LIGHTING DESIGN CALCULATION DOCUMENT
1.SCOPE:
The scope of the calculation is to design the lighting for sea water in take pump house with the given
illumination level.
2.REFERENCE:
1.IS:3646-code of practice for illumination
2.Cromton greaves lighting catalouge
3.Sizing criteria as per CI.NO.B7.9.9 of contract technical specification no.B7.9-illumination system.
The Lighting calculation have been carried out for the following area in sea water in take pump house and
jetty based on the lux level requirement as tabulated below.
SI.no AREA REQUIRED LUX LEVEL
1 Switchgear room 200
2 UPS battery charger room 200
3 Battery room 150
4 Control equipment room 400
5 Engg.room 150
6 Operator station 200
7 Mobile cleaning device room 200
8 Pump room 200
9 Jetty 10
Maintenance factor
Control room and A/C rooms :0.75
Other areas :0.7
Height of the working plane
Central control room :0.85m
other areas :0.00m
pump room :0.00m
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Note:
1.The type fitting to be used are given below (cromtom greaves catalouge):
SI.no Area Type of fixture
1 Switchgear room (vitreous enameld) IGP1324EB(2X40W)
2 IPFC1124EB(2X36W)
3 Control equipment room(decorative type) CRFD24EB(2X36W)
4 IHB1325IH(250W)
5 Street light(HPSV) SSG1315IH(150W)
6 Stair case IGP1214EB+RVE14 (36W)
7 Emergency D.C lighting IBH1110BC
8 Toilets IGP1214EB+RVE14 (36W)
9 Approach Road IGP1214EB+RVE14 (36W)
3. FORMULA'S TO BE USED:L x B
Room Index =
(L + B)XH
Where
L = Length of area to be illuminated
B = Breadth of area to be illuminated
H = Mounting height of light fitting above working plane
L x B x IRNo.of Fittings (NC) =
LOxCOUxMFxLLD
Illumination level in lux,NR x COU x LO x MF x LLD
IL =L x B
Where
NC = No. of light fittings calculated
NR = No. of light fittings Recommended
IR = Illumination required
IL = Illumination level in lux
COU = Co-efficient of utilisation
LO = Lamp output in lumen
MF = Maintenance factor
LLD = Lamp lumen depreciation factor (for fluorescent lamps only)
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
UPS and battery charger,battery rom(corrosion proof)
Mobile cleaning device room(HPMV) and Pump room(HPMV )
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Sheet 2 of 7
Length of area to be illuminated
Breadth of area to be illuminated
Mounting height of light fitting above working plane
No. of light fittings calculated
No. of light fittings Recommended
Illumination required
Illumination level in lux
Co-efficient of utilisation
Lamp output in lumen
Maintenance factor
Lamp lumen depreciation factor (for fluorescent lamps only)
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Sheet 3 of 7
4.NO.OF FITTINGS CALCULATION
LIGHTING DESIGN CALCULATION AT SWITCHGEAR ROOM
AREA
11.6 12.89
8.18 5
4.25 4.25
4.25 4.25
Room index 1.13 0.85
Reflection factorCeiling 70 70
wall 50 50floor 10 10
0.49 0.43
Maintenance factor(MF) 0.7 0.7
200 200
capacity of lamp in watts 2X36 2X36
Type of fitting IGP1324HSB+RPC24 IGP1324HSB+RPC24
lamp output in lumens 4900 4900
No.of fittings calculated 12.55 9.71
13 10
207.24 205.96
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
SWITCH GEAR ROOM(PART-1)
SWITCH GEAR ROOM(PART- 2)
Length of the room(L in mtrs)
Breadth of the room(B in mtrs)
Height of room from FFL (in mtrs)
Mounting height above working plane(H in mtrs)
Co-efficient of utilisation(COU)
Recommended illumination (lux)
No. of fittings recommended
Actual illumination level based on estimation in lux.
Note : As the specification call for VE reflector, since the VE reflector are not in market Powder Coating(PC) reflector which are equivalent to VE reflector are used.
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Sheet 4 of 7
LIGHTING DESIGN CALCULATION AT BATTERY ROOM AND CHARGER ROOM
AREA BATTERY ROOM
Length of the room(L in mtrs) 5 3.5
Breadth of the room(B in mtrs) 1.987 3.3
Height of room from FFL (in mtrs) 4.25 4.25
4.25 4.25
Room index 0.33 0.4
Reflection factor
Ceiling 70 70
wall 50 50
floor 10 10
Co-efficient of utilisation(COU) 0.25 0.25
Maintenance factor(MF) 0.7 0.75
Recommended illumination (lux) 150 200
capacity of lamp in watts 2X36 2X36
Type of fitting IPFC1124EB IPFC1124EB
lamp output in lumens 5100 5100
No.of fittings calculated 1.86 2.68
No. of fittings recommended 2 3
161.7 223.54
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
UPS BATTERY CHARGER ROOM
Mounting height above working plane(H in mtrs)
Actual illumination level based on estimation in lux.
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Sheet 5 of 7
LIGHTING DESIGN CALCULATION AT CENTRAL CONTROL ROOM
AREA ENGG. ROOM OPERATOR STATION
Length of the room(L in mtrs) 4 3.31 5
3.31 2 4.95
7.5 7.5 7.5
4 4 4
Room index 0.45 0.31 0.62
Reflection factorCeiling 70 70 70
wall 50 50 50floor 10 10 10
0.32 0.32 0.4
Maintenance factor(MF) 0.75 0.75 0.75
400 150 200
capacity of lamp in watts 2X36 2X36 2X36
Type of fitting CRFD24EB CRFD24EB CRFD24EB
lamp output in lumens 4900 4900 4900
No.of fittings calculated 5 0.94 3.74
No. of fittings recommended 5 1 4
399.7 159.88 213.82
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
CONTROL EQUIPMENT ROOM
Breadth of the room(B in mtrs)
Height of room from FFL (in mtrs)
Mounting height above working plane(H in mtrs)
Co-efficient of utilisation(COU)
Recommended illumination (lux)
Actual illumination level based on estimation in lux.
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Sheet 6 of 7
LIGHTING DESIGN CALCULATION AT PUMP ROOM
AREA
Length of the room(L in mtrs) 8.18 11.6
Breadth of the room(B in mtrs) 7.8 6.7
7.2 13.75
6.4 12.82
Room index 0.62 0.33
Reflection factor
Ceiling 70 70wall 50 50floor 10 10
Co-efficient of utilisation(COU) 0.56 0.49
Maintenance factor(MF) 0.7 0.7
Recommended illumination (lux) 200 200
capacity of lamp in watts 250 250
Type of fitting IHB1325IH IHB1325IH
lamp output in lumens 13500 13500
No.of fittings calculated 2.41 3.36
No. of fittings recommended 3 4
248.82 238.32
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
SCREEN WASH PUMP AREA
SEA WATER PUMP ROOM
Height of room from FFL (in mtrs)
Mounting height above working plane(H in mtrs)
Actual illumination level based on estimation in lux.
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD.CONSULTING ENGINEERS
Sheet 7 of 7
5.SUMMARY OF THE FITTINGS
S.NO TYPE OF FITTING QUANTITY TOTAL WATTS
1 IGP1324HSB+RPC24 ( Switgear Room) 23 2X36
2 IPFC1124EB (Battery Room) 5 2X36
3 11 2X36
4 IHB1325IH ( Pump Room) 7 250
5 IHB1325IH ( Screen Wash Pump Area) 2 250
6 SSG1315IH (Approach Jetty) 18 150
7 IGP1214EB+RVE14 ( Staircase) 8 1x36
8 IGP1214EB+RVE14 (Cable Cellar Room) 2 1x36
9 IGP1214EB+RVE14 (Toilets) 4 1x36
10 2 1x36
11 IBH1110BC (Emergency D.C lights) 10 100
12 SSG1315IH (Approach Road in Jetty) 2 1x36
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty
DOC. NO. : 6104-EL-DSN-700-1009
CRFD24EB (Control Equipment Room(CER), Operator Station, Enginner Room, Entrance of CER)
IGP1214EB+RPC14 (Switchgear room Entrance, Entrance to CER from Screen Wash Area)
CHENNAI PETROLEUM CORPORATION LTD.5.8MGD DESALINATION PLANT