Low Voltage CablesProduct Catalogue
CONTENTS
INTRODUCTION
HOW TO READ THIS CATALOGUE / APPLICABLE STANDARDS
PVC INSULATED CABLES
PVC CU / PVC ( SINGLE CORE )PVC Insulated, Non-Sheathed Cable, 450 / 750V, SS358, IEC60227, BS EN50525-2-31, MS 2112-3
PPS CU / PVC / PVC ( SINGLE CORE )PVC Insulated, PVC Sheathed Cable, 300/500v, MS2112-4
PPS CU / PVC / PVC ( SINGLE CORE )PVC Insulated, PVC Sheathed Cable, 0.6 /1kV, IEC60502
PCC CU / PVC / PVC ( MULTI-CORES )PVC Insulated, PVC Sheathed Cable, 600/1000V, MS2102
PSP CU / PVC / PVC / SWA / PVC ( MULTI-CORES )PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable, 600/1000V, MS2103
XLPE INSULATED CABLES
XP CU / XLPE / PVC ( SINGLE CORE )XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502
XP CU / XLPE / PVC ( 2 CORES - 5 CORES )XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502
XSP CU / XLPE / PVC / SWA / PVC ( 2 CORES - 5 CORES )XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, IEC60502
3
4
6
7
8
9
11
13
14
16
CONTENTS 1
LOW SMOKE ZERO HALOGEN FLAME RETARDANT CABLES
FRT-XH CU / XLPE / LSZH ( SINGLE CORE )XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
FRT-XH CU / XLPE / LSZH ( 2 CORES - 5 CORES )XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
FRT-XAH CU / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS6724
FRT-XSH CU / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS6724
18
19
21
22
www.taisin.com.my | 1
CONTENTS
LOW SMOKE ZERO HALOGEN FLAME RETARDANT FIRE RESISTANT CABLES
FR-H 110 CU / MGT / LSZH ( SINGLE CORE )Mica Taped, Cross-linked Polyole�n LSZH Insulated, Non-Sheathed Cable, 450 / 750V (0.6 / 1kV*), BS7211
FR-XH CU / MGT / XLPE / LSZH ( SINGLE CORE )Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
FR-XH CU / MGT / XLPE / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
FR-XAH CU / MGT / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )Mica Taped, XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
FR-XSH CU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS7846
FR-XOL CU / MGT / XLPE / OS / LSZH ( SINGLE PAIR )Mica Taped, XLPE Insulated, Overall Aluminium Foil Screened, LSZH Sheathed Cable, 300 / 500V, BS EN50288-7
APPENDIX A - EAppendix A - Schedule of Installation Methods of CablesAppendix B - Current Rating Capacity, Voltage Drop & Short Circuit RatingAppendix C - Rating FactorsAppendix D - Cable Cores Colour CodeAppendix E - Fire Performance Tests and Standards
TERMS & CONDITIONS OF SALES
24
25
26
28
29
31
3237455051
53
2 | www.taisin.com.my
INTRODUCTION
www.taisin.com.my | 3
Tai Sin Electric Cables (Malaysia) Sdn. Bhd. is principally engaged in the manufacturing and trading of electric wires and cables. Since its incorporation in 1999, Tai Sin has grown steadily over the years, building on the philosophy of providing quality products with excellent customer service and support. We have been catering to the cable needs and requirements of both large and small customers from a wide range of industries. Our Company supplies to electrical dealers, wholesalers and contractors for both private and public construction of infrastructure, industrial and commercial as well as residential properties.
Our products, marketed under the brand name “Tai Sin”, are renowned for its quality and conform to recognized manufacturing standards including the Malaysian Standard (MS), Singapore Standard (SS), British Standard (BS) and the International Electrotechnical Commission Standard (IEC).
Tai Sin �rmly believes in continuously improving on our quality and our factory is capable of manufacturing both standard as well as customized electric wires and cables made to speci�c requirements. As testimony of our entrenched commitment to the pursuit of excellence and in our drive to continuously improve our quality, Tai Sin obtained the ISO Quality Management System certi�cation as well as the Products Certi�cation licence from SIRIM QAS International Sdn. Bhd.
Further attestations of our beliefs to continuously improve in our quality as well as cater to the needs and requirements of our customers, has resulted in our products being awarded the Singapore Quality Mark by the Singapore Productivity and Standards Board (PSB) and relevant approval from Syarikat Sesco Berhad was also obtained for our East Malaysian market.
With the loyal support of our customers and suppliers, we are committed to further improve the quality of our products through research and development and serving our customers with faster turnaround time.
CERTIFIED TO MS 2112-3 : 2009CERTIFICATION NO.: PT024402
CERTIFIED TO MS 2112-4 : 2009CERTIFICATION NO.: PC000790
CERTIFIED TO MS 2102 : 2007CERTIFICATION NO.: PC000826
CERTIFIED TO MS 2103 : 2007CERTIFICATION NO.: PC000858
CERTIFIED TO IEC 60502-1 : 2004CERTIFICATION NO.: PT024403
This catalogue consists of three types of Low Voltage Cables and they are categorized into three di�erent sections,1) PVC & XLPE Insulated Cables, 2) Low Smoke Zero Halogen Flame Retardant Cables and 3) Low Smoke Zero HalogenFlame Retardant Fire Resistant Cables. In each section, the cables are further categorized by its electrical componentand conductor sizes, which ranges from 0.5mm2 to 1000mm2, armoured and non- armoured and with or withoutcopper-taped screened.
In this catalogue we have given each cable a name accompanied with the various short and long descriptions basedon its material used.
For example:
To better understand the contents of the cable, we have included a 3-dimentional image plus a cross-sectional imageof the cable for easy reference of its structure and components. The technical speci�cations and �gures are providedby our quality team to ensure the accurate use of our products. Technical properties such as Current Rating Factor andVoltage drop, and other essential technical details are provided in the Appendices at the last section of this catalogue.The latest Cable Installation Methods as well as the new harmonized wiring colour codes (as per IEE Wiring Regulations,17th Edition) are also provided in our Appendices for your easy reference.
For all other enquiries, please feel free to contact our friendly customer service hotline for further assistance.
HOW TO READ THIS CATALOGUE
ASTM D 2863Measuring the minimum oxygen concentration to support candle-like combustion of plastic (oxygen index).
BS6360(withdrawn and replaced by BS EN 60228:2005) Speci�cation for conductors in insulated cables and cords.
BS6387 / SS299Performance requirements for cables required to maintain circuit integrity under �re conditions.
BS6724600 / 1000V armoured electric cables having thermosetting insulation and low emission of smoke and corrosive gases when a�ect by �re.
BS7211Thermosetting insulated cables (non- armoured) for electric power and lighting with low emission of smoke and corrosive gases when a�ectedby �re.
FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured,LSZH Sheathed Cable, 0.6 / 1kV, BS7846
Full descriptionon the third line
This is the shortdescription
APPLICABLE STANDARDS
Below are the applicable standards that are used as reference in the construction of our low voltage cables.
4 | www.taisin.com.my
BS7629-1300 / 500V �re-resistant screened cables having low emission of smoke and corrosive gases when a�ect by �re.Part 1: Multicore and Multi-pair Cables.
BS7846600 / 1000V armoured �re-resistant electric cables having low emission of smoke and corrosive gases when a�ected by �re.
BS EN50288-7Multi-element metallic cables use in analogue and digital communication and control.Part 7: Sectional speci�cation for instrumentation and control cables.
BS EN50525-2-31Single core non-sheathed cables with thermoplastic PVC insulation
BS EN50525-3-41Single core non-sheathed cables with halogen-free crosslinked insulation, and low emission of smoke
BS EN60228Conductors of insulated cables.
IEC60227-3Polyvinyl Chloride insulated cables of rated voltages up to and including 450 / 750V Part 3: Non-sheathed cables for �xed wiring.
IEC60228Conductors of insulated cables.
IEC60331Fire-resistant characteristics of electric cables.
IEC60332-1 / BS EN60332-1Tests in electric cables under �re conditions.Part 1: Method of test on a single vertical insulated wire or cable.
IEC60332-3-22 / BS EN60332-3-22Tests on electric and optical �bre cables under �re conditions.Part 3-22: Test for vertical �ame spread of vertically-mounted bunched wires or cables (Category A).
IEC60332-3-24 / BS EN60332-3-24Tests on electric and optical �bre cables under �re conditions.Part 3-24: Test for vertical �ame spread of vertically-mounted bunched wires or cables (Category C).
IEC60502-1Power cables with extruded insulation and their accessories for rated voltages from 1kV up to 30kV.Part 1: Cables for Rated Voltages of 1kV and 3kV.
IEC60754-1 / BS EN50267-2-1Tests on gases evolved during the combustion of materials from cables.Part 1: Methods of determination of amount of halogen acid gas evolved during combustion of polymeric materials taken from cables.
IEC60754-2 / BS EN50267-2-2Tests on gases evolved during combustion of materials from cables.Part 2: Determination of degree of acidity (corrosive) of gases by measuring pH and conductivity.
IEC61034-2 / BS EN61034-2Measurement of smoke density of electric cables burning under de�ned conditions.Part 2: Test procedure and requirements.
SS358-3Polyvinyl Chloride insulated cables of rated voltages up to and including 450 / 750V.Part 4: Non-sheathed cables for �xed wiring.
APPLICABLE STANDARDS
Below are the applicable standards that are used as reference in the construction of ourlow voltage cables.
MS 2102Electrical cable and wire : 600/1000 (Um = 1200) V multi core PVC insulated cable - non-armoured
MS 2103Electrical cable and wire : 600/1000 (Um = 1200) V multi core PVC insulated cable - armoured
MS 2112-4Electrical cable and wire : Polyvinyl chloride (PVC) insulated cables of rated voltages up to and including 450/750 VPart 4 : Sheathed cables for �xed wiring.
MS 2112-3Electrical cable and wire : Polyvinyl chloride (PVC) insulated cables of rated voltages up to and including 450/750 VPart 3 : Non-sheathed cables for �xed wiring.
www.taisin.com.my | 5
Component1. Plain Annealed Copper Wire
2. PVC Compound
PVCCU / PVC ( SINGLE CORE )PVC Insulated, Non-Sheathed Cable, 450 / 750V, SS358, BS EN50525-2-31, IEC60227, MS2112-3
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
ApproximateWeight(kg/km)
SIN
GLE
CO
RE
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Insulation: Polyvinyl Chloride (PVC)Compound Type C
Insulation Colour: Black, Green/Yellow, Red, Yellow,Blue, White, Brown, Grey or Others
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 450/750V
Operating Temperature: -15ºC to 70ºC
Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2
140ºC for cable >300mm2
Test Voltage: 2.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: SS358, BS EN50525-2-31, IEC60227 MS2112-3
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
Mean Overall Diameter(Upper Limit)
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52
0.70.80.80.81.01.01.21.2
1.41.41.61.61.82.02.22.42.62.82.8
3.44.24.85.46.88.09.8
11.0
13.015.017.019.021.023.526.529.533.537.041.0
22.734.050.070.9
117.5177.4282.0380.3
515.8726.4
1002.91251.01538.71927.92522.63155.24018.05044.96443.4
1 x 1.51 x 2.51 x 41 x 6
1 x 101 x 161 x 251 x 35
19 / 1.53 1.2 11.0 376.01 x 351 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630
Table 1# For current rating and voltage drop, please refer to Table B1.1 and B2.1 on Page 37.
12
2
1
6 | www.taisin.com.my
www.taisin.com.my | 7
Component1. Plain Annealed Copper Wire
2. PVC Compound3. PVC Compound
123
3
2
1
PPSCU / PVC / PVC ( SINGLE CORE )PVC Insulated, PVC Sheathed Cable, 300/500 V, MS 2112-4
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Insulation: Polyvinyl Chloride (PVC)Compound Type PVC/C-70
Insulation Colour: Red or Black
Outer Sheath: Polyvinyl Chloride (PVC)Compound Type PVC/ST4-70
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 300/500 V
Operating Temperature: -15ºC to 70ºC
Final Short Circuit Temperature: 160ºC
Test Voltage: 2 kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: MS 2112-4
Conductor: MS IEC 60228
Flame Retardancy: IEC60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
No. of Cores and Nom. Conductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation Lower Limit Upper Limit
(mm)
Cable Overall Diameter
(mm) (mm)
ApproximateWeight(kg/km)
1 x 1.51 x 2.51 x 41 x 6
1 x 101 x 161 x 25
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
0.70.80.80.81.01.01.2
Thicknessof Sheath
(mm)
0.80.80.90.91.01.01.1
4.35.05.46.07.28.4
10.0
5.06.06.87.48.8
10.512.5
39.856.975.899.4159.3225.6342.6
SIN
GLE
CO
RE
Table 2# For current rating and voltage drop, please refer to Table B1.1 and B2.1 on Page 37.
Component1. Plain Annealed Copper Wire
2. PVC Compound3. PVC Compound
123
3
2
1
PPSCU / PVC / PVC ( SINGLE CORE )PVC Insulated, PVC Sheathed Cable, 0.6/1kV, IEC60502
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Insulation: Polyvinyl Chloride (PVC)Compound Type A
Insulation Colour: Red or Black
Outer Sheath: Polyvinyl Chloride (PVC)Compound Type ST 1
Outer Sheath Colour: Grey
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV
Operating Temperature: -15ºC to 70ºC
Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2
140ºC for cable >300mm2
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
1 x 1.51 x 2.51 x 41 x 6
1 x 101 x 161 x 251 x 35
1 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800
1 x 1000
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52127 / 2.85127 / 3.20
0.80.81.01.01.01.01.21.2
1.41.41.61.61.82.02.22.42.62.82.82.83.0
6.36.77.78.29.2
10.211.913.1
14.816.619.120.722.925.328.631.635.238.943.147.652.9
6880
108133180245357460
604818
1113136316682077269233454228527566828407
10535
SIN
GLE
CO
RE
1 x 35 19 / 1.53 1.2 13.2 455
Table 3# For current rating and voltage drop, please refer to Table B1.1 and B2.1 on Page 37.
8 | www.taisin.com.my
www.taisin.com.my | 9
Component1. Plain Annealed Copper Wire
2. PVC Compound3. PVC Compound
123
PCCCU / PVC / PVC ( MULTI-CORES )PVC Insulated, PVC Sheathed Cable, 600/1000 V, MS 2102
CONSTRUCTION
Conductor: Plain Annealed Copper, Class 2Stranded Circular or Compacted
Insulation: Polyvinyl Chloride (PVC) CompoundType PVC/A
Insulation Colour: 2 Cores:Red, Black3 Cores:Red, Yellow, Blue4 Cores:Red, Yellow, Blue, Black5 Cores:Red, Yellow, Blue, Black, Green/ Yellow6 Cores & above:White with Black numbering
Outer Sheath: Polyvinyl Chloride (PVC) CompoundType PVC ST1
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICS
Rated Voltage, Uo/U 600/1000 V
Operating Temperature: -15ºC to 70ºC
Final Short Circuit Temperature: 160ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: MS 2102
Conductor: MS IEC 60228
Flame Retardancy: IEC 60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
2 CO
RES
3 CO
RES
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 25
3 x 1.5
3 x 2.5
3 x 4
3 x 6
3 x 10
3 x 16
3 x 25
No. of Cores andNom. Conductor Area
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
7 / 0.53
7 / 0.67
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
0.80.81.01.01.01.01.2
0.8
0.8
1.0
1.0
1.0
1.0
1.2
Thickness ofSheath
(mm)
1.81.81.81.81.81.81.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
10.411.213.314.416.3
21.8
10.9
11.8
14.1
15.3
17.3
19.6
23.3
151187270338468645951
176
222
325
413
584
818
1219
Table 4# For current rating and voltage drop, please refer to Table B1.2 and B2.2 on Page 38.
3
2
1
18.4
10 | www.taisin.com.my
PCCCU / PVC / PVC ( MULTI-CORES )PVC Insulated, PVC Sheathed Cable, 600/1000 V, MS 2102
Table 5# For current rating and voltage drop, please refer to Table B1.2 and B2.2 on Page 38.
MU
LTI-C
ORE
S4
CORE
S
7 / 0.53
7 / 0.67
7 / 0.85
7 /1.04
7 / 1.35
7 / 1.70
7 / 2.14
7 / 0.53
7 / 0.67
7 / 0.85
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
0.8
0.8
1.0
1.0
1.0
1.0
1.2
0.8
0.8
1.0
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
11.8
12.8
15.3
16.7
18.9
21.5
25.6
12.7
13.8
16.6
13.7
14.9
17.5
19.2
20.3
22.4
24.1
26.7
26.9
29.8
207
264
391
502
727
1027
1540
247
318
475
301
392
469
621
673
903
914
1235
1196
1629
4 x 1.5
4 x 2.5
4 x 4
4 x 6
4 x 10
4 x 16
4 x 25
5 x 1.5
5 x 2.5
5 x 4
7 x 1.5
7 x 2.5
12 x 1.5
12 x 2.5
19 x 1.5
19 x 2.5
27 x 1.5
27 x 2.5
37 x 1.5
37 x 2.5
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
No. of Cores andNom. Conductor Area
Thickness ofSheath
(mm)
www.taisin.com.my | 11
PSPCU / PVC / PVC / SWA / PVC ( MULTI-CORES )PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable.600 /1000 V, MS 2103
12345
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular or Compacted
Insulation: Polyvinyl Chloride (PVC) CompoundType PVC/A
Insulation Colour:
Bedding: Polyvinyl Chloride (PVC) CompoundType PVC ST1
Bedding Colour: Black
Armour: Galvanized Steel Wire Armoured (SWA)
Outer Sheath: Polyvinyl Chloride (PVC) CompoundType PVC ST 1
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 600/1000 V
Operating Temperature: -15ºC to 70ºC
Final Short Circuit Temperature: 160ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: MS 2103
Conductor: MS IEC 60228
Flame Retardancy: IEC60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 70
Table 6# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 40.
Component1. Plain Annealed Copper Wire
2. PVC Compound3. PVC Compound
4. Galvanised Steel Wire Armoured5. PVC Compound
5
4
3
2
1
2 Cores :Red, Black3 Cores :Red, Yellow, Blue4 Cores :Red, Yellow, Blue, Black5 Cores :Red, Yellow, Blue, Black, Green / Yellow6 Cores & above :White with Black numbering
2 CO
RES
3 CO
RES
7 / 0.53
7 / 0.67
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
7 / 0.53
7 / 0.67
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
0.8
0.8
1.0
1.0
1.0
1.0
1.2
0.8
0.8
1.0
1.0
1.0
1.0
1.2
8.8
9.6
11.7
12.8
14.7
16.8
20.2
9.3
10.2
12.5
13.7
15.7
18.0
21.7
0.9
0.9
0.9
1.25
1.25
1.25
1.6
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
14.4
15.2
17.3
19.1
21.0
23.1
27.2
14.9
15.8
18.8
20.0
22.0
24.3
28.7
384
440
566
755
935
1173
1729
422
488
730
855
1079
1383
2055
2 x 1.5
2 x 2.5
2 x 4
2 x 6
2 x 10
2 x 16
2 x 25
3 x 1.5
3 x 2.5
3 x 4
3 x 6
3 x 10
3 x 16
3 x 25
No. of Coresand Nom.
Conductor Area(mm2)
No. andDiameter of
Wires(no./mm)
RadialThickness of
Insulation(mm)
DiameterUnder
Armour(mm)
ArmourWire
Diameter(mm)
Thicknessof Sheath
(mm)
CableOverall
Diameter(mm)
ApproximateWeight
(kg/km)
12 | www.taisin.com.my
PSPCU / PVC / PVC / SWA / PVC ( MULTI-CORES )PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,600 /1000 V, MS 2103
Table 7# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 40.
4 CO
RES
MU
LTI-C
ORE
S
7 / 0.53
7 / 0.67
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
7 / 0.53
7 / 0.67
7 / 0.85
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
7 / 0.53
7 / 0.67
0.8
0.8
1.0
1.0
1.0
1.0
1.2
0.8
0.8
1.0
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
10.2
11.2
13.7
15.1
17.3
19.9
24.0
11.1
12.2
15.0
12.1
13.3
16.0
17.7
18.7
20.8
22.5
25.1
25.3
28.2
0.9
0.9
1.25
1.25
1.25
1.6
1.6
0.9
0.9
1.25
0.9
0.9
1.25
1.25
1.6
1.6
1.6
1.6
1.6
1.6
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
15.8
16.8
20.0
21.4
23.6
26.9
31.0
16.7
17.8
21.3
17.7
19.6
22.3
24.0
25.7
27.8
29.5
32.3
32.5
35.6
474
552
833
985
1268
1786
2454
535
632
954
587
804
955
1157
1377
1674
1745
2183
2149
2701
4 x 1.5
4 x 2.5
4 x 4
4 x 6
4 x 10
4 x 16
4 x 25
5 x 1.5
5 x 2.5
5 x 4
7 x 1.5
7 x 2.5
12 x 1.5
12 x 2.5
19 x 1.5
19 x 2.5
27 x 1.5
27 x 2.5
37 x 1.5
37 x 2.5
No. of Coresand Nom.
Conductor Area(mm2)
No. andDiameter of
Wires(no./mm)
RadialThickness of
Insulation(mm)
DiameterUnder
Armour(mm)
ArmourWire
Diameter(mm)
Thicknessof Sheath
(mm)
CableOverall
Diameter(mm)
ApproximateWeight
(kg/km)
XPCU / XLPE / PVC ( SINGLE CORE )XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502
Component1. Plain Annealed Copper Wire
2. Cross-linked PolyethyleneCompound
3. PVC Compound
123
3
2
1
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: Natural
Outer Sheath: Polyvinyl Chloride (PVC)Compound Type ST2
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
1 x 161 x 251 x 35
1 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800
1 x 1000
7 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52127 / 2.85127 / 3.20
0.70.90.9
1.01.11.11.21.41.61.71.82.02.22.42.62.8
9.611.312.5
14.116.118.220.022.224.427.530.333.937.642.447.352.4
217322423
551767
1037128715771957253631554007502065228279
10367
SIN
GLE
CO
RE
Table 8# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 41.
1 x 35 19 / 1.53 0.9 12.4 423
www.taisin.com.my | 13
14 | www.taisin.com.my
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 252 x 35
2 x 50 (S)2 x 70 (S)2 x 95 (S)
2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.25 37 / 2.5261 / 2.2561 / 2.52
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
10.010.811.913.014.917.020.422.722.425.428.231.234.938.143.247.4
123153197252358505754984
12371711228728563523438756787028
2 CO
RES
Table 9Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 42.
XPCU / XLPE / PVC ( 2 CORES - 5 CORES )XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502
Component1. Plain Annealed Copper Wire
2. Cross-linked PolyethyleneCompound
3. PVC Compound
123
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular, Compacted or Sectored
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/ Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others
Assembly: Cores cabled together with �ller andcovered with Polyester (PET) Tape
Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
3
2
1
www.taisin.com.my | 15
XPCU / XLPE / PVC ( 2 CORES - 5 CORES )XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
3 x 1.53 x 2.53 x 43 x 6
3 x 103 x 163 x 253 x 35
3 x 50 (S)3 x 70 (S)3 x 95 (S)
3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)
4 x 1.54 x 2.54 x 44 x 6
4 x 104 x 164 x 25
4 x 35 (S)4 x 50 (S)4 x 70 (S)4 x 95 (S)
4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)
5 x 1.55 x 2.55 x 45 x 6
5 x 105 x 165 x 255 x 355 x 505 x 705 x 95
5 x 1205 x 1505 x 1855 x 2405 x 300
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.5319 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
10.511.412.513.815.818.121.824.225.028.932.635.840.445.050.554.663.7
11.312.313.615.017.219.823.924.327.031.435.339.144.849.857.163.472.880.8
12.113.314.716.618.821.626.329.334.240.045.350.656.262.870.878.3
150190252328477684
103513641766248033384166514764248335
1029713234
182233312411605876
13341622228432314354546367558446
11016137171755821991
214278375496737
10721640217628494170561770568680
108601409317520
3 CO
RES
Table 10Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 42.
4 CO
RES
5 CO
RES
16 | www.taisin.com.my
Component1. Plain Annealed Copper Wire
2. Cross-linked Polyethylene Compound3. PVC Compound
4. Galvanised Steel Wire Armoured5. PVC Compound
12345
5
4
3
2
1
XSPCU / XLPE / PVC / SWA / PVC ( 2 CORES - 5 CORES )XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular, Compacted or Sectored
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others
Assembly: Cores cabled together with �ller andcovered with Polyester (PET) Tape
Bedding: Polyvinyl Chloride (PVC) Compound TypeST2 or ST2 PVC Tape
Bedding Colour: Black
Armour: Galvanized Steel Wire Armoured (SWA)
Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 70
NominalConductor Area
(mm2)
No. andDiameterof Wires(no./mm)
RadialThickness
of Insulation(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 252 x 35
2 x 50 (S)2 x 70 (S)2 x 95 (S)
2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)
2 CO
RES
Table 11Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 44.
ArmourWire Diameter
(mm)
DiameterUnder Armour
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
8.39.1
10.211.313.215.318.721.021.224.226.829.632.936.542.246.2
0.90.90.90.9
1.251.251.61.61.62.02.02.02.02.52.52.5
13.914.715.816.919.521.625.728.028.331.735.338.341.846.852.957.1
445498573658913
11221603192121322736362642955065643482599793
XSPCU / XLPE / PVC / SWA / PVC ( 2 CORES - 5 CORES )XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502
NominalConductor Area
(mm2)
No. andDiameterof Wires(no./mm)
RadialThickness
of Insulation(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
3 x 1.53 x 2.53 x 43 x 6
3 x 103 x 163 x 253 x 35
3 x 50 (S)3 x 70 (S)3 x 95 (S)
3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)
4 x 1.54 x 2.54 x 44 x 6
4 x 104 x 164 x 25
4 x 35 (S)4 x 50 (S)4 x 70 (S)4 x 95 (S)
4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)
5 x 1.55 x 2.55 x 45 x 6
5 x 105 x 165 x 255 x 355 x 505 x 705 x 95
5 x 1205 x 1505 x 1855 x 240
3 CO
RES
Table 12Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 44.
ArmourWire Diameter
(mm)
DiameterUnder Armour
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.5319 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.25
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.7
8.89.7
10.812.114.116.420.122.523.827.531.034.038.242.649.353.261.7
9.610.611.913.315.518.122.222.525.829.833.536.944.048.655.561.470.2
10.411.613.014.617.119.924.627.632.838.243.348.255.061.268.6
0.90.90.90.9
1.251.251.61.61.62.02.02.02.52.52.52.52.5
0.90.90.9
1.251.251.61.61.61.62.02.02.52.52.52.52.5
3.15
0.90.9
1.251.251.251.61.61.62.02.02.52.52.52.52.5
14.415.316.417.720.422.727.129.531.135.839.742.948.553.160.264.573.4
15.216.217.519.621.825.129.229.733.338.542.447.254.559.566.873.183.8
16.017.219.320.923.426.931.634.841.347.153.458.765.972.580.5
487551643755
1057133719372353275938274825577173018741
111981335716606
541617733966
123417062306248233594671593575469404
11315141441709222157
597690918
108914031973269533454502590176329585
118071419317700
4 CO
RES
5 CO
RES
www.taisin.com.my | 17
18 | www.taisin.com.my
Component1. Plain Annealed Copper Wire
2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen
(LSZH) Compound
123
3
2
1
FRT-XHCU / XLPE / LSZH ( SINGLE CORE )XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: Natural
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
1 x 1.51 x 2.51 x 41 x 6
1 x 101 x 161 x 251 x 351 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800
1 x 1000
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52127 / 2.85127 / 3.20
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8
6.16.57.17.68.69.6
11.312.514.116.118.220.022.224.427.530.333.937.642.447.352.4
7589
110136186254367472612837
1114137416752066266132914159518866388394
10479
SIN
GLE
CO
RE
Table 13# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 41.
Component1. Plain Annealed Copper Wire
2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen
(LSZH) Compound
123
3
2
1
FRT-XHCU / XLPE / LSZH ( 2 CORES - 5 CORES )XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular, Compacted or Sectored
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others
Assembly: Cores cabled together with �ller andcovered with Polyester (PET) Tape
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 252 x 35
2 x 50 (S)2 x 70 (S)2 x 95 (S)
2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
10.010.811.913.014.917.020.422.722.425.428.231.234.938.743.247.4
137170220280399561841
109612401694224827823418423354586736
2 CO
RES
Table 14Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 42.
www.taisin.com.my | 19
FRT-XHCU / XLPE / LSZH ( 2 CORES - 5 CORES )XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
3 x 1.53 x 2.53 x 43 x 6
3 x 103 x 163 x 253 x 35
3 x 50 (S)3 x 70 (S)3 x 95 (S)
3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)
4 x 1.54 x 2.54 x 44 x 6
4 x 104 x 164 x 254 x 35
4 x 50 (S)4 x 70 (S)4 x 95 (S)
4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)
5 x 1.55 x 2.55 x 45 x 6
5 x 105 x 165 x 255 x 355 x 505 x 705 x 95
5 x 120
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.03
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2
0.70.70.70.70.70.70.90.91.01.11.11.2
10.511.412.513.815.818.121.824.225.028.932.635.840.445.050.554.663.7
11.312.313.615.017.219.823.926.727.031.435.339.144.849.857.163.472.880.8
12.113.314.716.318.821.626.329.334.240.045.350.6
159201265344500715
1082142417512434325640474967616979789852
12567
189242323425624901
13731815225431624241530265038104
10515130581662520785
223288388512759
1102168522342845398953486689
3 CO
RES
4 CO
RES
Table 15Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 42.
5 CO
RES
20 | www.taisin.com.my
www.taisin.com.my | 21
Component1. Plain Annealed Copper Wire
2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen
(LSZH) Compound4. Aluminium Wire Armoured5. Low Smoke Zero Halogen
(LSZH) Compound12345
5
4
3
2
1
FRT-XAHCU / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: Natural
)HZSL( negolaH oreZ ekomS woL:gniddeBCompound
Bedding Colour: Black
)AWA( deruomrA eriW muinimulA:ruomrA
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: BS6724
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
DiameterUnder Armour
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
1 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800
1 x 1000
SIN
GLE
CO
RE
Table 16# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page 43.
ArmourWire Diameter
(mm)
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52127 / 2.85127 / 3.20
12.914.916.818.621.023.226.128.732.536.040.445.550.4
1.251.251.251.251.61.61.61.62.02.02.02.52.5
18.620.622.725.227.830.233.135.940.744.449.055.560.6
93211491463176221812633327939665044616877119840
12071
5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others
Component1. Plain Annealed Copper Wire
2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen
(LSZH) Compound4. Galvanised Steel Wire Armoured
5. Low Smoke Zero Halogen(LSZH) Compound12345
FRT-XSHCU / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular, Compacted or Sectored
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black
Assembly: Cores cabled together with �ller andcovered with Polyester (PET) Tape
Bedding: Low Smoke Zero Halogen (LSZH)Compound
Bedding Colour: Black
Armour: Galvanized Steel Wire Armoured (SWA)
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Black
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: BS6724
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 70
5
4
3
2
1
RadialThickness of
Insulation (mm)
ApproximateWeight(kg/km)
No. andDiameter of
Wires (no./mm)
NominalConductorArea (mm2)
Cable OverallDiameter
(mm)
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 252 x 35
2 x 50 (S)2 x 70 (S)2 x 95 (S)
2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)
2 CO
RES
DiameterUnder Armour
(mm)
ArmourWire Diameter
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
7.68.89.9
11.012.915.018.421.120.723.726.729.532.836.840.945.3
0.90.90.90.90.9
1.251.61.61.61.62.02.02.02.52.52.5
12.313.714.815.918.720.825.128.027.831.035.038.041.546.951.255.8
341418496585769
10811496201421352728364243415117657480259596
Table 17Note : (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 44.
22 | www.taisin.com.my
www.taisin.com.my | 23
FRT-XSHCU / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724
RadialThickness of
Insulation (mm)
ApproximateWeight(kg/km)
No. andDiameter of
Wires (no./mm)
NominalConductorArea (mm2)
Cable OverallDiameter
(mm)
3 x 1.53 x 2.53 x 43 x 6
3 x 103 x 163 x 253 x 35
3 x 50 (S)3 x 70 (S)3 x 95 (S)
3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)
4 x 1.54 x 2.54 x 44 x 6
4 x 104 x 164 x 254 x 35
4 x 50 (S)4 x 70 (S)4 x 95 (S)
4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)
5 x 1.55 x 2.55 x 45 x 6
5 x 105 x 165 x 255 x 355 x 505 x 70
3 CO
RES
DiameterUnder Armour
(mm)
ArmourWire Diameter
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.14
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.60.70.70.70.70.70.90.91.01.1
8.09.4
10.511.813.816.120.222.623.327.030.933.938.142.948.052.360.8
8.810.311.613.015.217.822.325.125.329.733.437.242.747.354.660.569.7
9.611.312.714.316.820.024.727.732.738.1
0.90.90.90.9
1.251.251.61.61.61.61.62.02.52.52.52.52.5
0.90.90.9
1.251.251.251.61.61.62.02.02.52.52.52.52.5
3.15
0.90.90.9
1.251.251.61.61.62.02.0
12.714.315.416.719.622.127.129.730.435.139.442.648.053.058.563.071.9
13.515.216.518.821.024.529.232.232.638.242.147.152.857.865.371.682.7
14.516.218.520.122.826.931.835.041.046.8
375463556669981
128319592418275136104873582473008832
109791315316378
416526642880
115615312335291433514717598876259164
11059139391686521985
478599752
1007135219772764345645535961
4 CO
RES
Table 18Note : (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 44.
5 CO
RES
24 | www.taisin.com.my
Component1. Plain Annealed Copper Wire
2. Mica Tape3. Cross-linked Polyole�n Low Smoke
Zero Halogen Compound
123
FR-H 110CU / MGT / LSZH ( SINGLE CORE )Mica Taped, Cross-linked Polyole�n LSZH Insulated, Non-Sheathed Cable, 450 / 750V (0.6 / 1kV*),BS7211
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
1 x 1.51 x 2.51 x 41 x 6
1 x 101 x 161 x 251 x 351 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52
0.70.80.80.81.01.01.21.21.41.41.61.61.82.02.22.42.62.82.8
4.14.85.35.97.38.3
10.111.212.914.717.018.720.622.925.928.732.135.639.6
32466284
135195299397533740
101512571524192625103131397549786333
SIN
GLE
CO
RE
Table 19Note: For FR-H cables, Cross-linked LSZH Compound will be used as the insulation material.# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 41.* Condition apply.
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Fire Barrier: Mica Tape (MGT)
Insulation: Cross-linked Polyole�n (LSZH) LowSmoke Zero Halogen Compound
Insulation Colour: Orange or Others
ELECTRICAL CHARACTERISTICSOperating Voltage: 450 / 750V (0.6/1kV*)
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: BS7211
Conductor: IEC60228, BS EN60228
Fire Resistance: BS6387 (C,W,Z), SS299 (C), IEC60331
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
3
2
1
Component1. Plain Annealed Copper Wire
2. Mica Tape3. Cross-linked Polyethylene Compound
4. Low Smoke Zero Halogen(LSZH) Compound
1234
4
3
2
1
FR-XHCU / MGT / XLPE / LSZH ( SINGLE CORE )Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
1 x 1.51 x 2.51 x 41 x 6
1 x 101 x 161 x 251 x 351 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800
1 x 1000
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52127 / 2.85127 / 3.20
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8
6.16.57.17.68.69.6
11.312.514.116.118.220.022.224.427.530.333.937.642.447.352.4
7892
114141192261376482624851
1131139316952088268733194190522266758436
10525
SIN
GLE
CO
RE
Table 20# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 41.
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Fire Barrier: Mica Tape (MGT)
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: Natural
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Orange or Others
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Fire Resistance: BS6387 (C,W,Z), SS299 (C), IEC60331
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
www.taisin.com.my | 25
Component1. Plain Annealed Copper Wire
2. Mica Tape3. Cross-linked Polyethylene Compound
4. Low Smoke Zero Halogen(LSZH) Compound
1234
4
3
2
1
FR-XHCU / MGT / XLPE / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 252 x 35
2 x 50 (S)2 x 70 (S)2 x 95 (S)
2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
12.112.914.015.117.019.122.524.823.426.429.232.236.039.844.248.4
186223277343409639933
119612921750230828523484430255286806
2 CO
RES
Table 21Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 42.
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular, Compacted or Sectored
Fire Barrier: Mica Tape (MGT)
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others
Assembly: Cores cabled together with �ller andcovered with Polyester (PET) Tape
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Orange or Others
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit 250ºCTemperature:
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
26 | www.taisin.com.my
FR-XHCU / MGT / XLPE / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502
Table 22Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 42.
NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
Cable OverallDiameter
(mm)
ApproximateWeight(kg/km)
3 x 1.53 x 2.53 x 43 x 6
3 x 103 x 163 x 253 x 35
3 x 50 (S)3 x 70 (S)3 x 95 (S)
3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)3 x 500 (S)
4 x 1.54 x 2.54 x 44 x 6
4 x 104 x 164 x 254 x 35
4 x 50 (S)4 x 70 (S)4 x 95 (S)
4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)
5 x 1.55 x 2.55 x 45 x 6
5 x 105 x 165 x 255 x 355 x 505 x 705 x 95
5 x 120
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
7/ 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.03
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2
0.70.70.70.70.70.70.90.91.01.11.11.2
12.713.614.816.018.020.324.026.526.329.933.236.441.345.651.955.865.271.4
13.814.816.117.519.722.326.529.229.733.737.541.746.751.558.664.274.184.9
15.016.117.519.121.624.429.132.237.042.848.153.4
213259328413577801
1183153418262511333141275056625680829952
1267115789
254312400508718
100614961949236732804364543066348239
10648131771675220967
301372480613872
1229183523972979413755056855
3 CO
RES
4 CO
RES
5 CO
RES
www.taisin.com.my | 27
Component1. Plain Annealed Copper Wire
2. Mica Tape3. Cross-linked Polyethylene Compound
4. Low Smoke Zero Halogen(LSZH) Compound
5. Aluminium Wire Armoured6. Low Smoke Zero Halogen
(LSZH) Compound
12345
5
4
3
2
1
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2
Stranded Circular or Compacted
Fire Barrier: Mica Tape (MGT)
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: Natural
Bedding: Low Smoke Zero Halogen (LSZH)Compound
Bedding Colour: Black
)AWA( deruomrA eriW muinimulA:ruomrA
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Orange or Others
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: IEC60502-1
Conductor: IEC60228, BS EN60228
Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 10 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
NominalConductor Area
(mm2)
No. andDiameterof Wires(no./mm)
DiameterUnder Armour
(mm)
Armour WireDiameter
(mm)
ApproximateWeight(kg/km)
Cable OverallDiameter
(mm)
Table 23# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page 43.
1 x 501 x 701 x 95
1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800
1 x 1000
SIN
GLE
CO
RE
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20
127 / 2.52127 / 2.85127 / 3.20
FR-XAHCU / MGT / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )Mica Taped, XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, IEC60502
6
6
RadialThickness of
Insulation(mm)
1.01.11.11.21.41.61.71.82.02.22.42.62.8
14.316.318.220.122.024.327.129.733.537.041.446.551.4
1.251.251.251.61.61.61.61.62.02.02.02.52.5
20.522.524.427.028.931.234.236.841.845.550.156.661.9
99612651573193122692711337940565168630278569996
12269
28 | www.taisin.com.my
www.taisin.com.my | 29
Component1. Plain Annealed Copper Wire
2. Mica Tape3. Cross-linked Polyethylene Compound
4. Low Smoke Zero Halogen(LSZH) Compound
5. Galvanised Steel Wire Armoured6. Low Smoke Zero Halogen
(LSZH) Compound
12345
5
4
3
2
1
FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS7846
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular, Compacted or Sectored
Fire Barrier: Mica Tape (MGT)
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/ Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others
Assembly: Cores cabled together with �ller andcovered with Polyester (PET) Tape
Bedding: Low Smoke Zero Halogen (LSZH)Compound
Bedding Colour: Black
Armour: Galvanized Steel Wire Armoured (SWA)
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant
Outer Sheath Colour: Orange or Others
ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDSDesign Speci�cation: BS7846
Conductor: IEC60228, BS EN60228
Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 10 x cable overall diameter
Max. Pulling Tension (N/mm2): 70
6
6
NominalConductor Area
(mm2)
No. andDiameterof Wires(no./mm)
RadialThickness of
Insulation(mm)
DiameterUnder Armour
(mm)
ApproximateWeight(kg/km)
2 x 1.52 x 2.52 x 42 x 6
2 x 102 x 162 x 252 x 35
2 x 50 (S)2 x 70 (S)2 x 95 (S)
2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)
2 CO
RES
Cable OverallDiameter
(mm)
Table 24Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 44.
Armour WireDiameter
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8
9.611.012.613.215.017.020.623.221.824.827.830.634.038.042.046.4
0.90.90.90.9
1.251.251.61.61.61.62.02.02.02.52.52.5
11.416.017.018.220.222.926.730.229.032.236.239.242.848.252.457.0
438531607709888
12281657221022562859380445125298675682229847
30 | www.taisin.com.my
FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS7846
NominalConductor Area
(mm2)
No. andDiameterof Wires(no./mm)
RadialThickness of
Insulation(mm)
DiameterUnder Armour
(mm)
ApproximateWeight(kg/km)
3 x 1.53 x 2.53 x 43 x 6
3 x 103 x 163 x 253 x 35
3 x 50 (S)3 x 70 (S)3 x 95 (S)
3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)
4 x 1.54 x 2.54 x 44 x 6
4 x 104 x 164 x 254 x 35
4 x 50 (S)4 x 70 (S)4 x 95 (S)
4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)
5 x 1.55 x 2.55 x 45 x 6
5 x 105 x 165 x 255 x 355 x 505 x 705 x 95
5 x 120
Cable OverallDiameter
(mm)
Armour WireDiameter
(mm)
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7/ 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85
7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52
19 / 1.7819 / 2.1419 / 2.5237 / 2.03
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.60.70.70.70.70.70.90.91.01.11.11.2
10.211.712.814.116.118.222.524.924.728.131.634.639.143.649.553.662.4
11.212.914.115.617.820.224.927.628.132.135.739.344.749.156.261.471.1
12.314.215.617.219.622.727.630.635.540.946.451.5
0.90.90.90.9
1.251.251.61.61.61.62.02.02.52.52.52.52.5
0.90.90.9
1.251.251.251.61.61.62.02.02.52.52.52.52.5
3.15
0.90.90.9
1.251.251.61.61.62.02.02.52.5
15.016.717.819.122.024.329.532.131.935.540.243.449.153.860.164.473.6
16.017.919.121.523.726.331.934.835.540.744.549.354.959.767.072.684.2
17.319.220.823.125.729.734.838.043.949.756.461.9
477581677799
1139144021742627291637565029599375149046
112761346416724
541667782
1055133117092574316736225005629379619516
11386142841717922343
619755906
12101560221530513743485863178521
10194
3 CO
RES
Table 25Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 44.
4 CO
RES
5 CO
RES
Component1. Plain Annealed Copper Wire
2. Mica Tape3. Cross-linked Polyethylene Compound
4. Tinned Copper Drain Wire5. Aluminium / Polyester Tape6. Low Smoke Zero Halogen
(LSZH) Compound12345
5
4
3
2
1
FR-XOLCU / MGT / XLPE / OS / LSZH ( SINGLE PAIR )Mica Taped, XLPE Insulated, Overall Aluminium Foil Screened, LSZH Sheathed Cable,300 / 500V, BS EN50288-7
No. of Pairs NominalConductor Area
(mm2)
No. and Diameterof Wires(no./mm)
Radial Thicknessof Insulation
(mm)
ApproximateWeight(kg/km)
1P1P1PSI
NG
LEPA
IR
Cable OverallDiameter
(mm)
1.01.52.5
7 / 0.437 / 0.537 / 0.67
0.60.60.7
10.010.612.0
98113150
CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded
Circular
Fire Barrier: Mica Tape (MGT)
Insulation: Cross-linked Polyethylene (XLPE)Compound
Insulation Colour: Black, White or Others
Lay Up: Pair - Cores twisted to pair
Wrap Film: Polyester Binder Tape
Overall Screen: Aluminium/Polyester Tape, with aTinned Copper Drain Wire 0.5mm2
(7/0.3mm) (OS)
Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Characteristic and UV Resistant
Outer Sheath Colour: Orange or Others
ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 300/500V
Operating Temperature: -15ºC to 90ºC
Final Short Circuit Temperature: 250ºC
Test Voltage: 2kV for 1 minute
REFERENCE STANDARDSDesign Speci�cation: BS EN50288-7
Conductor: IEC60228, BS EN60228
Fire Resistance: BS6387 (C, W, Z), SS299 (C, W, Z),IEC60331
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2
INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter
Max. Pulling Tension (N/mm2): 50
Table 26Note: Class 5 conductors are available upon request.
6
6
www.taisin.com.my | 31
APPENDIX ATable A1.1Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity
NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.
Non-sheathed cables in conduit in a thermallyinsulated wall with an inner skin having athermal conductance of not less than 10 W/m2k
Multicore cable in conduit in a thermallyinsulated wall with an inner skin having athermal conductance of not less than 10 W/m2k
Multicore cable direct in a thermally insulatedwall with an inner skin having a thermalconductance of not less than 10 W/m2k
Non-sheathed cables in conduit on a woodenor masonry wall or spaced less than 0.3 x conduitdiameter from it c
Multicore cable in conduit on a wooden ormasonry wall or spaced less than 0.3 x conduitdiameter from it c
Non-sheathed cables in cable trunking on awooden or masonry wall6 - run horizontally b
7 - run vertically b, c
Multicore cable in cable trunking on a woodenor masonry wall8 - run horizontally b
9 - run vertically b, c
Non-sheathed cables in suspended cabletrunking b
Multicore cable in suspended cabletrunking b
Non-sheathed cables run in mouldings c, e
Non-sheathed cables in skirting trunking
Multicore cable in skirting trunking
Reference Methodto be used to determine
current-carrying capacity
Installation Method
noitpircseDselpmaxENumber
1
2
3
4
5
67
89
10
11
12
13
14
A
A
A
B
B
B
B*
B
B
A
B
B
b Values given for Installation Method B in Appendix A are for a single circuit. Where there is more than one circuit in the trunking the group rating factor given in Table C2.1 is applicable,irrespective of the presence of an internal barrier or partition.
c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.
e The thermal resistivity of the enclosure is assumed to be poor because of the material of construction and possible air spaces. Where the construction is thermally equivalent to InstallationMethods 6 or 7, Reference Method B may be used.
* Still under consideration in IEC.
ROOM
ROOM
ROOM
6 7
9
10 11
TV
ICT
TV
ICT
13 14
8
32 | www.taisin.com.my
www.taisin.com.my | 33
≥0.3 De
≥0.3 De
≥0.3 De
≥0.3 De
≥0.3 De
≥0.3 De
APPENDIX ATable A1.2Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity
NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.
Single-core or multicore cables:Fixed on (clipped direct), or spaced less than0.3 x cable diameter from a wooden or masonrywall c
Single-core or multicore cables:Fixed directly under wooden or masonry ceiling
Single-core or multicore cables:Spaced from a ceiling
Single-core or multicore cables:On unperforated tray run horizontally orvertically c, h
Single-core or multicore cables:On unperforated tray run horizontally orvertically c, h
Single-core or multicore cables:On brackets or on a wire mesh tray runhorizontally or vertically c, h
Single-core or multicore cables:Spaced more than 0.3 x the cable diameter froma wall
Single-core or multicore cables:On a ladder c
Single-core or multicore cable suspendedfrom or incorporating a support wire or harness
Reference Methodto be used to determine
current-carrying capacity
Installation Method
noitpircseDselpmaxENumber
20
21
22
30
31
32
33
34
35
C
B(Higher than standard ambient temperatures
may occur with this installation method)
E, F or G*(Higher than standard ambient temperatures
may occur with this installation method)
Cwith item 2 of Table C2.1
E or F
E or F
E, F or Gg
E or F
E or F
c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.
f The thermal resistivity of the enclosure is assumed to be poor because of the material of construction and possible air spaces. Where the construction is thermally equivalent to InstallationMethods 6, 7, 8 or 9. Reference Method B may be used.
g The factor in Table C2.1 may also be used.
h De = the external diameter of a multicore cable:– 2.2 x the cable diameter when three single-core cables are bound in trefoil, or– 3 x the cable diameter when three single-core cables are laid in �at formation.
* Still under consideration in IEC.
34 | www.taisin.com.my
DeV
DeV
DeV
DeV
DeV
DeV
VDe
APPENDIX ATable A1.3Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity
NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.
Bare or non-sheathed cables on insulators
Single-core or multicore cables:In a building void c, h, i
Non-sheathed cables:- In conduit- In a building void- In masonry having a thermal resistivity not
greater than 2 K.m/W c, i, j
Single-core or multicore cables:- In conduit- In a building void- In masonry having a thermal resistivity not
greater than 2 K.m/W c, j
Non-sheathed cables:- In cable ducting- In a building void- In masonry having a thermal resistivity not
greater than 2 K.m/W c, i, j
Single-core or multicore cables:- In cable ducting- In a building void- In masonry having a thermal resistivity not
greater than 2 K.m/W c, i, j
Non-sheathed cables:- In cable ducting- In masonry having a thermal resistivity not
greater than 2 K.m/W c, h, i
Single-core or multicore cables:- In cable ducting- In masonry having a thermal resistivity not
greater than 2 K.m/W c, h, i
Single-core or multicore cables:- In a ceiling void- In a suspended �oor h, i
Non-sheathed cables in �ush cable trunkingin the �oor
Reference Methodto be used to determine
current-carrying capacity
Installation Method
noitpircseDselpmaxENumber
36
40
41
42
43
44
45
46
47
50
G
Where 1.5 De ≤ V ≤ 20 DeUse B
Where 1.5 De ≤ VUse B
Where 1.5 De ≤ VUse B
Where 1.5 De ≤ VUse B
Where 1.5 De ≤ VUse B
Where 1.5 De ≤ V ≤ 50 DeUse B
Where 1.5 De ≤ V ≤ 50 DeUse B
Where 1.5 De ≤ V ≤ 50 DeUse B
B
c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.
g The factors in table C2.1 may also be used.
h De = the external diameter of a multicore cable:- 2.2x the cable diameter when three single-core cables are bound in trefoil, or- 3x the cable diameter when three single-core cables are laid in �at formation.
i V = the smaller dimension or diameter of a masonry duct or void, or the vertical depth of a rectangular duct, �oor or ceiling void or channel.
j De = external diameter of conduit or vertical depth of cable ducting.
DeV
www.taisin.com.my | 35
TV
ICT
TV
ICT
VDe
APPENDIX ATable A1.4Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity
NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.
Multicore cable in �ush cable trunking in the�oor
Non-sheathed cables in �ush trunking c
Multicore cable in �ush trunking c
Non-sheathed cables or single-core cablesin conduit in an unventilated cable channel runhorizontally or vertically c, i, k, m
Non-sheathed cables in conduit in an open orventilated cable channel in the �oor l, m
Sheathed single-core or multicore cable inan open or ventilated cable channel runhorizontally or vertically m
Single-core or multicore cable direct inmasonry having a thermal resistivity not greaterthan 2 K.m/W- Without added mechanical protection n, o
Single-core or multicore cable direct inmasonry having a thermal resistivity not greaterthan 2 K.m/W- With added mechanical protection n, o
(e.g. capping)
Non-sheathed cables or single-core cablesin conduit in masonry having a thermalresistivity not greater than 2 K.m/W o
Multicore cables in conduit in masonryhaving a thermal resistivity not greater than2 K.m/W o
Reference Methodto be used to determine
current-carrying capacity
Installation Method
noitpircseDselpmaxENumber
51
52
53
54
55
56
57
58
59
60
B
B
B
Where 1.5 De ≤ VUse B
B
B
C
C
B
B
c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.
k De = external diameter of conduit.
i V = the smaller dimension or diameter of a masonry duct or void, or the vertical depth of a rectangular duct, �oor or ceiling void or channel. The depth of the channel is more importantthan the width.
i For multicore cable installed as method 55, use current-carrying capacity for Reference Method B.
m It is recommended that these installation methods are used only in areas where access is restricted to authorized persons so that the reduction in current-carrying capacity and the �re hazarddue to the accumulation of debris can be prevented.
n For cables having conductors not greater than 16mm2, the current carrying capacity may be higher.
o Thermal resistivity of masonry is not greater than 2 K.m/W. The term masonry is taken to include brickwork, concrete, plaster and the like (excludes thermally insulating materials).
52 53
36 | www.taisin.com.my
Multicore unarmoured cable in conduit or incable ducting in the ground
Single-core unarmoured cable in conduit orin cable ducting in the ground
Sheathed, armoured or multicore cablesdirect in the ground– Without added mechanical protection
(see note)
Sheathed, armoured or multicore cablesdirect in the ground– With added mechanical protection
(eg. cable covers)(see note)
Reference Methodto be used to determine
current-carrying capacity
Installation Method
noitpircseDselpmaxENumber
70
71
72
73
D
D
D
D
Note: The inclusion of directly buried cables is satisfactory where the soil thermal resistivity is of the order of 2.5K.m/W. For lower soil resistivities, the current-carrying capacity for directly buriedcables is appreciably higher than for cables in ducts.
APPENDIX ATable A1.5Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity
NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.
www.taisin.com.my | 37
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.1: Single-core copper conductor, 70ºC PVC insulated, non-armoured, with or without sheathed cables,Ambient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity(cable buried in ground): 2.5K.m/W
ConductorCross-
SectionalArea
Reference Method A(enclosed in conduit
in thermally insulatingwall etc)
Reference Method B(enclosed in conduit
on wall or in trunking etc)
Reference Method C(clipped direct)
Reference Method F(in free air or on a perforated cable tray horizontal or vertical)
2 Cables,Single-Phase
a.c. or d.c.
Touching Spaced by One Cable Diameter
3 or 4 Cables,3-Phase a.c.
2 Cables,Single-Phase
a.c. or d.c.
3 or 4 Cables,3-Phase a.c.
2 Cables,Single-Phase
a.c. or d.c.Flat and
Touching
3 or 4 Cables,3-Phase
a.c. Flat andTouching or
Trefoil
2 Cables,Single-Phase
a.c. or d.c.Flat
3 Cables,3-Phasea.c. Flat
3 Cables,3-Phase
a.c. Trefoil
2 Cables, Single-Phasea.c. or d.c., or
3 Cables, 3-Phase a.c. Flat
Horizontal Vertical
AAAAAAAAAAAmm2
1.01.52.546
10162535507095
120150185240300400500630800
1000
1114.520263446618099
119151182210240273321367
–––––
10.513.518243142567389
108136164188216245286328
–––––
13.517.52432415776
101125151192232269300341400458546626720
––
1215.5212836506889
110134171207239262296346394467533611
––
15.5202737476587
114141182234284330381436515594694792904
10301154
14182533435979
104129167214261303349400472545634723826943
1058
–––––––
131162196251304352406463546629754868
100510861216
–––––––
114143174225275321372427507587689789905
10201149
–––––––
110137167216264308356409485561656749855971
1079
–––––––
146181219281341396456521615709852982
113812651420
–––––––
130162197254311362419480569659795920
107011881337
Voltage Drop ( IN mV/A/m )Table B2.1: Single-core copper conductor, 70ºC PVC insulated, non-armoured, with or without sheathed cables,Ambient air temperature: 30ºC, Conductor operating temperature: 70ºC
ConductorCross-
SectionalArea
2 Cables, Single-Phase a.c.
Reference Methods C & F(clipped direct, on tray or in free air)
Cables Spaced*,Flat
mV/A/mmm2
1.01.52.546
1016
2535507095
120150185240300400500630800
1000
3 or 4 Cables, 3-Phase a.c.
Reference Methods C & F(clipped direct, on tray or in free air)
2 Cablesd.c.
Cables Touching,Flat
Cables Touching,Trefoil
ReferenceMethods A & B
(enclosed inconduit ortrunking)
Cables Spaced*Cables Touching
ReferenceMethods A & B
(enclosed inconduit ortrunking)
mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
442918117.34.42.8
1.751.250.930.630.460.360.290.23
0.1800.1450.1050.0860.0680.0530.042
442918117.34.42.8
442918117.34.42.8
442918117.34.42.8
3825159.56.43.82.4
3825159.56.43.82.4
3825159.56.43.82.4
3825159.56.43.82.4
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
r x z1.80 0.33 1.801.30 0.31 1.300.95 0.30 1.000.65 0.29 0.720.49 0.28 0.560.39 0.27 0.470.31 0.27 0.410.25 0.27 0.370.195 0.26 0.330.160 0.29 0.310.130 0.26 0.290.110 0.26 0.280.094 0.25 0.27
– –
r x z1.75 0.20 1.751.25 0.195 1.250.93 0.190 0.950.63 0.185 0.660.47 0.180 0.500.37 0.175 0.410.30 0.175 0.340.24 0.170 0.290.185 0.165 0.250.150 0.165 0.220.120 0.160 0.200.098 0.155 0.1850.081 0.155 0.1750.068 0.150 0.1650.059 0.150 0.160
r x z1.75 0.29 1.801.25 0.28 1.300.93 0.28 0.970.63 0.27 0.690.47 0.27 0.540.37 0.26 0.450.29 0.26 0.390.24 0.26 0.350.185 0.25 0.310.150 0.25 0.290.115 0.25 0.270.093 0.24 0.260.076 0.24 0.250.061 0.24 0.250.050 0.24 0.24
r x z1.50 0.29 1.551.10 0.27 1.100.81 0.26 0.850.56 0.25 0.610.42 0.24 0.480.33 0.23 0.410.27 0.23 0.360.22 0.23 0.320.17 0.23 0.290.14 0.23 0.270.12 0.22 0.250.10 0.22 0.250.08 0.22 0.24
– –
r x z1.50 0.175 1.501.10 0.170 1.100.80 0.165 0.820.55 0.160 0.570.41 0.155 0.430.32 0.150 0.360.26 0.150 0.300.21 0.145 0.260.160 0.145 0.220.130 0.140 0.1900.105 0.140 0.1750.086 0.135 0.1600.072 0.135 0.1500.060 0.130 0.1450.052 0.130 0.140
r x z1.50 0.25 1.551.10 0.24 1.100.80 0.24 0.840.55 0.24 0.600.41 0.23 0.470.32 0.23 0.400.26 0.23 0.340.21 0.22 0.310.160 0.22 0.270.130 0.22 0.250.105 0.21 0.240.086 0.21 0.230.072 0.21 0.220.060 0.21 0.220.052 0.20 0.21
r x z1.50 0.32 1.551.10 0.32 1.150.80 0.32 0.860.55 0.31 0.630.40 0.31 0.510.32 0.30 0.440.26 0.30 0.400.21 0.30 0.360.160 0.29 0.340.130 0.29 0.320.100 0.29 0.310.081 0.29 0.300.066 0.28 0.290.053 0.28 0.290.044 0.28 0.28
BS 6004MS 2112-3MS 2112-4SS 358IEC 60227IEC 60502-1
38 | www.taisin.com.my
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.2: Multi-core, 70ºC PVC insulated, PVC sheathed non-armoured cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
1.01.52.546
10162535507095
120150185240300400
*With or without a protective conductor.
ConductorCross-Sectional
Area
Reference Method A(enclosed in conduit in thermally
insulating wall etc)
Reference Method B(enclosed in conduit on a wall or
in trunking etc)
Reference Method C(clipped direct)
One 2-CoreCable*,
Single-Phasea.c. or d.c.
One 3-CoreCable* or
One 4-Core Cable,3-Phase a.c.
A
Reference Method E(in free air or on a perforated cable tray
horizontal or vertical)
One 2-CoreCable*,
Single-Phasea.c. or d.c.
One 3-core Cable*or One 4-Core
Cable,3-Phase a.c.
One 2-CoreCable*,
Single-Phasea.c. or d.c.
One 3-CoreCable* or
One 4-Core Cable,3-Phase a.c.
One 2-CoreCable*,
Single-Phasea.c. or d.c.
One 3-CoreCable* or
One 4-Core Cable,3-Phase a.c.
AAAAAAAmm2
1114
18.5253243577592
110139167192219248291334
–
1013
17.523293952688399
125150172196223261298
–
1316.5233038526990
111133168201232258294344394470
11.51520273446628099
118149179206225255297339402
1519.52736466385
112138168213258299344392461530634
13.517.5243241577696
119144184223259299341403464557
17223040517094
119148180232282328379434514593715
14.518.52534436080
101126153196238276319364430497597
Voltage Drop ( IN mV/A/m )Table B2.2: Multi-core 70ºC PVC insulated, PVC sheathed non-armoured cablesAmbient temperature: 30ºC, Conductor operating temperature: 70ºC
2-Core Cable, d.c.
mV/A/mmm2
1.01.52.546
1016
2535507095
120150185240300400
3 or 4 Core Cable, 3-Phase a.c.
mV/A/mmV/A/m
r x z1.75 0.170 1.751.25 0.165 1.250.93 0.165 0.940.63 0.160 0.650.47 0.155 0.500.38 0.155 0.410.30 0.155 0.340.25 0.150 0.290.190 0.150 0.240.155 0.145 0.210.115 0.145 0.185
2-Core Cable, Single-Phase a.c.ConductorCross-Sectional
Area
442918117.34.42.8
1.751.250.930.630.460.360.290.23
0.1800.1450.105
442918117.34.42.8
3825159.56.43.82.4
r x z1.50 0.145 1.501.10 0.145 1.100.80 0.140 0.810.55 0.140 0.570.41 0.135 0.430.33 0.135 0.350.26 0.130 0.290.21 0.130 0.250.165 0.130 0.210.135 0.130 0.1850.100 0.125 0.160
MS 2102IEC60502-1
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
www.taisin.com.my | 39
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.3: Single-core 70ºC PVC insulated, PVC sheathed armoured cables (non-magnetic armour)Ambient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
ConductorCross-
SectionalArea
Reference Method C(clipped direct)
Reference Method F(in free air or on a perforated cable tray horizontal or vertical)
2 Cables,Single-Phase
a.c. or d.c.�at
retemaiD elbaC enO yb decapSgnihcuoT
3 or 4 Cables,3-Phase a.c.
�at
2 Cables,Single-Phase
a.c. or d.c.�at
3 Cables,3-Phase a.c.
�at
2 Cables,d.c.
2 Cables,Single-Phase a.c.
3 or 4 Cables,3-Phase a.c.
Horizontal Vertical
AAAAAAAAAAAmm2
507095
120150185240300400500630800
1000
193245296342393447525594687763843919975
179225269309352399465515575622669710737
205259313360413469550624723805891976
1041
189238285327373422492547618673728777808
181231280324373425501567657731809886945
229294357415479548648748885
1035121814411685
216279340396458525622719851997
117413901627
229287349401449511593668737810893943
1008
217272332383429489568640707777856905967
230286338385436490566616674721771824872
212263313357405456528578632676723772816
Touching
3 Cables,3-Phase a.c.
trefoilHorizontal VerticalHorizontal Vertical
Voltage Drop ( IN mV/A/m )Table B2.3: Single-core 70ºC PVC insulated, PVC sheathed armoured cables (non-magnetic armour)Ambient temperature: 30ºC, Conductor operating temperature: 70ºC
Reference Method C & F(clipped direct, on tray or free air)
mm2 mV/A/m
ConductorCross-
SectionalArea
507095
120150185240300400500630800
1000
0.930.630.460.360.290.23
0.1800.1450.1050.0860.0680.0530.042
r x z0.93 0.22 0.950.64 0.21 0.680.48 0.20 0.520.39 0.195 0.430.31 0.190 0.370.26 0.190 0.320.20 0.180 0.270.160 0.180 0.240.140 0.175 0.220.120 0.170 0.210.105 0.165 0.1950.095 0.160 0.1850.091 0.155 0.180
2 Cables,d.c.
3 or 4 Cables, 3-Phase a.c.2 Cables, Single-Phase a.c.
Touching Spaced* Trefoil and Touching Flat and Touching Flat and Spaced*
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
m/A/Vmm/A/Vmm/A/Vmm/A/Vmm/A/Vm
r x z0.92 0.30 0.970.66 0.29 0.720.51 0.28 0.580.42 0.28 0.500.34 0.27 0.440.29 0.27 0.390.23 0.26 0.350.190 0.26 0.320.180 0.24 0.300.165 0.23 0.290.150 0.22 0.270.145 0.21 0.250.140 0.190 0.24
r x z0.80 0.190 0.820.56 0.180 0.580.42 0.175 0.450.33 0.170 0.370.27 0.165 0.320.22 0.160 0.270.175 0.160 0.230.140 0.155 0.210.120 0.130 0.1950.105 0.145 0.1800.091 0.145 0.1700.082 0.140 0.1600.079 0.135 0.155
r x z0.79 0.26 0.840.57 0.25 0.620.44 0.25 0.500.36 0.24 0.430.30 0.24 0.380.25 0.23 0.340.20 0.23 0.300.165 0.22 0.280.160 0.21 0.260.145 0.20 0.250.135 0.195 0.230.125 0.180 0.220.125 0.165 0.21
r x z0.79 0.34 0.860.59 0.32 0.680.47 0.31 0.570.40 0.30 0.500.34 0.30 0.450.29 0.29 0.410.24 0.28 0.370.20 0.28 0.340.21 0.25 0.320.190 0.24 0.300.175 0.22 0.280.170 0.195 0.260.165 0.170 0.24
IEC 60502-1
40 | www.taisin.com.my
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.4: Multi-core 70ºC PVC insulated, PVC sheathed armoured cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
ConductorCross-Sectional
Area
Reference Method C(clipped direct)
A
Reference Method D(direct in ground or in ducting in ground,
in or around buildings)
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-Core Cable,3-Phase a.c.
mm2
1.52.546
10162535507095
120150185240300400
Reference Method E(in free air or on a perforated cable tray
etc, horizontal or vertical)
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-Core Cable,3-Phase a.c.
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-Core Cable,3-Phase a.c.
AAAAA
212838496789
118145175222269310356405476547621
182533425877
102125151192231267306348409469540
223141537297
128157190241291336386439516592683
192635456283
110135163207251290332378445510590
22293746607899
119140173204231261292336379
–
1824303850648298
116143169192217243280316
–
Voltage Drop ( IN mV/A/m )Table B2.4: Multi-core 70ºC PVC insulated, PVC sheathed armoured cablesAmbient temperature: 30ºC, Conductor operating temperature: 70ºC
ConductorCross-Sectional Area
2-Core Cable,d.c.
mV/A/m
3 or 4-Core Cable,3-Phase a.c.
mm2
2-Core Cable,Single-Phase a.c.
mV/A/mmV/A/m
1.52.546
1016
2535507095
120150185240300400
2918117.34.42.8
1.751.250.930.630.460.360.290.23
0.1800.1450.105
2918117.34.42.8
25159.56.43.82.4
r x z1.75 0.170 1.751.25 0.165 1.250.93 0.165 0.940.63 0.160 0.650.47 0.155 0.500.38 0.155 0.410.30 0.155 0.340.25 0.150 0.290.190 0.150 0.240.155 0.145 0.210.115 0.145 0.185
r x z1.50 0.145 1.501.10 0.145 1.100.80 0.140 0.810.55 0.140 0.570.41 0.135 0.430.33 0.135 0.350.26 0.130 0.290.21 0.130 0.250.165 0.130 0.210.135 0.130 0.1850.100 0.125 0.160
MS 2103
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
www.taisin.com.my | 41
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.5: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured,with or without sheath (PVC / LSZH) cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
1.01.52.546
10162535507095
120150185240300400500630800
1000
14192635456181
106131158200241278318362424486
–––––
1317233140547395
117141179216249285324380435
–––––
172331425475
100133164198253306354393449528603683783900
––
15202837486688
117144175222269312342384450514584666764
––
192534465981
109143176228293355413476545644743868990
113012881443
17.5233141547499
130161209268326379436500590681793904
103311791323
–––––––
161200242310377437504575679783940
1083125413581520
–––––––
141176216279342400464533634736868998
115112751436
–––––––
135169207268328383444510607703823946
108812141349
–––––––
182226275353430500577661781902
10851253145415811775
–––––––
161201246318389454527605719833
10081169136214851671
ConductorCross-
SectionalArea
Reference Method A(enclosed in conduit
in thermally insulatingwall etc)
Reference Method B(enclosed in conduit
on a wall orin trunking etc)
Reference Method C(clipped direct)
Reference Method F(in free air or on a perforated cable tray etc,
horizontal or vertical etc)
2 Cables,Single-Phase
a.c. or d.c.
Touching Spaced by One Cable Diameter
3 or 4 Cables,3-Phase a.c.
2 Cables,Single-Phase
a.c. or d.c.
3 or 4 Cables,3-Phase a.c.
2 Cables,Single-Phase
a.c. or d.c.Flat and
Touching
3 or 4 Cables,3-Phase
a.c. Flat andTouching or
Trefoil
2 Cables,Single-Phase
a.c. or d.c.Flat
3 Cables,3-Phasea.c. Flat
3 Cables,3-Phase
a.c. Trefoil
2 Cables, Single-Phasea.c. or d.c., or
3 Cables, 3-Phase a.c. Flat
Horizontal Vertical
AAAAAAAAAAAmm2
Reference Method G(in free air)
Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for
70ºC thermoplastic insulated cables must be used.
ConductorCross-
SectionalArea
2 Cablesd.c.
2 Cables, Single-Phase a.c.
Reference MethodsA & B
(enclosed inconduit ortrunking)
mV/A/m
3 or 4 Cables, 3-Phase a.c.
Reference Methods C, F & G(clipped direct, on tray or in free air)
Reference MethodsA & B
(enclosed inconduit ortrunking)
Reference Methods C, F & G(clipped direct, on tray or in free air)
mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmm2
1.01.52.546
1016
2535507095
120150185240300400500630800
1000
463119127.94.72.9
1.851.350.990.680.490.390.320.25
0.1900.1550.1200.0930.0720.0560.045
463119127.94.72.9
463119127.94.72.9
463119127.94.72.9
402716106.84.02.5
402716106.84.02.5
402716106.84.02.5
402716106.84.02.5
Voltage Drop ( IN mV/A/m )Table B2.5: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, with or without sheath (PVC / LSZH) cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC
Cables Touching,Trefoil
Cables Touching,Flat
Cables Spaced*,Flat
CablesTouching
CablesSpaced*
r x z1.85 0.31 1.901.35 0.29 1.351.00 0.29 1.050.70 0.28 0.750.51 0.27 0.580.41 0.26 0.480.33 0.26 0.430.27 0.26 0.370.21 0.26 0.330.175 0.25 0.310.140 0.25 0.290.120 0.25 0.280.100 0.25 0.27
– –
r x z1.85 0.190 1.851.35 0.180 1.350.99 0.180 1.000.68 0.175 0.710.49 0.170 0.520.39 0.165 0.430.32 0.165 0.360.26 0.165 0.300.20 0.160 0.250.160 0.160 0.220.130 0.155 0.200.105 0.155 0.1850.086 0.155 0.1750.072 0.150 0.1700.063 0.150 0.165
r x z1.85 0.28 1.851.35 0.27 1.350.99 0.27 1.000.68 0.26 0.730.49 0.26 0.560.39 0.25 0.470.32 0.25 0.410.25 0.25 0.360.195 0.25 0.310.155 0.25 0.290.125 0.24 0.270.098 0.24 0.260.078 0.24 0.250.064 0.24 0.250.054 0.24 0.24
r x z1.60 0.27 1.651.15 0.25 1.150.87 0.25 0.900.60 0.24 0.650.44 0.23 0.500.35 0.23 0.420.29 0.23 0.370.23 0.23 0.320.185 0.22 0.290.150 0.22 0.270.125 0.22 0.250.100 0.22 0.240.088 0.21 0.23
– –
r x z1.60 0.165 1.601.15 0.155 1.150.86 0.155 0.870.59 0.150 0.610.43 0.145 0.450.34 0.140 0.370.28 0.140 0.310.22 0.140 0.260.170 0.140 0.220.140 0.140 0.1950.110 0.135 0.1750.090 0.135 0.1600.074 0.135 0.1500.062 0.130 0.1450.055 0.130 0.140
r x z1.60 0.27 1.651.15 0.26 1.200.86 0.26 0.890.59 0.25 0.650.43 0.25 0.490.34 0.24 0.420.28 0.24 0.370.22 0.24 0.330.17 0.24 0.290.135 0.24 0.270.110 0.24 0.260.085 0.24 0.250.068 0.23 0.240.055 0.23 0.240.047 0.23 0.24
IEC 60502-1BS 7211*based on600/1000VapplicationBS 7889
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
r x z1.60 0.190 1.601.15 0.180 1.150.86 0.180 0.870.59 0.175 0.620.43 0.170 0.460.34 0.165 0.380.28 0.165 0.320.22 0.165 0.280.170 0.165 0.240.135 0.160 0.210.110 0.160 0.1950.088 0.160 0.1800.071 0.160 0.1700.059 0.155 0.1650.050 0.155 0.165
42 | www.taisin.com.my
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.6: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, thermoplastic (PVC / LSZH) sheathed cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
ConductorCross-Sectional
Area
Reference Method A(enclosed in conduit
in thermally insulating wall etc.)
A
Reference Method C(clipped direct)
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-CoreCable*,
3-Phase a.c.
mm2
1.01.52.546
10162535507095
120150185240300400
Reference Method B(enclosed in conduit on a wall
or in trunking etc.)
One 3 or 4-CoreCable,
3-Phase a.c.
A
Voltage Drop ( IN mV/A/m )Table B2.6: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, thermoplastic (PVC / LSZH) sheathed cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC
ConductorCross-Sectional Area
2-Core Cable,d.c.
mV/A/m
3 or 4-Core Cable,3-Phase a.c.
mm2
2-Core Cable,Single-Phase a.c.
mV/A/mmV/A/m
1.01.52.546
1016
2535507095
120150185240300400
463119127.94.72.9
1.851.350.980.670.490.390.310.25
0.1950.1550.120
463119127.94.72.9
402716106.84.02.5
r x z1.85 0.160 1.901.35 0.155 1.350.99 0.155 1.000.67 0.150 0.690.50 0.150 0.520.40 0.145 0.420.32 0.145 0.350.26 0.145 0.290.200 0.140 0.240.160 0.140 0.210.130 0.140 0.190
r x z1.60 0.140 1.651.15 0.135 1.150.86 0.135 0.870.59 0.130 0.600.43 0.130 0.450.34 0.130 0.370.28 0.125 0.300.22 0.125 0.260.175 0.125 0.210.140 0.120 0.1850.115 0.120 0.165
Reference Method E(in free air or on a perforated cable tray
etc, horizontal or vertical)
A
One 2-Core Cable,Single-Phase
a.c. or d.c.
A
One 3 or 4-CoreCable,
3-Phase a.c.
One 2-Core Cable,Single-Phase
a.c. or d.c.
AAAA
One 3 or 4-CoreCable,
3-Phase a.c.
One 2-Core Cable,Single-Phase
a.c. or d.c.
14.518.5253342577699
121145183220253290329386442
–
1316.5223038516889
109130164197227259295346396
–
17223040516991
119146175221265305334384459532625
1519.52635446080
105128154194233268300340398455536
192433455880
107138171209269328382441506599693803
17223040527196
119147179229278322371424500576667
212636496386
115149185225289352410473542641741865
182332425475
100127158192246298346399456538621741
Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for
70ºC thermoplastic insulated cables must be used.
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
IEC 60502-1BS 7629-1
www.taisin.com.my | 43
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.7: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured (non-magnetic armour),thermoplastic (PVC / LSZH) sheathed cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
ConductorCross-
SectionalArea
Reference Method C(clipped direct)
Reference Method F(in free air or on a perforated cable tray horizontal or vertical)
2 Cables,Single-Phase
a.c. or d.c.�at
retemaiD elbaC enO yb decapSgnihcuoT
3 or 4 Cables,3-Phase a.c.
�at
2 Cables,Single-Phase
a.c. or d.c.�at
3 Cables,3-Phase a.c.
�at
2 Cables,d.c.
2 Cables,Single-Phase a.c.
3 or 4 Cables,3-Phase a.c.
Horizontal Vertical
AAAAAAAAAAAmm2
507095
120150185240300400500630800
1000
237303367425488557656755853962
108211701261
220277333383437496579662717791861904961
253322389449516587689792899
1016114612461345
232293352405462524612700767851935987
1055
222285346402463529625720815918
102711191214
284356446519600688815943
11371314152818092100
270349426497575660782906
10941266147417442026
282357436504566643749842929
1032113912041289
266337412477539614714805889989
109211551238
288358425485549618715810848923992
10421110
266331393449510574666755797871940978
1041
Touching
3 Cables,3-Phase a.c.
trefoilHorizontal VerticalHorizontal Vertical
Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for
70ºC thermoplastic insulated cables must be used.
Voltage Drop ( IN mV/A/m )Table B2.7: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured (non-magnetic armour), thermoplastic (PVC / LSZH)sheathed cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC
Reference Method C & F(clipped direct, on tray or in free air)
mm2 mV/A/m
ConductorCross-
SectionalArea
507095
120150185240300400500630800
1000
0.980.670.490.390.310.25
0.1950.1550.1150.0930.0730.0560.045
r x z0.99 0.21 1.000.68 0.200 0.710.51 0.195 0.550.41 0.190 0.450.33 0.185 0.380.27 0.185 0.330.21 0.180 0.280.170 0.175 0.250.145 0.170 0.220.125 0.170 0.210.105 0.165 0.1950.090 0.160 0.1900.092 0.155 0.180
2 Cables,d.c.
3 or 4 Cables, 3-Phase a.c.2 Cables, Single-Phase a.c.
Touching Spaced* Trefoil and Touching Flat and Touching Flat and Spaced*
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
m/A/Vmm/A/Vmm/A/Vmm/A/Vmm/A/Vm
r x z0.98 0.29 1.000.69 0.29 0.750.53 0.28 0.600.43 0.27 0.510.36 0.27 0.450.30 0.26 0.400.24 0.26 0.350.195 0.25 0.320.180 0.24 0.300.165 0.24 0.290.150 0.23 0.270.145 0.23 0.270.140 0.21 0.25
r x z0.86 0.180 0.870.59 0.170 0.620.44 0.170 0.470.35 0.165 0.390.29 0.160 0.330.23 0.160 0.280.180 0.155 0.240.145 0.150 0.210.125 0.150 0.1950.105 0.145 0.1800.092 0.145 0.1700.086 0.140 0.1650.080 0.135 0.155
r x z0.84 0.25 0.880.60 0.25 0.650.46 0.24 0.520.38 0.24 0.440.31 0.23 0.390.26 0.23 0.340.21 0.22 0.300.170 0.22 0.280.160 0.21 0.270.145 0.20 0.250.135 0.195 0.240.130 0.180 0.230.125 0.170 0.21
r x z0.84 0.33 0.900.62 0.32 0.700.49 0.31 0.580.41 0.30 0.510.34 0.29 0.450.29 0.29 0.410.24 0.28 0.370.20 0.27 0.340.20 0.27 0.330.190 0.24 0.310.175 0.23 0.290.175 0.195 0.260.165 0.180 0.24
IEC 60502-1BS 5467BS 6724
44 | www.taisin.com.my
APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.8: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured, thermoplastic(PVC / LSZH) sheathed cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W
Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for
70ºC thermoplastic insulated cables must be used.
Voltage Drop ( IN mV/A/m )Table B2.8: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured, thermoplastic (PVC / LSZH) sheathed cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC
ConductorCross-Sectional Area
2-Core Cable,d.c.
mV/A/m
3 or 4-Core Cable,3-Phase a.c.
mm2
2-Core Cable,Single-Phase a.c.
mV/A/mmV/A/m
1.52.546
1016
2535507095
120150185240300400
3119127.94.72.9
1.851.350.980.670.490.390.310.25
0.1950.1550.120
3119127.94.72.9
2716106.84.02.5
r x z1.85 0.160 1.901.35 0.155 1.350.99 0.155 1.000.67 0.150 0.690.50 0.150 0.520.40 0.145 0.420.32 0.145 0.350.26 0.145 0.290.20 0.140 0.240.16 0.140 0.210.13 0.140 0.190
r x z1.60 0.140 1.651.15 0.135 1.150.86 0.135 0.870.59 0.130 0.600.43 0.130 0.450.34 0.130 0.370.28 0.125 0.300.22 0.125 0.260.175 0.125 0.210.140 0.120 0.1850.115 0.120 0.165
ConductorCross-Sectional
Area
Reference Method C(clipped direct)
A
Reference Method D(direct in ground or in ducting in ground,
in or around buildings)
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-Core Cable,3-Phase a.c.
mm2
1.52.546
10162535507095
120150185240300400
Reference Method E(in free air or on a perforated cable tray
etc, horizontal or vertical)
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-Core Cable,3-Phase a.c.
One 2-Core Cable,Single-Phase
a.c. or d.c.
One 3 or 4-Core Cable,3-Phase a.c.
AAAAA
2736496285
110146180219279338392451515607698787
233142537394
124154187238289335386441520599673
2939526690
115152188228291354410472539636732847
253344567899
131162197251304353406463546628728
253343537191
116139164203239271306343395446
–
21283644587596
115135167197223251281324365
–
IEC 60502-1BS 5467BS 6724BS 7846
Note: *Spacings larger than one cable diameter will result in a larger voltage drop.
www.taisin.com.my | 45
APPENDIX CRating Factor for Ambient Temperature
The current-carrying capacities in this work standard are based upon the following reference ambient temperatures:i) For non-sheathed and sheathed cables in air, irrespective of the installation method : 30ºCii) For buried cables, either directly in the soil or in ducts in the ground : 20ºC
When the ambient temperature in the intended location of the non-sheathed or sheathed cables di�ers from the reference ambient temperature,please refer to the appropriate rating factors as below table (Table C1.1 and C1.2).
Table C1.1: Rating factors for ambient airtemperatures other than 30ºC to be applied to thecurrent-carrying capacities for cables in free air.
Table C1.2: Rating factors for ambient groundtemperatures other than 20ºC to be applied to thecurrent-carrying capacities for cables buried toground.
Ambient TemperatureºC
EPLXCVP
253035404550556065707580859095
1.031.000.940.870.790.710.610.50
–––––––
1.021.000.960.910.870.820.760.710.650.580.500.41
–––
Ground TemperatureºC
EPLXCVP
101520253035404550556065707580
1.101.051.000.950.890.840.770.710.630.550.45
––––
1.071.041.000.960.930.890.850.800.760.710.650.600.530.460.38
Table B3.1: Short Circuit Ratings for Low Voltage Cables
I = Short Circuit Rating (kA)
S = Nominal Conductor Area (mm2)
t = Duration of Short Circuit (Sec)
K = Insulation Material Speci�c Constant
XLPE & Cross-linked Polyole�n (XLSZH) Insulated Cable
K= 0.143
PVC Insulated Cable
K= 0.115 ( S ≤ 300 mm2)
K= 0.103 ( S > 300mm2)
NominalConductor Area
Short Circuit Ratingfor 1 second
XLPE & XLSZH
1.52.546
10162535507095
120150185240300400500630800
1000
(mm2)
Short Circuit Ratingfor 1 second
PVC
(kA) (kA)
0.21450.35750.5720.8581.43
2.2883.5755.0057.15
10.0113.58517.1621.45
26.45534.3242.957.271.5
90.09114.4143
0.17250.2875
0.460.691.151.84
2.8754.0255.758.05
10.92513.8
17.2521.275
27.634.541.251.5
64.8982.4103
The maximum permissible short circuit current of cables up to 1kVwith copper conductors could be calculated with the following formula
Where
APPENDIX BShort Circuit Rating
I (kA) = _______S
t x K
46 | www.taisin.com.my
Table C2.1: Rating factors for one circuit or one multicore cable or for a group of circuits,or a group of multicore cables, to be used with current-carrying capacities of Tables B1.1to Tables B1.8.
Arrangement(cables touching) 1
Number of circuits or multicore cables To be used withcurrent-carrying
capacities,Reference
2 3 4 5 6 7 8 9 12 16 20
Bunched in air,on a surface,
embedded orenclosed
Single layer on wallor �oor
Single layermulticore on a
perforatedhorizontal or
vertical tray cablesystem
Single layermulticore on cableladder system or
cleats, etc
1.00
1.00
1.00
1.00
Note:1. These factors are applicable to uniform groups of cables, equally loaded.
2. Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no rating factor need be applied.
3. The same factors are applied to: - groups of two or three single-core cables:- multicore cables.
4. If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and the corresponding factor is applied to the tables for two loadedconductors for the two-core cables, and to the Tables for three loaded conductors for the three-core cables.
5. If a group consists of n single-core cables it may either be considered as n/2 circuits of two loaded conductors or n/3 circuits of three loaded conductors.
6. The rating factors given have been averaged over the range of conductor sizes and types of installation included in Tables B1.1 to B1.8 the overall accuracy of tabulated values is within 5%.
7. For some installations and for other methods not provided for in the above table, it may be appropriate to use factors calculated for speci�c cases, see for example Table C3.1 to C3.2.
8. When cables having di�ering conductor operating temperature are grouped together, the current rating is to be based upon the lowest operating temperature of any cable in the group.
9. If, due to known operating conditions, a cable is expected to carry not more than 30 % of its grouped rating, it may be ignored for the purpose of obtaining the rating factor for the rest of thegroup. For example, a group of N loaded cables would normally required a group rating factor of Cg applied to the tabulated It. However, if M cables in the group carry loads which are notgreater than 0.3 CgIt amperes the other cables can be sized by using the group rating factor corresponding to (N-M) cables.
0.80
0.85
0.88
0.87
0.70
0.79
0.82
0.82
0.65
0.75
0.77
0.80
0.60
0.73
0.75
0.80
0.57
0.72
0.73
0.79
0.54
0.72
0.73
0.79
0.52
0.71
0.72
0.78
0.50
0.70
0.72
0.78
0.45
0.70
0.72
0.78
0.41
0.70
0.72
0.78
0.38
0.70
0.72
0.78
MethodsA to F
Method C
MethodsE and F
Table C1.3: Rating factors for cables buried direct in the ground or in an underground conduitsystem to BS EN 50086-2-4 for soil thermal resistivities other than 2.5 K.m/W to be appliedto the current-carrying capacities for Reference Method D
Thermal resistivity K.m/WRating factor for cables in buried ducts
Rating factor for direct buried cables
30.960.90
0.51.281.88
0.81.201.62
11.181.5
1.51.1
1.28
21.051.12
2.511
Note:1. The rating factors given have been averaged over the range of conductor sizes and types of installation included in the relevant tables in this appendix. The overall accuracy of rating factors is
within ± 5%.
2. The rating factors are applicable to cables drawn into buried ducts For cables laid direct in the ground the rating factors for thermal resistivities less than 2 5 K.m/W will be higher. Where moreprecise values, are required they may be calculated by methods given in BS 7769 (BS IEC 60287).
3. The rating factors are applicable to ducts buried at depths of up to 0.8 m.
APPENDIX CRating Factor for Soil Thermal Resistivities
www.taisin.com.my | 47
APPENDIX CTable C2.2: Rating factors for more than one circuit, cables laid directly in theGround-Reference Method D in Tables A1.1 to A1.5. Single-core or multicore cables.
Numberof circuits
Cable-to-cable clearance (a)
Nil (cablestouching)
One cablediameter
0.125m 0.25m 0.5m
23456
0.750.650.600.550.50
0.800.700.600.550.55
0.850.750.700.650.60
0.900.800.750.700.70
0.900.850.800.800.80
Note:1. Values given apply to an installation depth of 0.7m and a soil thermal resisitivity of 2.5K.m/W. These are average values for the range of cable sizes and types quoted for Table B1.1 to B1.8.
The process of averaging, together with rounding o�, can result in some cases in errors of up to ± 10%. (Where more precise values are required they may be calculated by methods given inBS 7769 (BS IEC 60287)).
2. In case of a thermal resistivity lower than 2.5 K.m/W the rating factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).
MulticoresCables
Single-CoreCables
aa
a a
Table C2.3: Rating factors for more than one circuit, cables laid in ducts in the ground- Reference Method D in Tables B1.1 to B1.8
Numberof cables
Duct-to-duct Clearance (a)
Nil (ductstouching)
0.25m 0.5m 1.0m
23456
0.850.750.700.650.60
0.900.850.800.800.80
0.950.900.850.850.80
0.950.950.900.900.90
Note:1. Values given apply to an installation depth of 0.7m and a soil thermal resisitivity of 2.5K.m/W. These are average values for the range of cable sizes and types quoted for Table B1.1 to B1.8.
The process of averaging, together with rounding o�, can result in some cases in errors of up to ± 10%. (Where more precise values are required they may be calculated by methodsgiven in BS 7769 (BS IEC 60287).
2. In case of a thermal resistivity lower than 2.5 K.m/W the rating factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).
i. Multicore Cables in a Single-Way Ducts
MulticoresCables
a
Number ofsingle-corecircuits of
2 or 3 cables
Duct-to-duct Clearance (a)
Nil (ductstouching)
0.25m 0.5m 1.0m
23456
0.800.700.650.600.60
0.900.800.750.700.70
0.900.850.800.800.80
0.950.900.900.900.90
Note:1. Values given apply to an installation depth of 0.7m and a soil thermal resistivity of 2.5K.m/W. These are average values for the range of cable sizes and types quoted for Table B1.1 to B1.8.
The process of averaging, together with rounding o�, can result in some cases in errors of up to ± 10%. (Where more precise values are required they may be calculated by methodsgiven in BS 7769 (BS IEC 60287)).
2. In case of a thermal resistivity lower than 2.5 K.m/W the rating factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).
ii. Single-Core Cables in Non-Ferrous Single-Way Ducts
Single-CoresCables
a a
48 | www.taisin.com.my
Spaced
≥20mm
De De
Spaced
≥225mm De
De
≥20mm
SpacedDe De
APPENDIX CTable C3.1Rating factors for groups of more than one multicore cables, to be applied to referencecurrent-carrying capacities for multicore cables in free air- Reference Method E in Tables B 1.1 to B1.8
Perforated cable traysystems (Note 3)
Perforated cable traysystems (Note 3)
Vertical perforated cabletray systems (Note 4)
Vertical perforated cabletray systems (Note 4)
Unperforated cable traysystems
Cable ladder systems,cleats, wire mesh tray,etc (Note 3)
Cable ladder systems,cleats, wire mesh tray,etc (Note 3)
Note 1: Values given are averages for the cable types and range of conductor sizes considered in Tables B1.1 to B1.8. The spread of values is generally less than 5%.
Note 2: Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other. Values for such installations maybe signi�cantly lower and must be determined by an appropriate method.
Note 3: Values are given for the vertical spacing between cable trays of 300mm and at least 20mm between cable trays and wall. For closer spacing the factors should be reduced.
Note 4: Values are given for horizontal spacing between cable trays of 225mm with cable trays mounted back to back. For closer spacing the factors should be reduced.
Installation Method in Table A1.1 to A1.5
31
31
31
31
30
32
33
34
32
33
34
Number of cables per tray or ladder
1
Numberof trays or
ladders
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.97
0.97
0.97
0.97
1.00
1.00
1.00
1.00
1.00
1.00
1
2
3
6
1
2
3
1
2
1
2
1
2
3
6
1
2
3
6
1
2
3
2
0.87
0.86
0.84
1.00
0.99
0.98
0.88
0.91
0.91
0.84
0.83
0.82
0.81
0.86
0.85
0.84
1.00
0.99
0.98
3
0.80
0.79
0.77
0.98
0.96
0.95
0.81
0.89
0.88
0.78
0.76
0.75
0.73
0.80
0.79
0.77
1.00
0.98
0.97
4
0.77
0.76
0.73
0.95
0.92
0.91
0.76
0.88
0.87
0.75
0.72
0.71
0.69
0.78
0.76
0.73
1.00
0.97
0.96
6
0.73
0.71
0.68
0.91
0.87
0.85
0.71
0.87
0.85
0.71
0.68
0.66
0.63
0.76
0.73
0.68
1.00
0.96
0.93
9
0.68
0.66
0.64
–
–
–
0.70
–
–
0.68
0.63
0.61
0.58
0.73
0.70
0.64
–
–
–
See item 4 of Table C2.1
See item 4 of Table C2.1
See item 4 of Table C2.1
Touching
≥20mm
Touching
≥225mm
Touching
≥20mm
Touching
≥300mm
≥20mm
≥300mm
≥300mm
www.taisin.com.my | 49
Spaced
≥225mm ≥2 De
De
≥300mm
≥2 De De
APPENDIX CTable C3.2Rating factors for groups of one or more circuits of single-core cables to be applied to referencecurrent-carrying capacity for one circuit of single-core cables in free air- Reference Method F in Tables B1.1 to B1.8
Use as a multiplierto rating for:
3
Perforated cable traysystems (Note 3)
Vertical perforated cabletray systems (Note 4)
Cable ladder systems,cleats, wire mesh tray,etc. (Note 3)
Perforated cable traysystems (Note 3)
Vertical perforated cabletray systems (note 4)
Cable ladder systems,cleats, wire mesh tray,etc. (Note 3)
Note 1: Values given are averages for the cable types and range of conductor sizes considered in Tables B1.1 to B1.8. The spread of values is generally less than 5%.
Note 2: Factors apply to single layer groups of cables (or trefoil groups) as shown above and do not apply when cables are installed in more than one layer touching each other. Values for suchinstallations may be signi�cantly lower and must be determined by an appropriate method.
Note 3: Values are given for vertical spacing between cable trays of 300mm and at least 20mm between cable trays and wall. For closer spacing the factors should be reduced.
Note 4: Values are given for horizontal spacing between cable trays of 225mm with cable trays mounted back to back. For closer spacing the factors should be reduced.
Note 5: For circuits having more than one cable in parallel per phase, each three-phase set of conductors is to be considered as a circuit for the purpose of this table.
Installation Method in Table A1.1 to A1.5
31
31
32
33
34
31
31
32
33
34
Three cables inhorizontal formation
Three cables invertical formation
Three cables inhorizontal formation
Three cables in trefoilformation
Three cables in trefoilformation
Three cables in trefoilformation
Number of Three-Phase circuits per tray or ladder
21
Numberof trays or
ladders
0.87
0.81
0.78
–
–
0.96
0.89
0.86
0.96
0.89
0.86
0.89
0.86
1.00
0.93
0.90
0.91
0.87
0.85
0.86
0.84
0.97
0.93
0.90
0.98
0.93
0.92
0.91
0.90
1.00
0.95
0.94
0.98
0.96
0.95
0.96
0.95
1.00
0.98
0.97
1.00
0.97
0.96
1.00
1.00
1.00
0.97
0.96
1
2
3
1
2
1
2
3
1
2
3
1
2
1
2
3
Touching
≥225mm
Touching
≥300mm
Touching
≥300mm
≥2 De De
≥300mm
≥20mm
≥20mm
≥20mm
≥20mm
50 | www.taisin.com.my
APPENDIX DTable D1.1Cable Cores Colour Code
Function
Protective conductorFunctional earthing conductor
AC Power CircuitSingle Phase Circuit- Phase- Neutral
Three Phase Circuit- Phase1- Phase2- Phase3- Neutral
DC Two-Wire Unearthed Circuit- Positive- Negative
DC Two-Wire Earthed Circuit- Positive (of negative earth)- Negative (of negative earth)- Positive (of positive earth)- Negative (of positive earth)
DC Three-Wire Circuit- Positive- Mid-wire (may be earthed)- Negative
Alpha-Numeric Existing Core Colours New Harmonized Core Colour
––
LN
L1L2L3N
L+L–
L+MNL–
L+ML–
Green / YellowCream
RedBlack
RedYellowBlueBlack
RedBlack
RedBlackBlackBlue
RedBlackBlue
Green / YellowCream
BrownBlue
BrownBlackGreyBlue
BrownGrey
BrownBlueBlueGrey
BrownBlueGrey
In March 2004, the Amendment No.2: AMD 14905 to BS 7671:2001 (IEE Wiring Regulations Sixteenth Edition) has been harmonized with the CENELECStandard HD 384.5.514: Identi�cation including 514.3: Identi�cation of conductor and with the CENELEC Harmonization Document HD 308 S2: 2001Identi�cation of cores in cables and �exible cords.
The change in cable core colours is a major development that will a�ect the way wiring cable colours are distinguished and installed. Currently,for three phase �xed electrical installations, the wiring cable colours for the ìlineî connections are red, yellow and blue respectively. The new threephase harmonized cable core colours will be brown, black and grey, following that of the new BS 7671:2008 Requirements for electrical installations,IEE Wiring Regulations, 17th Edition. A number of countries in the European Union as well as Hong Kong and Singapore have implemented theseharmonized cable core colours.
For any new electrical installation that involved extension from existing wiring system, BS 7671 has been modi�ed to align with these cable core colourswhere suitable marking/labelling method eg. Colour tapes, sleeves, discs or by alphanumeric (letters and/or numbers) is allowed . See below �gures:-
L LN N
L LN N
SINGLE-PHASE CIRCUITSdezinomraHgnitsixE
L1 L1L2 L2L3 L3N N
THREE-PHASE CIRCUITSdezinomraHgnitsixE
L LN N
SINGLE-PHASE CIRCUITSweNgnitsixE
L1 L1L2 L2L3 L3N N
THREE-PHASE CIRCUITSdezinomraHgnitsixE
Label & Colour sleeze shall beprovided at interface.
Label & Colour sleeze shall beprovided at interface.
Identi�cation of Cores in Cables
www.taisin.com.my | 51
A GUIDE TO FIRE PERFORMANCE TESTS & STANDARDS FOR CABLESCables and wires are like blood vessels in the body which keep us alive. They supply the essential energy to every part of residential, public,commercial and industrial buildings as well as vital infrastructure facilities, to provide power for lighting, computer systems, electrical appliancesand machinery, etc. Comply with various relevant performance standards to ensure integrity and reliability.
This guide provides you with an idea of the mandated tests and standards to ensure cables and wires meet international �re performancerequirements.
TYPES OF FIRE PERFORMANCE CABLESIt is important for cables to have �re survival properties because they are widely distributed throughout a building and can be the main cause of�re transmission to una�ected areas. There are 2 types of characteristics for Fire Performance: Active - which ensures the cable, continues to transmitpower and signals during a �re, and Passive - which limits the spread of �re that can cause severe damage to property and red uces the emissionof fumes and toxic gases that can lead to loss of human lives.
These safety features are necessary to allow occupants of buildings and facilities to have the time to evacuate without being hurt or overcome by�re, toxic gases and fumes.
In Europe and the United States, where most of the �re performance standards originated, there is a slight di�erence in concerns over �re behaviour.The European countries are concerned about all aspects of �re-a�ected cables, including harmful halogen, smoke and gas contents, whereas theconcern over in the United States is the �ame spread and smoke characteristics from cables.
Cables are therefore rated for their various Fire Resistant, Flame Retardant, Low Smoke Zero Halogen (LSZH) and Low Smoke Fume (LSF) characteristics.
FLAME RETARDANT CABLESFlame Retardant cables are designed to minimise the spread of �ame in the event of a �re. Whether it is a single wire or a bundled wire cable, it issupposed to retard �ame spread so that the �re may ideally be limited to a small area and allow for emergency response to put it out. Our PVC-based cables have this characteristic and are widely used for their low cost.
LOW SMOKE AND FUME CABLES (LSF)LSF cables are slow to ignite and they burn slowly. LSF cables emit much smaller amount of smoke and fumes, with characteristics similar to thatof LSZH-FRT cables. Although its emission will still have halogen but the content is much lesser than that from PVC cables. To ensure better �reperformance, LSF cables are manufactured with �ame retardant PVC blended with HCL and smoke absorbent material for maximum e�iciency.
LOW SMOKE ZERO HALOGEN FLAME RETARDANT CABLES (LSZH-FRT)Halogens are harmful non-metal elements such as �uorine (F), chlorine (Cl), bromine (Br), iodine (I), and astatine (At). FRT cables are designed withspecial materials not only with self-extinguishing property, but also with low smoke and fume emissions without halogens, as well as an absenceof toxic gas emission in case of combustion. Thus, LSZH-FRT cables outperform PVC and LSF cables with additional protection from �re spread andthe emission of toxic gas and corrosive elements. These cables are suitable for use in inadequately ventilated areas such as those in aircraft, ships,and military facilities.
FIRE RESISTANT CABLESFire Resistant cables are designed with superior �re resistant property to continue to operate in the event of a �re for a speci�c period of time(usually between 30 and 180 minutes). They are speci�ed for used in vital installations and essential support facilities, such as a �re alarm system,as they are designed to withstand �re and maintain circuit integrity. In such cables the stranded annealed copper conductor is sealed with a �re-resisting mica tape wrap, so that even after the insulation has been burnt phase-to phase and phase-to-earth contact can be prevented. They arealso designed to withstand mechanical shock and perform under wet condition.
STANDARDS FOR FLAME RETARDANCY (European & British Standards)There are three classes of tests for �ame propagation in cables. They are the IEC 60332-1, IEC 60332-2 and IEC 60332-3 standards. The EuropeanCommittee for Electromechanical Standardization (CENELEC) - which adopts the standards of the International Electro-technical Committee (IEC)- uses the �rst two to assess �ame propagation characteristics of a single wire, and the IEC 60332-3 for similar characteristics test for bundled cables,which is more stringent.
The British Standards for �ame propagation test for single wire and bundled wires and cables are the BS EN 60332-1 (formerly known as BS4066-1) and BS EN 50266-2 (formerly known as BS 4066-3).
FLAME TEST ON SINGLE VERTICAL INSULATED WIRE/CABLE(IEC 60332-1, BS EN 60332-1)The �ame propagation characteristic of a single wire or cable is tested using a 60cm cable specimen that is �xed vertically in a metal chamber. Acalibrated gas burner adjusted with the recommended �ow rates of gas and air is lighted and applied at 45-degree angle on the surface of the testsample at 475 mm (+/- 5mm) from the lower edge of the upper horizontal clamp. The �ame is applied continuously for a duration (60 - 480 sec)corresponding to the diameter of the wire/cable. After the �ame has been extinguished, the specimen is cleaned and examined. It passes the testif the charring does not reach 50mm from the lower edge of the top clamp, or the charring does not extend beyond 475mm from the point of �ameapplication.
FLAME TEST ON BUNCHED WIRES/CABLES(IEC 60332-3, BS EN 50266-2)This test comprises four categories (A, B, C & D) according to the volume of combustible material per metre of cable. It determines the bunchedcable’s ability to limit �ame spread.
The test sample consists of several pieces of cable each 3.5 m long, in order to have the required quantity of combustible material per metre ofspecimen. The cables are installed in a metal chamber on the front of a vertical ladder and are subjected to a gas burner �ame for a speci�ed timeunder controlled air �ow. At the end of the speci�ed duration, the burnt and charred portion of the cable must not be more than 2.5 m from theburner point.
APPENDIX E
52 | www.taisin.com.my
STANDARDS FOR FIRE RESISTANCEIEC 60331-11 (APPARATUS 750ºC)IEC 60331-21 (CABLES RATED UP TO 0.6/1.0kV)To verify circuit integrity in the event of a �re, the cable sample is held on a �ame at about 750ºC for 3 hours under its rated voltage. The samplemust then be re-energised in not less than 12 hours after the test, and to pass, the specimen must not breakdown and circuit integrity must bemaintained.
BS6387This test is performed to investigate the cable’s ability to maintain circuit integrity under three conditions - �re only, �re with spray of water, and�re with mechanical shock.
Resistance to �re - the cable while performing at its rated voltage is subjected to gas burner �re at the speci�ed temperature for the respectivecategories - Category A - 3 hours at 650ºC, Category B - 3 hours at 750ºC and Category C - 3 hours at 950ºC.
Resistance to �re and water (Category W) is another cable specimen with rated voltage running is exposed for 15 minutes to �ame at 650º C anda further 15 minutes to �re and a continuous spray of water.
Resistance to �re and mechanical shock in this test a new cable sample with rated voltage running is mounted on a vertical panel which is struckwith a steel bar for 15 minutes while subjected to a �ame. The burning temperatures required for the respective categories are Category X (650ºC),Category Y (750ºC) and Category Z (950ºC).
STANDARDS FOR HALOGEN, SMOKE EMISSION, CORROSIVITY AND TOXICITYSMOKE DENSITY(IEC 61034-2, BS EN 61034-2)To measure the density of smoke from a burning cable, samples are placed horizontally in a 3 square metre metal cabinet and burned by �amefrom 100 cubic cm of alcohol in a metal tray. A fan is used to ensure uniformity of the smoke and light transmittance is measured by a photometricsystem in the cabinet. The result is expressed as percentage light transmittance and the specimen is rated to have passed the test if the value ismore than 60%, as the higher the percentage the less smoke is emitted.
HALOGEN EMISSION(IEC 60754-1, BS EN 50267-2-1)To determine the amount of corrosive gases, such as �uorine, chlorine, bromine, astatine and iodine released by the cable, samples of non-metallicmaterials (1g) are burned in a tubular oven at up to 800ºC. Controlled air �ow inside the chamber absorbs the resulting gases in water, which istested for its acidity. If the specimen yields less than 5 mg/g of hydrochloric acid it is rated Halogen Free, but if the yield is between 5 mg/g and15 mg/g it is classed as Low Smoke & Fumes. The results do not determine whether the specimen is totally halogen free.
SMOKE CORROSIVELY(IEC 60754-2, BS EN 50267-2-2)This method determines the corrosiveness of the gases released from the cables by burning the insulation material in a furnace at ≤935ºC withrated air supply for 30 minutes. The e�uent gases are absorbed into distilled water, which is then measured for its pH and conductivity. A pH-valueof above 4.3 and conductivity of over 10µS / mm must be achieved.
TOXICITY INDEX(ES713)This Naval Engineering Standard method is used to analyse noxious gas emitted from the burning specimen and the amount that each of the gascan cause fatality. Sample of the cable insulating material (~1.0 g) is burned in a chamber with a volume of 0.7-1m3 and the ga ses emitted duringcombustion are detected and collected in order to determine the quantities of the elements, such as carbon dioxide, carbon monoxide, sulphurdioxide, nitric oxide, acids, ammonia, etc. The Toxicity Index is derived from the calculated quantity of each gas produced when 100g (scaled up)of the material is burnt in air in a volume of 1m3 and the particular resulting concentration fatal to human when exposed to it for 30 minutes, thusdetermining the critical toxicity factor. The higher the index, the more toxic the insulating material when burnt in a �re. For example, the toxicityindex of a FRT cable is generally known to be lower than 5.
OTHER RELEVANT STANDARDSLIMITING OXYGEN INDEX (LOI)(ISO4589-2, BS ISO7211-3)LOI is de�ned as the minimum concentration of oxygen required to support �aming combustion in a �owing air mixture of oxygen and nitrogen(in this instance, the downward burning of a vertically-mounted test specimen such as a candle.) The oxygen concentration is recorded as volumepercentage. A higher LOI value (oxygen concentration) means better �ame retardancy. For example, with 21% oxygen index the material will burnby itself automatically at room temperature; LSZH cables require a higher index between 33% and 42%. The test method allows accuracy of + 0.5%to be achieved.
TEMPERATURE INDEX (TI)(ISO4589, BS 2782.1)Research has shown that compared to the conventional oxygen index, higher temperature at which a material will burn in air is a better determinantof combustibility. When air temperature rises, the Oxygen Index Value falls, thus, the test for Temperature Index (TI) has been developed from theLOI method. The apparatus used for the TI test is essentially similar to that of the LOI test but the incoming combustion gas is heated. It tests the�ammability of the sample with a small �ame to �nd the optimum temperature at which the specimen will burn automatically. When a specimenburns automatically in the air with 21% oxygen, the temperature at this point is known as the TI. In the case of coal, the oxygen index will dropto 21% and it will burn automatically when the air temperature reaches 150ºC. This temperature for coal is recorded as its TI.
APPENDIX E
www.taisin.com.my | 53
1. APPLICATION OF TERMS & CONDITIONSThese conditions govern the sales and purchase of goods ordered by Buyer from Seller (“the goods”) and shall override any terms and conditions whether previouslyor hereafter stipulated incorporated or referred to by Buyer whether orally in its purchase order or other documents.
2. DELIVERYa. Any time for delivery named by Seller is an estimate only and Seller is not liable to make good any damage or loss arising out of any such delay.b. Delivery shall be deemed to have been made if seller delivers the goods to the location speci�ced by the Buyer and Delivery Order is endorsed by any person
present thereat. Seller not responsible to ensure the goods have been delivered to or is collected by Buyer or its authorized personnel and shall not be liablefor any loss or damage to Buyer by reason of unauthorized collection of the goods.
c. Should Buyer fail to take delivery of goods, Seller shall be entitled (without derogation of its rights under Law) to charge Buyer for storage and insurance forthe goods calculated from the date �xed for delivery.
d. The Seller reserves the right to deliver goods by installments and each installment shall be deemed to have been sold under a separate contract. Failure todeliver any installment shall not entitle the buyer to repudiate the contract.
e. O� loading and/or handling will in all events be the responsibility of the Buyer.f. If the goods to be delivered are, at the Buyer’s discretion, delivered to the destination other than the Buyer’s premises, the Seller will arrange such delivery for
the Buyer and all costs for carriage and insurance will be to the Buyer’s account.g. Availability of the goods when o�ered ex-stock is subject to such goods being sold in another transaction between the date when the Seller advises the goods
are available, and the date when it receives the Buyer’s order. Any delivery time o�ered for products made to special customer order is indicative only, and theSeller shall not be liable for any loss or damage whatsoever arising as a consequence or result of any such failure to deliver.
3. PRICEThe quoted price for the goods are subject to change in the event of any imposition or increase in taxes, levies or duties whatsoever on the goods, its componentsor raw materials.
4. PAYMENTPayments for the goods shall be made within the time stipulated in the invoice. Interest at 1.5% per month will be charged on late payment.
5. TIME OF THE ESSENCETime within which the Buyer is to pay for the goods shall be of the essence of this Contract.
6. ACCEPTANCEBuyer shall inspect the goods immediately upon delivery. Unless Seller receives notice that the goods are not in accordance with the Buyer’s order and the goodsreturned to Seller within 24 hours from the date of delivery, the goods shall be deemed to have been accepted by the Buyer PROVIDED ALWAYS Seller will notaccept return of used goods and Buyer shall not reject any goods which are in accordance with the Buyer’s order.
7. DESCRIPTIONNotwithstanding any description of the goods given by the Seller or Buyer, no sale of goods shall constitute or be construed as a sale by description.
8. WARRANTIESSave and except for written warranties (if any) given by Seller, the Seller does not give any warranties as to the quality, state, condition or �tness of the goods ortheir suitability for any purpose or for use under any speci�c conditions, notwithstanding that such purpose or condition may be known or made known to Seller.
9. DEFECTSSave and except as noti�ed pursuant to Clause 6) above, Seller shall be under no liability to Buyer either in contract or tort for loss, injury or damage sustained byBuyer or any third party by reason of defects in the goods whether latent or otherwise but Buyer will keep Seller indemni�ed against any such claim.
10. TITLETitle to the goods remains vested in Seller receives the full purchase price. If such payment is overdue, the Seller may without prejudice to any other rights sue forthe purchase price, recover or re-sell the goods and the Buyer grants the Seller, its servants/agents the right and/or license to enter the Buyer’s premise and/or anyother premise where the goods are stored. If any of the goods are sold by Buyer before title has passed to Buyer, Buyer shall hold the proceeds of sale and all rightsagainst purchaser in trust for Seller.
11. RISKRisk passes to Buyer upon delivery of goods to Buyer.
12. DEFAULTIf Buyer fail to pay Seller on due date, commits a breach of any of its obligation herein, becomes insolvent or commits an act of bankruptcy, Seller may withoutprejudice to its other rights and without giving any notice, suspend/cancel further deliveries, stop any delivery in transit under this Contract or any other contractsand/or limit/cancel the Buyer’s credit as to time and/or amount for executed, executory or future orders, and/or request for securities or guarantees. Seller shallnot be liable to Buyer for any damages which Buyer may su�er or incur by reason thereof.
13. CANCELLATION OF CREDITNotwithstanding anything herein contained, Seller reserves the right to limit/cancel the credit of the Buyer as to time and/or amount without giving any reasonsthereof and to demand full settlement immediately of all sums that may be owing by Buyer notwithstanding that the credit period has not expired.
14. FORCE MAJEURESeller shall not be liable to Buyer for failure to deliver the goods by reason of any breakdown of plant, �re, explosion, Act of God, or outbreak of hostilities, nationalemergency, industrial disputes, shortage of labour, raw materials, energy or any causes beyond Seller’s control and which seller is unable to prevent by the exerciseof reasonable diligence, whether of the class of causes enumerated herein or not.
15. APPROPRIATION OF PAYMENTSAll payments received from the Buyer will be applied towards settlement of the Buyer’s oldest debts comprising the earliest invoices, debit notes (including debitnotes for overdue interest) and other charges howsoever arising PROVIDED ALWAYS Seller may appropriate any payments towards account of interest beforeprincipal in respect of any debt as the Seller shall in its absolute discretion deem �t.
16. STATEMENT OF ACCOUNTAll amounts stated in the invoices and statement of accounts of Seller shall be conclusive of the amounts due and owing by Buyer to Seller and shall be bindingagainst Buyer in any legal proceedings.
17. RIGHTS OF SET-OFFSeller entitled to set-o� against Buyer’s debts all monies now or hereafter standing to the credit of Buyer’s account with Seller and for this purpose Buyer shall giveirrevocable authority to Seller to collect on behalf of Buyer and give valid receipt and discharge in respect of all such monies owing to the Buyer.
18. WAIVERNo failure or delay by the Seller in exercising any rights hereunder shall operate as a waiver hereof nor shall any single or partial exercise of right preclude any furtherexercise thereof or the exercises of any other right.
19. SALE OF GOODS ACT (“the Act”)The terms and conditions in favour of the Seller hereunder shall be in addition to and not in substitution for any term condition warranty expressed or implied infavour of the Seller under the Act or any statutory and re-enactment thereto for the time being enforced.
20. INFRINGEMENT OF PATENTS DESIGNSBuyer shall indemnify Seller against all damages, claims, costs and expenses which Seller may become liable as a result or work done or goods sold in accordancewith Buyer’s speci�cations which involve infringement of any patents, registered designs or trademarks.
21. NOTICESAny notices, communications or demands shall be deemed to have been su�ciently given if sent by prepaid post to the address of the addressee stated herein orto the addressee’s last known place of business and shall be presumed to have reached the address in ordinary course of post.
General Disclaimer We have taken reasonable measures to ensure that the information and data represented in this catalogue is accurate and currentwarranty regarding such information or data, and hereby expressly disclaims all responsibility and legal liability to persons or entities that use or access its content, based on their reliance on any informationor data that is available through this catalogue. We are not liable for all expenses, losses, damages and costs you might incur as a result of the information being inaccurate or incomplete in any way, andfor any reason.
TERMS & CONDITIONS OF SALES
Factories and Regional O�ces
Tai Sin Electric Limited24 Gul CrescentJurong TownSingapore 629531Tel: (+65) 6672 9292Fax: (+65) 6861 4084E-Mail: [email protected]: www.taisin.com.sg
Tai Sin Electric Cables(Malaysia) Sdn. Bhd.PTD 37433 & 37434O� Jalan Perindustrian Senai 3Kawasan Perindustrian Senai Fasa 2P.O.Box 73, 81400 SenaiJohor Darul Takzim, MalaysiaTel: (+60) 7 599 8888Fax: (+60) 7 599 8898E-Mail: [email protected]: www.taisin.com.my
Tai Sin Electric Cables(VN) Co., Ltd.No.20, VSIP II Street 2Viet Nam - Singapore Industrial Park 2Hoa Phu Ward, Thu Dau Mot TownBinh Duong Province, VietnamTel: (+84) 650 3635 088Fax: (+84) 650 3635 077E-Mail: [email protected]: www.taisin.com.vn
(Updated as at November 2015)