  • 8/11/2019 Line Sizing Slides

    1/22

    31% of large property damage

    losses are caused by failures inpiping systems.

    Some lines reach 60 inches indiameter - larger than manyequipment items.

  • 8/11/2019 Line Sizing Slides

    2/22

    MB & EB balances must include: Normal mass balance - base case.

    Start-up, shut down or upsetdevn.

    Recycle of off-spec products.

    Equipment bypass conditions.

    MB for flare, fire water, sewers,

    steam, condensate and CTWheaders.

  • 8/11/2019 Line Sizing Slides

    3/22

    Limiting line velocities notknown or ignored.

    Velocity greater than 15 fps in CSpipe can cause erosion.

    Low velocities (< 3 fps) can cause

    entrained solids to settle and pluglines.

  • 8/11/2019 Line Sizing Slides

    4/22

    Poor record keeping during Phase 3prevents detailed follow-up inPhase 4 design stage.

    PSV lines need to be checked inPhase 4.

    Pump lines need to be checked inPhase 4.

  • 8/11/2019 Line Sizing Slides

    5/22

    Corrosiveness of fluid unknown.

    At high temps, degradation mayproduce acidic components. (La.

    HumbleTherm example). Pipe not suitable for unexpected

    cold temperatures.

    Pipe not suitable for unexpected

    extreme high temperatures.

  • 8/11/2019 Line Sizing Slides

    6/22

    Compressible fluid flow not well

    understood by process engineers. Flows at Mach 1 (Sonic Flow) can

    be destructive.

  • 8/11/2019 Line Sizing Slides

    7/22

  • 8/11/2019 Line Sizing Slides

    8/22

  • 8/11/2019 Line Sizing Slides

    9/22

    Two Phase Flow not well

    understood by process engineers. Horizontal Flow - Baker Chart.

    Vertical Down Flow.

    Vertical Up Flow.

  • 8/11/2019 Line Sizing Slides

    10/22

  • 8/11/2019 Line Sizing Slides

    11/22

    Siphons may form readily May have damaging pulsating

    flow

  • 8/11/2019 Line Sizing Slides

    12/22

  • 8/11/2019 Line Sizing Slides

    13/22

    May have damaging pulsating

    flow 4 ft. dia. Cooling tower inlet pipe

    experiences severe vibration, fails& floods plant

  • 8/11/2019 Line Sizing Slides

    14/22

  • 8/11/2019 Line Sizing Slides

    15/22

    Two phase flow pressure drops

    may be higher than expected andthereby limit performance.

  • 8/11/2019 Line Sizing Slides

    16/22

    Flashing liquids often not

    considered during processdesign.

    Two phase flow can be acomplex, transient problem.

  • 8/11/2019 Line Sizing Slides

    17/22

    PSVs are usually sized for single

    phase flow. Two phase flow can occur when

    vessels operated above maximumfill limit.

    Two phase flow can occur whenflows are higher than expected.

  • 8/11/2019 Line Sizing Slides

    18/22

    Draining water from KO Pot toopen sewer during rain storm.

    Flammable vapor entrained dueto formation of liquid vortex.

    Lightning strikes near plant ISBL. Sewer explodes, wrecks cold box

    in Ammonia Plant.

    One operator killed.

  • 8/11/2019 Line Sizing Slides

    19/22

    Flow in reactor manifolds.

    Flows in branched piping. Flows in shell-side of exchangers.

  • 8/11/2019 Line Sizing Slides

    20/22

    System or vessel design pressuresexceeded when EBV suddenlystops flow.

    EO transfer example.

    See computer spreadsheet design

    program.

  • 8/11/2019 Line Sizing Slides

    21/22

  • 8/11/2019 Line Sizing Slides

    22/22

    Which flow regime should youavoid for horizontal, two phaseflow?

    If a liquid vortex forms on drainingfrom a vessel, what safety problemscan this create?

    When can a PSV which is sized for

    single phase flow experience twophase flow?