lv eaton common single line diagram
DESCRIPTION
Common Low Voltage single line diagram for EATONTRANSCRIPT
![Page 1: LV Eaton common single line diagram](https://reader035.vdocuments.mx/reader035/viewer/2022080210/553efd564a795946178b46a8/html5/thumbnails/1.jpg)
Low voltage systems for all applications
Dedicated low voltage system contacts: Tel: 01296 393 322 Fax: 01296 310 334 E-mail: [email protected] Website: www.eaton.com/uk
Total SolutionEaton’s comprehensive Low Voltage System product portfolio has been specifi cally designed to meet the needs of all types of installation. The extensive portfolio includes:
• Power supply and control assemblies (PSCs)
• Package sub-stations
• Main Switchboards
• Sub-main Switchboards
• Busbar trunking
• Motor control centres
• Power factor correction
• Harmonic fi ltration
• Voltage reduction devices
• Engineered assemblies
Power distribution busbar trunking
Lux lighting LP & MP distribution XP Cu low loss XP Al low loss
Verifi ed in accordance with IEC 60439-2, EN 60439-2, BSEN 60439-2
Rated Voltage, Ue (V) 415 415 1000 1000
Rated insulation voltage, Ui (V) 690 500 (LP) 690 (MP) 1000 1000
Rated Frequency (Hz) 50 50 50 50
Horizontal busbar ratings, Ith (A) 25–63 40–800 500–6300 800–4000
Vertical busbar ratings, Ith (A) 25–63 40–800 500–6300 800–4000
Busbar withstand ratings, Icw (kA) 2.6 (25A), 2.8 (40A), 80 40–100 40–100 3.4 (63A) (fuse rated at busbar Ith)
IP Rating IP41, IP55 IP4X, IP54 IP4X, IP54 IP4X, IP54
Confi guration 4 & 6 Bar (25 & 40A), 5 Bar 3, 4, 5, 5N*, 6 Bar 3, 4, 5, 5N*, 6 Bar 4 Bar (63A) (* = 200% Neutral) (* = 200% Neutral)
Busbar Material Copper Copper Copper Aluminium
Casing Material Aluminium Aluminium Aluminium Aluminium
Standard Lengths (m) 1, 3 1, 2, 3 1, 2, 3, Custom 1, 2, 3, Custom lengths from 200mm lengths from 200mm
Feeder confi gurations 4 End, Reverse End & Centre End, Reverse End & End, Reverse End & Centre Fed, Flange Centre Fed, Flange
Feeder Terminal Capacity (mm2) 2.5 25 (40A) 4 x 240 4 x 240 35 (63–80A) 70 (100–125A) 70 (125–160A) 150 (250A) 2 x 95 (400A) 2 x 185 (630A) 2 x 300 (800A)
Tap Offs Per 3m 3 8 (40-400A) 8 8 7 (630A) 6 (800A)
Tap Off Faces 1 1 2 2
Tap Off Types 4 Pole 6A BS1363 Twin Socket Fused Combination Fused Combination 6 Pole 8A BS60309 SP or TP Socket Switches 63–630A Switches 63–630A 6 Pole 10A, All Fusible SP or TP MCB MCCBs MCCBs SPSN RCCB 20–630A 20–630A RCBO BS88 Fuse 8 to 100A Switched BS88 Fuse 8 to 100A MCCBs 16–250A TPN or 4P Fuse Combination Switches: 160A,–250A SPN 160–315A TPN Residential riser
Sub-main switchboards
Verifi ed and Certifi ed in accordance with IEC 61439-2, EN 61439-2, BSEN 61439-2, IEC 60439-1, EN 60439-1, BSEN 60439-1
Rated Voltage, Ue (V) 415, other ratings on request
Rated Frequency (Hz) 50, 60, 400
Rated insulation voltage, Ui (V) 1000
Rated Impulse withstand, Uimp (kV) 6–8
Horizontal busbar ratings, Ith (A) 400–1250
Vertical busbar ratings, Ith (A) 400–1250
Busbar withstand ratings, Icw (kA) 35, 50kA
IP Rating IP31, IP41, IP42
Construction style Modular, cubicle with steel end plates
Paint fi nish RAL 7035
Form of separation Form 2 Type 2, Form 3B Type 2, Form 4 Types 2, 5, 6
Access Front
Cabling access Top or bottom
Standard Modules MCCBsFused Combination SwitchesMCBsDigital and Analogue meteringDNO Metering chambersProtection relaysSurge divertersPower factor correction modulesHarmonic fi ltration modules
Engineered assemblies
Verifi ed and Certifi ed in accordance with Relevant IEC and BSEN Standards
Rated Voltage, Ue (V) 415, other ratings on request
Rated insulation voltage, Ui (V) 1000
Rated Frequency (Hz) 50, 60, 400
Rated Impulse withstand, Uimp (V) 6–8
IP Rating IP31 to IP65
Paint fi nish RAL 7035
Form of separation 1 to 4
Access Front
Cabling access Top or bottom
Devices & Modules ACBsMCCBsFused Combination SwitchesMCBsDigital and Analogue meteringDNO Metering chambersProtection relaysSurge divertersChange-over Units
Power factor correction units
Verifi ed and Certifi ed in accordance with IEC 61439-2, EN 61439-2, BSEN 61439-2, IEC 60439-1, EN 60439-1, BSEN 60439-1
Rated Voltage, Ue (V) 415, other ratings on request
Rated Frequency (Hz) 50Hz
Rated insulation voltage, Ui (V) 1000
Rated Impulse withstand, Uimp (kV) 6–8
kVAr Up to 1600
Step sizes (kVAr) 12.5, 25, 50, 100
Types Standard and de-tuned
IP Rating IP31
Paint fi nish RAL 7035
Form of separation Form 1, Form 2, Form 4 Types 2, 6
Access Front
Cabling access Top or bottom
Devices ACBsMCCBsFused Combination SwitchesStage ProtectionDIN or BS88 Fuses
Package sub-stations
MV SWITCHGEARMV Ring Main Units Eaton Xiria Vacuum
MV Circuit Breakers/Switchboards Eaton SVS Vacuum
Verifi ed in accordance with IEC 62271-100, IEC 62271-102, IEC 62271-103, IEC 62271-105, IEC 62271-200, IEC 60265, IEC 60044-1, IEC 60044-2
TRANSFORMERS Verifi ed in accordance with IEC60726, BS171
Type Cast Resign, Vacuum Impregnated
Ratings (MVA) 0.5–4
Rated Voltage, Ue (kV) Primary: 6, 11, 12 Secondary: 0.4 – 0.69
Rated Frequency (Hz) 50
Vector Group Dyn11 (others on request)
Rated insulation voltage, Ui (kV) Primary: 75 Secondary: 1
Rated Impulse withstand, Uimp (kV) MV:75 LV:6-8
Power Frequency Withstand (kV) MV: 28 LV: 3
Winding material Aluminium or Copper
Insulation Class F
Impedance (%) 6-7
IP Rating Transformer Housing: IP20 & IP21
Construction style Modular, cubicle with steel end plates
Paint fi nish RAL 7035
Access Front or front and Rear
Cabling access Top or bottom
LV SWITCHBOARDS Eaton See “Main Switchboards”
Generator connection points
Verifi ed and Certifi ed in accordance with IEC 61439-2, EN 61439-2, BSEN 61439-2, IEC 60439-1, EN 60439-1, BSEN 60439-1
Rated Voltage, Ue (V) 415–690
Rated Frequency (Hz) 50, 60, 400
Rated insulation voltage, Ui (V) 1000
Rated Impulse withstand, Uimp (kV) 6–8
Current Ratings, Ith (A) 250–3200
IP Rating IP56, IP65
Construction style Flush-front, free-standing steel enclosure, fl oor or wall mounting
Standard colour RAL 7035
Form of separation Form 4 Types 2, 6, 7
Access Front
Cabling access Top or bottom
Standard Modules ACBsMCCBsFused Combination SwitchesTerminal inTerminal outInterlocked plugs-socketsCable lug connections
High IP rating insulated switchboards
Verifi ed and Certifi ed in accordance with IEC 61439-2, EN 61439-2, BSEN 61439-2, IEC 60439-1, EN 60439-1, BSEN 60439-1
Rated Voltage, Ue (V) 415–690
Rated Frequency (Hz) 50, 60, 400
Rated insulation voltage, Ui (V) 1000
Rated Impulse withstand, Uimp (kV) 6–12
Horizontal busbar ratings, Ith (A) 500–600
Busbar withstand ratings, Icw (kA) 35, 50
IP Rating IP56, IP65
Construction style Modular Polycarbonate Enclosures
Standard colour RAL 7035
Form of separation Form 4 Types 2, 7
Protection Class Total Insulation
Impact strength Enclosures IK09 Covers IK10
Access Front
Cabling access Top or bottom
Standard Modules MCCBsFused Combination SwitchesMCBsFusesDigital and Analogue meteringDNO Metering chambersSurge diverters
Main switchboards
Verifi ed and Certifi ed in accordance with IEC 61439-2, EN 61439-2, BSEN 61439-2, IEC 60439-1, EN 60439-1, BSEN 60439-1, IEC 61641
Rated Voltage, Ue (V) 415–690 other ratings on request
Rated Frequency (Hz) 50, 60, 400
Rated insulation voltage, Ui (V) 1000
Rated Impulse withstand, Uimp (kV) 6-8
Horizontal busbar ratings, Ith (A) 500–6300
Vertical busbar ratings, Ith (A) 700–2500
Busbar withstand ratings, Icw (kA 1s) 35, 50, 80, 100
IP Rating IP31, IP42, IP54
Construction style Modular, cubicle with steel end plates
Paint fi nish RAL 7035
Form of separation Form 4 Types 2, 3, 5, 6, 7
Cable boxes Externally and/or internally mounted
Access Front or front and Rear
Cabling access Top or bottom
Standard Modules ACBsMCCBsFused Combination SwitchesMCBsDigital and Analogue meteringDNO Metering chambersArcon arc-fault protectionProtection relaysSurge divertersPower factor correction modulesHarmonic fi ltration modulesVoltage reduction modules
Motor control centres
Verifi ed and Certifi ed in accordance with IEC 61439-2, EN 61439-2, BSEN 61439-2, IEC 60439-1, EN 60439-1, BSEN 60439-1, IEC 61641
Rated Voltage, Ue (V) 415–690 other ratings on request
Rated Frequency (Hz) 50, 60
Rated insulation voltage, Ui (V) 1000
Rated Impulse withstand, Uimp (kV) 6–12
Horizontal busbar ratings, Ith (A) 500–6300
Vertical busbar ratings, Ith (A) 500–1420
Busbar withstand ratings, Icw (kA 1s) 35, 50, 80, 100
IP Rating IP42, IP54
Construction style Modular, cubicle with steel end plates
Paint fi nish RAL 7035
Form of separation Form 4 Types 2, 3, 5, 6, 7
Cable boxes Externally and/or internally mounted
Access Front or front and Rear
Cabling access Top or bottom
Standard Modules ACBsMCCBsFused Combination SwitchesDOL and Star-delta StartersSoft-StartersVariable Speed DrivesMotor Management Systems (Eaton Clink II)Digital and Analogue meteringArc-free constructionProtection relaysSurge diverters