LIGHTNING AND SURGE PROTECTION FOR INDUSTRIAL, COMMERCIAL AND DOMESTIC
ELECTRICAL INSTALLATIONS
WWW.SURGEDEVICES.CO.UK
Surge Protection Devices and its Partner Companies have been solving problems in Lightning and Surge Protection for over 50 years.
ISO 9001 European designed and manufactured, state of the art products which exceed the requirements of the latest Standards and our competitors’ specifications.
Because we specialise in Lightning and Surge protection we can offer you the very best, most cost-effective solution of any company in this field.
We carry out many seminars with consultants and specialist training organisations as well as attending exhibitions and conferences both in the UK and overseas where our specialist knowledge is renowned.
SPD Ltd stands for innovation, quality and excellent customer service.
FREE technical help. Assistance with product selection and design.We can carry out site surveys.We can assist with compliance to the latest requirement of the Wiring Regulations. BS7671 and BSEN62305 Lightning Standards.
Wind Turbines
Serv
ers
Schools
domestic
Surge Protection Specialists2
New Standard BSEN62305-4 1st Sept 2008 & 17th Edition Wiring Regs Amendments 1st Jan 2012.
This new standard replaced BS6651 on the above date, it is now mandatory to fit a lightning current arrester on main incoming panels which are situated in buildings with external lightning conductors or fed by an overhead line. This type of arrester is designated as a Type 1, we recommend a combined T1+T2+T3 arrester as this gives additional surge protection for no added cost. The minimum discharge capability for a T1 arrester has to be 50Ka 10/350μs.
Panels or sub-distboards feeding external circuits such as car park lighting, CCTV etc should also have a combined T1+T2+T3 arrester fitted as standard.
An example of a T1+T2+T3 combined arrester is 10651 LED Level 1, 100Ka 10/350μs.
An introduction to Lightning Surge Protection
Lightning/Surge protection for electrical and electronic systems to the new British and European Standard BS EN 62305-4. Surge Protection Devices Ltd offer the complete solution to protect vital systems from damage.
Recently introduced standards put equal importance on protecting the electrical installation and electrical equipment as to the building itself.
Modern micro electronic components are very sensitive to overvoltages and because many systems are networked they rely on each other for the system to operate. If one part of the system gets damaged due to lightning or surges, the whole system will not operate. The consequential losses suffered during such events i.e. downtime and lost production, can be very high.
We offer a wealth of experience in helping to decide which product best suits your needs. Our catalogue contains our most popular products however we have many more products and components to suit a range of applications.
For panels and sub boards in buildings without external lightning conductors and fed by underground cables a T2 surge arrester is sufficient. Sub-distribution boards or local control panels more than 10 metres from the main incomer and not feeding external circuits then a Type 2 surge arrester can be used. An example of a T2 surge arrester is Part no SY2-C40X.
Final sub-circuits and sensitive electronic equipment, e.g. fire/burglar panels, PLC’s which are fitted more than 10 metres from the last surge arrester should have a T3 surge arrester fitted at the panel or equipment to be protected. An example of a T3 surge arrester is SY2-D/LED.
For further information on surge protection recommendations please call us on 01484 851747.
Hospitals
MOD
Solar
3
SPD Type 1 SPD Type 2 SPD Type 3
General distribution of lightning current when a building is hit by lightning. LV power system protection thanks to cascaded 3-stage protection.
Main Incoming Position
Type 1
PROTECTION AGAINST
DIRECT LIGHTNING
CURRENTS
(LIGHTNING CURRENT
ARRESTER)
10/350μs
Sub Dist. Board Position
Type 2
PROTECTION AGAINST
INDIRECT LIGHTNING
EFFECTS
(SURGE ARRESTER)
8/20μs
Socket Outlet or Final Sub
Type 3
PROTECTION AGAINST
SWITCHING OVERVOLTAGES
(SURGE ARRESTER)
8/20μs
Surge Protection Specialists4
Type 1+2+3 Combined Lightning & Surge Arresters, DIN Rail Mountable. Fully Compliant to EN/IEC61643-11, BS/IS/EN62305, BS7671
Part No. 10651 LED
Maximum continuous operating voltage Uc 275 V AC
Lightning impulse current (10/350)- charge- specific energy
IimpQW/R
25kA12,5As156kJ/
Total lightning current (10/350)L1 + L2 + L3 + N - PE
Itotal 100kA
Max. discharge current (8/20) per mode Imax 120kA
Nominal discharge current (8/20) per mode In 50kA
Voltage protection level at Iimp Up <1.2kV
Response time tA <25ns
Temporary overvoltage (TOV) UT 335V/5 sec.
Rec. Back-up fuse / MCCB 63A/100A
Max. Back-up fuse (“V” connection) 63AgL/gG
Short circuit withstand capability at max back-up fuse
Ip 80kArms
Weight m 1125g
Lifetime min 100 000 h
Let through voltage (I) 3ka 8/20μs, short circuit current to BS6651+1999 AppC 600V
Part No. 1065 I LED
LPL Level 1 100kA 10/350μs
Part No. 10650/LED
Maximum continuous operating voltage Uc 275 V AC
Lightning impulse current (10/350)- charge- specific energy
IimpQW/R
25kA12,5As156kJ/
Total lightning current (10/350)L1 + N-PE 50kA
Itotal 50kA
Max. discharge current (8/20) per mode Imax 120kA
Nominal discharge current (8/20) per mode In 50kA
Voltage protection level at Iimp Up < 1.2kV
Response time tA < 25ns
Temporary overvoltage (TOV) UT 335 V/5 sec.
Rec. Back-up fuse / MCCB 63A/100A
Max. Back-up fuse (“V” connection) 63AgL/gG
Short circuit withstand capability at max back-up fuse
Ip 80kArms
Weight m 565g
Let through voltage (I) 3ka 8/20μs, short circuit current to BS6651+1999 AppC 600V
Part No. 10650 LED
For 2 pole level 1 100kA 10/350μs specify HS50-50 1+1LED
2 Pole Data Sheet
4 Pole Data Sheet LED Indication Version
LPL Level 3/4 50kA 10/350μs
TP+N Part No. 10651LED
SP+N Part No. 10650LED
5
Type 1+2+3 Combined Lightning and Surge Arresters - DIN Rail Mountable. Fully Compliant to EN/IEC61643-11, BS/EN/IEC62305, BS7671
Part No. 383811
Maximum continuous operating voltage Uc 275 V AC
Lightning impulse current (10/350)- charge- specific energy
IimpQW/R
25kA12,5As156kJ/
Total lightning current (10/350)L1 + L2 + L3 + N - PE
Itotal 100kA
Max. discharge current (8/20) per mode Imax 150kA
Nominal discharge current (8/20) per mode In 70kA
Voltage protection level at Iimp Up <1.5kV
Response time tA <25ns
Temporary overvoltage (TOV) UT 335V/5 sec.
Rec. Back-up fuse / MCCB 63A/100A
Max. Back-up fuse (“V” connection) 63AgL/gG
Short circuit withstand capability at max back-up fuse
Ip 80kArms
Weight m 1125g
Lifetime min 100 000 h
Let through voltage (I) 3ka 8/20μs, short circuit current to BS6651+1999 AppC 600V
383811
Part No. 383812
Maximum continuous operating voltage Uc 275 V AC
Lightning impulse current (10/350)- charge- specific energy
IimpQW/R
25kA12,5As156kJ/
Total lightning current (10/350)L1 + L2 + L3 + N - PE
Itotal 50kA
Max. discharge current (8/20) per mode Imax 150kA
Nominal discharge current (8/20) per mode In 70kA
Voltage protection level at Iimp Up <1.5kV
Response time tA <25ns
Temporary overvoltage (TOV) UT 335V/5 sec.
Rec. Back-up fuse / MCCB 63A/100A
Max. Back-up fuse (“V” connection) 63AgL/gG
Short circuit withstand capability at max back-up fuse
Ip 80kArms
Weight m 565g
Lifetime min 100 000 h
Let through voltage (I) 3ka 8/20μs, short circuit current to BS6651+1999 AppC 600V
383812
For 2 pole level 1 100kA 10/350μs specify HS50-50 1+1LED
4 Pole Data Sheet Window Indication Version
2 Pole Data Sheet
64
TP+NPart No. 383811
SP+NPart No. 383812
LPL Level 3/4 50kA 10/350μs
LPL Level 1 100kA 10/350μs
Surge Protection Specialists6
383811 ENC
383812 ENC
• Type 1 + 2 + 3 combined direct lightning and surge arrester TP+N
• Complete in high quality IP65 Polycarbonate enclosure
• Meets level 1, 2, 3 + 4 100KA 10/350μs
• Conforms to BSEN62305 EN61643-11, BS7671 Amendment Wiring Regs.
• Use where building have external lightning protection or fed by overhead lines
• Visual and remote indication as standard
• Low through voltage
• Available with 63AMP backup MCB (add ‘M’ to part number - e.g. 383811 ENC M)
• Each pole individually replaceable
• SP+N version 50KA 10/350μs. Level 3-4 if 100KA needed then please ask for HS 50-50 1+1 ENC 100KA 10/350μs version
• Use 63/100 AMP backup fuse or MCB
• Cable size to be 25mm² min.
Lightning and Surge Protection for Industrial, Commercial and Domestic Electric Installations
Dimensions (CM) : H20 x W26 x D11
Dimensions (CM) : H20 x W20 x D11
Type 1 + 2 + 3 Combined arresters in enclosures
TP+N
SP+N
4 Pole Data Sheet Window Indication Version
2 Pole Data Sheet
7
Maximum continuous operating voltage Uc 275 V AC
Lightning impulse current (10/350)- charge- specific energy
1mpQW/R
25kA12,5As39kJ/
Max. discharge current Imax 100kA
Nominal discharge current (8/20) In 20kA
Temporary overvoltage (TOV) UT 335V/5 sec.
Voltage protection level at Iimp Up <1.2kV
Response time tA <25ns
Rec. Back-up fuse / MCCB 63 AMPS
Lifetime min. 100 000h
Short circuit withstand capability at max back-up fuse
Ip 60kA rms
Weight m 140g
Let through voltage (I) 3ka 8/20μs, short circuit current to BS6651+1999 AppC App C = 600V
Part No. 1 Pole 10020
Part No. 2 Pole 10020/2
Part No. 4 Pole 10020/4
Type 1 + 2 + 3 Combined Lightning/Surge Arresters for DIN Rail Mounting
Part No. 10020
Part No. 10020/4
Surge Protection Specialists8
Part No. 10020/4 ENC
Part No. 10020/4 ENCM
• Type 1 + 2 + 3 Level 3/4 50KA 10/350μs
• Very low let-through voltage (less than 600v)
• Fast response time less than <25ns
• For LPL Zones 0-3
• IP65 Polycarbonate enclosure H20cm W20cm D11cm
• With or without backup 63AMP MCB
• Follow currents completely eliminated
• Visual and remote monitoring as standard
• Enhanced protection to BSEN 62305
• 1st Amendment, 17th Edition Wiring Regs. Compliant
Type 1 + 2 + 3 Combined Lightning/Surge Arresters in Complete Enclosures
TP+N
TP+N + MCB
9
Type 1 + Type 2 +Type 3 Combined Lightning/Surge Arrester for DIN Rail Mounting
4 Pole Lightning/Surge Arrester
Max. continuous operating voltage Uc 275 V AC
Lightning impulse current- charge- specific energy
IimpQW/R
12,5 kA6,25 As39 KJ/Ω
Total lightning current (10/350)L1 + L2 + L3 + N → PE
Itotal 50 kA
Nominal discharge current (80/20) In 20 kA
Voltage protection level Up < 1,2 kV
Temporary overvoltage (TOV) UT 335 V / 5 sec
Response time tA < 25ns
Max. backup fuse 160 AgL/gG
Short-circuit withstand capability at max. back-up fuse
Ip 60 kArms
Lifetime min. 100 000 h
Weight m 560g
Part no 16057
Part no spare module 16058• Arrester Type 1 + Type 2 + Type 3• 4-pole arrester pluggable• 3-phase power supply network TN-C-S• LPZ 0-1• LPL III, IV Itotal 50kA 10/350μs• Very low let-through voltage• Visual indication of status• Remote signal contacts• Recomended back-up fuse/MCB Min 63
AMPS• Cable size 16mm² to 25mm²
Part No. 16057
TP+N
Surge Protection Specialists10
Type 2/3 Enhanced Surge Arrester 2 pole (SP+N)
Type 2/3 Enhanced Pluggable Surge Arresters
Type 2/3 DIN Rail Mountable Surge Arresters
Part No. SY1-C 40X
Protect sensitive electronic equipment with high quality surge arresters.Today’s highly sensitive electronics require a higher level of protection; you can achieve this by using the following Lightning/Surge Arresters from Surge Protection Devices Ltd. They are quick and easy to install and are high-tech products at competitive prices compared with other brands.
SPD According to IEC61643-1 EN61643-11 Type 2/3
Maximum continuous operating voltage UcV
(350V DC)275 VAC
Voltage protection level In UpVoltage protection level at 5kA UpVoltage protection level at 3kA Up
≤ 1.3kV< 0.9kV< 0.6kV
Nominal discharge currentIn (8/20μs)kA 20kA
Nominal discharge currentImax (8/20μs)kA 40kA
WithstandShort Circuit
50kARMS
Response time in ns <25ns
Dimensions W 72mm H 90mm D 66mm Din-rail mountable
Enclosure material Yellow/GreyUL94 V-O
Degree of protection IP20
Recommended backup MCB/fuse 32A to 63A
Terminal capacityPhase line Neutral line - 2.5~35mm²Earth Line - 4.0~35mm²Signal Line - 1.0mm²
Visual indication of status Green OKRed Replace Module
Remote Alarm Contact Contact closes if any part of the device fails
SPD According to IEC61643-1 EN61643-11 Type 2/3
Maximum continuous operating voltage UCV 275 V
Voltage protection level Up3kA (8/20μs)kA < 0.6kV
Nominal discharge currentIn (8/20μs)kA 5kA
Maximum discharge currentImax (8/20μs)kA 10kA
Response time < 25ns
Dimensions W 18mm H 90mm D 66mm
Enclosure material Grey UL94 V-O
Degree of protection IP20
Recommended backup MCB/fuse 32A or less
Terminal capacity 1.5~4mm²
Visual indication of status Black OKRed Replace Module
DIN rail mountable Yes
Part No. SY2-DPluggable version
Part No. SY2-D LEDLED version
Part No. SY2-C 40X
SP+N TP+N
SP+N SP+N
11
SY2-C40X ENC
SY1-C40X ENC
• Type 2/3 Enhanced TP+N Pluggable Surge Arrester
• Complete in high quality IP65 Polycarbonate enclosure
• High surge capacity 40,000 AMPS per pole
• Conforms to BSEN62305, EN61643-11 and BS7671 1st Amendment Wiring Regs.
• Use where there is no external lightning protection and no overhead lines
• Also use on sub-dist boards to protect sensitive electronic equipment
• Connection in parallel means no current limitations
• Visual and remote indication as standard
• Low let through voltage
• Available with 63AMP backup MCB (add ‘M’ to part number - e.g. SY2-C40X ENCM)
• Each pole individually replaceable
• Use 32A to 63A backup MCB
• Cable size 6mm² - 16mm²
Type 2/3 Enhanced Pluggable Surge Arresters in Enclosures
Dimensions (CM) : H20 x W12 x D11
Dimensions (CM) : H20 x W12 x D11
TP+N
SP+N
Surge Protection Specialists12
Surge Arrester Type 2/3 Compact Type LED Indication
P-3k is a three-phase surge arrester type 2/3 according to EN61643-11 and IEC 61643-1 suitable for use in TNS, TNC and TT systems. These are parallel devices intended for protection of electronic appliances against impulse surge. All varistors are fitted with thermal fuses to prevent short and also permanent overloading.
These units are to be connected as near to the protected appliance as possible, e.g. local control panel, dist board.The right function of P-3k230 devices is indicated by target disconnection of mechanical thermal fuses which react to varistors overheating above c. 120˚C.
Nominal voltage UN 230 V AC
Max. continuous operating voltage Uc 275 V AC
Nominal discharge current In(8/20) In 3 kA (L/N, L/PE)5 kA (N/PE)
Combined impulse Uoc 6 kV (L/N, L/PE)10 kV (N/PE)
Voltage protection level at Uoc Up<1,2 V (L/N)<1,2 kV (L/PE)<1,2 kV (N/PE)
Power loss at winding temp. 20˚C c. 3VA / 0,1 VA
Response time tA <25ns (L/N)<100ns (L/PE, N/PE)
Recommended backup fuse 16A
Lifetime min. 100.000 h
Weight m 140/205g
Part no 30 105
Part No. 30 105
Recommended connection of 30105 Basic circuit diagram of 30105
13
Surge Protection Specialists
Type 3 Surge ArresterFor electrical installation systems
Type 3 to EN61643-11
Surge protection device for electrical installation systems
32006 is surge arrester type 3 according to EN 61643-11 dsigned for installation into electrical installation systems, e.g.: cable ducts, flush-mounted sockets or fire alarm panels as an additional protection measure.
32006 contains an acoustic fault indicator (buzzer) and is earth leakage free.
Nominal voltage Un 230 V AC
Max. continuous operating voltage Uc 275 V AC
Nominal discharge current In (8/20) In 3 kA (L/N, L/PE)5 kA (N/PE)
Combined impulse Uoc 6 kV (L/N) 10 kV (N/PE)
Voltage protection level at Uoc Up1 kV (L/N) <1 kV (L/PE)<1,2 kV (N/PE)
Power loss at winding temp. 20˚C 0,5 W
Response time TA <25 ns (L/N)<100 ns (L/PE, N/PE)
Recommended backup fuse 16A
Temporary overvoltage (TOV) UT 335V/5 s (L/N)1200V + U0/200 ms (L/PE)
Lifetime Min. 100.000 h
Failure indication 32006 inbuilt piezosiren
Weight m 20/30g
Part No. 32006
Basic circuit diagram of 32006
Recommended connection of 32006
14
Surge Arresters - Varistor and EMC/EMI FilterType 3
Nominal voltage UN 230 V AC
Max. continuous operating voltage Uc 275 V AC
Nominal current IN 8A
Nominal discharge current In(8/20) In 3 kA (L/N, L/PE)5 kA (N/PE)
Combined impulse Uoc 6 kV (L/N, L/PE)10 kV (N/PE)
Voltage protection level at Uoc Up<850 V (L/N)<1,5 kV (L/PE)<1,2 kV (N/PE)
Asymmetrical attenuation of filter (band-stop filter)
min. 80dB at 4MHzmin. 40dB (0,15 - 30MHz)
Filters constraintsCxCyL
150 nF22 nF1,2 mH
Power loss at winding temp. 20˚C <2,2 W
Response time tA <25ns (L/N)<100ns (L/PE, N/PE)
Recommended backup fuse 6A
Lifetime min. 100.000 h
Weight m 130g
Part no 30 080
PI-k and PI-k16 are type 3 single phase surge arresters with a high frequency filter according to EN61643-11 and IEC 61643-1. They are produced for nominal current within the range of 8, 16, 25, 32 for mounting on DIN rail 35mm. For protection of single-phase electronic appliances in L.V. supply systems against impulse surge and high-frequency disturbance.
Nominal voltage UN 230 V AC
Max. continuous operating voltage Uc 275 V AC
Nominal current IN 16A
Nominal discharge current In(8/20) In 3 kA (L/N, L/PE)5 kA (N/PE)
Combined impulse Uoc 6 kV (L/N, L/PE)10 kV (N/PE)
Voltage protection level at Uoc Up<850 V (L/N)<1,5 kV (L/PE)<1,2 kV (N/PE)
Asymmetrical attenuation of filter (band-stop filter)
min. 80dB at 4MHzmin. 40dB (0,15 - 30MHz)
Filters constraintsCxCyL
220 nF22 nF1,8 mH
Power loss at winding temp. 20˚C <3,5 W
Response time tA <25ns (L/N)<100ns (L/PE, N/PE)
Recommended backup fuse 16A
Lifetime min. 100.000 h
Weight m 170/224g
Part no 30 004
Part No. 30 080
Part No. 30 004
15
Nominal voltage UN 230 V AC
Max. continuous operating voltage Uc 275 V AC
Nominal current IN 25A
Nominal discharge current In(8/20) In 3 kA (L/N, L/PE)5 kA (N/PE)
Combined impulse Uoc 6 kV (L/N, L/PE)10 kV (N/PE)
Voltage protection level at Uoc Up<850 V (L/N)<1,5 kV (L/PE)<1,2 kV (N/PE)
Asymmetrical attenuation of filter (band-stop filter)
min. 80dB at 4MHzmin. 40dB (0,15 - 30MHz)
Filters constraintsCxCyL
220 nF22 nF2,3 mH
Power loss at winding temp. 20˚C <3,5 W
Response time tA <25ns (L/N)<100ns (L/PE, N/PE)
Recommended backup fuse 25A
Lifetime min. 100.000 h
Weight m 240g
Part no 30 017
Nominal voltage UN 230 V AC
Max. continuous operating voltage Uc 275 V AC
Nominal current IN 32A
Nominal discharge current In(8/20) In 3 kA (L/N, L/PE)5 kA (N/PE)
Combined impulse Uoc 6 kV (L/N, L/PE)10 kV (N/PE)
Voltage protection level at Uoc Up<850 V (L/N)<1,5 kV (L/PE)<1,2 kV (N/PE)
Asymmetrical attenuation of filter (band-stop filter)
min. 80dB at 4MHzmin. 40dB (0,15 - 30MHz)
Filters constraintsCxCyL
220 nF22 nF2,3 mH
Power loss at winding temp. 20˚C <4 W
Response time tA <25ns (L/N)<100ns (L/PE, N/PE)
Recommended backup fuse 32A
Lifetime min. 100.000 h
Weight m 240g
Part no 30 005
2-Stage MOV Surge Arrester and EMC / EMI Filter
Part No. 30 005
Part No. 30 017
Surge Protection Specialists16
Telephone/Fax/ModemSurge Arrester
Technical Data
Number of protected pairs 2
Nominal voltage Un 170v
Max. continuous operating voltage Uc 204v
Nominal current IN 100mA
C2 Max. discharge current (8/20) 1MAX 2kA
Nominal discharge current (8/20) IN 1kV
Voltage protection level at 1kV/μs Up 520v
Response time TA <30ns
Data rate 10MBit/s
Series impedance per line 1,5-10 Ω
Parasitic capacitance C 1,5nF
Operating temperature change ϑ -40°C ÷ + 80°C
Category tested acc. to IEC 61643:21-2000 A2, B2, C2, C3, D1
For BT Type Sockets. Test category D+C+B to BSEN 61643-21
Single or 10 Pair Telephone Surge Arrester for Installation into Krone LSA Disconnections Strips, Test Category D+C+B to BSEN 61643-21
Technical Data
Nomincal direct voltage 110V=
Max. continuous operating direct voltage (Uc) 180v=
Max. continuous operating alternating voltage (Uc) 180~
Residual voltage at 1kV/μs <250V
Nominal operating current at 25°C 145mA
C2 nominal discharge current (8/20μs) In 5kA
Max. impulse discharge current (8/20μs) (Imax) 10kA
Protection level at In (Up) 220V
Response time (tA) <1ns
Thermal response time at 230V/23 A ac and ambient temp. 25°C (TA) <2s
Capacitance wire-earth (C) <0.1nF
Series inductance at 25°C (L) 47μH
Series resistance per line at 25°C (R) 3-6 Ω
Max. transmission frequency (fg) ≤1.2MHz
Operating temperature range -40°C to + 80°C
Enclosure material / colour Thermoplastic, grey or yellow
Dimensions (L x W x H) 110 x 2.25 x 40mm
Net weight / pc 90g
Part No. DTB2/ART
Can also be used on ISDN Fast Transmission Lines
Part No. DP1 LSA180
Part No. DP10LSA180
Part No. TELCO/EB
17
Data Signal Line Arresters/CCTV
DATA SIGNAL ARRESTER 2 POLE
Part No. SP5 SP12 SP15 SP24 SP30 SP48 SP60 SP110
Nominal voltage: Un 5V- 12V- 15V- 24V- 30V- 48V- 60V- 110V-
Max. continuous voltage DC.Uc 6V- 14.5V- 17.8V- 26.8V- 34.8V- 55.1V- 65V- 170V-
Max. continuous voltage: AC.Uc 4.2V 10.2V 12.5V 18.9V 24.5V 38.9V 50V 130V
Nominal current: In 1A
C2 Total Nominal Discharge Current In (8/20μs) 20kA
D1 Total Lightning Impulse Current (10/350μs) Iimp 20kA
Voltage protective level: Upin
Core/Core ≤50V ≤70V ≤85V ≤100V ≤130V ≤200V ≤240V ≤730V
Core/PE ≤45V ≤60V ≤70V ≤80V ≤80V ≤120V ≤150V ≤400V
Voltage protective level: Up 1kc/μS
Core/Core ≤16V ≤38V ≤50V ≤70V ≤95V ≤150V ≤180V ≤520V
Core/PE ≤8V ≤19V ≤25V ≤35V ≤50V ≤75V ≤90V ≤260V
Response time: tA ≤1ns ≤25ns
Resistance 1Ω 1.5 Ω 1.6 Ω 1.8 Ω 1.8 Ω 1.8 Ω 1.8 Ω
Insertion loss ≤0.3dB
Working frequency ≤0.3MHz
Degree of protection IP20
Dimensions 90H x 14W x 65D mm
Enclosure material Polyamide PA6.6
Connector Screw terminals
Signal Surge Protection Device. REP-SP Series
Model No. D-24/BNC
Nominal voltage (V) Un 24
Max. continuous voltage (V) Uc 24/28
C2 nominal discharge current (8/20μs) per line In 5kA
C2 nominal discharge current (8/20μs) shield-PG In 10kA
Voltage protection level(8/20μs, V) Up
Line-Shield ≤300
Shield-Ground ≤700Voltage protection level(1KVμs, V) Up
Line-Shield ≤50Shield-Ground ≤600
Transmission Speed (bps) Vs 10Mbps
Series impedence per line (Ohm) 3Ohm
Inerstion loss (dB) 0.5@10MHz
Response time Ta 1ns
Type of connection IN/OUT BNC Female/Male
Dimensions (mm) 70x25x25
Environment Temperature °C -25~+70
Surge arresters for coaxial ethernet network systems protection. Protects against surges at the boundaries from lightning protection zone 0 3
• Data network protector in accordance with IEC614321.• Limit the transients with gas discharge tubes and
transzorb diodes.• Two-stage protection circuit in aluminium housing.• BNC connector for ethernet systems.• Simple installation.• Also application for the protection of video signals,
cameras and/or TV systems
SP-30 SP-48
Co-Axial BNC C.C.T.V Arrester
Surge Protection Specialists18
Protection of PHOTOVOLTAIC/SOLAR SYSTEMS
SPD According to IEC61643-1 EN61643-11 Type 2
Maximum continuous operating voltage UcV 1060v DC
Voltage protection level In Up 4kv
Nominal discharge current In (8/20μs) kA 20kA
Maximum discharge current In (8/20μs) kA 40kA
Withstand short circuit 50kARMS
Response time ns <25ns
Dimensions W 54 x H 90 x D 66mmDin-rail mountable
Enclosure material GreyUL94 V-O
Degree of protection IP20
Recommended backup MCB/fuse 32A to 63A
Terminal capacity
Phase line Neutral line 2.5~35mm²
Earth line 4.0~35mm²
Signal line 1mm²
Visual indication status Green - OK Red - Replace Module
Din rail mountable Yes
Type 2 to EN61643-11
• Fault indication• Remote signal contact optional• Pluggable and replaceable modules
Type 2 to EN61643-11
• Fault indication• Remote signal contact optional• Pluggable and replaceable modules
SPD According to IEC61643-1 EN61643-11 Type 2
Maximum continuous operating voltage UcV 640v
Voltage protection level Up 2.2kv
Nominal discharge current In (8/20μs) kA 20kA
Maximum discharge current In (8/20μs) kA 40kA
Response time <25ns
Dimensions W 36 x H 90 x D 66mm
Enclosure material GreyUL94 V-O
Degree of protection IP20
Recommended backup MCB/fuse 32A to 63A
Terminal capacity
Phase line Neutral line 2.5~35mm²
Earth line 4.0~35mm²
Signal line 1mm²
Visual indication status Green - OK Red - Replace Module
Din rail mountable Yes
Surge protection devices for the protection of the DC side before inverter
Type 1 + 2 Available - Please Contact The Sales Office
Part No. SPD PV1000
Part No. SPD PV600
19
TEL: 01484 851747FAX: 01484 852594EMAIL: [email protected]
Surge Protection DevicesUnit 1 Ash Royd FarmRoyd RoadMelthamHolmfirthWest YorkshireHD9 4BG
www.surgedevices.co.uk
• We offer free technical help and assistance with product selection and design.
• We can carry out site surveys.• We can assist with compliance to the latest
requirement of the Wiring Regulations BS7671 and BSEN62305 Lightning Standards.