Page 1: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Power Safe Solutions for All

ISO 14001:2004 Certified ISO 9001:2008 Certified

LOW VOLTAGE HRC FUSE RANGE

LAWSON

Page 2: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Power Safe Solutions for All

LAWSON

LAWSON FUSES INDIA LTDLawson Fuses India Ltd is a wholly owned subsidiary of Lawson Fuses Ltd,a long established UK

company with a worldwide reputation for product quality and service excellence.

Page 3: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

LOW VOLTAGE HRC FUSE RANGE

500Volt DIN NH Fuse System Description Fuse-links, sizes 000, 00, 0, 01, 02, 03 Solid/Neutral Links, sizes 00, 0, 01, 02, 03 Replacement Handle Fuse-bases, size 00, 01, 02, 03

415 Volt BS Fuse System Fuse-linksDescription Fuse-link current ratings and dimensions Motor Circuit Protection Fuse-links

660/690Volt BS Fuse System Industrial Fuse-Links DescriptionFuse-link current ratings and dimensions

415 Volt BS System Fuse-holdersDescription Fuse-holder current ratings and dimensions Fuse-holder accessories Solid/Neutral Links

400/415 Volt Electricity Supply Fuse-Links Description Fuse-link current ratings and dimensions Fuse-holders

Cylindrical Fuse-Links 500 Volt Cylindrical Fuse-Links current ratings and dimensions

House Service Cut-Out Fuse-Links 400/415 Volt House Service Cut-Out Fuse-Llinks

Fuse-holder current ratings and dimensions

Street Lighting Cut-Out Fuse-Links230/240 Volt Street Lighting Cut-Out Fuse-Links

240/690 Volt BS Semiconductor Protection Fuse-Links Fuse-Llink current ratings and dimensions IndicatorsComparatives

INDEX

Modular Fuse-holders

LAWSON

Page2-323333

4-6456

7-878

9-119

101111

12-13121313

14-1514

1414

1515

1515

16-17161617

Power Safe Solutions for All Page 1

Page 4: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

500 Volt NH System Fuse-links with Blade Contacts toIEC60269-2/IS13703-2

ACCESSORIES

The fuse-links meet the requirements of the latest

editions of IEC60269-2 together with IS 13703-2.

transformers or capacitors.

Power Safe Solutions for All Page 2

The fuse-links have marking on the front and back faces of the

body so that the marking is visible whether the fuse-links are

mounted in a fuse-base or a fuse-switch.

LAWSON

Page 5: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

DIMENSION

Power Safe Solutions for All Page 3

**ratings also available from 25A onwards in these sizes

, 80, 100

****

DIMENSION

Universal Replacement Handle

SIZES0

010203

SIZES00000

List Ref

DUCH

Current Rating (A)

630

DIMENSIONDIMENSION

Fuse-base Current Ratings and Principal Dimensions

n2 k

p2

b

h

v

YX

w1w2

bolt sizel

Size

00123

List ref

DFB00DFB01DFB02DFB03

Current Ratings(A)

160250400630

Dimensions (mm)

v

56.5

80

80

80

b

93

150

150

150

h

100

175

200

210

j

M8

M10

M10

M12

K

56

85

94

106

n2

33.5

59

59

59

p2

21

36

36

36

w1

00

30

30

30

y

7.5

10.5

10.5

10.5

x

14

20

20

20

w2

25

25

25

25

DIMENSION

LAWSON

Page 6: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

415 Volt BS System Fuse-links with Bolted Connections toIEC60269-2/BS88-2/IS13703-2

The fuse-l inks meet the requirements

of the latest editions of IEC60269-2 together with

IS 13703-2 and BS88-2.

withstand

Power Safe Solutions for All Page 4

LAWSON

Page 7: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Offset tags

Offset plain tags

Power Safe Solutions for All Page 5

LAWSON

Central tags single hole fixing

Central tags double hole fixing

Page 8: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

IES/IS/BS REF

List Ref

Current Rating Cont M motor

(A) (A)

Equivalent Standard List ref

Dimensions(mm) A (max)

B (max)

D (max)

E (max)

F (max)

G (nom)

H (nom)

J (nom)

K (max)

N (nom)

F1

DNS 20M25 DNS 35.5 13.3 62 11

0.8 - - - - 3.5 20M32 32M40*^ 39 17.5 62 11 0.8 - - - - 3.5 32M50*^ 32M63*^

A1 DNIT 20M25 DNIT 36.5 13.3 56 10 0.8 44.5 4.1 aos 14.3 - 20M32 32M40*^ 39 17.5 62 11 1.2 44.5 5.5 aos 18 - 32M50*^ 32M63*^

A2 DTIA 32M40 DTIA 49 22 86 8.7 1.2 73 5.5 8 24

- 32M50 32M63

A3 DTIS 63M80 DTIS 49 26 89 13 1.2 73 5.5 aos 28 - 63M100 100M125*

A4 DTCP 100M125 DTCP 51 30 110 20 2.5 94 8.7 11 33 - 100M160 100M260

As A4 DTFP 200M250 DTFP 51 41 110 20 2.5 94 8.7 11 45 - 200M315

B1 DTC 100M125 DTC 49 30 137 20 3.2 111 8.7 16 - - 100M160 100M200

B2 DTF 200M250 DTF 49 41 137 20 3.2 111 8.7 16 - - 200M315

MOTOR CIRCUIT PROTECTION FUSE-LINKS

A motor circuit protection fuse-link has a dual basis of current rating. The lower rationg is the maximum

continuous current rating determined by the rating of the equipment in which the fuse-link is normally fitted.

The higher rating is the operational current rating determined by the time/current characteristic of the fuse-

link. The list reference incorporates both ratings seperated by the letter "M" .(egDNS20M32)

*non-standardized current rating ^barrel exceeds standardized dimensions aos = asial open-ended slot

FUSE-LINK SELECTION FOR 3 PHASE 415V a.c.INDUCTION MOTOR CIRCUITS

ASSISTED START (7xFLC for 10sec)

FUSE-LINK RATING

(A)

MAXIMUM

MOTOR FLC

"gG' "gM" 2 - 1.3 4 - 2.4 6 - 4.3 10 - 6.4 16 - 11 20 - 14 25 20M25 19 32 - 24 40 32M40 31 50 - 46 63 - 51 80 - 69 100 - 94 125 - 110 160 - 150 200 - 180 250 - 220 315 - 250 355* - 310 400 - 340 450* 400M500* 380 500 - 430 560* - 460 630 - 500 670* - 530 710* - 550 750* - 570 800 - 600

MOTOR RATING

DOL START 7xFLC for 10sec

FUSE-LINK RATING

(A)

ASSISTED START 3.5xFLC for 20sec

FUSE-LINK RATING (A)

KW HP FLC "gG" "gM" "gG" "gM" 0.75 1 2 6 - 4 - 11 1.5 2.5 10 - 6 - 1.5 2 3.5 10 - 6 - 2.2 3 5 16 - 10 - 3 4 6.5 20 - 16 -

4 5 8 25 20M25 16 - 5.5 7.5 11 32 20M32 20 - 7.5 10 14 40 32M40 25 20M25 10 13.5 19 50 32M50 32 20M32

11 15 21 50 32M50 32 -

15 20 28 63 32M63 40 32M40 18.5 25 35 80 63M80 50 -

22 30 41 100 63M100 50 - 26 35 48 100 63M100 63 - 30 40 55 125 100M125 80 63M80

33 45 62 160 100M160 80 63M80 37 50 69 160 100M160 100 - 45 60 83 200 100M200 100 -

5355 70 97 200 100M200 125 100M125 60 75 100 200 100M200 125 100M125 67 80 110 250 200M250 160 -

75 90 120 250 200M250 160 - 90 1 135 250 200M250 160 - 93 1.5 160 315 200M315 200 -

110 2 170 355* - 200 - 130 3 200 400 - 250 200M250 150 4 230 400 - 315 -

160 5 260 450* - 315 - 170 7.5 280 500 - 355* - 180 10 290 500 - 355* -

200 13.5 320 560* - 400 - 220 15 350 630 - 400 - 250 20 380 670* - 450 -

260 25 420 710* - 500 - 300 30 450 750* - 560 -

DOLSTART (7xFLC for 10 sec)

FUSE-LINK RATING (A)

MAXIMUM MOTOR

FLC

"gG" "gM"

2 O.6 4 1.3 6 2.3 10 4.1 16 6.0 20 7.9 25 10 32 13 40 18 50 26 63 30 80 40 100 54 125 61 160 82 200 110 250 150 315 170

MAXIMUM FULL LOAD CURRENT STARTING CAPABILITY

This data is based upon normal condition and average efficiencies and power factors. Conditions such as long run-up times, large numbers of starts in succession, high

ambient temperatures or abnormal transients during starting may necessitate adjustments to fuse-link selection.

Power Safe Solutions for All Page 6

LAWSON

Page 9: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Power Safe Solutions for All Page 7

LAWSON

INDUSTRIAL FUSE-LINKS WITH BOLTED CONNECTIONS TYPE SS

These Fuse-Links are manufactured in the UK and Comply with the quality assurance systems employed by Lawson Fuses Ltd.

Page 10: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Power Safe Solutions for All Page8

LAWSON

INDUSTRIAL FUSE-LINKS WITH BOLTED CONNECTIONS TYPE SS

Dimensional Drawings

Page 11: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Lawson Type “DBFF” Fuse Holders accommodate

Industrial fuse-links with offset blade and bolted

connections to IEC60269-2 together with

IS 13703-2 and BS88-2.

The fuse-holders meet the requirements of IS 13703-2

Power Safe Solutions for All Page 9

Also have 415V compact dimenion fuse-holders to BS88,IEC60269, IS13703 Type DCF (Clip Fit Range)

To Improve the mechanical and electrical

connection of the cable the 32A, 63A and

100A terminal blocks incorporate double

terminal screws.

LAWSON

Page 12: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Power Safe Solutions for All

DIMENSION

Page 10

*All bases include integral DIN-rail adaptor.

LAWSON

REFERENCE CURRENT RATING

(A)

LAWSON FUSE-LINK

REFERENCE

DBFF 20 F1 FC/FC BK 20/32 DNS

DBFF 20 F1 FC/BBC BK 20/32 DNS

DBFF 20 F1 BC/BC BK 20/32 DNS

DCF 32 FC/FC BK 32A DNS(F1)*

DCF 32 FC/BBC BK 32A DNS(F1)*

DCF 32 FC/BC BK 32A DNS(F1)*

DCF 32 FC/BC BK 32A DNS(F1)*

Page 13: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

F

H

G

D

E

J

F

H

L

G

D L E

J

N

E

D

BS SYSTEM SOLID/NEUTRAL LINKS

FUSE-HOLDER ACCESORIES

Fuse-base Terminal Shrouds

Cable Ferrules

DIN Rail Adaptor

D(max) E(max) F(max) G(nom) H(nom) J(nom) L(nom) N(nom)

DSLA1 20 56 10 0.8 44.5 4.1 qos - -

DSLA2 32 86 8.7 1.2 73 5.5 8 - -

DSLA1L 63 65 11 1.2 53 5.5 qos - -

DSLA3 63 89 13 1.2 73 5.5 qos - -

DSLA4 125 110 20 2.5 94 8.7 11 - -

DSLB1 100 137 20 3.2 111 8.7 16 - -

DSLB2 200 137 20 3.2 111 8.7 16 - -

DSLB3 315 137 26 3.2 111 8.7 16 - -

DSLB4 400 137 26 5 111 8.7 16 - -

DSLC1 400 210 26 5 133 10.3 16 26 -

DSLC2 630 210 26 6.4 133 10.3 16 26 -

DSLC3 800 210 26 9.5 133 10.3 16 26 -

DSLF1 32 62 11 0.8 - - - - 3.5

Dimensions(mm)

List Ref current Rating(A)

Power Safe Solutions for All Page 11

LAWSON

Page 14: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Rated Voltage: 415V a.c., Breaking Range and Utilization Category: gU, Rated Breaking Capacity:80kA

400/415 Volt Electricity Supply Distribution Fuse-Links BS88-2/ IEC60269-2

Performance Data-Electricity Supply Fuse-Links

The range has a rated voltage of 415 V a.c. and has been certifiedat a test recovery voltage of 110%.These fuse-links are therefore suitablefor use on systems with voltages up to 457V a.c. The rated & test voltages also ensure that the range meets all the transitional voltage requirementsspecified within the harmonized nominal voltage of 400V a.c.

Performance Data and Product Detail

ELECTRICITY SUPPLY FUSE-LINKS TYPE J

Lawson Type “J” fuses are for use in a .c . e lec t r i c i t y supp ly ne tworks . They are installed in distribution boards, feederpillars, line boxes, pole mounted cut-outs andheavy duty service intakes. The range includes all the current ratings up to 400A specified in BS88-2/IEC60269-2 for fuse-links with the standard 82mm and 92mm fixing centres,together with additional non-standardized current ratings.

*Standardized current rating to BS88-2/IEC 60269-2

BS 88-2/IEC 60269-2

20,32,40,50,63,

80,100*,125,160*,200*,

250*,315*,355*,400*

DJSU

20,32,40,50,63,

80,100*,125,160*,200*,

250*,315*,355*,400*

RATED

VOLTAGE

(V a.c.)

RATED

BREAKING

CAPACITY (kA)

BS/IEC

STANDARDSLIST REF.

RATED CURRENTS

(A)

DJPU

415 80

DJPU & DJSU

Power Safe Solutions for All Page 12

LAWSON

Page 15: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Principal Dimensions

DFH 92 Fuse Holders

S u i t a b l e f o r D J S U f u s e - L i n k srated up to 630A. Breaking Capacity rating of 80kA at 415V a.c. testedin compliance with BS 88-1/IEC 60269-1and BS 88-2/IEC 60269-2

DFH 82 Fuse Holders S u i t a b l e f o r D J P U f u s e - L i n k srated up to 400A. Breaking Capacityrating of 80kA at 415V a.c. testedin compliance with BS 88-1/IEC 60269-1and BS 88-2/IEC 60269-2

FUSE-HOLDERS FOR ELECTRICITY SUPPLY FUSE-LINKS TYPE DFH

*Standardized current rating to BS88-2/IEC 60269-2

A B C D F G K L M

Max Nom Max Max Max Nom Max Max Max

Min

20,32,40,50,63,

80,100,125,160*,200*

31

DIMENSIONS(mm)

LIST REF.

CURRENT

RATINGS

(A)

STANDARDIZED DIMENSIONS

DJPU 45 18 31 2.4

250*,315*,355*,400*

DJSU

20,32,40,50,63,

80,100,125,160*,200*

250*,315*,355*,400*

132

112 82

31 16 6.53

41 18 6.45

92

41 8.05

16

20

45

8.13

22 38 3.2

Rated Voltage: 415V a.c., Breaking Range and Utilization Category: gU, Rated Breaking Capacity:80kA

400/415 Volt Electricity Supply Distribution Fuse-Links BS88-2/IEC60269-2

DIMENSION

Power Safe Solutions for All Page 13

LAWSON

Page 16: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Rated Voltage 500V a.c., Breaking Range & Utilization Category:gG, Rated Breaking Capacity 80kA

500 Volt Cylindrical Fuse-Links to IEC60269-2

CYLINDRICAL FUSE-LINKS TYPE DFN

ROUND TYPE

Power Safe Solutions for All Page 14

LAWSON

DIAMETER LENGTH

6 0.9

10 1.0

16 1.7

20 2.0

25 3.0

32 3.0

10 1.0

16 1.8

20 3.0

25 3.1

32 4.7

40 4.9

50 5.0

63 6.0

RATED

POWER

DISSPATION

(W)

LIST

REFERENCE

RATED

CURRENT

(A)

RATED

VOLTAGE

RATED

BREAKING

CAPACITY

PRINCIPAL

DIMENSIONS (mm)

as per IEC

80 kADFN 14G 14 51

DFN 10G

500V a.c.

500V a.c. 80 kA10 38

Lawson Type DFN Cylindrical fuse-links are used widely in both commercial and industrial applications.The fuse-linksare tested in compliance with IEC 60269-2. A complementary range of solid/neutral links is available.

30

40

50

60

80

100

IIB

BS1361TYPE

CURRENT RATING

(A)

LISTREFERENCE

PRINCIPAL DIMENSIONS

mm inL

mm inD

57

142

30.16

3161

15 DRH15

20

2522.23 57

IIA 30

40

45

50

60

80

78

142

DRH20

DRH25

DRH30

DRH40

DRH45

DRH50

DRH60

DRH80

DRHL30

DRHL40

DRHL50

DRHL60

DRHL80

DRHL100

Current ratings and principal dimensions

HOUSE SERVICE CUT-OUT FUSE LINKS TYPE DRH & DRHL

400/415 Volt House Service Cut-Out Fuse-Links to BS1361 and IEC60269-3

DRH

DRHL

Rated voltage:415Va.c. Fusing factor:not exceeding1.5(Class Q1)Rated breaking capacity:33kA at 0.3p.f.(tested at 80kA at 0.15p.f.)

Page 17: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Voltage & Current Ratings and Principal Dimensions

MODULAR FUSE-HOLDER TYPE LMSC

LMSC10 Fuse-holder

Suitable for the cylindrical 10x38mm fuse- l inks rated up to 32A.Break ing capac i ty ra t ing o f 80kA at 500V a.c. tested in compliance with IEC60269-1

Suitable for the cylindrical 14x51mm fuse- l inks rated up to 63A.Break ing capac i ty ra t ing o f 80kA at 500V a.c. tested in compliance with IEC60269-1

LMSC14 Fuse-holder

LENGTH DIAMETER

LMSC10 500 80 kA DFN10G6,10,16,

20,25,3238 10

LMSC14 500 80 kA DFN14G10,16,20,25,

32,40,50,6351 14

PRINCIPAL

DIMENSIONS (mm)

as per IEC

FUSE-

HOLDER

LIST

REFERENCE

VOLTAGE

RATING

(V a.c.)

RATED

BREAKING

CAPACITY

CYLINDRICAL

FUSE-LINK

LIST

REFERENCE

CURRENT

RATING (A)

FUSE HOLDER

Power Safe Solutions for All Page 15

LAWSON

LENGTHDIMETER

51

3810

14

CURRENT RATING

(A)

LISTREFERENCE

FIXING CENTRE

inmm

38.5

2

4

6

10

16

20

25

32

121

DLST2 DLST4 DLST6DLST10DLST16 DLST20 DLST25 DLST32

STREET LIGHTING TYPE DLST

Current ratings and fixing centre

230/240 Volt Street Lighting Cut-Out Fuse-Links to BS88: Part 1 and IEC602669-1 Rated Voltage 240V a.c., Breaking Range & Utilization Category:gG, Rated Breaking Capacity: 20kA at 240Va.c.

Dimensions in mm

Page 18: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Rated Voltages:240/690V a.c Rated breaking capacities: 100KA at 240/690V a.c & 120/350V d.c

SEMICONDUCTOR FUSE-LINKS WITH BOLTED CONNECTIONS TYPE LSC

Semiconductor Protection Fuse-Links to BS88: Part4.IEC60269-4

Principal ratings

A comprehensive range of Fuse-Links for the protection of semiconductor devices. The 240 and 690 volt, series comply with the performance and dimensional requirements of BS88; Part 4 and IEC60269-4. These Fuse-Links are manufactured in the UK and Comply with the quality assurance systems employed by Lawson Fuses Ltd.A range of Hi-Speed Fuse-Links to DIN 43620 is also available. Ranges of cylindrical Fuse-Links are available for mounting in fuse clips, fuse holders, fuse blocks or fused switches.

IndicatorsTrip-indicator fuse-links are available for use in parallel with the main fuse-link Indicator fuse-links can either be attached to the associated fuse-link or mounted separately in panel mounted fuse clips. A push-on adaptor and micro switch attachment is available for use with the trip indicator to give the facility of remote indication.

Power Safe Solutions for All Page 16

LAWSON

Page 19: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

LSCA630

LSCA500

LSCA400

LSCA350

LSCA315

LSCA250

LSCA200

LSCA160

LSCA125

LSCA100

LSCA80

LSCA63

LSCA50

LSCA40

LSCA32

LSCA25

LSCA20

LSCA16

LSCA10

630FPA2

500FPA2

400FPA2

315FPA

250FPA

200FPA

160FPA

Comparatives

This comparative table is provided only as a guide to semiconductor fuse-link products in the market place. Lawson Fuses do not claim an identical match with the corresponding product codes as these specifications may change without notice. For detailed comparisons please contact Lawson marketing team.

Power Safe Solutions for All Page 17

LAWSON

Page 20: LOW VOLTAGE HRC FUSE RANGE - LAWSON FUSES …lawsonfuses-india.com/LAWSON HRC CATALOGUE.pdf · Power Safe Solutions for All LAWSON LAWSON FUSES INDIA LTD Lawson Fuses India Ltd is

Power Safe Solutions for All

The products referred in this publication are manufactured and tested to the specification indicated on the product as applicable to the appropriate type reference number. To provide protection within the capability of the statedratings and related performance characteristics the product must be correctly installed by competent personnel.

The information contained in this publication is correct at the time of publication, but the company reserve the right to change the design or construction of any listed product. The company also reserves the right to supply products differing in construction or performance.

LAWSON

LFIL/HRC/CAT/04/14

Miniature Circuit Breakers230/400 Volt,6A to 63 A ,10KA ,SP,SPN,DP,TP,TPN & FP with B & C Curves

MCB IsolatorsCurrent Ratings 40,63 & 100A,SP,DP,TP & FP

Residual Current Circuit BreakersCurrent Ratings 16,25,32,40,63,80 & 100A,DP & FP with Current Sensivity 30/100/300mA

Distribution BoardsSPN,TPN Horizontal,TPN Vertical,PPI & Phase Selector DBs

Plug and Socket Distribution BoardsSPN & TPN Plug & Socket DBs

Metal & Plastic EnclosuresMetal EnclosuresPlastic Enclosures

Contact : Team LawsonTel : +91-11-45540763/64/65

LAWSON FUSES INDIA LIMITEDL - 2, UDYOG NAGAR, NEW DELHI-110041, INDIA.

Email: [email protected] website :

Registered Office:D-4,Udyog Nagar,New Delhi-110041.India.

All items from the Lawson Fuses Ltd range of products are alsoavailable from Lawson Fuses India Ltd.

See for product details, technical data and application guide.www.lawson-fuses.co.uk

OTHER PRODUCTSavailable from

LAWSON FUSES INDIA LTD

FINAL DISTRIBUTION PRODUCTS

c Lawson Fuses India Limited 2014