low_voltage_switchboard
TRANSCRIPT
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
SIVACON: The Obvious Solution forGlobal Challenges
• Safety and proven quality for every system by type testing ( TTA )
• Know-how of technological leader SIEMENS
• Manufactured by AUTOMATICA - authorisedSIVACON Technology Partner
• Globally applicable switchgear of SIEMENS
• A product of the German`s technology made in ROMANIA
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
The Unique Combination
• High standard
• Type-tested
• Know-how
• Image & resources
• Close customer contact
• High flexibility
• Regional experience
AUTOMATICA
•SIVACON•Technology
•Partner
Proximity to the customer +
World trade name
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
PartnershipCertificate
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
AUTOM
ATICA
IT Tool SIMARIS SIVACON Goal: Support for the Business Success
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
SIVACON 8PT - Design Overview
Applicable as - Power Center- Main Distribution Board- Sub Distribution Board- Motor Control Center
- Process Automation
3 Main Current classes- 3200 A- 4000 A- 7400 A
Innovative Module Technology
Manufacturing friendly concept
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Busbar Systems 8PT
Rated current up to 3200 A up to 4000 A up to 7400 A30 kA up to 80 kA/1s 30 kA up to 100 kA/1s 150 kA/1s
17,3 kA up to 45 kA/3s 17,3 kA up to 80 kA/3s 120 kA/3sRated peak withstand current 75 kA up to 200 kA 75 kA up to 250 kA 375 kA
Poles1 x 40 x 10 3 x 40 x 10 3 x 80 x 10 + 3 x 40 x 10
up to up to up to2 x 100 x 10 3 x 100 x 10 3 x 100 x 10 + 3 x 100 x 10
Busbar location
Cubicle depth 600 / 800 / 1000 mm 800 / 1000 / 1200 mm 800 / 1000 / 1200 mm
Cubicle height 2200 mm 2200 mm 2600 mm
Rated short-time withstand current
Cross section per phase
at the top
3- and 4-pole
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Circuit-Breaker Design -Type FCB
Compact, Reliable and User-Friendly
Functions: Supply, Feeder, or Coupling Cubicle
- cubicle width: 600, 800, 1000, 1200 mm
- Equipped with withdrawable or fixed mounted 3WN or 3WL circuit breakers
- Current range from 630 to 6300 A
- Reliable travel of the circuit breaker while the door is closed
- Cable or busbar connection optionally from above or below
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Outgoing Feeders Fixed-mounted Design - Type OFF
Economical, Reliable and Variable
- cubicle width: 600mm (without separate cable connection compartment)
800mm, 1000, 1200 mm
- Any combination of modular cable feeders
- Installation of non-fused and fused devices of nominal current up to 630 A (3NP, 3RV, 3VF, 3VL, 3KL)
- Vertical busbar system with rated current: 1400A
- Type: 3- and 4-pole
- Device connection without hole punching or drilling
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Outgoing Feeders Fixed-mounted Design OFFD for In-Line Fuse Switch-Disconnector 3NJ4
Economical, Reliable and Variable
- Cubicle width: 600 mm, 800 mm, 1000 mm
- Installation of in-line fuse switch-disconnectors
type 3NJ4
- Cable feeders up to 630 A
- Max. 25 cable feeders up to 160 A
- Current transformer available
- Internal separation max. Form 2b
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Outgoing Feeders Plug-in Design OFPDfor In-Line Switch-Disconnector 3NJ6 with Fuses
Plugged in Swiftly, Always Safe
• Cubicle width: 1000mm, 1200mm
• Internal separation: Form 1, Form 2b, Form 3b, Form 4b
• 3- and 4- pole
• Rated current of the vertical busbar up to 2100A
• Short-circuit strength Ipk: 125 kA Icw: 50kA/1s
• Cable feeders up to 630A
• Up to 34 plug-in, in-line switch-disconnectors
• Degree of protection: up to IP41
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Power Factor Correction Cubicle PFCLower Costs with Enhanced Safety
• Cubicle width: 800mm
• Ventilated up to IP42
• Non-choked power factor correction-unit 4RY (Modl) up to 500 kvar per unit
• Choked power factor correction-unit 4RF (Modl) up to 350 kvar
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Cubicle for Customised Solution CCS
Plenty of Space for Flexibility
• Cubicle width: 600 mm, 800 mm, 1000 mm
• Internal separation: Form 1, Form 2b, Form 4a
• Cubicle-high doors
• Cubicle distribution busbar system :- Rated current: up to 1200 A- Rated short-time withstand current: up to 65kA/1s- 3- and 4-pole- Cross section per phase: 1 x 40 x 10 or
1 x 60 x 10 mm
• Standard mounting parts:- Transverse traverses- Mounting plate sheet metal
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Plug-in Design OFPMVersatile with Safety
Functions: Motor Control Center in Plug-In Design
• Cubicle width: 1000mm
• Device compartment height: 1700mm
• Internal separation: Form 1 and 2b
• Fused and non-fused construction
• Motor feeders up to 250kW
• Cable feeders up to 630A
• High component density up to 22 plug-in modules per cubicle
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Plug-in Design
• Vertical busbar system:
- Rated current: up to 1170A
- Short-circuit strength Ipk: up to 163 kA
Icw: up to 65 kA/1s
Icw : up to 50 kA/3s
- Type: 3- and 4-pole
- Cross section of vertical busbar per phase: 1 x 40 x 10 or1 x 60 x 10 mm
- Additionally with save-to-touch cover (IP20B)
- Sidewise guide rails for safe in-plugging
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Plug-in unit
Power contacts 3- and 4-pole
Base plate
Device support
Terminal block for control circuit
Smallest height plug-in of unit: 75mm
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Plug-in unit
Plug-in unit, module height 75 mmDirect on line starting for motors up to 11 kWFuseless design
Plug-in unit, module height 175 mmDOL starting and reversing formotors up to 45 kWFused design
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Withdrawable-unit Design OFWHighly Available with Safety
Functions: Motor Control Center in Withdrawable-Unit Design
• Cubicle width: 600 / 1000mm
• Cable connecting compartment at the rear or at the right side in the cubicle
• Internal separation: Form 3b, Form 4b
• Module grid: 50 mm
• Up to 17 withdrawable units with 100mm per cubicle
• Fused and non-fused design
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Withdrawable-unit Design - Withdrawable Principle
Disconnected position: Test position: Connected position:
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Withdrawable-unit Design
• Vertical busbar system:
- Rated current: up to 1170A
- Short-circuit strength Ipk: up to 163 kAIcw: up to 65 kA/1s
Icw : up to 50 kA/3s
- Type: 3- and 4-pole
- Cross section of vertical busbar per phase: 1 x 40 x 10 or 1 x 60 x 10 mm
- Save-to-touch cover (IP20B)
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Withdrawable-unit Design
• Disconnected, test, connected position
• Nominal current up to 630A
• With fused and non-fused design
• Unit sizes: 100, 150, 200, 300, 400, 500, 600, 700mm
• Positioning support to overcome the insertion forces
• Hinged front panel for module hight200mm
• Lockable in disconnected position
• Star-delta circuit from unit size 200mm
• 40-pole control plug with module slot for PROFIBUS connection
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Withdrawable-unit Design - The intelligent connection between motor feeder and automation- / process control system
SIMOCODE-DP
PROFIBUS-DP cyclical exchange of dataof control-, and signal data. Moreover exchange of diagnostics by changing and parameterization at SPS-running-up
PC or PU withWin-SIMOCODE-DP/Professional
SIMATIC S5/S7/C7/M7 and PCS7 withPROFIBUS-DP Communication processor
PROFIBUS-DP-standard extension, online parameterization, diagnostics and test via acyclical reading and writing of data
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
Type-tested Switchgear and Controlgear Assembly ( TTA )
SIGNED, SEALED and DELIVERED SAFETYReference standard: IEC 60439-1
• Verification of temperature rise limits by test
• Verification of dielectric properties by test
• Verification of the short-circuit withstand strength by test
• Verification of the protective circuit
• Verification of clearances and creepage distances
• Verification of mechanical operation
• Verification of the degree of protection
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
SIVACONInternal arc testing
Test underinternal fault conditions
• Not specified in IEC 60439-1
• Special test to IEC 61641 (Report) orVDE 0660 Part 500,supplement 2
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
SIVACONInternal arcs - Test sequence
0 ms 40 ms 80 ms 120 ms
160 ms 200 ms 280 msArc strikes in circuit-breaker panel Burning duration tp = 310 ms U = 690 V + 5 % Icw = 52 kA
Low-Voltage Switchboard SIVACON 8PT
AUTOMATICA
SIVACONTechnical informations / Operating Instructions