Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 1 03.22.19
Limelight by Lutron Wireless Lighting Control System
Limelight by Lutron is a wireless lighting control system for exterior parking garage and parking lot applications. Limelight by Lutron uses a high-density mesh wireless technology to communicate between the Limelight gateway and the Limelight nodes (Radio Sensor Modules) at every luminaire.
Features• Limelight by Lutron does not require wireless
repeaters and typical jobs are completed with a single gateway. A cellular gateway option eliminates the need to get an Ethernet connection.
• Single sign-on for Lutron interior and exterior controls when connected to Enterprise Vue.
• Fixtures can be grouped together to turn an entire floor on at once to make sure there is plenty of light available in safety-critical areas. In areas with cameras, the unoccupied level can be set to a reduced light level instead of OFF.
• Limelight by Lutron uses sensors to intelligently reduce power consumption and will email monthly reports of energy usage data.
Model Number Installation to Fixture Description
LL-ETHGATE N/A Limelight by Lutron Gateway Panel Assembly – Ethernet based
LL-CELLGATE N/A Limelight by Lutron Gateway Panel Assembly – Cellular based
LL-PIR-L OEM Limelight by Lutron PIR Sensor Assembly – for 8 to 15 ft (2.4 to 4.6 m) mounting height
LL-PIR-M OEM Limelight by Lutron PIR Sensor Assembly – for >15 to 30 ft (>4.6 to 9.1 m) mounting height
LL-PIR-H OEM Limelight by Lutron PIR Sensor Assembly – for >30 to 40 ft (>9.1 to 12.2 m) mounting height
LL-INTMOUNT OEM Limelight by Lutron Radio Sensor Module (RSM) PCB Assembly
LL-EN-INTMOUNT OEM Limelight by Lutron Radio Sensor Module PCB Assembly (Enclosed)
LL-EXTMOUNT-L Field – retrofit Limelight by Lutron UL Listed Field-installable Radio Sensor Module (RSM) - for 8 to 15 ft (2.4 to 4.6 m) mounting height
LL-EXTMOUNT-M Field – retrofit Limelight by Lutron UL Listed Field-installable Radio Sensor Module (RSM) - for >15 to 30 ft (>4.6 to 9.1 m) mounting height
LL-EXTMOUNT-H Field – retrofit Limelight by Lutron UL Listed Field-installable Radio Sensor Module (RSM) - for >30 to 40 ft (>9.1 to 12.2 m) mounting height
LL-ETHGATELL-CELLGATE
LL-PIR*LL-EXTMOUNT
LL-INTMOUNT* LL-EN-INTMOUNT*
OR
+
* Controls inside the box are integrated into the fixture
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 2 03.22.19
System Components
Limelight by Lutron Enabled Luminaire
The Limelight by Lutron wireless radio sensor module (RSM) is currently integrated into a variety of luminaires. Fixtures with an integrated RSM can turn on/off and provide full dimming drive capability using 0–10 V. A Limelight by Lutron enabled fixture requires no special communication wiring or special installation instructions. Installation is equivalent to a simple (non-Limelight) luminaire. When AC (120 – 277 V~) power is applied, the fixture powers up with a factory default setting of 100% light output until the Limelight by Lutron commissioning process begins.
Contact Lutron for assistance in identifying current OEM fixture offerings for your application at 1.844.LUTRON1.
Limelight by Lutron Gateway
• The gateway serves as the communication hub between the RSMs and the Web User Interface.
• Up to 800 RSMs per gateway.• Installs in a utility closet or ceiling mounted nearest the
center of the RF mesh.• Connects to the internet via an Ethernet cable or
cellular connection.• Secured in an IP65 tamper-proof housing.
Through an internet connection, the gateway communicates to the cloud server. Fixtures can be grouped into multiple zones, operating hours established, with information on the system’s status and performance immediately available. Every fixture in the system is individually addressable.
Limelight by Lutron Radio Sensor Module (RSM)
Every RSM has a fully integrated wireless radio. The radios leverage the Zigbee communication (IEEE 802.15.4) protocol, with high-density mesh technology built on top. These radios provide:
• A robust, redundant communications scheme.• Communication between multiple floors above or
below in parking facilities.Each radio communicates to the “neighbor” radios around it, creating a high-density mesh (on average, each radio will be in communication with 8 to 12 other radios). This redundant communications system enables Limelight by Lutron to be self-healing. If a radio ever stops functioning or is vandalized, the other radios will immediately search out and establish communication with other neighbors in the mesh. This high-density mesh system enables the Limelight by Lutron control system to operate smoothly even in the most difficult conditions.– Occupancy Sensor: Projecting from the underside
of each of the radios is a passive infrared occupancy sensor.e Creates maximum coverage of the garage floor.e Captures all sensing activity (time of day and
fixture number) in a centralized database for activity reporting and analysis.
– Daylight Sensor: Daylight harvesting capabilities are supported.e Provides daylight measure every 15 minutes
(programmable).e Measures foot candles per fixture to analyze for
maximum harvesting capability.
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 3 03.22.19
Specifications
Limelight by Lutron Gateway Panel Assembly
Models
• LL-ETHGATE – Ethernet Based• LL-CELLGATE – Cellular Based – 3 years of cellular data is included in the price of
the LL-CELLGATE – For additional cellular contract lengths, please
contact your local Lutron representative
Standards
• For commercial use, Class A only• cULus Listed• FCC15.247 / IC RSS-247
Power
• Maximum current draw: 120 V~ 60 Hz 0.3 A Maximum power consumption: 15 W (51.2 BTU/hr)
• Power Cord (standard 3-prong plug)• AC Power Indicator LED (green)
Operating Temperature
• -4 °F – 122 °F (-20 °C – 50 °C)
Physical
• Dimensions: 11.28 in (286.5 mm) x 7.48 in (190 mm) x 5.5 in (139.7 mm)
• Lock Protection capable (padlock not provided)• Solid body: ABS/PC plastic, UL94-5VB flammability
rating• Clear cover: Polycarbonate plastic with UL94V-0
flammability rating, UV stabilized• AC power cord: Black, 5 ft (1.5 m), straight plug to
standard 120 V~ outlet (receptacle required)
Mounting
• Four (4) mounting brackets pre-attached• Wall anchors (supplied by others)• Mount vertical with space for field service access to
side connectors • Not intended for direct exposure to the elements
Location Recommendations
• Maintenance closet or environment-friendly location• Mount away from dense metal obstructions (maintain
at least 2 ft [0.6 m])• Nearest to the middle of the RF Mesh/Parking facility
preferred
Connections
• Ethernet (LL-ETHGATE only) – CAT5 (or equivalent) cable, straight-through wiring
(T568B) cable supplied by others – Field wired with RJ45 Ethernet plug (by others) – Waterproof mating connector · Requires field crimped connector (RJ45 crimp tool
supplied by others) – IT Network Configuration:
www.lutron.com/limelightITguide• Cellular (LL-CELLGATE only) – QuickCarrier USB - with SIM Socket – GSM 3G HSPA+ technology• Mount to wall and power on – For LL-ETHGATE, also connect Ethernet – For Emergency application – The gateway should be
installed on normal power only (NOT Emergency) for proper system functionality. Please see Application Note #715 (P/N 048715) at www.lutron.com
• At startup, display will confirm connection to cloud services
Warranty
• http://Lutron.com/limelightwarrantycontinued on next page...
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 4 03.22.19
Specifications (continued)
Limelight by Lutron Radio Sensor Module PCB Assembly
Model
• LL-INTMOUNT• LL-EN-INTMOUNT (LL-EN-INTMOUNT is
LL-INTMOUNT plus a plastic enclosure )
Standards
• RoHS Compliant• FCC 15.247/IC RSS-247• cULus Recognized for internal mounting at a
fixture OEM
Power Requirements
• Input power: 120 – 277 V~ (± 10%) 50/60 Hz (phase-to-phase possible)
• Device consumption: 1.0 W (load enabled) 0.5 W (load disabled)
• Maximum Load: 5 A at 120 V~ 3.65 A at 277 V~
Environment
• LL-INTMOUNT: -40 °F – 176 °F (-40 °C – 80 °C)• LL-EN-INTMOUNT: -40 °F – 158 °F (-40 °C – 70 °C)
Warranty
• http://Lutron.com/limelightwarranty
Features
• Control up to a 1000 W luminaire• Power Measurement Accuracy +/- 5%• Isolated 0 – 10 V- dimming output, capable of sinking
up to 1.0 mA of 0 – 10 V- signal• On board temperature sensor, accurate to +/-2 ˚C• 4 pin terminals for remote connection to LL-PIR• Works with ballasts and drivers whose inrush current
does not exceed NEMA410 standards for electronic ballast/driver
• Integrated ZigBee radio transceiver – IC and FCC approved Title 47 Part 15 Subpart
B and Subpart C section 15.247 for Digital Transmission Systems Operating within the band 2400-2483.5 MHz
– RF transmissions security: 128 AES plus application layer
• Can be configured to control non-dim loads
continued on next page...
Note: Outdoor fixtures should be minimum IP-65 rated
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 5 03.22.19
Specifications (continued)
Limelight by Lutron PIR Sensor Assembly
Model
• LL-PIR
Standards
• cULus Recognized (for internal mounting at a fixture OEM)
• IP65 capable (when lens assembly is installed correctly at fixture manufacturer)
Power Requirements
• 2.7 – 3.3 V- (provided by LL-INTMOUNT/ LL-EN-INTMOUNT)
• 50 mW maximum (20 mW typical)
Operating Temperature
• -40 °F – 158 °F (-40 °C – 70 °C)
Occupancy Sensor Assembly
• UL rated silicone washer for water and dust seal (IP65 – wet locations)
• Threaded nut for secure fit• 4-wire harness with low profile connector
(10 in [254 mm])
Warranty
• http://Lutron.com/limelightwarranty
Features
• Reduced false triggers for more energy savings• Small footprint allows it to fit almost anywhere• Wide or narrow field of view with wireless
settings adjustment• Wirelessly choose between multiple profiles to
optimize settings for various environments (flat lot, parking deck, high wind, various heights 8 – 40 ft [2.4 – 12.2 m])
• Integrated Daylight Sensor measures light to 1500 fc• On board temperature sensor, accurate to +/-2 °C• LED with wireless brightness adjustment to provide
user feedback• Wireless field re-programmable• Recommended mounting heights (8 – 40 ft
[2.4 – 12.2 m]) – Low: 8 – 15 ft (2.4 – 4.6 m) (ex. parking garage) – Medium: >15 – 30 ft (>4.6 – 9.1 m) (ex. pole lights) – High: >30 – 40 ft (>9.1 – 12.2 m) (ex. specialty poles)• Occupancy detection can be disabled (ships disabled,
requires system activation to enable) – Daylight Sensor can be disabled independently of
occupancy detection
continued on next page...
Note: Outdoor fixtures should be minimum IP-65 rated
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 6 03.22.19
Specifications (continued)
Limelight by Lutron UL Listed Field-installable Radio Sensor Module (RSM)
Model• LL-EXTMOUNT
Standards• cULus Listed – UL244A – UL773A – CSA 22.2 No. 205• IP65• FCC 15.247/IC RSS-247
Power Requirements
• Input power: 120 – 277 V~ (± 10%) 50/60 Hz (phase-to-phase possible)
• Device consumption: 1.0 W (load enabled) 0.5 W (load disabled)
• Maximum Load: 5 A at 120 V~ 3.65 A at 277 V~)
Operating Temperature• -40 °F – 158 °F (-40 °C – 70 °C)
External Housing• Aluminum Alloy• 0.5 in (12.7 mm) NPT thread male• Silver color only
Installation• The Limelight by Lutron UL Listed RSM must be
physically connected to a conductive surface that is earth grounded (i.e. conduit, junction box, luminaire, etc.)
• The Limelight by Lutron UL Listed RSM should always be mounted with the occupancy sensor lens pointing toward the ground surface
• The internal RF antenna polarization is optimized to work best when the occupancy sensor lens pointing toward the ground surface
• See wiring diagram for details. If being used as a non-dim load controller, cap the violet wire and cap the gray wire
Water Ingress
• The UL Listed RSM has been tested to the IP65 (wet locations) dust and water ingress protection standards
Mounting
• Regardless of whether factory or field installed, it is the responsibility of the installer to attach the Limelight by Lutron to the fixture in a manner that maintains the IP65 integrity
• Lutron will only warranty water ingress issues if proper attachment methods are observed
Wet Location Mounting
• An excellent method of attachment to a fixture is a Myers Hub (not included)
• There are a variety of styles depending on the luminaire type, environment and desired occupancy coverage
• Ensure that the Myers Hub includes an O-ring gasket that has excellent environmental ratings
• When using a Myers Hub, the best solution is to use a thread sealant. If thread sealant is not available, apply high torque in all areas
• Observe all national and local codes
Warranty
• http://Lutron.com/limelightwarranty
continued on next page...
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 7 03.22.19
Specifications (continued)
Limelight by Lutron UL Listed Field-installable Radio Sensor Module (RSM) (continued)
Features
• Control up to a 1000 W luminaire• Power Measurement Accuracy +/- 5%• Isolated 0 – 10 V- dimming output, capable of sinking
up to 1.0 mA of 0 – 10 V- signal• On board temperature sensor, accurate to +/-2 ˚C• Works with ballasts and drivers whose inrush current
does not exceed NEMA410 standards for electronic ballast/driver
• Integrated ZigBee radio transceiver – IC and FCC approved Title 47 Part 15 Subpart B and
Subpart C section 15.247 for Digital Transmission Systems Operating within the band 2400-2483.5 MHz
– RF transmissions security: 128 AES plus application layer
• Can be configured to control non-dim loads
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 8 03.22.19
Dimensions
LL-ETHGATE
Cloud ConnectionStatus Rev 2.3
DISPLAY
Dimensions shown as in (mm)
Mounting Brackets (4)
11.28 (286.5)
PWR LED
ETH0
DISPLAY
Cloud Connection Status Rev 2.3
7.48 (190)
5.5 (139.7)
continued on next page...
LL-CELLGATE
Cloud ConnectionStatus Rev 2.3
DISPLAY
Mounting Brackets (4)
11.28 (286.5)
7 (177.8)
PWR LED
DISPLAY
Cloud Connection Status Rev 2.3
7.48 (190)
5.5 (139.7)
LL-INTMOUNT
Top View Bottom ViewTallest component approx. 0.8 (20.3)
Tallest component
approx. 0.16 (4)
2.69 (68.3)1.12 (28.5)
1.12 (28.5)
1.12 (28.5)
1.12 (28.5)
1.24 (31.5)
0.57 (14.5)
0.19 (4.8)
0.57 (14.5)
0.57 (14.5)
0.24 (6.1)
0.24 (6.1)
0.57 (14.5)0.829 (21.1)
Diameter: 2.751 (69.9)
Hole Diameter 2.751 (69.9)
Diameter clearance areas both sides of PCB 0.23 (5.84)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 9 03.22.19
Dimensions (continued)Dimensions shown as in (mm)
LL-EN-INTMOUNT
Alternate Mounting Slots 4X Ø0.164 (4.16)
Mounting Hole 2X Ø0.177 (4.5)
Alternate Mounting Slots 2X2X 0.239 (6.07)
2.3 (58.4)
2.3 (58.4)
2X 2.25 (57.2)
2.98 (75.7)
3.5 (89)
3.98 (101)
1.23 (31.2)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 10 03.22.19
Dimensions (continued)
LL-PIR
LL-PIR-L Lens LL-PIR-M Lens LL-PIR-H Lens
Dimensions shown as in (mm)
Ø1.18 (Ø30)
Ø0.06 (Ø1.5)
2.375 (60.3)
2.375 (60.3)
3.17 (80.5)
1.07 (27.2)
0.875 (22.2)
0.875 (22.2)
Ø0.99 (Ø25.1)
1.08 (27.4)
1.5 (38.1)
≤0.14 (3.5)
LL-PIR Lens assembly
LL-PIR PCB assembly
Nut (supplied)Fixture
Gasket (supplied)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 11 03.22.19
Dimensions (continued)Dimensions shown as in (mm)
LL-EXTMOUNT
Diameter: 4.409 (112.0)
1/2 – 14 NPT threads
2.24 (56.9)
1.74 (44.2)
LL-PIR
Connector is polarized so that it cannot be inserted in the wrong orientation
To LL-PIR To LL-INTMOUNT or LL-EN-INTMOUNT
10 (254)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 12 03.22.19
Wiring Diagram (LL-INTMOUNT / LL-PIR)
Wiring Diagram (LL-EXTMOUNT)
0–10 V Driver/Ballast
0–10 V Driver/Ballast
LL-INTMOUNT or LL-EN-INTMOUNT
LL-EXTMOUNT
LL-PIR
Luminaire Power Connection
Luminaire Power Connection
Line/Hot (black)
Neutral or 2nd Phase (white)
Switched Hot (red)
DIM+ (purple)
DIM- (grey)
Wiring
Line/Hot (black)
Neutral or 2nd Phase (white)
Switched Hot (red)
DIM+ (purple)
DIM- (grey)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 13 03.22.19
:
CoverageAll units on the graph are shown in ft (m)
Limelight by Lutron PIRLimelight by Lutron PIR can be configured wirelessly to have different profiles depending on its environment.
• Profile can be adjusted (in the software) to reduce coverage.
Height: 8 ft (2.4 m), LL-PIR-L and LL-EXTMOUNT-L:22.5 (6.9)
15 (4.6)
7.5 (2.3)
0
7.5 (2.3)
15 (4.6)
22.5 (6.9) 22.5
(6.9)15
(4.6)7.5 (2.3)
0
0
0 2 (0.6)
2 (0.6)
5 (1.5)
5 (1.5)
8 (2.4)
8 (2.4)
18 (5.5)
18 (5.5)
8 (2.4)
7.5 (2.3)
15 (4.6)
22.5 (6.9)
36 (11)
50' 25' 0' 25' 50'
0'
50'
25'
25'
50'
100'0'10' 10'20' 20'30' 30'40' 40'
0'
27'
40'50'50'
15'
50' 25' 0' 25' 50'
0'
50'
25'
25'
50'
100'0'10' 10'20' 20'30' 30'40' 40'
0'
27'
40'50'50'
15'
:
:
Height: 20 ft (6.1 m), LL-PIR-M and LL-EXTMOUNT-M
Height: 40 ft (12.2 m), LL-PIR-H and LL-EXTMOUNT-H
20 (6.1)
10 (3)
0
0
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
18 (5.5)
18 (5.5)
15 (4.6)
15 (4.6)
12 (3.7)
12 (3.7)
9 (2.7)
9 (2.7)
6 (1.8)
6 (1.8)
3 (0.9)
3 (0.9)
0
10 (3)
20 (6.1)
20 (6.1)
10 (3)
0
0
0
0
15 (4.6)
27 (8.2)
40 (12.2) 40
(12.2)30
(9.1)20
(6.1)20
(6.1)30
(9.1)50
(15.2)10 (3)
10 (3)
50 (15.2)
40 (12.2)
0
10 (3)
20 (6.1)
25 (7.6)
50 (15.2)
100 (30.5)
50 (15.2)
50 (15.2)
50 (15.2)
25 (7.6)
25 (7.6)
25 (7.6)
40 (12.2)
20 (6.1)
20 (6.1)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 14 03.22.19
Technical System Overview
Log in using Enterprise Vue (sold separately) or direct access to the Limelight by Lutron cloud server (included with system).
LutronCloud Platform
Limelight by Lutron Enabled Luminaire
• Each luminaire is shipped with the Limelight by Lutron radio and sensor (optional) integrated into the luminaire
• A retrofit (external mount) is also available• Each Limelight by Lutron sensor has occupancy
and daylighting• Up to 800 luminaires controlled by a single
gateway as long as no other range restrictions are violated *
Gateway
• Wireless high-density mesh to luminaries• Cellular or Ethernet to the cloud• Wall-mounted inside a facility utility closet
Web-Based Interface Capabilities
• Ability to turn all fixtures on (via override) with a single button
• Ability to run diagnostics on a fixture• Ability to check fixture status and identify errors• Ability to flash any fixture• Ability to see the total number of connected luminaries
* For Parking Garages, nodes should be no further than 4 floors above or below the gateway. (i.e. If the gateway is on floor 1, then nodes can be on floors 1–5. If the gateway is on floor 5, then nodes can be on floors 1–9).
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 15 03.22.19
Technical System Overview (continued)
Web-based Interface
• Standalone system OR• Connect to Enterprise Vue for single login and
navigation. See the Enterprise Vue Software spec submittal (3691076) at www.lutron.com for more information
Wireless Range Best Practices
RF range recommendations
Parking Garage Flat Lot
3 nodes within this distance of the gateway
50 ft (15.2 m) 250 ft (76.2 m)
Max distance from the gateway to any one node
500 ft (152.4 m) 3000 ft (914.4 m)
Max distance from node to node
50 ft (15.2 m) 300 ft* (91.4 m)
Gateway proximity to dense metal obstructions (including electrical panels)
Minimum 2 ft (0.6 m) away Minimum 2 ft (0.6 m) away
Max number of luminaires controlled by a single gateway
Up to 800, as long as no other range restrictions are violated. Nodes should be no farther than 4 floors above or below the gateway (i.e. If the gateway is on floor 1, then nodes can be on floors 1–5. If the gateway is on floor 5, then nodes can be on floors 1–9).
Up to 800, as long as no other range restrictions are violated
* Nodes without a direct line of sight to another node should be placed no farther than 150 ft (45.7 m) apart.
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 16 03.22.19
Key Design Rules
1. Maximum of 800 nodes per gateway
2. Keep at least 3 nodes close to the gateway without dense metal between the gateway and the nodes. a. For a parking garage, keep within 50 ft (15.2 m) b. For a flat lot, keep within 250 ft (76.2 m)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 17 03.22.19
Key Design Rules (continued)
3. Maximum distance from gateway to the farthest node a. For a parking garage, do not go further 500 ft (152.4 m) b. For a flat lot, 3000 ft (914.4 m)
4. Maximum node-to-node distance a. For a parking garage, the distance should not exceed 50 ft (15.2 m) b. For a flat lot, 300 ft (91.4 m) (nodes without a direct line of sight to another node should be placed no
farther than 150 ft [45.7 m] apart)
SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Limelight by Lutron Wireless Lighting Control System Wireless Controls
3691100f 18 03.22.19
Typical One-Line Diagram Components
)Lutron, Limelight, and Lutron are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.Zigbee is a trademark of Zigbee Alliance.UL is a trademark of UL LLC.
To network (QS-EO or Corporate Ethernet network)
To Limelight by Lutron cloud
RF signal to/ from gateway
0–10 V- Dim
Switched Power, 1000 W max.
Switched Power, 1000 W max.
RF signal to/ from gateway
LL-ETHGATELimelight by Lutron gateway with Ethernet
connection, IP65 rated (not intended for direct exposure to the elements),
120 V~ 60 Hz with 5 ft (1.5 m) power cord
LL-CELLGATELimelight by Lutron gateway with cellular
connection, IP65 rated (not intended for direct exposure to the elements),
120 V~ 60 Hz with 5 ft (1.5 m) power cord
LL-EXTMOUNT - (L/M/H)120–277 V~ 50/60 Hz, Limelight by Lutron, ULR Listed, field-installable, radio sensor module (RSM) with integral
occupancy and daylight sensors
Switching0–10 V- Dimming
E
Input power (normal)
Legend:
18 AWG (1.0 mm2) wires
CAT5E or better cable for Lutron network terminated with RJ45 connectors (provided by others). 328 ft (100 m) maximum run