linx dvi 8x8 rev 1.1 - syscomtec distribution ag · 2020. 10. 13. · figure 1-1 linx dvi 8x8...

64
Linx DVI 8x8 Matrix Switcher User’s Guide Revision 1.1 — May 2008

Upload: others

Post on 30-Jan-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • Linx DVI 8x8 Matrix SwitcherUser’s Guide

    Revision 1.1 — May 2008

  • . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DOCUMENT• Linx DVI 8x8 Matrix Switcher User’s Guide• P/N 350-8794 Revision 1.1• May 2008

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COPYRIGHT© 2008 RGB Spectrum, Inc. All rights reserved.

    This guide is for use with the RGB Spectrum Linx DVI 8x8 Matrix Switcher. Use for any other purpose is not permitted. This guide was prepared for viewing on a PC; a copy may be printed as required.

    • The RGB Spectrum logo is a trademark of RGB Spectrum, Inc. in the United States and other countries.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .NOTICERGB Spectrum reserves the right to make any modification to this guide or the information contained herein at any time without notice.

    All features, functions, and specifications are subject to change without notice or obligation.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMPANY ADDRESSRGB Spectrum 950 Marina Village Pkwy. Alameda, CA 94501

    • Telephone: (510) 814-7000• Fax: (510) 814-7026

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ACKNOWLEDGEMENTThe RGB Spectrum Web Control Panel (WCP) uses the GoAhead WebServer.

    Copyright © 2003 GoAhead Software, Inc. All rights reserved

    Pentium is a registered trademark of Intel Corporation in the United States and other countries.Windows is a registered trademark of Microsoft Corporation in the United States and other countries.Java is a trademark of Sun Microsystems, Inc. in the United States and other countries.

  • . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LIMITED WARRANTYRGB Spectrum (RGB) warrants that this product will be free from defects in material and workmanship, under normal use and service when correctly installed and maintained, for a period of three (3) years from date of shipment. RGB’s liability under this warranty is limited solely to replacing, repairing or issuing credit for any product which is shown to be defective during the warranty period. Purchaser shall (i) notify RGB promptly in writing of any claims, and (ii) provide RGB with an opportunity to inspect and test the product claimed to be defective. Warranty does not cover misuse, abuse, improper installation or application, improper maintenance or repair, alteration, accident or negligence in use, improper temperature, humidity or other environmental condition, storage, transportation or handling. RGB Spectrum shall have no obligations under this warranty with respect to any defect unless it receives notice and a description of such defect no later than five (5) business days following the expiration of the warranty period.

    THE WARRANTIES STATED HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING (BUT NOT LIMITED TO) ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

    IN NO EVENT SHALL RGB BE LIABLE FOR ANY SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR LOSS, DAMAGE OR EXPENSE DIRECTLY OR INDIRECTLY ARISING FROM THE PURCHASER’S INABILITY TO USE THE PRODUCT EITHER SEPARATELY OR IN COMBINATION WITH ANY OTHER EQUIPMENT OR FACILITIES, OR FROM ANY OTHER CAUSE.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EXTENDED WARRANTYAn annual extended warranty may be purchased. Should the product fail to operate properly during the covered period, RGB Spectrum will repair the product and restore it to normal operation without charge for labor and parts. For further information on obtaining an extended warranty, email [email protected] or call (510) 814-7000.

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide i

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . .TABLE OF CONTENTS

    List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ivList of Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v

    Chapter 1 Introduction and Installation. . . . . . . . . . . . . . 1Physical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2EDID Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    EDID Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Hot Plug Event . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4EDID priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4EDID list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4EDID Management . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Input Equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Video Inputs and Outputs . . . . . . . . . . . . . . . . . . . . 5Control Connections . . . . . . . . . . . . . . . . . . . . . . . . 5

    RS-232 Control. . . . . . . . . . . . . . . . . . . . . . . . . 510/100 BASE-T Control . . . . . . . . . . . . . . . . . . 6

    Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Chapter 2 Communications Setup. . . . . . . . . . . . . . . . . . 7Serial Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Launching a HyperTerminal Window . . . . . . . . . . . 7Ethernet Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Setting the PC IP Address . . . . . . . . . . . . . . . . . . 10Beginning a Telnet Session . . . . . . . . . . . . . . . . . 11

    Changing the Linx DVI 8x8 Matrix Switcher IP Address. 13

    Chapter 3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Command Line Operation . . . . . . . . . . . . . . . . . . . . . . . 14

    System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 14Communication Settings. . . . . . . . . . . . . . . . . . . . 15Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Presets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15EDID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Exporting and Importing System Settings. . . . . . . 16

    PRESETS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 16System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16EDID. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17All . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide ii

    . . .

    . .

    Front Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 18XY Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . 18Presets Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Status Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20System Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Web Control Panel Operation. . . . . . . . . . . . . . . . . . . . . 22Routing Window . . . . . . . . . . . . . . . . . . . . . . . . . . 23Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . 25Presets Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26EDID Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27System Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    Network Settings . . . . . . . . . . . . . . . . . . . . . . 28Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Serial Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    Chapter 4 Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Command Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Command Help. . . . . . . . . . . . . . . . . . . . . . . . . . . 30Command Arguments. . . . . . . . . . . . . . . . . . . . . . 31Predefined Parameter Values. . . . . . . . . . . . . . . . 31Query the Current Setting. . . . . . . . . . . . . . . . . . . 31

    Commands Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . 31Communications Commands . . . . . . . . . . . . . . . . . . . . . 34Switch Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Preset Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38EDID Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Miscellaneous Commands . . . . . . . . . . . . . . . . . . . . . . . 42

    Chapter 5 Transferring Files and Updating Firmware . 44Transferring Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    Downloading a File from the Linx Switcher. . . . . . 44Uploading a File to the Linx Switcher . . . . . . . . . . 46

    Update System Firmware . . . . . . . . . . . . . . . . . . . . . . . . 48

    Chapter 6 Maintenance and Troubleshooting. . . . . . . . 49Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    Appendix A Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 51

    Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 51Communications Specifications . . . . . . . . . . . . . . . . . . . 51DVI Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 52Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54RS-232 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide iii

    . . .

    . .

    Appendix B Contact Information. . . . . . . . . . . . . . . . . . . . 56

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide iv

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LIST OF FIGURESFigure 1-1 Linx DVI 8x8 Matrix Switcher Front Panel . . . . . . . . . . . . . 2Figure 1-2 Linx DVI 8x8 Matrix Switcher Rear Panel . . . . . . . . . . . . . 2Figure 1-3 Selecting EDID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Figure 2-1 HyperTerminal Path. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 2-2 Connection Description Dialog . . . . . . . . . . . . . . . . . . . . . 8Figure 2-3 Connect To Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 2-4 COM Properties Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 2-5 Local Area Network Properties Window . . . . . . . . . . . . . 10Figure 2-6 Entering an IP Address for the PC. . . . . . . . . . . . . . . . . . 11Figure 2-7 Run Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 2-8 Telnet Connected. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 3-1 XY Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Figure 3-2 XY Control Panel Ready to Take Change . . . . . . . . . . . . 19Figure 3-3 Presets Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Figure 3-4 Matrix Status Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 3-5 System Information Page . . . . . . . . . . . . . . . . . . . . . . . . 21Figure 3-6 Entering the IP Address in the Browser. . . . . . . . . . . . . . 22Figure 3-7 Web Control Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 3-8 Routing Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 3-9 Preview Preset Routings . . . . . . . . . . . . . . . . . . . . . . . . . 24Figure 3-10 Configuration Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Figure 3-11 Presets Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 3-12 Name and Save Preset . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 3-13 EDID Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Figure 3-14 System Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Figure 5-1 Run Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Figure 5-2 FTP Download Session . . . . . . . . . . . . . . . . . . . . . . . . . . 45Figure 5-3 Run Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Figure 5-4 FTP Upload Session . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Figure A-1 DVI Input and Output Connectors . . . . . . . . . . . . . . . . . . 52Figure A-2 Ethernet Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Figure A-3 RS-232 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide v

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LIST OF TABLESTable 1-1 Accessory Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Table 4-1 Alphabetical List of Commands . . . . . . . . . . . . . . . . . . . . 31Table 4-2 Communications Commands. . . . . . . . . . . . . . . . . . . . . . 34Table 4-3 Switch Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Table 4-4 Preset Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Table 4-5 EDID Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Table 4-6 Miscellaneous Commands. . . . . . . . . . . . . . . . . . . . . . . . 42Table 6-1 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 50Table A-1 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 51Table A-1 Communications Specifications. . . . . . . . . . . . . . . . . . . . 51Table A-2 Digital Input and Output Specifications . . . . . . . . . . . . . . 52Table A-3 DVI Connector Pin Assignments . . . . . . . . . . . . . . . . . . . 52Table A-4 Ethernet Connector Pin Assignments . . . . . . . . . . . . . . . 54Table A-5 RS-232 Connector Pin Assignments . . . . . . . . . . . . . . . . 55

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 1

    1INTRODUCTION AND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .INSTALLATION

    The Linx DVI 8x8 Matrix Switcher is a non-blocking digital router. Housed in a rugged steel chassis, it is ideal for challenging environments including mobile applications. System features include:

    • Eight DVI single-link inputs and outputs• Up to 1600 x 1200 pixel resolution at 60 Hz - 1.65 Gbit/sec• Supports HD resolutions including 1920 x 1080p, 1920 x 1200,

    and 2048 x 1080p at 60Hz

    • EDID management~ Automatic pass-through~ Programmable input or output

    • Automatic or selectable cable equalization on inputs up to 50 meters

    • Pixel reclocking on input and output• Embedded operating system• Temperature controlled fan with washable front panel filter• Multiple control methods

    ~ Front panel touch screen~ Command interface (serial or network)~ Graphic user interface over Ethernet

    • Single or multi-point controlItems in the Linx Switcher accessory kit include the items shown in .

    Table 1-1 Accessory Kit

    Item Part Number

    User CD containing this manual 610-8793-01

    Power cord - DomesticOR

    Power cord - International

    510-8026-01

    510-8026-02

  • I N T R O D U C T I O N A N D I N S TA L L A T I O NPhysical Description

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 2

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PHYSICAL DESCRIPTIONThe Linx Switcher 2 RU chassis has standard rackmount brackets. Front panel features include:

    • Touch screen• Air filter• Indicator LEDs

    ~ Active - Communication active~ Link - Ethernet link is present~ Power - AC power is on~ Alarm - System is overheated

    Figure 1-1 Linx DVI 8x8 Matrix Switcher Front Panel

    All connections are made on the rear panel of the Linx Switcher.

    Figure 1-2 Linx DVI 8x8 Matrix Switcher Rear Panel

    Features on the rear panel include:

    active link pow

    erala

    rm

    L in x D V I 8 x 8

    Output-1 Output-2 Output-3 Output-4 Output-5 Output-6 Output-7 Output-8

    Input-1 Input-2 Input-3 Input-4 Input-5 Input-6 Input-7 Input-8

    10-100 BASE-T

    RS-232

    10/100 BASE-T Ethernet Port

    RS-232Serial Port DVI Inputs

    DVI Outputs AC Power

    • RS-232 port • 10/100 BASE-T port• Eight DVI inputs • Eight DVI outputs• Input/output LED indicators • AC power connector

  • I N T R O D U C T I O N A N D I N S TA L L A T I O NEDID Control

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 3

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EDID CONTROL

    EDID, extended display identification data, is information which enables a graphics adapter source to output a graphics standard best suited for the connected display monitor. This information includes the display resolution and frame rate. Linx Switcher supports EDID management providing a choice of what EDID to supply to the source and arbitrates when an input is routed to multiple output ports connected to displays of differing capabilities.

    Figure 1-3 Selecting EDID

    . . . . . . . . . EDID REGISTERS There are three EDID registers within the Linx Switcher:• Display EDID - Contains EDID for each output passed through

    from the display device. The contents of the display register may be saved as an entry in the EDID list.

    • Emulated EDID - Contains EDID for each output selected from the EDID list.

    • Fixed EDID - Contains fixed EDID for each input selected from the EDID list.

    The factory default resolution for each register is 1280 x 1024 at a frame rate of 60 Hz.

    EDID I/F

    Emulated EDID

    Display EDID

    Output 1

    Output 8

    Emulated EDID

    Display EDID

    Input 8 Fixed EDID

    Static EDID

    User selected from EDID timing table

    User selected from EDID timing table

    User selected from EDID timing table

    Input EDID Priority

    Arbitration

    Input #8 EDID

    Output #1 EDID

    Output #8 EDID

    EDID data for input #8 is stored here

    Pass Through EDID

    Select between lowest resolution or lowest output

    number

    Dynamic EDID

  • I N T R O D U C T I O N A N D I N S TA L L A T I O NEDID Control

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 4

    . . .

    . .

    The block diagram in Figure 1-3 illustrates the selection of EDID to be passed to the host graphics adapter. The data is stored in the EDID interface which can be read when the Linx Switcher is powered on or off.

    . . . . . . . . . HOT PLUG EVENT When a display is connected to an output port, a hot plug event occurs and the Linx Switcher downloads the display EDID parameters to the display EDID register.

    A hot plug event also occurs when a graphics source, host, is connected to a Linx Switcher input port. A host can read the EDID interface when the Linx Switcher is powered off.

    . . . . . . . . . EDID PRIORITY When an input is routed to multiple outputs, a number of options are available. Fixed EDID can be selected from the EDID list or a priority scheme used to select EDID from one of the output ports. Priority can be set to select the active output with the lowest resolution or the lowest numbered active output. EDID priority is applied to emulated and display pass-through data.

    Only active outputs are considered when establishing priority. Active outputs are those having parameters stored in the Linx Switcher EDID display register; these may be outputs currently connected or those with assigned emulated EDID.

    . . . . . . . . . EDID LIST The EDID list is used to apply parameters to the fixed and emulated EDID registers. Entries in the list are numbered 1 to 100. Data contained in the list include:

    • List index number• Name• Display device manufacturer’s ID• Resolution and frame rate

    Advanced users may view and modify additional timing parameters with third-party software such as Phoenix EDID Designer freeware available at http://www.tucows.com/preview/329441.

    . . . . . . . . . EDID MANAGEMENT EDID management may be performed through the WCP or command line operation. EDID management is discussed in the Web Control Panel Operation and Command Line Operation sections of this chapter and in Chapter 4 . Management functions include:

    • Loading EDID from the EDID list to a register• Saving display EDID to the EDID list• Naming an EDID list entry• Viewing an entry in the EDID list• Deleting an EDID list entry• Exporting and importing an EDID list entry

  • I N T R O D U C T I O N A N D I N S TA L L A T I O NInput Equalization

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 5

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .INPUT EQUALIZATION Input equalization is used to compensate for the losses caused by the electrical and physical characteristics of a DVI cable. The longer the cable, the greater the need for equalization.

    Input equalization is used to compensate for losses based on input cable length. A non-equalized input may result in one of the following on the displayed output:

    • “Sparkles”• Drop-out• No signal

    Equalization for an input can be set to OFF, AUTO, or to a level between 1 and 50. Enter a level value if the default setting, AUTO, does not yield quality output.

    No equalization should be needed for cables under 5 meters (15 feet) in length or for fiber optic cables. For longer cables, set the manual equalization level to a value that corresponds to the length, in meters, of the cable. Each cable is unique relative to the amount of equalization it may require. Tune equalization by entering higher or lower levels to reach the final setting.

    The input equalization command, INputEQualizer, is described on page 36; input equalization is not available on the front panel or WCP.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .INSTALLATION

    . . . . . . . . . RACK MOUNTING If the Linx Switcher is to be rack mounted, it should be done before making any cable connections. Use screws compatible with the rack to secure the front of the unit.

    VIDEO INPUTS AND

    . . . . . . . . . OUTPUTSThe quality of DVI cables is important to the performance when long lengths are use. Cable using 24 AWG conductors may provide good results up to 50 meters. Cable equalization is only available on input channels so operation with 50-meter output cables will require an external equalizer.

    CONTROL

    . . . . . . . . . CONNECTIONSUse of all the Linx Switcher commands and function requires connection through the RS-232 or 10/100 BASE-T port.

    R S - 2 3 2 C O N T R O L

    Connect the Linx Switcher RS-232 to a PC using a cable with standard RJ-11 connectors.

  • I N T R O D U C T I O N A N D I N S TA L L A T I O NInstallation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 6

    . . .

    . .

    1 0 / 1 0 0 B A S E - T C O N T R O L

    Connection to the 10/100 BASE-T port uses cables with RJ-45 connectors.

    • Direct connection — Use an Ethernet crossover cable.

    • LAN connection — Use a standard Ethernet cable.

    . . . . . . . . . POWER Connect the Linx Switcher to a power source using the supplied cord.

    Note Computers that are set up to communicate on the network are typically configured to have a dynamic IP address. In this configuration, the computer is provided with a suitable IP address by a network DHCP server. When connecting directly to the Linx Switcher a server will not be available; a static IP address must be set manually on the computer. Refer to the Setting the PC IP Address on page 10.

    Note The Linx Switcher is configured at the factory with the default IP address 192.168.1.200. Before connecting to a network, verify that this is a valid IP address on the network. Contact the network manager for assistance. The IP address can be changed using the IPADDRess command from either the serial port or from a Telnet session over the Ethernet port. For more details see Changing the Linx DVI 8x8 Matrix Switcher IP Address on page 13.

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 7

    2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMUNICATIONS SETUP

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SERIAL COMMUNICATION

    LAUNCHING A

    HYPERTERMINAL

    . . . . . . . . . WINDOWA command line interface is provided for Linx DVI 8x8 Matrix Switcher using the serial port. A full description of available commands is provided in Chapter 4 on page 30.PCs running the Microsoft Windows operating system are provided with serial emulation software known as HyperTerminal. This provides a convenient method to communicate with the Linx Switcher.

    Use the following steps to launch a HyperTerminal window on a PC:

    1. Connect the Linx Switcher to a PC as described in section RS-232 Control on page 5.

    2. Click Start > Programs > Accessories > Communications > HyperTerminal.

    Figure 2-1 HyperTerminal Path

  • C O M M U N I C A T I O N S S E T U PSerial Communication

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 8

    . . .

    . .

    This action displays the Connection Description Dialog, a sample of which is shown below.

    Figure 2-2 Connection Description Dialog

    3. In the dialog:~ Enter a name.~ Choose an icon.~ Click OK to display the Connect To dialog box.

    Figure 2-3 Connect To Dialog

    4. In the Connect To dialog box, ignore the Country, Area Code and Phone Number fields. In the Connect Using field, select the PC’s COM port to which the serial cable from Linx Switcher is connected.

  • C O M M U N I C A T I O N S S E T U PEthernet Control

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 9

    . . .

    . .

    5. Click OK to display the COM Properties dialog box.

    Figure 2-4 COM Properties Dialog

    6. Configure the PC to the Linx Switcher’s default settings as follows:

    ~ Bits per second (baud): 9600~ Data bits: 8 ~ Parity: None~ Stop bits: 1~ Flow control: XOn / XOff

    If any parameters have been changed, enter accordingly.

    7. Click OK to display the HyperTerminal window.

    8. Confirm the communication with the Linx Switcher by typing ver and pressing ENTER. The current firmware version should be displayed. If not, check the settings outlined above and repeat.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ETHERNET CONTROLThe Linx DVI 8x8 Matrix Switcher can be controlled from the 10/100 Base-T Ethernet port using either a graphical user interface or a command line interface.The graphical interface uses a standard web browser such as the Microsoft Internet Explorer; the Linx Switcher can be connected to a standard LAN or directly as a peer-to-peer connection. The command line interface uses a Telnet session to a private port.

    Connection of the Linx Switcher via the Ethernet port requires it to have a unique, static IP address. The factory default IP address is

  • C O M M U N I C A T I O N S S E T U PEthernet Control

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 10

    . . .

    . .

    192.168.1.200. Consult the network administrator to obtain a valid IP address before commencing the network setup.

    To use the Linx Switcher on a Local Area Network (LAN), change the unit’s IP address before putting it on the network. This avoids potential conflicts between Linx Switcher’s default IP address and the network. See Changing the Linx DVI 8x8 Matrix Switcher IP Address on page 13 for instructions.

    SETTING THE PC

    . . . . . . . . . IP ADDRESSA PC connected directly to Linx Switcher through the 10/100 BASE-T port must be assigned a static IP address. For Microsoft Windows operating system, use the procedure below to set the PC network address to one compatible with the Linx Switcher:

    1. Use an Ethernet crossover cable or hub to connect directly between the Linx Switcher’s Ethernet port and the network port of a PC.

    2. From the PC Start menu, select Control Panel.3. In the Control Panel, select Network Connections.4. In Network Connections, right click on Local Area

    Connection and select Properties. A window similar to that shown in Figure 2-5 will open.

    Figure 2-5 Local Area Network Properties Window

    5. Select Internet Protocol (TCP/IP) and click on Properties.6. Click the Use the following IP address radio button.7. Enter an IP address compatible with the current address of the

    Linx Switcher. If this is the factory default of 192.168.1.200, a PC address 192.168.1.nnn may be entered where nnn is a number between 1 and 255 except 200.

  • C O M M U N I C A T I O N S S E T U PEthernet Control

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 11

    . . .

    . .

    Figure 2-6 Entering an IP Address for the PC

    8. Close all windows opened during this procedure.

    BEGINNING A

    . . . . . . . . . TELNET SESSIONWith the IP address of the PC set, a Telnet session can be started.

    1. From the PC Start menu at the bottom of the Windows desktop select Run...

    2. In the Open dialog box type cmd as shown in Figure 2-7.

    Figure 2-7 Run Window

    3. Click OK to open the Windows command window.

    4. At the prompt in the command window type:telnet 8000

    where represents the Linx DVI 8x8 Matrix Switcher’s current IP address.

  • C O M M U N I C A T I O N S S E T U PEthernet Control

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 12

    . . .

    . .

    Example: If the Linx DVI 8x8 Matrix Switcher’s IP address has not been changed from its default value, type:

    telnet 192.168.1.200 8000

    ... and press ENTER.5. At the Password prompt type:

    RGB

    ... and press ENTER. The password must be entered in upper case.

    At this point, the Telnet window starts and the Linx DVI 8x8 Matrix Switcher responds with the product name and copyright notice as shown in the figure below.

    Figure 2-8 Telnet Connected

    To change the Linx Switcher IP address, see the following section.

    Note To close a Telnet session, type EXIT and press ENTER.

  • C O M M U N I C A T I O N S S E T U PChanging the Linx DVI 8x8 Matrix Switcher IP Address

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 13

    . . .

    . .

    CHANGING THE LINX DVI 8X8

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MATRIX SWITCHER IP ADDRESS

    With a Hyperterminal or Telnet session initiated, use the following steps to change the Linx Switcher IP address to one compatible with the local area network.

    1. To change the current IP address, type IPADDR followed by the new IP Address provided by the network administrator.

    Example: If the new IP address is 192.168.1.190, type:IPADDR 192.168.1.190

    ... and press ENTER.

    The Linx Switcher responds with the following message:The system must be restarted for your changes to take effect.

    Do you want to restart the system (y/n)?

    2. Type y to accept the new address, or n to retain the current address.

    If y is pressed in the step above, the Linx Switcher reboots and the Telnet connection is lost.

    3. To re-establish the Telnet connection, press ENTER to display the command prompt. Type telnet 8000 using the new IP address.

    In addition to setting the IP address, the IP subnet mask (IPSubNET) and gateway (IPGateWay) can also be set as required. This completes the procedure for setting up the IP address.The Linx Switcher can now be connected to a LAN for control over the Ethernet port using ASCII commands from the Telnet Window or from the Web Control Panel using a standard web browser.

    Important When the IP address is set from the Ethernet port, the Telnet connection (and communication) will be lost. This behavior is to be expected. Restart the Telnet session using the new IP address.

    Note To close a Telnet session, type EXIT and press ENTER or use the keystroke sequence Control + D.

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 14

    3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPERATION

    Operation of the Linx DVI 8x8 Matrix Switcher can be done through command lines, front panel controls, or the graphic interface web control panel (WCP). All functions are support under command line operation; capabilities of the front panel and WCP operation are reduced.

    Transferring files and updating firmware is discussed in Chapter 5 on page 44. A detailed discussion of commands can be found in Chapter 4 on page 30.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMAND LINE OPERATION

    Command line control of the Linx Switcher can be done through the RS-232 or Ethernet connection. See Chapter 2 on page 7 for establishing communication with these ports. Commands are grouped in the following categories:

    • System Settings• Communication Settings• Switch Settings• Presets• EDID• Exporting and Importing System Settings

    . . . . . . . . . SYSTEM SETTINGS The Linx Switcher can operate without making modification of any system settings. However, commands are provided to set parameters as required.

    SYStemTIME - Use to display or set the system 24-hour clock.

    HOSTNAME - An optional name may be assigned to the Linx Switcher with this command. Without an argument, this command displays the current host name.

    Additional system commands are:

    SYStemReSeT- Reset the system without turning the power off and on.

    VERsion - Displays the system, front panel and firmware versions.

  • O P E R A T I O NCommand Line Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 15

    . . .

    . .

    RestoreFactoryDefaults - CAUTION: Executing this command will delete all presets and return all system parameters to their factory default values.

    UpdateFirmWare - Installs firmware that has been uploaded to the Linx Switcher. See Chapter 5 for a full discussion on updating firmware.

    COMMUNICATION

    . . . . . . . . . SETTINGSUse of communications commands are discussed in Chapter 2 .

    . . . . . . . . . SWITCH SETTINGS Four commands can be used to set input/output values and to display current parameters.

    NAMEOUTput - Use this command to assign an optional descriptive name to the outputs. The system default is “Output #”

    NAMEINput - Use this command to assign an optional descriptive name to the inputs. The system default is “Input #.”

    ROUTE - Assigns an input source to an output destination. A single input can be routed to one or more output destinations.

    OUTputENable - Enables/disables one or all outputs.

    OUTputSouRCe - Associate an output to an input. An output can only be associated with a single input.

    INputEQualizer - Compensate for the losses caused by the electrical and physical characteristics of a DVI cable

    . . . . . . . . . PRESETS Presets define specific input/output routing which can be loaded with a single command. Presets are numbered 1 to 99. Preset commands are:

    NAMEPreSeT - Presets are referred to by number, but may be named; issuing the command without a name argument displays the current preset name.

    SHoWPreSeT - List the name and the input/output routing for a preset.

    LiStPreSeT - Lists the names of a range of presets.

    DELetePreSeT - Deleting a preset removes a name if present and all input/output settings.

    SaVePreSeT - Save a single input-to-output routing or save the complete current configuration.

    RECALLPreSeT - Load the input/output settings of a saved preset.

  • O P E R A T I O NCommand Line Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 16

    . . .

    . .

    . . . . . . . . . EDID EDID commands are used to set the display resolution and timing to be used by the graphics host. See EDID Control for an explanation of EDID management.

    EDIDMode - Set the EDID mode to fixed or dynamic.

    DISPLAYMODE - Set the display EDID mode to emulated or pass-through.

    EDIDPRiority - Select minimum resolution or output number as priority criteria.

    LoaDFixedEDID - Load EDID list entry into input fixed EDID register.

    LoaDEmulateEDID - Load EDID list entry to the output emulate register.

    SaVeEDID - Save content of the display register to an EDID list entry.

    DELeteEDID - Delete an EDID list entry.

    NAMEEDID -Name an EDID list entry.

    LiStEDID - List the parameters for one or more EDID list entries.

    EXportEDID - Exports an EDID list entry to memory for FTP transfer.

    IMportEDID - Imports an EDID list entry after FTP transfer.

    EXPORTING AND

    IMPORTING SYSTEM

    . . . . . . . . . SETTINGSSystem settings can be exported to a text file and transferred to a PC for subsequent import back to a Linx Switcher. It is recommended that settings be exported prior to updating firmware. Exporting and importing can also be used to transfer settings between multiple switchers. See Transferring Files on page 44 for instructions on transferring exported files to and from the Linx Switcher.

    EXPORTSETTINGS - The exported parameters can be selected by entering the appropriate argument to the command. These are presets, system, EDID, or all.

    P R E S E T S

    The name assigned for all 99 presets is listed. This is followed by the output 1 and its input number for all presets; subsequent outputs and input routes for all presets follows.

    S Y S T E M

    The model number and firmware version are saved to a file.

  • O P E R A T I O NCommand Line Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 17

    . . .

    . .

    E D I D

    Exporting a single EDID list entry allows advanced users to use third-party software to make changes to timing parameters.

    A L L

    In addition to the preset, EDID, and system parameters, All includes the communication values for baud rate, echo, and handshake.

    IMPORTSETTINGS - After a settings file has been uploaded from a PC to the Linx Switcher, this command is issued to load the saved values.

  • O P E R A T I O NFront Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 18

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FRONT PANEL OPERATION

    The Linx DVI 8x8 Matrix Switcher front panel supports a limited number of system commands. The four pages which may be displayed on the front panel are:

    • XY Control Panel• Presets Page• Status Page• System Page

    The XY Control Panel is the default menu displayed at power-up.

    Figure 3-1 XY Control Panel

    To display a window, touch the desired button on the bottom of the window. To enable a new configuration on a page, touch the TAKE button.

    . . . . . . . . . XY CONTROL PANEL The XY Control Panel can be used to view the current output/input assignments or to make changes to those assignments. See Figure 3-1.

    Use the up or down arrows to step through the outputs to view the current inputs assigned.

    To change the input assigned to an output:

    1. Use the up or down arrow to display the desired output. 2. Use the up or down arrow to display the desired input.

    An input not currently assigned to the displayed output will be shown in reverse video.

    XY CONTROL PANELOUTPUT

    03 Conference Room

    07 Input number 7INPUT

    XY PST STAT SYS TAKE

  • O P E R A T I O NFront Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 19

    . . .

    . .

    Figure 3-2 XY Control Panel Ready to Take Change

    3. Press TAKE to complete the new assignment.

    The input and TAKE will then be shown in normal contrast.

    . . . . . . . . . PRESETS PAGE Use the up and down arrows to view existing preset routings. Front panel operation does not support the creation or assignment of presets. Stepping through the presets, TAKE will be displayed in reverse contrast.

    Figure 3-3 Presets Page

    XY CONTOL PANELOUTPUT

    03 Conference Room

    04 Input number 4INPUT

    XY PST STAT SYS TAKE

    Note If TAKE is not pressed before selecting a different page, the selection made on the XY Control Panel will be lost.

    PRESETS

    XY PST STAT SYS TAKE

    1 2 3 4 5 6 7 812345678

    OUTPUTS

    SELECT

    15

    Configuration 1

    5 6

  • O P E R A T I O NFront Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 20

    . . .

    . .

    To view settings, use the up or down arrow to step through the 99 presets. The preset number, input/output routings, and the preset name, if defined, are displayed. If no valid input is connected to an input port, the input port number will be shown in reverse video.

    The presence of a diamond in a row indicates that this assignment will override the current assignment. If there is no diamond in a row, no change will be made to that output. Use the Matrix display to determine current routing.

    To select a preset routing:

    1. Use the up or down arrow to step to the desired preset.2. Touch TAKE to change to the displayed preset.

    The TAKE button will change to normal video.

    . . . . . . . . . STATUS PAGE The status page displays the current routing of input to output ports. If a valid input is not present, the input number and assigned output numbers will be displayed in reverse video. No controls are supported on the status page.

    Figure 3-4 Matrix Status Page

    MATRIX STATUS

    XY PST STAT SYS TAKE

    1 2 3 4 5 6 7 812345678

  • O P E R A T I O NFront Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 21

    . . .

    . .

    . . . . . . . . . SYSTEM PAGE System information is displayed on the System page. Changes to system settings can be made through a command line interface or through the web control panel only

    Figure 3-5 System Information Page

    Model number - No change possible

    Firmware version - Indicates the current firmware revision. See Update System Firmware on page 48 for information on updating firmware.

    Hardware version - No change possible.

    FPGA version - Displays the current FPGA version. This is automatically updated when the firmware is updated.

    IP Address - Indicates the current IP address. Change the setting using a command line interface or the web control panel (WCP).

    Baud Rate - Displays the current baud rate of the RS-232 interface. Change the setting using the command line interface or the WCP.

    SYSTEM INFORMATION

    XY PST STAT SYS TAKE

    MODEL:F/W VER:H/W VER:FPGA VER:IP ADDR:BAUD RT:

    LINX DVI 8x81.001.001.00192.168.1.2029600

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 22

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .WEB CONTROL PANEL OPERATIONThe web control panel, WCP, provides a graphic alternative to command-line control. This method uses the Linx DVI 8x8 Matrix Switcher’s internal web server, allowing set-up and operation from a standard browser.

    The functions of the WCP are described in the following sections:

    • Routing Window• Configuration Tab• Presets Tab• EDID Tab• System Tab

    See the Ethernet Control in Chapter 2 for instructions on connecting to the Linx Switcher via the Ethernet port. The Linx Switcher on a LAN (Local Area Network) must have an IP address compatible with the LAN.

    • The Microsoft Internet Explorer web browser version 7 with default settings is recommended.

    • Windows font size should be set to Normal (96 DPI) for correct display of the WCP. To verify this setting:

    ~ Select Display from the Windows Control Panel. ~ Click on the Settings tab.~ Click on Advanced.~ Select Normal (96 DPI).

    • Ensure a copy of Java™ Runtime Environment software, version 1.4.2, 1.5.0 or higher, is installed on the PC. (The software version may be referred to 4.2 and 5.0.) A copy of Java is provided on the CD or can be downloaded free of charge from the official Sun Microsystems web site at http://www.java.com/en/download/manual.jsp

    • Disable any pop-up blockers before launching the WCP.When the physical connections have been made, launch an internet web browser and connect to the Linx DVI 8x8 Matrix Switcher by entering its IP address into the URL address line.

    Example: If the Linx DVI 8x8 Matrix Switcher IP address is 192.168.1.200, the browser entry would be as illustrated below.

    Figure 3-6 Entering the IP Address in the Browser

    The WCP, shown in Figure 3-7, opens.

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 23

    . . .

    . .

    Figure 3-7 Web Control Panel

    . . . . . . . . . ROUTING WINDOW The left side of the WCP displays information about preset or current input/output routing. Routing changes can be made by clicking on the desired row/column. Any input may be routed to one or more outputs.

    Figure 3-8 Routing Window

    Notice that as the cursor is moved over the routing window, the input and output numbers are highlighted.

    Select Preset

    Load Selected Pres

    Preview Preset

    ut Status

    ut Names

    Output NamesEnable/Disable Out

    Routing

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 24

    . . .

    . .

    Select Preset - Use the drop down list to select a preset numbered 1 to 99.

    Load Preset - Click to load the currently displayed preset. The current routing display is updated. Routings are modified only for those designated in the preset; unspecified outputs retain existing inputs.

    Preview Preset - Check to show routings for the indicated preset. Preset routings are shown in red in preview mode.

    Figure 3-9 Preview Preset Routings

    Enable/Disable Outputs - Enabled outputs are indicated in green. Click an output number to disable it; diabled outputs are indicated in red.

    Output Names - Displays the names assigned using the Configuration tab to the eight outputs.

    Input Status - A detected valid input is indicated in green. Red indicates no input.

    Routing - The current routing is indicated by green dots; preset preview routing is indicated by red dots. Routing may be changed by clicking in the desired row/column. To change a preset, click the Presets tab.

    Note No changes to the preset or current routing can be made when Preview preset’s routing is checked.To make changes to presets, go to the Preset tab.

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 25

    . . .

    . .

    Input Names - Displays the names assigned using the Configuration tab to the eight inputs.

    CONFIGURATION

    . . . . . . . . . TABThe Configuration tab is used to name inputs and outputs and to set EDID parameters.

    Figure 3-10 Configuration Tab

    Input Number - Select an input number from the drop-down list.

    Input Name - To name or rename an input, type the desired name and press ENTER.

    Input EDID Assignment - Select between a Dynamic EDID, determined by the output EDID, or select a Fixed EDID from the drop-down list. EDID assignment corresponds to the EDIDMode command. See EDID Control in Chapter 1 for more information.

    Priority Rule - When dynamic EDID is selected for an input routed to multiple outputs, the priority rule determines which output EDID will be used. The priority can be the output with the lowest resolution or the lowest numbered output.

    Output Number - Select an output number from the drop-down list.

    Output Name - To name or rename an output, type the desired name and press ENTER.

    Note Control-Z may be used to undo a single operation only: either a loaded preset or route one input to all outputs (right mouse click). The mouse cursor must be placed within the routing matrix borders.

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 26

    . . .

    . .

    Output EDID Selection - Select to use the Pass Through EDID or Emulated EDID from the drop-down list. EDID selection corresponds to the DISPLAYMODE command.

    . . . . . . . . . PRESETS TAB Routing for presets is done in the Routing Window; the Presets tab is used to save and name the presets. Presets can be created and viewed from this tab but cannot be loaded; click another tab to enable preset loading.

    Figure 3-11 Presets Tab

    Preset List - Select a preset number, 1 to 99, from the drop-down list.

    Show Preset’s Routings - Check to display the indicated preset in the routing window.

    Delete - Click to delete the indicated preset. A window opens asking to confirm or cancel the deletion.

    Create Preset - Click Save to save the routings displayed in the routing window to the preset number listed above. A window will open allowing a preset name to be entered. Click OK to save.

    Figure 3-12 Name and Save Preset

    To create a preset:

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 27

    . . .

    . .

    1. Select a preset number2. Check Show preset’s routing.3. In the routing window, click on the appropriate row/column for

    each output to be included in the preset.

    4. Click Save.5. Enter a preset name if desired and click OK.

    . . . . . . . . . EDID TAB The EDID tab is used to manage the entries in the EDID list. EDID information is captured from connected outputs and may be saved to the EDID list. Displayed EDID information includes the name, manufacturer’s ID, and manufacturer’s model code.

    Figure 3-13 EDID Tab

    EDID List - Select an EDID entry from 1 to 100. Previously saved information will be displayed.

    Save - After an EDID list entry and an output port have been selected, click Save to save the display information.

    Rename - Use to rename an existing EDID list entry.

    Delete - Deletes an EDID list entry.

    Select Display ID to Save into the List - Select the output whose EDID values are to be saved to the EDID list.

    To create an entry in the EDID list:

    1. Select the output number connected to the display whose EDID is to be saved.

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 28

    . . .

    . .

    2. Select an entry from the EDID list. This can be an empty entry or new information can be saved to a previously defined entry.

    3. Click SAVE. A window opens to allow a name to be entered. If no name is entered, the resolution and frame rate are used.

    4. Click OK to save the EDID list entry.

    . . . . . . . . . SYSTEM TAB The System tab supports modifications to the network and serial port settings. Product information and current system temperature are displayed.

    Figure 3-14 System Tab

    N E T W O R K S E T T I N G S

    Network settings can be modified. Enter new data and click Apply.

    Hostname - Enter an optional name for the Linx Switcher.

    IP Address - If the IP address is changed, the WCP must be restarted by entering the new address in the browser.

    Subnet Mask - Modify the subnet mask as required.

    Default Gateway - Modify the default gateway as required.

    I N F O

    System information is display only.

    Product ID - The product name is factory-entered and not subject to change.

  • O P E R A T I O NWeb Control Panel Operation

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 29

    . . .

    . .

    Firmware Version - The version number will be updated when new firmware is installed.

    Serial Number - The product serial number is factory-entered and not subject to change.

    MAC Address - The MAC address is factory-entered and not subject to change.

    Board Temperature - Displays the current system temperature.

    WCP Version - Displays the version number of the WCP. Version number updates when the WCP software is updated.

    S E R I A L P O R T

    Baud - Select a baud rate from the drop-down list. The default is 9600.

    Echo - Turn echo on or off. Default is ON.

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 30

    4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMANDS

    Serial commands can be issued through the Linx DVI 8x8 Matrix Switcher RS-232 port or through the Ethernet port using Telnet. See Chapter 2 for connection instructions.

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMAND FORMATAll commands take the following form:

    COMMAND_NAME ...

    … followed by ENTER.

    The majority of commands have both long and short forms:

    • The long form version is an easily understood word or the concatenation of two or more words.

    • The short form version is an abbreviation of the command name indicated in bold face, upper case. However, commands are not case sensitive.

    The command BAUDrate could be entered in four different ways:BAUDRATE

    baudrate

    BAUD

    baud

    . . . . . . . . . COMMAND HELP Command: Help There are two primary ways to use the Linx Switcher’s help feature:

    • Type Help to list all commands.• Type Help followed by the command to get command-specific

    help.

    Example: Type H inname to get help on the input name command.

    • Type Help followed by the first character or characters of a command name to get a list of all commands beginning with those characters.

    Example: Type H IP to get help on the commands associated with IP addressing.

  • C O M M A N D SCommands Summary

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 31

    . . .

    . .

    COMMAND

    . . . . . . . . . ARGUMENTSRequired parameter values are shown in angle brackets < > and optional parameters are contained in square brackets [ ].

    COMMAND [value2]

    In this example, is a required parameter and [value2] is an optional parameter.

    PREDEFINED

    PARAMETER

    . . . . . . . . . VALUESSome commands have predefined values, and only these may be entered as arguments. Predefined parameter values are indicated as:

    Example: The choices for BAUDrate are:

    QUERY THE

    . . . . . . . . . CURRENT SETTINGMany commands will report back on the current parameter settings. To establish the current parameters associated with the command enter the command without any arguments. Linx Switcher will respond with the current settings of the selected parameter.

    Example: To display the current IP address of the Linx Switcher, enter the IPADDRess command without entering an argument.

    Typing the command:IPADDR

    might return:192.168.1.201

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMANDS SUMMARY

    Note Do not use the delete key when entering commands. The backspace key may be used.

    Table 4-1 Alphabetical List of Commands

    Command Type Description

    BAUDrate Communication Sets the baud rate for the serial port.

    DELeteEDID EDID Deletes the EDID parameters from the EDID list.

    DELetePreSeT Switch Deletes specific preset or all presets.

    DISPLAYMODE EDID Sets the display ID reported for dynamic EDID mode.

    ECHO Communication Turns the serial echo on/off.

    EDIDMode EDID Sets EDID mode to fixed or dynamic.

  • C O M M A N D SCommands Summary

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 32

    . . .

    . .

    EDIDPRiority EDID Sets the EDID priority when input is routed to multiple outputs.

    EXportEDID EDID Transfers the specified EDID list entry to the Linx Switcher memory for transfer to a target device.

    EXPORTSETTINGS Miscellaneous Writes a list of system attribute names and values to a text file.

    HANDShaking Communication Selects hardware or software handshaking for the serial control port.

    Help Miscellaneous Displays information about commands.

    HOSTNAME Communication Sets or reports the Ethernet hostname.

    IMportEDID EDID Imports a single entry from the Linx Switcher memory to a specified EDID list index.

    IMPORTSETTINGS Miscellaneous Loads a list of system attribute names and values.

    INputEQualizer Switch Sets the level of input equalization to compensate for cable length.

    INputSTATus Switch Displays input channel status.

    IPADDRess Communication Sets or reports the Linx Switcher IP address.

    IPGateWay Communication Sets or reports the network gateway IP address.

    IPSubNET Communication Sets or reports the subnet mask.

    LiStEDID EDID Lists EDID information for one or more EDID list entries.

    LiStPreSeT Switch Shows routing for a range of presets.

    LoaDEmulateEDID EDID Loads EDID parameters to the specified emulate register.

    LoaDFixedEDID EDID Loads EDID parameters to the specified fixed register.

    MACADDRess Communication Displays the Linx Switcher MAC (hardware) address.

    NAMEEDID EDID Names the entered EDID list entry.

    NAMEINput Switch Adds names to input channels.

    NAMEOUTput Switch Adds names to output channels.

    NAMEPreSeT Switch Adds a name to a preset.

    OUTputENable Switch Enable or disable one or all outputs.

    OUTputSouRCe Switch Sets routing path: to output # from input #.

    RECALLPreSeT Switch Loads a saved preset.

    RestoreFactoryDefaults Miscellaneous Restores all system settings to factory default values.

    ROUTE Switch Sets routing path: from input # to output #

    Table 4-1 Alphabetical List of Commands (Continued)

    Command Type Description

  • C O M M A N D SCommands Summary

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 33

    . . .

    . .

    SaVeEDID EDID Saves the EDID parameters from an output to a specified EDID list index.

    SaVePreSeT Switch Saves preset routings.

    SHoWPreSeT Switch Shows all routing for selected preset number.

    SYStemINFO Miscellaneous Reports model, serial number, IP and Ethernet addresses, firmware version.

    SYStemReSeT Miscellaneous Restarts the system without powering off and on.

    SYStemTIME Miscellaneous Sets or reports system time.

    UpdateFirmWare Miscellaneous Updates the system firmware.

    VERsion Miscellaneous Reports the firmware version.

    Table 4-1 Alphabetical List of Commands (Continued)

    Command Type Description

  • C O M M A N D SCommunications Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 34

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMUNICATIONS COMMANDSSee Chapter 2 for details on setting up communications.

    Table 4-2 Communications Commands

    Command Arguments Description

    BAUDrate

    Sets the serial port baud rate. Operation at the highest speed possible is recommended.

    Example: To set the baud rate to 19200 type:

    baud 19200 and press ENTER.Without an argument, the current baud rate is displayed.

    Default: 9600

    ECHO Turns the serial echo On/Off.

    Example: To turn the echo off, type:

    echo off and press ENTER.Omit the argument to display the current state.

    Default: ON

    HANDShaking Sets the type of flow control on the serial port. Hardware handshaking uses CTS/RTS control. Software handshaking protocol is XON/XOFF.

    Example: To set handshaking to hardware, type:

    hands hw and press ENTER.Omit the argument to display the current setting.

    Default: Software

    HOSTNAME Sets the Ethernet hostname. A maximum of 23 alphanumeric and underscore characters may be used; spaces may not be used.

    Example: To remove a host name type:

    hostname "" and press ENTERWithout an argument, this command returns the current host name.

    Default: none

  • C O M M A N D SCommunications Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 35

    . . .

    . .

    IPADDRess Changes the IP address of the Linx Switcher.

    Example: to set the IP address to 192.168.35.101, type:

    IPADDR 192.168.35.101 and press ENTER.

    Use the SYStemReSeT command to reboot the unit to activate the new IP address.

    Without an argument, this command reports the current IP address.

    Default: 192.168.1.200

    IPGateWay Changes the IP gateway address of the Linx Switcher.

    Example: to set the IP gateway address to 192.168.1.102, type:

    ipgw 192.168.1.102 and press ENTER.

    Use the SYStemReSeT command to reboot the unit to activate the new IP gateway address.

    Without an argument, this command reports the current IP gateway address.

    Default: 192.168.1.1

    IPSubNET Changes the IP subnet address of the Linx Switcher.

    Example: to set the IP subnet address to 255.255.255.1, type:

    ipsnet 255.255.255.1 and press ENTER.

    Use the SYStemReSeT command to reboot the unit to activate the new IP subnet address.

    Without an argument, this command reports the current IP subnet address.

    Default: 255.255.255.0

    MACADDRess none Displays the physical Ethernet Media Access Controller address.

    Table 4-2 Communications Commands (Continued)

    Command Arguments Description

  • C O M M A N D SSwitch Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 36

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SWITCH COMMANDS

    Table 4-3 Switch Commands

    Command Arguments Description

    INputEQualizer

    Defines the equalization setting for one or all inputs. See Input Equalization in Chapter 1 . Level values are 1 to 50.

    Example: To set the equalization level of input 3 to 25, type:

    ineq 3 25 and press ENTER.To display the current equalization value, enter only the input argument.

    INputSTATus The status display will include the input number, yes or no to indicate the presence of a valid input signal, and the number of any associated outputs.

    Example: To display the status of input 1, type:

    instat 1 and press ENTER.

    NAMEINput Enter an input number and the name to be assigned to it. The name can be up to 23 alphanumeric characters; spaces are permitted.

    Example: To assign the name “Level 3” to input 3, type:

    namein 3 Level 3 and press ENTER.If a name is not entered, the command will return the current name of the indicated input.

    NAMEOUTput

    Enter the desired output number followed by the name to be assigned. The name can be up to 23 alphanumeric characters; spaces are permitted.

    Example: To assign the name “Conference Room” to output 5, type:

    nameout 5 Conference Room and press ENTER.

    If a name is not entered, the command will return the current name of the indicated output.

  • C O M M A N D SSwitch Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 37

    . . .

    . .

    OUTputENable

    Enable or disable one or all outputs. If an output has been disabled, loading a preset will not re-enable it; issue an OUTputENable command to do so.

    Example: To disable all outputs, type:

    outen all off and press ENTER.Enter only the output # or all to display the current status.

    OUTputSouRCe Enter the output number followed by the number of the input to be assigned.

    Example: To route input 2 to output 7, type:

    outsrc 7 2 and press ENTER.To get the current status for the specified output, omit the input argument.

    ROUTE Enter the input number followed by the desired output assignment. An input can be assigned to one or more outputs.

    Example: To route input 3 to output 4, type:

    route 3 4 and press ENTER.To display the current status of an input, omit the output argument.

    Table 4-3 Switch Commands (Continued)

    Command Arguments Description

  • C O M M A N D SPreset Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 38

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PRESET COMMANDS

    Table 4-4 Preset Commands

    DELetePreSeT Deleting a preset clears it of any input/output assignments and removes the name if one has been entered. A prompt to confirm the delete is displayed.

    Example: To clear preset 90, type:

    delpst 90 and press ENTER.

    SHoWPreSeT Enter the number of the desired preset to display its name, if entered, and all input/output settings.

    LiStPreSeT

    Lists preset names in specified range or all presets.

    Example: To list presets 10 through 20, type:

    lspst 10 20 and press ENTER.

    NAMEPreSeT

    For a preset name, enter a maximum of 23 alphanumeric characters; spaces may be used.

    Example: To name preset 11 “Training”, type:

    namepst 11 Training and press ENTER.

    Without a preset name, this command returns the current name of the preset number entered.

    RECALLPreSeT Enter the desired preset number to load input/output assignments.

    Example: To load preset 15, type:

    recallpst 15 and press ENTER.

    SaVePreSeT [input #,output #]

    Enter only a preset number to save the current input/output configuration. Enter a single input number and output number to save to the selected preset; other existing input/output assignments are not modified. Input and output numbers must be separated by a comma.

    Example: To save the current routing to preset 12, type:

    presetsave 15 and press ENTER.Example: To assign input 1 to output 6 in preset 10, type:

    svpst 10 1,6 and press ENTER.

  • C O M M A N D SEDID Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 39

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EDID COMMANDSSee EDID Control in Chapter 1 for details.

    Table 4-5 EDID Commands

    Command Arguments DescriptionEDIDMode

    Sets the EDID mode for one or all inputs to FIXED or DYNAMIC. In fixed mode, EDID parameters are user defined regardless of output routing.

    Example: To set the mode to DYNAMIC for all inputs, type:

    edidm all dynamic and press ENTER.

    To display the current setting, do not enter a mode.

    DISPLAYMODE

    Sets the display ID that is reported when the EDIDMODE is set to DYNAMIC. EMULATED uses the EDID list entry specified with the LoaDEmulateEDID command. PASSthrough provides EDID from the display connected to the specified output.

    Example: To set the display mode to PASSthrough for output 4, type:

    displaymode 4 pass and press ENTER.

    To display the current setting, do not enter a mode.

    EDIDPRiority

    In DYNAMIC mode with an input routed to multiple outputs, this command sets minimum resolution or output number as the criteria for selecting the EDID to be used. When the priority is set to MINRES, the EDID information associated with the lowest resolution output used will be reported. When the priority is set to OUTNUM, the lowest number output EDID information is reported.

    Example: To report EDID information from the lowest resolution output for all inputs, type:

    edidpri all minres and type ENTER.

    To display the current setting, enter the output number or all only.

  • C O M M A N D SEDID Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 40

    . . .

    . .

    LoaDFixedEDID

    Loads the EDID parameters from the EDID list entry to the fixed register of the specified input.

    Example: To load EDID list entry 21 to the input 5 fixed register, type:

    ldfedid 5 21 and press ENTER.To display the current EDID list entry loaded, omit the EDID list argument.

    LoaDEmulateEDID

    Loads EDID parameters of the specified EDID list entry to the EDID emulate display register of the specified output.

    Example: To load the parameters from EDID list entry 75 to all output emulate registers, type:

    ldeedid all 75 and press ENTER.To display the EDID information currently in the emulate display register, omit the EDID list number.

    SaVeEDID Saves the EDID parameters of the specified output to the EDID list number entered.

    Example: Save the EDID information of output 6 to timing index number 31, type:

    svedid 31 6 and press ENTER.

    DELeteEDID Deletes the EDID information from the specified EDID list number.

    Example: To clear all EDID settings from the EDID list, type:

    deledid all and press ENTER.

    NAMEEDID

    When an EDID list entry is created using the SaVeEDID command, the default name is the resolution of the specified output; use this command to rename an entry. To delete a name, enter the EDID list number followed by ““.

    EDID list entry names can be up to 23 characters in length and may include alpha, numeric, and punctuation characters.

    Example: To assign the name ViewSonic to EDID list entry 45, type:

    nameedid 45 ViewSonic and press ENTER.

    To display the current name of an EDID list entry omit the name argument.

    Table 4-5 EDID Commands (Continued)

    Command Arguments Description

  • C O M M A N D SEDID Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 41

    . . .

    . .

    LiStEDID |

    Lists the manufacturer’s ID and product code and the name for a range of EDID list entries.

    Example: To display EDID parameters for list numbers 10 to 20, type:

    lsedid 10 20 and press ENTER.

    EXportEDID [file name.txt]

    Transfers the specified EDID list entry to the Linx Switcher memory for transfer to a target device. See Transferring Files in Chapter 5 for instructions on downloading and uploading files.

    Example: To save EDID list entry 15 to file dell_2.txt, type:

    exdid 15 dell_2.txt and press ENTER.

    If the filename is omitted it is automatically generated from the name of the EDID list entry.

    IMportEDID

    Imports a single entry from the Linx Switcher memory to a specified EDID list index. The file name is case sensitive. See Transferring Files in Chapter 5 for instructions on downloading and uploading files.

    Example: To copy EDID parameters from the file sony_1.txt to EDID list entry 16, type:

    imedid 16 sony_1.txt and press ENTER.

    Table 4-5 EDID Commands (Continued)

    Command Arguments Description

  • C O M M A N D SMiscellaneous Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 42

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MISCELLANEOUS COMMANDS

    Table 4-6 Miscellaneous Commands

    Command Arguments DescriptionHelp [command] See Command Help on page 30 for details.

    EXPORTSETTINGS [file name.txt]

    Writes a list of system attributes to a text file. The file name may be up to 23 characters in length; use any alpha numerics or underscore. The name must include the .txt extension. The resulting file may be downloaded from the Linx Switcher through the Ethernet port. See Downloading a File from the Linx Switcher on page 44 for complete instructions.

    See Exporting and Importing System Settings on page 16 for details on stored parameters.

    Example: To export the routing of all presets to a file named “Presets,” type:

    exportsettings presets Presets.txt and press ENTER.

    Default file name: export.txt

    IMPORTSETTINGS Loads a list of system attributes from a saved file. The file must include the extension .txt.

    See Exporting and Importing System Settings on page 16 for details on loaded parameters.

    Example: To load the settings file system.txt, type:

    importsettings system.txt and press ENTER.

    RestoreFactoryDefaults none Restores all user settings to their factory default values.

    SYStemINFO none Reports model, serial number, IP and Ethernet addresses, firmware version

    SYStemReSeT none Causes the Linx Switcher to reboot. This command allows the system firmware to be restarted without having to use the front panel power switch. Use to begin using new IP values.

  • C O M M A N D SMiscellaneous Commands

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 43

    . . .

    . .

    SYStemTIME Sets the system time using a 24-hour clock. Without an argument it returns the current system time.

    Example: To set the system time to 9:30:15 on June 20, 2007, type:

    2007 06 20 09 30 15 and press ENTER.

    UpdateFirmWare none Refer to Update System Firmware on page 48 for a complete discussion of updating firmware.

    VERsion none Reports the system, front panel and channel processors firmware versions.

    Table 4-6 Miscellaneous Commands (Continued)

    Command Arguments Description

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 44

    5TRANSFERRING FILES AND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPDATING FIRMWARE

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TRANSFERRING FILESFiles may be downloaded from and uploaded to the Linx DVI 8x8 Matrix Switcher using File Transfer Protocol (FTP) via connection through the Ethernet port. See Ethernet Control on page 9 for information on IP address requirements.

    DOWNLOADING A

    FILE FROM THE

    . . . . . . . . . LINX SWITCHERUse this procedure to download files created with the EXportEDID or EXPORTSETTINGS command.

    1. From the PC Start menu at the bottom of the Windows desktop select Run...

    2. In the Run dialog box type cmd as shown in Figure 5-1.

    Figure 5-1 Run Window

    3. Press ENTER or click OK to open the command window.Figure 5-2 illustrates the following steps.

    4. Change to the desired PC directory. In the figure below, the directory linx is selected.

    5. At the prompt, type ftp followed by the IP address. In the example below the IP address is 192.168.1.220 and press ENTER.

    6. When prompted for a user name enter rgb in lowercase and press ENTER.

    7. Enter the password spectrum in lowercase and press ENTER.

  • TR A N S F E R R I N G F I L E S A N D U PD A T I N G F I R M W A R ETransferring Files

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 45

    . . .

    . .

    Figure 5-2 FTP Download Session

    8. Type ls and press ENTER to view the files available for download. export.txt, a file created with the EXPORTSETTINGS command is listed in Figure 5-2.

    9. Type get and press ENTER to copy the file to the PC. In the example shown above, the command is get export.txt. Note that the filename is case sensitive.

    10. Type bye and press ENTER to disconnect from the Linx Switcher.

    11. Type dir and press ENTER to view file copied to the PC.12. Close the command window by typing exit and pressing

    ENTER.

  • TR A N S F E R R I N G F I L E S A N D U PD A T I N G F I R M W A R ETransferring Files

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 46

    . . .

    . .

    UPLOADING A FILE

    TO THE

    . . . . . . . . . LINX SWITCHERUse the following procedure to upload a file containing exported settings, EDID parameters, or a firmware upgrade file.

    1. From the PC Start menu at the bottom of the Windows desktop select Run...

    2. In the Run dialog box type cmd as shown in Figure 5-1.

    Figure 5-3 Run Window

    3. Press ENTER or click OK to open the command window.Figure 5-4 illustrates the following steps.

    4. Change to the PC directory containing the file to be uploaded. In the figure below, the directory linx is selected.

    5. Type dir and press ENTER to verify the desired file is present.6. At the prompt, type ftp followed by the IP address and press

    ENTER. In the example below the IP address is 192.168.1.220.7. When prompted for a user name enter rgb in lowercase and

    press ENTER.8. Enter the password spectrum in lowercase and press ENTER. 9. Type put and press ENTER. In this example

    firmware file presets.txt is being uploaded.10. Type ls and press ENTER to list the files in the Linx Switcher.

    The uploaded file will be displayed.

    11. Type bye and press ENTER to disconnect from the Linx Switcher.

    12. Type exit and press ENTER to close the command window.

  • TR A N S F E R R I N G F I L E S A N D U PD A T I N G F I R M W A R ETransferring Files

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 47

    . . .

    . .

    Figure 5-4 FTP Upload Session

  • TR A N S F E R R I N G F I L E S A N D U PD A T I N G F I R M W A R EUpdate System Firmware

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 48

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPDATE SYSTEM FIRMWAREIt is recommended that all system settings be exported and copied to a PC before updating firmware. See the EXPORTSETTINGS command and download instructions on page 44.

    1. Determine the current firmware version by one of the following:~ On the front panel, touch SYS to view the system

    parameters.

    ~ Issue the command ver through the serial port or a Telnet window.

    ~ View the System tab of the WCP.2. Download the latest revision of the firmware from the RGB

    Spectrum web site Support section: http://www.rgb.com/en/Support/ The upgrade is a file named FWLNX_x.y.z.tgz, where x.y.z represents the version number. The file name is case sensitive. Copy this file onto a local drive on the PC.The use of a broadband connection is highly recommended. Do not rename the file.

    3. Follow the instructions in section Uploading a File to the Linx Switcher on page 46 to copy the firmware to the Linx Switcher.

    4. Using HyperTerminal through the RS-232 port or Telnet through the 10/100 BASE-T port issue the UpdateFirmWare command.

    5. After the Linx Switcher reboots, start a new HyperTerminal or Telnet session as required.

    http://www.rgb.com/en/Support/DGy.asp

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 49

    6MAINTENANCE AND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TROUBLESHOOTING

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MAINTENANCEThe front panel filter must be checked on a regular basis to prevent overheating the Linx DVI 8x8 Matrix Switcher. Once a month would be an appropriate interval in a clean environment. If the Linx Switcher is used where dust and dirt are a problem, it is recommended that the filter be inspected weekly.

    If the Linx Switcher overheats, the alarm indicator on the front panel will light. Overheating may be caused by:

    1. Operating in an environment with a temperature exceeding 122° F (50° C).

    2. Failed fan or blocked air intake.3. Clogged air filter; wash or replace.

    ~ Wash the filter in mild dish detergent. ~ Rinse in clear water.~ Press it between paper towels to remove excess

    moisture.

    ~ All to air dry.To order additional filters from RGB, request part number 410-8905.

  • M A I N T E N A N C E A N D TR O U B L E S H O O T I N GTroubleshooting

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 50

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TROUBLESHOOTING

    Table 6-1 Troubleshooting Guide

    Problem Symptom Action

    Power No AC power.

    Check that the power cord is correctly connected to the Linx Switcher and to an AC power source and that the power switch is in the ON position.

    If an output from a graphics adapter is connected to a Linx Switcher output while power is off, the switcher will not power on. Check the output connections.

    Telnet

    Invalid password. Correct password is RGB; this must be upper case.

    User name and password entered but connection to host is lost.

    8000 must be entered following the IP address in the telnet command.Example:

    telnet 192.168.34.70 8000

    Cannot connect to host.Check that the PC has a static IP address compatible with the Linx Switcher and network.

    Output No output present.

    Output has been disabled. Use OUTputENable to display or change an output status.

    The display is not capable of the resolution sent to it. Set the output display mode to pass-through and the EDID mode of the input to dynamic.When a single input is routed to multiple outputs, EDID priority may not yield compatible resolution. Set EDID priority to minimum resolution.When EDID priority is set to lowest output number, the output with the most universal EDID should be connected to the lowest output port.If the EDID works for some displays, try setting the display mode to emulate for all the outputs in the group.

    The souce has stopped sending a signal. Check that the input status box at the bottom of the WCP routing window is green or use the INputSTATus command.

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 51

    A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SPECIFICATIONS

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PHYSICAL SPECIFICATIONS

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMMUNICATIONS SPECIFICATIONS

    Table A-1 Physical Specifications

    Parameter Specification

    Dimensions

    (excluding rack ears)

    3.49” H, 17.125” W, 12.5” D

    2 RU

    Weight 16.4 lb (7.5 kg)

    Air Filter Washable foam

    Input Voltage 85 to 264 VAC

    Power Consumption 65 W, maximum

    Table A-1 Communications Specifications

    Port Specification

    Ethernet 10/100 BASE-T

    RS-232 serial Baud: 9600 to 15,200

    Bits: 8

    Stop bits: 1

    Parity: None

    Flow control: XOn/XOff

  • SP E C I F I C A T I O N SDVI Inputs and Outputs

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 52

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DVI INPUTS AND OUTPUTS

    There are eight DVI input and eight DVI output ports on the rear panel. Each provides a single link with a maximum bandwidth of 1.65 Gbps.

    The table below lists the high resolution digital input and output specifications.

    Only the digital pins of the DVI-I connector are used.

    Figure A-1 DVI Input and Output Connectors

    Table A-2 Digital Input and Output Specifications

    Parameter Specification

    Type DVI - single link

    Number 1

    Maximum bandwidth 1.65 Gbps

    Standard resolution 640 x 480 to 1600 x 1200

    HD resolution 920 x 1080p, 1920 x 1200, and 2048 x 1080p

    Connector type DVI-I

    Table A-3 DVI Connector Pin Assignments

    Pin Signal

    1 TMDS data 2-

    2 TMDS data 2+

    3 TMDS data 2/4 shield

    4 —

    5 —

    6 DDC clock

  • SP E C I F I C A T I O N SDVI Inputs and Outputs

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 53

    . . .

    . .

    7 DDC data

    8 —

    9 TMDS data 1-

    10 TMDS data 1+

    11 TMDS data 1/3 shield

    12 —

    13 —

    14 +5V power used at 300 mA

    15 Ground

    16 Hot plug detect

    17 TMDS data 0-

    18 TMDS data 0+

    19 TMDS data 0/5 shield

    20 —

    21 —

    22 TMDS clock shield

    23 TMDS clock+

    24 TMDS clock-

    Table A-3 DVI Connector Pin Assignments (Continued)

    Pin Signal

  • SP E C I F I C A T I O N SEthernet Port

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 54

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ETHERNET PORT

    10/100 BASE-T Ethernet connection is supported through the RJ45 port on the rear panel.

    • Supports control of the full set of Linx DVI 8x8 Matrix Switcher commands over a network connection using a Telnet server/client architecture.

    • Internal Linx DVI 8x8 Matrix Switcher web server provides the Web Control Panel (WCP) a graphical user interface via a standard web browser.

    Figure A-2 Ethernet Connector

    The 10/100 BASE-T port can connect to a network using a standard Ethernet cable. When a network is not used, connection requires an Ethernet hub or a crossover cable.

    Table A-4 Ethernet Connector Pin Assignments

    Pin Signal Wire Color

    1 TX Data + White/Orange

    2 TX Data - Orange

    3 RX Data + White/Green

    4 — Blue

    5 — White/Blue

    6 RX Data - Green

    7 — White/Brown

    8 — Brown

    1 8

  • SP E C I F I C A T I O N SRS-232 Port

    350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 55

    . . .

    . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS-232 PORT

    Linx DVI 8x8 commands can be sent through the RS-232 port to control the system.

    • The RS-232 port transfers commands using the asynchronous serial protocol at 9600 to 115, 000 baud.

    • The port is configured as DCE and can handle full duplex transfer.

    • Support for hardware and software handshaking is provided.

    Figure A-3 RS-232 Connector

    Table A-5 RS-232 Connector Pin Assignments

    Pin Circuit Description

    1 CD Carrier Detect

    2 TD Transmit Data

    3 RD Received Data

    4 — (not connected)

    5 AB Signal Ground (common return)

    6 DSR Data Set Ready

    7 CTS Clear to Send

    8 RTS Request to Send

    9 — (not connected)

  • 350-8794 V1.1 Linx DVI 8x8 Matix Switcher User’s Guide 56

    B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CONTACT INFORMATION

    RGB Spectrum can be reached by phone, fax, mail and e-mail as listed below:

    • RGB Spectrum950 Marina Village ParkwayAlameda, CA 94501

    • Phone: 510-814-7000• Fax: 510-814-7026• E-Mail (technical support): [email protected]• E-Mail (sales and product information): [email protected]• Website: www.rgb.com

    Table of ContentsList of FiguresList of Tables

    Introduction and InstallationPhysical DescriptionEDID ControlEDID RegistersHot Plug EventEDID priorityEDID listEDID Management

    Input EqualizationInstallationRack MountingVideo Inputs and OutputsControl ConnectionsRS-232 Control10/100 BASE-T ControlPower

    Communications SetupSerial CommunicationLaunching a HyperTerminal Window

    Ethernet ControlSetting the PC IP AddressBeginning a Telnet Session

    Changing the Linx DVI 8x8 Matrix Switcher IP Address

    OperationCommand Line OperationSystem SettingsCommunication SettingsSwitch SettingsPresetsEDIDExporting and Importing System SettingsPRESETSSystemEDIDAll

    Front Panel OperationXY Control PanelPresets PageStatus PageSystem Page

    Web Control Panel OperationRouting WindowConfiguration TabPresets TabEDID TabSystem TabNetwork SettingsInfoSerial Port

    CommandsCommand FormatCommand HelpCommand ArgumentsPredefined Parameter ValuesQuery the Current SettingIPADDR

    Commands SummaryCommunications CommandsSwitch CommandsPreset CommandsEDID CommandsMiscellaneous Commands

    Transferring Files and Updating FirmwareTransferring FilesDownloading a File from the Linx SwitcherUploading a File to the Linx Switcher

    Update System Firmware

    Maintenance and TroubleshootingMaintenanceTroubleshooting

    SpecificationsPhysical Spec