC 3
bus-mounted onto distribution busbar and exchangeable under voltage.
Cable entry from top or bottom via a separate termination cabinet
available in the widths 350, 450, 650 mm
Connection with busbar from above Cabinet base enables transport
with a fork-lift truck
The outgoing circuits up to 630 A can be replaced during operation (without disconnecting the switchgear assembly)
Assembled, metal-enclosed, low voltage switchgear assembly in cabinet form as a free-
standing unit as a type-tested switchgear and controlgear assembly TTA in accordance
with IEC 60 439-1/EN 60 439 -1, degree of protection IP 31.
Cabinet system consisting of extendable, individual panels of the same design in widths
of 250, 350, 450 and 650 mm- Standardised and type-tested modules enable the creation of all circuit variants of a
modern and reliable energy supply
- Sufficient wiring compartments save time when connecting the cables
- Practical devices for transport and installation make it easier to work on site
Built-in devices:Main busbar system:
- EMC-compliant, with N/PEN conductor in the area of the phase conductors (if required)
- N/PEN conductor with the same current carrying capacity as the phase conductors
(if required)
Circuit-breaker 160-630 A: Circuit-breaker 800-6300 A:
- Removable part - Withdrawable part
- Withdrawable part- Fixed part
Switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:
- Removable part
Reactive current compensation:
- Removable part
(via distribution busbar)
(no cable connection required))
Connection:
- cable from top, bottom or from the rear side
- with busbar from top or bottom
Areas of application:
Main distribution board for the reliable supply of energy- of industrial, commercial and trade buildings
- of railway companies, particulary in technical areas of all commercial departments
- of administration buildings, hospitals, exhibition halls etc.
Power functional unit NS 250/630
in polyfast as plug-in technology
Power functional unit NS 250/630
with polyfast as withdrawable part
Power functional unit as
removable part
Power functional unit NS 250/630
in polyfast as plug-in technology
12
-
8/3/2019 LV Switch Gear Assemblies
13/2413
SAS
with HENCONNECT plug-in technology
for power functional units
Replacement or removement of individual power functional units
entirely from the assembly even though the circuit to which it is
connected may be live.
Switchgear
switch-disconnector with fuse
circuit-breaker
in plug-in technology
newwith HENCONNECT
plug-in technology
for power functional units
13
-
8/3/2019 LV Switch Gear Assemblies
14/2414
SAS
with HENCONNECT plug-in technology
for power functional units
Switch-disconnector with strip type HRC fuse
Sizes: HRC 00 / 160 A up to HRC 3 / 630 A
Main incoming circuit: disconnecable
Main outgoing circuit: fixed connection
- Replacement or removement of the switchgear or connecting the cable even though
the circuit to which it is connected may be live increases the availability of electrical
energy in production lines and buildings and saves costs.
- Switch-disconnectors with HRC fuse including double disconnection (before and after
the HRC fuse *) increase personal safety during switching operation and removing the
HRC fuse (replacing of the fuse is possible because all parts are not live).
Remote interrogation of all electrical va-
lues, fuse monitoring and remote operati-
on via motor drive are possible with a
BUS system (Type: SASIL).
Individual power function units can be re-
placed or removed even though the circuit
to which it is connected may be live.
The power functional units are bus-
mounted onto a distribution busbar,
centreline spacing 185 mm..
The distribution busbar up to 2000 A
is covered (IP XXB).
The connections can be realized in
form 4a.
It is possible to carry out connections
safely without interrupting the other
outgoing circuits.
Horizontal layout: Vertical layout:
Switch-disconnector with fuse in plug-in
technology
SAS 2000
operation
behind the
door:
protection
class I
and
protectionclass II
up to IP 54
SAS 2000/5000
operation
from the front:
protection class I
IP 30
SAS 2000
operationbehind the door:
protection class I
and
protection class II
up to IP 54
14
*
-
8/3/2019 LV Switch Gear Assemblies
15/2415
SAS
with HENCONNECT plug-in technology
for power functional units
Circuit-breaker 80 - 630 A
Main incoming circuit: disconnecable
Main outgoing circuit: fixed connection
- Replacement or removement of the switchgear or connecting the cable even though
the circuit to which it is connected may be live increases the availability of electrical
energy in production lines and buildings and saves costs.
- The incoming parts of circuit-breakers up to 630 A are linked with the distribution
busbar in plug-in technology. The plugged parts are removable even though the circuit
to which it is connected may be live.
Control wiring is linked via plug-in contacts.
Power functional units up to 80 A in plug-
in technology, 3- or 4-pole.
Main incoming circuit: disconnectable.Main outgoing circuit: fixed.
Power functional units up to 160-630 A in
plug-in technology, 3- or 4-pole.
Main incoming circuit: disconnectable.Main outgoing circuit: fixed.
The power functional units are bus-
mounted onto a distribution busbar,
centreline spacing 70 mm.
The distribution busbar up to 2000 A
is covered (IP XXB).
Individual power function units can be re-
placed or removed even though the circuit
to which it is connected may be live.
Current transformers can be mounted on
the power functional unit.
Control wiring is connected via easily
accessible control terminals.
Circuit-breaker in HENCONNECT
plug-in technology
-
8/3/2019 LV Switch Gear Assemblies
16/2416
SAS
with HENCONNECT plug-in technology
for power functional units
Circuit-breaker 80 630 A
Main incoming and outgoing circuits: disconnecable
- Replacement or removement of the switchgear or connecting the cable even though
the circuit to which it is connected may be live increases the availability of electrical
energy in production lines and buildings and saves costs.
- The incoming parts of circuit-breakers up to 630 A are linked with the distribution
busbar in plug-in technology. The plugged parts are removable even though the circuit
to which it is connected may be live.
Control wiring is linked via plug-in contacts.
Power functional units up to 160-630 A in
plug-in technology, 3- or 4-pole.
Main incoming and outgoing circuits:
disconnectable
The plugged part is wear-resistant and re-
movable even though the circuit to which
it is connected may be live.
The power functional units are bus-
mounted onto a distribution busbar,
centreline spacing 70 mm.The distribution busbar up to 2000 A
is covered (IP XXB).
Individual power function units can be re-
placed or removed even though the circuit
to which it is connected may be live.
Current transformers can be installed
within the termination compartment.
The connections can be realized in
form 4a.
It is possible to carry out connections
safely without interrupting the other
outgoing circuits.
Circuit-breaker in HENCONNECT
plug-in technology
16
-
8/3/2019 LV Switch Gear Assemblies
17/241717
SAS
with HENCONNECT plug-in technology
for power functional units
Termination cabinet
- Termination cabinet in 3 widths (400, 600, 850 mm)
Can be combined left or right or between cabinets with outgoing circuits
(refer to combination examples on page 18)
-The cabinet width is selectable depending on the number of connecting cables .
and the maximum dimensions on site.
The use of cable fixing rails on two levels
enables a larger number of outgoing
cables to be fixed in position.
Termination cabinet
400 mm wide
The N (PEN) and PE connecting bars are
designed with EMC compliance.
Termination cabinet600 mm wide
The connections can be realized in
form 4a.
It is possible to carry out connections
safely without interrupting the other
outgoing circuits.
Termination
cabinet
850 mm wide
Termination cabinet
-
8/3/2019 LV Switch Gear Assemblies
18/2418
SAS
with HENCONNECT plug-in technology
for power functional units
Combination examples
SAS 5000
Left:Switch-disconnector
with fuse,
main incoming circuit in
HENCONNECT
plug-in technology,
cabinet 650 mm wide
Right:
Termination cabinet
400 mm wide
SAS 2000
Left:Termination cabinet
600 mm wide
Right:
Switch-disconnector
with fuse,
main incoming circuit
in HENCONNECT
plug-in technology,
cabinet 650 mm wide
SAS 2000
Left:
Circuit-breaker,
main incoming and
outgoing circuit in
HENCONNECT
plug-in technology,
cabinet 650 mm wide
Right:
Termination cabinet
600 mm wide
SAS 5000
Left:
Switch-disconnector
with fuse,
main incoming circuit
in HENCONNECT
plug-in technology,
cabinet 650 mm wide
Centre: Termination
cabinet 600 mm wide
Right:
Switch-disconnector
with fuse,
main incoming circuit
in HENCONNECT
plug-in technology,
cabinet 650 mm wide
SAS 5000
Left:
Circuit-breaker,
main incoming circuit
in HENCONNECT
plug-in technology;
cabinet 650 mm wide
Right:
Termination cabinet
850 mm wide
SAS 5000Left:
Circuit-breaker,
main incoming
and outgoing
circuit in
HENCONNECT
plug-in technology,
cabinet 850 mm
wide
Centre:
Termination
cabinet
850 mm wide
Right:
Switch-disconnector with fuse, main incoming circuit in HENCONNECT
plug-in technology, cabinet 650 mm wide
-
8/3/2019 LV Switch Gear Assemblies
19/2419
References
Examples
Zwischentitel
folgt
-
8/3/2019 LV Switch Gear Assemblies
20/24
Mi 1000
up to 1000 A, degree of protection IP 65
Low voltage switchgear assembly:
Mi 1000
Mi 1000 switchgear assembly installed in the protective
cabinet for controlling and monitoring railway platform
lighting with remote signalling device.
Low voltage switchgear assembly:
Mi 1000
Railway company
Subdistribution board
Low voltage switchgear assembly:
Mi 1000
Wind power station
Mi installed in cable distribution cabinet
20
-
8/3/2019 LV Switch Gear Assemblies
21/2421
SAS 600 / SAS 600i
up to 630 A, degree of protection IP 30/40/54
Low voltage switchgear assembly:
SAS 600
Car dealer
SAS 600, main distribution board with 3 cabinets,
rated busbar current 250 A,circuit-breaker 160 A
Cabinet 1: Measurement of consumption from the power
supply company
Cabinet 2: Low voltage main distribution board
Low voltage switchgear assembly:
SAS 600
Historical hotel site
Low voltage switchgear assembly:
SAS 600
Exhibition centre
Subdistribution boards SAS 600, SAS 2000 and
SV-Wall-mounted distribution boards for halls,
main entrances and auxiliaries for general power supply
-
8/3/2019 LV Switch Gear Assemblies
22/24
SAS 2000 / SAS 2000i
up to 2500 A, degree of protection IP 30/40/54
Low voltage switchgear assembly:
SAS 2000
Office and administrative building
Low voltage switchgear assembly:
SAS 2000
Shopping centre
Low voltage switchgear assembly:
SAS 2000
Hospital
Distribution board for supplying the medical area
22
-
8/3/2019 LV Switch Gear Assemblies
23/2423
SAS 5000
up to 5000 A, degree of protection IP 30
Low voltage switchgear assembly:
SAS 5000
Hospital
Low voltage switchgear assembly:
SAS 5000
Hospital
Low voltage switchgear assembly:
SAS 5000
Broadcast and telestation, Inselberg
-
8/3/2019 LV Switch Gear Assemblies
24/24
X0
6.0
5/?/??
Gustav Hensel GmbH & Co. KGIndustrial Electrical Power Distribution System
HENSEL products are available from MARYLAND METRICS
P.O. Box 261 Owings Mills, MD 21117 USAph: (410)358-3130 (800)638-1830 fx: (410)358-3142 (800)872-9329