line document number description qty. no. 1 - ssd/ovp2 … · document #: 3423.13 3.2 1.56 39.7...
TRANSCRIPT
3.0076.2
2.0050.8
1.0025.4
.399.9
.399.9
.7519.1
.133.2
1.5639.7
2
3
45
6
APPLY A THIN LAYER OF TEFGEL (ITEM 7) ON METAL-TO-METAL INTERFACES USING BRUSH (ITEM 8) BEFORE ASSEMBLY1. ITEM 2 TO SSD/OVP2 TERMINAL PADS2. ITEM 2 TO TERMINAL LEADS3. SSD/OVP2 TERMINAL PADS TO TERMINAL LEADS
1
3
CENTERLEAD ON
INSIDE
A
EXTRA LEADS PLATE PUSHED UP TIGHT AGAINST
SSD/OVP2 HOUSING
DETAIL A SCALE 1 : 3
EXTRA LEADS PLATE PUSHED UP TIGHT AGAINST
SSD/OVP2 HOUSING
EXTRA LEADS PLATE BETWEEN SSD/OVP2 TERMINALS IN THIS ORIENTATION
DOCUMENT #: 3423
NOTE: ONE KIT (CATALOG #: MTR-1) ENABLES UP TO (5) LEADS TO BE CONNECTED TO ONE TERMINAL.
LINE NO.
DOCUMENT NUMBER DESCRIPTION QTY.
1 - SSD/OVP2 12 3423 BUS DECOUPLER EXTRA LEADS PLATED 13 1194 WASHER FLAT 5/16" 64 1195 WASHER SPLIT LOCK 5/16" 35 1196 NUT HEX 5/16-18 36 2441 SCREW HEX 5/16-18X1" 37 3041 TEFGEL SAMPLE 1
SHEET: SCALE
DWG SIZEDATE DRAWNDOCUMENT #
DESCRIPTION
MTR-1 TERMINAL EXTENSION KIT FOR SSD/OVP-2
1000911
B1:1 DRAWN:ANGULAR: 1
1-PLACE / FRAC: .03
UNITS: INCHES
2-PLACE: .0153-PLACE: .005
UNLESS NOTED
ANSI Y14.5M 1994 APPLIES
63
OF 5JPW2015-09-17
REV
DWG APPROVAL:
DATE APPROVAL
JVW2019-03-14C
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187STOUGHTON, WI 53589608-877-9900DAIRYLAND.COM
OPTIONAL INSTALLATION
SWX-100 SWITCH
DECOUPLER
MTR-1 TO GROUND
TO CP PROTECTED STRUCTURE
(-) NEGATIVE
(+) POSITIVE
OPTIONAL INSTALLATION
DECOUPLER
MTR-1
TO GROUND
(-) NEGATIVE (+) POSITIVE
TO CP PROTECTED STRUCTURE
SHEET: SCALE
DWG SIZEDATE DRAWNDOCUMENT #
DESCRIPTION
MTR-1 TERMINAL EXTENSION KIT FOR SSD/OVP-2
1000912
B1:4 DRAWN:ANGULAR: 1
1-PLACE / FRAC: .03
UNITS: INCHES
2-PLACE: .0153-PLACE: .005
UNLESS NOTED
ANSI Y14.5M 1994 APPLIES
63
OF 5JPW2015-09-17
REV
DWG APPROVAL:
DATE APPROVAL
JVW2019-03-14D
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187STOUGHTON, WI 53589608-877-9900DAIRYLAND.COM
APPLY A THIN LAYER OF TEFGEL (ITEM 7) ON METAL-TO-METAL INTERFACES USING BRUSH (ITEM 8) BEFORE ASSEMBLY1. ITEM 2 TO SW-50 TERMINAL PADS2. ITEM 2 TO TERMINAL LEADS3. SW-50 TERMINAL PADS TO TERMINAL LEADS
5 43
2
3
6
1
EXTRA LEADS PLATE PUSHED UP TIGHT AGAINSTSW-50 HOUSING 1.00
25.4
3.0076.2
.399.9
2.0050.8
.399.9
.7519.1
DOCUMENT #: 3423
.133.2
1.5639.7
NOTE: ONE KIT (CATALOG #: MTR-2) ENABLES UP TO (5) LEADS TO BE CONNECTED TO ONE TERMINAL.
LINE NO.
DOCUMENT NUMBER DESCRIPTION QTY.
1 3630 SW-50-ENCL 12 3423 BUS DECOUPLER EXTRA LEADS PLATED 13 1010 WASHER FLAT 3/8 64 1055 WASHER SPLIT LOCK 3/8" 35 1054 NUT HEX 3/8-16 36 1557 SCREW HEX 3/8-16X1" 37 3041 TEFGEL SAMPLE 18 2441 SCREW HEX 5/16-18X1" 39 1194 WASHER FLAT 5/16" 610 1195 WASHER SPLIT LOCK 5/16" 311 1196 NUT HEX 5/16-18 3
SHEET: SCALE
DWG SIZEDATE DRAWNDOCUMENT #
DESCRIPTION
MTR-2 TERMINAL EXTENSION KIT FOR SW-50
1000913
B1:1 DRAWN:ANGULAR: 1
1-PLACE / FRAC: .03
UNITS: INCHES
2-PLACE: .0153-PLACE: .005
UNLESS NOTED
ANSI Y14.5M 1994 APPLIES
63
OF 5JPW2015-09-17
REV
DWG APPROVAL:
DATE APPROVAL
JVW2019-03-14C
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187STOUGHTON, WI 53589608-877-9900DAIRYLAND.COM
APPLY A THIN LAYER OF TEFGEL (ITEM 6) ON METAL-TO-METAL INTERFACES USING BRUSH (ITEM 7) BEFORE ASSEMBLY1. ITEM 1 TO PCR TERMINAL PADS2. ITEM 1 TO BRACKETS
TERMINAL EXTENSION KIT INSTRUCTIONS
APPLY TEFGEL (ITEM #6 - FURNISHED) TO THE FACE 1.OF THE PCR TERMINAL TO WHICH THE COPPER BUS FOR EXTRA LEADS IS TO BE ATTACHED.ATTACH THE COPPER BUS TO THIS TERMINAL PAD 2.USING THE HARDWARE THAT WAS FURNISHED IN THE TERMINAL PAD WITH THE PCR AND TIGHTEN THE NUTS SECURELY.APPLY TEFGEL ON THE BOTTOM SIDES OF EACH 3.TERMINAL PAD ON THE LEADS TO BE ATTACHED AND SECURE TO THE COPPER BUS WITH THE HARDWARE PROVIDED WITH THE KIT, HAND TIGHTENING EACH NUT.ORIENT THE ADDED LEADS AS DESIRED AND 4.SECURELY TIGHTEN THE NUTS.
THIS TERMINAL EXTENSION KIT CAN BE ADDED TO EITHER PCR TERMINAL
2
1
34 5
.7519.1
2.5063.5
4.25108
.6315.9
2.3860.3
5.00127
3.0076.2
6X .56314.29
DOCUMENT #: 3045
.133.2
BILL-OF-MATERIAL (BOM) TABLELINE NO.
DOCUMENT NUMBER DESCRIPTION QTY.
1 3045 BRACKET TERMINAL EXTENSION PCR PLATED 12 1019 SCREW HEX 1/2-13X1.250" 43 1020 WASHER FLAT 1/2" 1.38 ODX0.09" THICK 44 1576 WASHER SPLIT LOCK 1/2" 45 1021 NUT HEX 1/2-13 46 3041 TEF-GEL 1
SHEET: SCALE
DWG SIZEDATE DRAWNDOCUMENT #
DESCRIPTION
MTR-3 Terminal Extension Kit for PCR
1000914
B1:1 DRAWN:ANGULAR: 1
1-PLACE / FRAC: .03
UNITS: INCHES
2-PLACE: .0153-PLACE: .005
UNLESS NOTED
ANSI Y14.5M 1994 APPLIES
63
OF 5JPW2015-09-17
REV
DWG APPROVAL:
DATE APPROVAL
JVW2019-03-14C
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187STOUGHTON, WI 53589608-877-9900DAIRYLAND.COM
3
1
2
4
5
6
APPLY THIN LAYER OF TEFGEL ON METAL-TO-METAL
INTERFACES BEFORE ASSEMBLY
5X .34 8.7 THRU
0 0
.5
012
.7
1.
5038
.1
2.
5063
.5
3.
5088
.9
2.
0050
.8
4.
0010
1.6
00
.7519.1
2.0752.7
2.56
65.1
DOCUMENT #: 3654
.133.2
NOTE: INSTALL BOLTED TERMINAL FROM SWX-100-ENCL FOR FOURTH LEAD
CONNECTION
NOTE: ONE KIT (CATALOG #: MTR-4) ENABLES UP TO (4) LEADS TO BE CONNECTED TO ONE TERMINAL.
1. REMOVE BOLTED TERMINAL FROM SWITCH TERMINAL OF SWX-100-ENCL.2. REMOVE 5/16’’ HARDWARE FROM MTR-4 KIT WHERE THERE IS NO TERMINAL.3. APPLY THIN LAYER OF TEFGEL ON METAL-TO-METAL INTERFACES.4. INSTALL BOLTED CONNECTOR ON MTR-4 KIT.5. INSTALL MTR-4 KIT ON SWITCH TERMINAL OF SWX-100-ENCL.
* FOURTH TERMINAL COMES FROM SWX-100-ENCL.
LINE NO.
DOCUMENT NUMBER DESCRIPTION QTY.
1 3654 Bus Isolation Switch Extra Leads Plated 1
2 3455 Terminal Bolted Hex Socket HD #8-1/0 Plated w/ Modified Set Screw 3*
3 2441 Screw Hex 5/16-18x1" 44 1194 Washer Flat 5/16" 45 1195 Washer Split Lock 5/16" 46 1196 Nut Hex 5/16-18 47 3041 Tef-Gel 1
SHEET: SCALE
DWG SIZEDATE DRAWNDOCUMENT #
DESCRIPTION
MTR-4 TERMINAL EXTENSION KIT FOR SWX-100-ENCL
1000915
B1:2 DRAWN:ANGULAR: 1
1-PLACE / FRAC: .03
UNITS: INCHES
2-PLACE: .0153-PLACE: .005
UNLESS NOTED
ANSI Y14.5M 1994 APPLIES
63
OF 5JPW2015-09-17
REV
DWG APPROVAL:
DATE APPROVAL
JVW2019-03-14C
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187STOUGHTON, WI 53589608-877-9900DAIRYLAND.COM