Lighting Design - Why Maintenance Factors Matter
![Page 2: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/2.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
Task visibility
Practical
Glare control
Energy Efficient
Managed
Colour
Modeling
Contrast
Effective
Atmosphere
Ambience
StimulatingSatisfaction
SafeErgonomic
Integrated
ColourfulHealthyInteresting
![Page 3: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/3.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
![Page 4: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/4.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
![Page 5: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/5.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
![Page 6: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/6.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
Lighting in the workplace: Good practice
39 Both interior and exterior lighting need to achieve a reasonable uniform illuminance in all relevant working areas, ie illuminance across any given task area needs to be uniform. For more information see CIBSE Code for lighting.
Minimum lighting recommendations
93 The illuminance needed depends on how much detail needs to be seen. It also depends on the age of the worker, and the speed and accuracy by which the task needs to be performed. These performance- related requirements and light levels are detailed in the CIBSE Code for lighting.
![Page 7: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/7.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
Ceiling
ρ
= 0.7 - 0.9
Em = 30 lux, Uo = 0.1
Walls
ρ
= 0.5 - 0.8
Em = 50 lux, Uo = 0.1
Floor
ρ
= 0.2 - 0.4
0.3-0.7
0.6 minimum
50%-60% w/p
30%-90% w/p
(Purple text – values as in SLL Lighting Guide 7)
![Page 8: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/8.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
Task areaImmediate surround – width at least 0.5m around the task area
Background area – width at least 3m (within the limits of the space)
![Page 9: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/9.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
Task visibility
Practical
Glare control
Energy Efficient
Managed
Colour
Modeling
Contrast
Effective
Atmosphere
Ambience
StimulatingSatisfaction
SafeErgonomic
Integrated
ColourfulHealthyInteresting
![Page 10: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/10.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
maintained illuminance
minimum average illuminance
NOTE 1 Value below which average illuminance should not fall.
NOTE 2 It is the average illuminance at the time maintenance should be carried out.
From EN 12665:2011
![Page 11: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/11.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
The lighting scheme should be designed with an overall maintenance factor (MF) calculated for the selected lighting equipment, environment and specified maintenance schedule.
The MF has a great impact on energy efficiency. The assumptions made in the derivation of the MF shall be optimized in a way that leads to a high value. Guidance on the derivation of MF for artificial lighting systems can be found in CIE 97-2005.
![Page 12: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/12.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat is managed?
Task visibility
Practical
Glare control
Energy Efficient
Managed
Colour
Modeling
Contrast
Effective
Atmosphere
Ambience
StimulatingSatisfaction
SafeErgonomic
Integrated
ColourfulHealthyInteresting
![Page 13: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/13.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
The light levels in an installation depreciate over time
This is dependant upon ?
![Page 14: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/14.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
The light levels in an installation depreciate over time
This is dependant upon
-Ageing of the lamp-Lamp failures-Dirt on the luminaire-Dirt on light reflecting surfaces
![Page 15: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/15.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
The light levels in an installation depreciate over time
This is dependant upon- Ageing of the lamp- Lamp failures- Dirt on the luminaire- Dirt on light reflecting surfaces
These combine to make up the scheme maintenance factor
“ratio of the average illuminance on the working plane after a certain period of use of a lighting installation to the average illuminance obtained under the same condition for the installation considered conventionally as new”(CIE 17.4:1987)
![Page 16: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/16.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
The light levels in an installation depreciate over time
This is dependant upon
-Ageing of the lamp-Lamp failures-Dirt on the luminaire-Dirt on light reflecting surfaces
![Page 17: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/17.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
The light levels in an installation depreciate over time
This is dependant upon
-Ageing of the lamp-Lamp failures-Dirt on the luminaire-Dirt on light reflecting surfaces
![Page 18: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/18.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
The light levels in an installation depreciate over time
This is dependant upon-Ageing of the lamp-Lamp failures-Dirt on the luminaire-Dirt on light reflecting surfaces
The maintenance cycle specifies-When the luminaire is cleaned-When the lamp is replaced-When reflecting surfaces are cleaned
The scheme maintenance factor is the worst case relative illuminance over this maintenance cycle
![Page 19: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/19.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
![Page 20: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/20.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – lamp lumen maintenance factor (LLMF)
Ageing of the lamp
Let us assume for an office area annual operating hours are 2500 hours (BS EN 15193:2007)
If we decide to change the lamps every 4 years that is the equivalent of every 10,000 hours
![Page 21: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/21.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – lamp lumen maintenance factor (LLMF)
91%
![Page 22: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/22.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – lamp lumen maintenance factor (LLMF)
Ageing of the lamp
Let us assume for an office area annual operating hours are 2500 hours (BS EN 15193:2007)
If we decide to change the lamps every 4 years that is the equivalent of every 10,000 hours
So the lamp lumen maintenance factor is 0.91
![Page 23: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/23.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – lamp survival factor (LSF)
Lamp failures
Let us assume in our office area we do not do spot lamp replacement, but bulk replace the lamps
We decided to change the lamps every 4 years
![Page 24: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/24.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – lamp survival factor (LSF)
95%
![Page 25: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/25.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – lamp survival factor (LSF)
Lamp failures
Let us assume in our office area we do not do spot lamp replacement, but bulk replace the lamps
We decided to change the lamps every 4 years
So the lamp survival factor is 0.95
![Page 26: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/26.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Type Luminaire type Luminaire description
A Bare batten Bare lamp luminaires
B
Open top housing (natural ventilated and “self cleaning” types)
Direct-indirect luminaries without cover, direct-indirect luminaries with indirect reflector and closed optical device, wallwashing luminaries (vertical opening), wall mounted luminaries open top and base, downlights with open top
CClosed top housing (unventilated)
Recessed and surface mounted luminaries (e.g. with louvers), downlights, spotlights
D Enclosed IP2X
General purpose luminaries with closed covers and optics
E Dust proof IP5X
Dust proof IP5X (protected, clean room luminaries)
FIndirect lighting and uplight
Free standing, pendent, wall mounted uplighters with closed base, cove lights
GAir handling and forced ventilated
Air handling body and optic used with air-conditioning or ventilation systems
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – luminaire maintenance factor (LMF)
Dirt on the luminaire
Luminaire types are classified according to the table shown (extracted from CIE 97:2005)
![Page 27: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/27.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – luminaire maintenance factor (LMF)
Dirt on the luminaire
Luminaire types are classified according to the table shown (extracted from CIE 97:2005)
These are used to reference a table of luminaire maintenance factors
TypeLuminaire type Luminaire description
A Bare batten Bare lamp luminaires
B
Open top housing (natural ventilated and “self cleaning” types)
Direct-indirect luminaries without cover, direct-indirect luminaries with indirect reflector and closed optical device, wallwashing luminaries (vertical opening), wall mounted luminaries open top and base, downlights with open top
C
Closed top housing (unventilated )
Recessed and surface mounted luminaries (e.g. with louvers), downlights, spotlights
D Enclosed IP2X
General purpose luminaries with closed covers and optics
E Dust proof IP5X
Dust proof IP5X (protected, clean room luminaries)
FIndirect lighting and uplight
Free standing, pendent, wall mounted uplighters with closed base, cove lights
GAir handling and forced ventilated
Air handling body and optic used with air-conditioning or ventilation systems
![Page 28: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/28.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – luminaire maintenance factor (LMF)
Environments are split into very clean (VC), clean (C), normal (N) and dirty (D)
A maintenance value is read by determining the luminaire type and environment, and then deciding the cleaning interval
Elapsed time between cleanings in years
0 0.5 1.0 1.5 2.0 2.5 3.0
Environment
Luminaire type Any VC C N D VC C N D VC C N D VC C N D VC C N D VC C N D
A 1 0,98 0.95 0.92 0.88 0.96 0.93 0.89 0.83 0,95 0.91 0.87 0.80 0.94 0.89 0.84 0.78 0,93 0.87 0.82 0.75 0.92 0.85 0.79 0.73
B 1 0,96 0.95 0.91 0.88 0.95 0.90 0.86 0.83 0,94 0.87 0.83 0.79 0.92 0.84 0.80 0.75 0,91 0.82 0.76 0.71 0.89 0.79 0.74 0.68
C 1 0,95 0.93 0.89 0.85 0,94 0.89 0.81 0.75 0,93 0.84 0.74 0.66 0,91 0.80 0.69 0.59 0,89 0.77 0.64 0.54 0,87 0.74 0.61 0.52
D 1 0,94 0.92 0.87 0.83 0.94 0.88 0.82 0.77 0,93 0.85 0.79 0.73 0.91 0.83 0.77 0.71 0,90 0.81 0.75 0.68 0.89 0.79 0.73 0.65
E 1 0,94 0.96 0.93 0.91 0,96 0.94 0.90 0.86 0,92 0.92 0.88 0.83 0,93 0.91 0.86 0.81 0,92 0.90 0.85 0.80 0,92 0.90 0.84 0.79
F 1 0,94 0.92 0.89 0.85 0.93 0.86 0.81 0.74 0,91 0.81 0.73 0.65 0.88 0.77 0.66 0.57 0,86 0.73 0.60 0.51 0.85 0.70 0.55 0.45
G 1 1,00 1.00 0.99 0.98 1,00 0.99 0.96 0.93 0,99 0.97 0.94 0.89 0,99 0.96 0.92 0.87 0,98 0.95 0.91 0.86 0,98 0.95 0.90 0.85
![Page 29: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/29.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Environment Activity or Task area
Very Clean
Clean
Clean rooms, semi conductor plants, hospital clinical areas, computer centres
Offices, schools, hospital wards
NormalShops, laboratories, restaurants, warehouses, assembly areas, workshops
DirtySteelworks, chemical works, foundries, welding, polishing, woodwork
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – luminaire maintenance factor (LMF)
Dirt on the luminaire
The environment type for the application can be determined using the table shown. However these should be adjusted if the conditions are different from the norm
![Page 30: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/30.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – luminaire maintenance factor (LMF)
For our example we will decide to clean the luminaires every 2 years
An office is normally considered a clean environment
Assume we are using a recessed luminaire, which is luminaire type C
Therefore our luminaire maintenance factor is 0.80
Elapsed time between cleanings in years
0 0.5 1.0 1.5 2.0 2.5 3.0
Environment
Luminaire type Any VC C N D VC C N D VC C N D VC C N D VC C N D VC C N D
A 1 0,98 0.95 0.92 0.88 0.96 0.93 0.89 0.83 0,95 0.91 0.87 0.80 0.94 0.89 0.84 0.78 0,93 0.87 0.82 0.75 0.92 0.85 0.79 0.73
B 1 0,96 0.95 0.91 0.88 0.95 0.90 0.86 0.83 0,94 0.87 0.83 0.79 0.92 0.84 0.80 0.75 0,91 0.82 0.76 0.71 0.89 0.79 0.74 0.68
C 1 0,95 0.93 0.89 0.85 0,94 0.89 0.81 0.75 0,93 0.84 0.74 0.66 0,91 0.80 0.69 0.59 0,89 0.77 0.64 0.54 0,87 0.74 0.61 0.52
D 1 0,94 0.92 0.87 0.83 0.94 0.88 0.82 0.77 0,93 0.85 0.79 0.73 0.91 0.83 0.77 0.71 0,90 0.81 0.75 0.68 0.89 0.79 0.73 0.65
E 1 0,94 0.96 0.93 0.91 0,96 0.94 0.90 0.86 0,92 0.92 0.88 0.83 0,93 0.91 0.86 0.81 0,92 0.90 0.85 0.80 0,92 0.90 0.84 0.79
F 1 0,94 0.92 0.89 0.85 0.93 0.86 0.81 0.74 0,91 0.81 0.73 0.65 0.88 0.77 0.66 0.57 0,86 0.73 0.60 0.51 0.85 0.70 0.55 0.45
G 1 1,00 1.00 0.99 0.98 1,00 0.99 0.96 0.93 0,99 0.97 0.94 0.89 0,99 0.96 0.92 0.87 0,98 0.95 0.91 0.86 0,98 0.95 0.90 0.85
![Page 31: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/31.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – room surface maintenance factor (RSMF)
Dirt on light reflecting surfaces
For the effect of dirt on the room surfaces three pieces of information are required
-Surface reflectance’s- Environment cleanliness (as for the luminaire maintenance factor)-Room surface cleaning interval
A table of room surface maintenance factors is then consulted
![Page 32: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/32.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – room surface maintenance factor (RSMF)
reflectances environment 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
0.80/0.70/0.20 very clean 1.00 0.97 0.96 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
clean 1.00 0.93 0.92 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
normal 1.00 0.88 0.86 0.86 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
dirty 1.00 0.81 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80
0.80/0.50/0.20 very clean 1.00 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
clean 1.00 0.95 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94
normal 1.00 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
dirty 1.00 0.86 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
0.80/0.30/0.20 very clean 1.00 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
clean 1.00 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
normal 1.00 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
dirty 1.00 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
0.70/0.70/0.20 very clean 1.00 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
clean 1.00 0.94 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
normal 1.00 0.89 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
dirty 1.00 0.83 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81
0.70/0.50/0.20 very clean 1.00 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
clean 1.00 0.96 0.95 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94
normal 1.00 0.92 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
dirty 1.00 0.87 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86
0.70/0.30/0.20 very clean 1.00 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
clean 1.00 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
normal 1.00 0.95 0.94 0.94 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
dirty 1.00 0.92 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
0.50/0.70/0.20 very clean 1.00 0.98 0.97 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
clean 1.00 0.95 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
normal 1.00 0.91 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89
dirty 1.00 0.85 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84
0.50/0.50/0.20 very clean 1.00 0.98 0.98 0.98 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
clean 1.00 0.97 0.96 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
normal 1.00 0.94 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
dirty 1.00 0.89 0.89 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
0.50/0.30/0.20 very clean 1.00 0.99 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
clean 1.00 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
normal 1.00 0.96 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
dirty 1.00 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
![Page 33: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/33.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – room surface maintenance factor (RSMF)
Dirt on light reflecting surfaces
For the effect of dirt on the room surfaces three pieces of information are required
-Surface reflectance’s- Environment cleanliness (as for the luminaire maintenance factor)-Room surface cleaning interval
A table of room surface maintenance factors is then consulted
So if we assume-Reflectance’s 70/50/20-Office environment, therefore clean-A cleaning interval of 5 years
![Page 34: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/34.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – room surface maintenance factor (RSMF)
reflectances environment 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
0.80/0.70/0.20 very clean 1.00 0.97 0.96 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
clean 1.00 0.93 0.92 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
normal 1.00 0.88 0.86 0.86 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
dirty 1.00 0.81 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80
0.80/0.50/0.20 very clean 1.00 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
clean 1.00 0.95 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94
normal 1.00 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
dirty 1.00 0.86 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
0.80/0.30/0.20 very clean 1.00 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
clean 1.00 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
normal 1.00 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
dirty 1.00 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
0.70/0.70/0.20 very clean 1.00 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
clean 1.00 0.94 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
normal 1.00 0.89 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
dirty 1.00 0.83 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81
0.70/0.50/0.20 very clean 1.00 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
clean 1.00 0.96 0.95 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94
normal 1.00 0.92 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
dirty 1.00 0.87 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86
0.70/0.30/0.20 very clean 1.00 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
clean 1.00 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
normal 1.00 0.95 0.94 0.94 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
dirty 1.00 0.92 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
0.50/0.70/0.20 very clean 1.00 0.98 0.97 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
clean 1.00 0.95 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
normal 1.00 0.91 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89
dirty 1.00 0.85 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84
0.50/0.50/0.20 very clean 1.00 0.98 0.98 0.98 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
clean 1.00 0.97 0.96 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
normal 1.00 0.94 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
dirty 1.00 0.89 0.89 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
0.50/0.30/0.20 very clean 1.00 0.99 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
clean 1.00 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
normal 1.00 0.96 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
dirty 1.00 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
![Page 35: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/35.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle – room surface maintenance factor (RSMF)
Dirt on light reflecting surfaces
For the effect of dirt on the room surfaces three pieces of information are required
-Surface reflectance’s-Environment cleanliness (as for the luminaire maintenance factor)-Room surface cleaning interval
A table of room surface maintenance factors is then consulted
So if we assume-Reflectance’s 70/50/20-Office environment, therefore clean-A cleaning interval of 5 years
Therefore the room surface maintenance factor is 0.94
![Page 36: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/36.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
So for this example the scheme maintenance factor would be
MF = LLMF * LSF * LMF * RSMF
MF = 0.91 * 0.95 * 0.80 * 0.94
MF = 0.65
![Page 37: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/37.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
So for this example the scheme maintenance factor would be
MF = LLMF * LSF * LMF * RSMF
MF = 0.91 * 0.95 * 0.80 * 0.94
MF = 0.65
This means to ensure that the installation never falls below the maintained light level (assuming the maintenance schedule is adhered to) we must OVERLIGHT the area to 154% of the design level. So for example
Maintained light level = 500lx
Initial light level = 769lx
![Page 38: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/38.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Optical IP rating
Pollution category
Exposure time (years)
1.0 1.5 2.0 2.5 3.0
IP2X High 0.53 0.48 0.45 0.43 0.42
Medium 0.62 0.58 0.56 0.54 0.53
Low 0.82 0.80 0.79 0.78 0.78
IP5X High 0.89 0.87 0.84 0.80 0.76
Medium 0.90 0.88 0.86 0.84 0.82
Low 0.92 0.91 0.90 0.89 0.88
IP6X High 0.91 0.90 0.88 0.85 0.83
Medium 0.92 0.91 0.89 0.88 0.87
Low 0.93 0.92 0.91 0.90 0.90
Lighting Design - Why Maintenance Factors MatterScheme maintenance cycle
Note that the example given was for interior lighting.
For exterior lighting no room surface maintenance factor is used.
The luminaire maintenance factor is calculated differently, according to the table shown.
![Page 39: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/39.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterHow do we calculate the effect of our maintenance schedule?
It also means we need to define a maintenance schedule
Change lamps 4 years
Clean luminaires 2 years
Clean room surfaces 5 years
If we do not convey this to the customer we cannot guarantee the light levels
(If the customer requires a set maintenance factor, for example 0.8, we should then take no responsibility for the maintenance regime and can only guarantee light levels at start of life)
![Page 40: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/40.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD24
Using control to offset maintenance factors
Constant Illuminance
To improve the efficiency of an installation the lighting can be controlled to only produce the correct amount of light at any time.
At start of life the lights are dimmed, as the installation ages the dimming is gradually reduced
Lighting Design - Why Maintenance Factors Matter
2
11% MFsavings
![Page 41: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/41.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD21
Using control to offset maintenance factors
Maintenance factor : 0.65
%savings= 1-[(1+MF)/2]
%savings= 1-[(1+0.65)/2] = 0.175
Saving : 17.5%
Lighting Design - Why Maintenance Factors Matter
2
11% MFsavings
![Page 42: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/42.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – main influences
Change the lamp
Clean the luminaire
Clean the room
![Page 43: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/43.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – tracking them through time
![Page 44: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/44.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD29
Lamps and Gear
Looking at maintenance factors – tracking them through timeLighting Design - Why Maintenance Factors Matter
Clean room surfaces : 6 yearClean luminaires : 2 yearGroup relamp : 2 yearMF : 0.79
L80 @ 40,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.72
![Page 45: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/45.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD30
Lamps and Gear
Looking at maintenance factorsLighting Design - Why Maintenance Factors Matter
Clean room surfaces : 6 yearClean luminaires : 2 yearGroup relamp : 2 yearMF : 0.79
L80 @ 40,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.72
L70 @ 50,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.69
![Page 46: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/46.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD31
Lamps and Gear
Looking at maintenance factorsLighting Design - Why Maintenance Factors Matter
Clean room surfaces : 6 yearClean luminaires : 2 yearGroup relamp : 2 yearMF : 0.79
L80 @ 40,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.72
L70 @ 50,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.69
Building Type
Installation life to 100,000 hours (years)
100,000 / to
Offices 40
Education 50
Hospitals 20
Hotels 20
Restaurants 40
Sports 25
Retail 20
Manufacturing 25
![Page 47: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/47.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD32
Lamps and Gear
Looking at maintenance factors – initial lighting levelsLighting Design - Why Maintenance Factors Matter
Clean room surfaces : 6 yearClean luminaires : 2 yearGroup relamp : 2 yearMF : 0.79
L80 @ 40,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.72
L70 @ 50,000 hoursClean room surfaces : 6 yearClean luminaires : 2 yearSpot replacementMF : 0.69
Em 500 lxEinitial 633 lx
Em 500 lxEinitial 694 lx
Em 500 lxEinitial 725 lx
![Page 48: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/48.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Clean room surfaces every 4 years instead of 6 years
![Page 49: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/49.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD32
Lamps and Gear
Looking at maintenance factors – effect of room surfaces Clean room surfaces every 4 years instead of 6 years
Lighting Design - Why Maintenance Factors Matter
Clean room surfaces : 4 yearClean luminaires : 2 yearGroup relamp : 2 yearMF : 0.79
L80 @ 40,000 hoursClean room surfaces : 4 yearClean luminaires : 2 yearSpot replacementMF : 0.72
L70 @ 50,000 hoursClean room surfaces : 4 yearClean luminaires : 2 yearSpot replacementMF : 0.69
Em 500 lxEinitial 633 lx
Em 500 lxEinitial 694 lx
Em 500 lxEinitial 725 lx
![Page 50: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/50.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Clean room surfaces every 4 years instead of 6 years
0.79
0.69
![Page 51: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/51.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Clean room surfaces every 4 years instead of 6 years
0.79¦
0.79
0.69¦
0.69
![Page 52: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/52.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Change luminaire type to an indirect solution
![Page 53: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/53.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Clean room surfaces every 6 years (indirect)
0.79 direct¦
0.74 indirect
0.69 direct¦
0.65 indirect
![Page 54: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/54.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Clean room surfaces every 4 years instead of 6 years (indirect)
0.74 @6¦
0.74 @4
0.65 @6¦
0.65 @4
![Page 55: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/55.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors – effect of room surfaces Clean room surfaces every 4 years instead of 6 years
![Page 56: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/56.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD32
Lamps and Gear
Looking at maintenance factors What influence does relamping period have?
Lighting Design - Why Maintenance Factors Matter
Clean room surfaces : 4 yearClean luminaires : 2 year
Group relamp : 2 yearMF : 0.79
L80 @ 40,000 hoursClean room surfaces : 4 yearClean luminaires : 2 yearSpot replacementMF : 0.72
L70 @ 50,000 hoursClean room surfaces : 4 yearClean luminaires : 2 yearSpot replacementMF : 0.69
Em 500 lxEinitial 633 lx
Em 500 lxEinitial 694 lx
Em 500 lxEinitial 725 lx
![Page 57: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/57.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors What influence does relamping period have – 2 years to 4 years?
0.69¦
0.69
0.79 T26@2¦
0.70 T26@4
![Page 58: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/58.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD32
Lamps and Gear
Looking at maintenance factors What influence does relamping period have?
Lighting Design - Why Maintenance Factors Matter
Clean room surfaces : 4 yearClean luminaires : 2 year
Group relamp : 4 yearMF : 0.70
L80 @ 40,000 hoursClean room surfaces : 4 yearClean luminaires : 2 yearSpot replacementMF : 0.72
L70 @ 50,000 hoursClean room surfaces : 4 yearClean luminaires : 2 yearSpot replacementMF : 0.69
Em 500 lxEinitial 714 lx
Em 500 lxEinitial 694 lx
Em 500 lxEinitial 725 lx
![Page 59: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/59.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors What influence does lamp technology have – T26 to T16?
0.79 T26@2¦
0.70 T26@4
0.70 T26@4¦
0.76 T16@4
![Page 60: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/60.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors What influence does luminaire cleaning interval have?
![Page 61: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/61.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors What influence does luminaire cleaning interval have?
0.76 T16@2¦
0.73 T16@4
0.69 LED@2¦
0.64 LED@4
![Page 62: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/62.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors COST
Clean room surfaces : 6 yearClean luminaires : 2 yearGroup relamp : 4 year
![Page 63: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/63.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors COST
Clean room surfaces : 6 yearClean luminaires : 4 yearGroup relamp : 4 year
~170
~80
![Page 64: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/64.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors Reducing installation life from 15 years
4x18W T8Clean room surfaces : 6 yearClean luminaires : 4 yearGroup relamp : 4 yearMaintenance factor 0.67
4x14W T16Clean room surfaces : 6 yearClean luminaires : 4 yearGroup relamp : 4 yearMaintenance factor 0.73
LED L70@50,000 hrsClean room surfaces : 6 yearClean luminaires : 4 yearSpot replacementMaintenance factor 0.64
LED L80@40,000 hrsClean room surfaces : 6 yearClean luminaires : 4 yearSpot replacementMaintenance factor 0.67
Em 500 lxEinitial 746 lx
Em 500 lxEinitial 685 lx
Em 500 lxEinitial 781 lx
Em 500 lxEinitial 746 lx
![Page 65: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/65.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors Reducing installation life from 15 years to 10 years
4x18W T8Clean room surfaces : 6 yearClean luminaires : 4 yearGroup relamp : 4 yearMaintenance factor 0.67
4x14W T16Clean room surfaces : 6 yearClean luminaires : 4 yearGroup relamp : 4 yearMaintenance factor 0.73
LED L70@50,000 hrsClean room surfaces : 6 yearClean luminaires : 4 yearSpot replacementMaintenance factor 0.72 (0.64@15)
LED L80@40,000 hrsClean room surfaces : 6 yearClean luminaires : 4 yearSpot replacementMaintenance factor 0.74 (0.67@15)
Em 500 lxEinitial 746 lx
Em 500 lxEinitial 685 lx
Em 500 lxEinitial 694 lx
Em 500 lxEinitial 676 lx
![Page 66: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/66.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors
Cleaning room surfaces more frequently makes little difference
However changing luminaire distribution does
Changing the luminaire cleaning interval has an impact
For conventional sources changing the lamp life has a large impact
The lifetime of LED cannot be over- extended
![Page 67: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/67.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors
So for sensible use of modern technology it really comes down to cost through life
![Page 68: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/68.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors
If I can reduce maintenance times I can save money – luminaire design!
![Page 69: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/69.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterLooking at maintenance factors
Accessibility will have a big influence on maintenance costs
![Page 70: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/70.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
Task visibility
Practical
Glare control
Energy Efficient
Managed
Colour
Modeling
Contrast
Effective
Atmosphere
Ambience
StimulatingSatisfaction
SafeErgonomic
Integrated
ColourfulHealthyInteresting
![Page 71: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/71.jpg)
Lighting Design - Why Maintenance Factors Matter · Peter Thorns © ZLD
Lighting Design - Why Maintenance Factors MatterWhat does a lighting design guarantee?
A design without....
-A maintenance factor
-Calculated according to a documented maintenance schedule
-Presented to the customer as part of the solution
....is a guess!
![Page 72: Lighting Design Why Maintenance Factors Matter](https://reader030.vdocuments.mx/reader030/viewer/2022032704/55cf8efc550346703b97bb07/html5/thumbnails/72.jpg)
Lighting Design - Why Maintenance Factors Matter