lead liberty series 1000 - c&d technologies home 1000 valve regulated lead-calcium battery for...
TRANSCRIPT
Telecom• CustomerPremise• Broadband• Wireless• PBX• Repeaters• FixedWireline• OutsidePlants• UndergroundBatteryVaults
LIBERTY® SERIES 1000VALVE REGULATED LEAD-CALCIUM BATTERY FOR STANDBY APPLICATIONS
Capacitiesfrom100to600Ampere-hours(8hoursto1.75VPC)343to2060Wattspercell(15minsto1.67VPC)
C&DTechnologiesvalveregulatedlead-acid(VRLA)batteriesareengineeredtoprovideperformancereliabilityandconsistencyoverthelifeoftheproduct.DesignedusingC&D’spatentedprocesses,these
productsofferlongbatterylifewithminimalmaintenance.TheversatileLiberty®Series100010-yearVRLAproductfitsvirtuallyanywhereandprovidessuperiorperformanceinthemostdemandingapplications.
SPECIFICATIONSElectrolyte at 77°F (25°C) 1.300specificgravitynominalsulfuricacid
System float voltages 2.25–2.27voltspercell
Life expectancy 10years,fullfloatserviceat77°F(25°C)
Container and cover High-impact,flame-retardantPVCFlammabilityratings:UL94-V0;ASTMD-635,self-extinguishingOxygenindex>32
Safety vent system Low-pressurereleasevalvewithflasharrester
Note:ACripplecurrentfromthechargershallnotexceed5percentofthe8hour(ampere-hour)ratingofthebattery.
UPS • DataCenters• NetworkOperationsCenters• IndustrialProcessControlFacilities• SemiconductorManufacturing• Banks&FinancialMarkets• PowerGenerationPlants• Hospital&TestingLaboratories• Emergency911responsecenters
Switchgear Utility• ElectricUtility• RailwaySignals• EmergencySystems• ManufacturingFacilities-AssemblyLines-ProcessControls• Petrochemicalprocessingplants• Pipelines
LEAD
RETURN
RECYCLE
ULRecognizedComponent
APPLICATIONS
12-373
12-373/0115/CD www.cdtechno.com
FEATURES & BENEFITS• Advanced,computer-controlledthermalcover-to-jarweldforgreaterreliabilityandconsistency
• Automated,state-of-the-art,cast-onstrapprocessensuresconsistent,high-quality,lowelectrical-resistancewelds
• Through-the-partitionintercellconnectionshortenscurrentpathsandincreasesperformance
• Copper-to-copperconnectionsminimizeresistance,especiallyathighrates,andshortenmaintenancetimebyreducingtheneedforretorquingconnections
• Patentedandtime-testedC&Dpostsealdesignwithsecondaryepoxysealtoincreaseintegrity -Leak-freeoperation -Superiorreliability
• Two-foldventsystem,comprisedofalow-pressuresafetyvalvewithflasharrester,minimizesbulgingandpreventsflashbackexplosionfromexternalignitionsource
• Thickradialgriddesignforbothpositiveandnegativeplatesimprovescurrentcarryingcapacityandperformanceresultinginlongfloatlife
• Fullyautomatedvacuumandfillingoperationresultsinuniformacidvolumedistributionandconsistentfloatvoltage
• Immobilizedelectrolytetechnologyusinganabsorbentglassmatdesign(AGM)offerssafehandlingandstorage
• Non-spillabledesignationforlowershippingcost•High-impactresistantPVCcontainerandcoverprovideexcellentwatervaporretention,preventingdryoutandoxygeninfiltration
MEASURABLE QUALITY AND OUTSTANDING PERFORMANCE• 100percentofcellstestedforconductance,voltageandcapacity
• TestedinaccordancewithBellcoreTR-NWT-000766specifications
• 100percentofcellstestedto95percentcapacityatthe8hourrateto1.75VPC
LS 12-100 LS 6-200 LS 4-300 LS 2-600*
Nominal voltage 12volts 6volts 4volts 2volts
Number of cells 6/unit 3/unit 2/unit 1/unit
Rated 8-hr to capacity (ampere-hours to 1.75 VPC)
100Ahto10.5volts
200Ahto5.25volts
300Ahto3.5volts
600Ahto1.75volts
Rated 15-min capacity (watts per cell to 1.67 VPC) 344 688 1030 2060
Internal resistance per cell 0.000786Ohms 0.000393Ohms 0.000262Ohms 0.000131Ohms
Short circuit current 2545A 5089A 7634A 15267A
Unit height 8.95in(227mm)
8.95in(227mm)
8.95in(227mm)
8.95in(227mm)
Unit length (includes handles)
16.58in(421mm)
16.58in(421mm)
16.58in(421mm)
16.58in(421mm)
Unit width 6.84in(174mm)
6.84in(174mm)
6.84in(174mm)
6.84in(174mm)
Weight 95lbs(43kg) 95lbs(43kg) 95lbs(43kg) 95lbs(43kg)
Plate thicknesspositive 0.140in
(3.56mm)
negative 0.085in(2.16mm)
Terminal characteristics
0.625indiameter,threadedcopperinsert,0.75indeep.Fastenwith1/4-20stainlesssteelhexbolt/washer.
*2cellsconnectedinparallelfor2-voltunits
SPECIFICATION
12-373/0115/CD 2 www.cdtechno.com
RATINGS IN AMPERES AT 77°F (25°C)
Final volts per cell
Reserve Time
Models 1 min 5 min 10 min 15 min 30 min 1 hr 2 hr 3 hr 4 hr 5 hr 6 hr 8 hr 10 hr 20 hr
1.95 LS12-100LS6-200LS4-300LS2-600
123.2246.5372.6739.4
115.1230.2348.5690.6
104.8209.5317.8628.6
94.6189.3287.6567.8
70.0140.1213.4420.2
45.791.4139.1274.2
28.156.385.5168.8
20.741.362.0124.0
16.332.749.098.0
13.527.040.581.0
11.623.134.769.3
9.118.127.254.3
7.515.022.545.0
4.18.312.424.8
1.90 LS12-100LS6-200LS4-300LS2-600
187.5374.9562.41124.7
169.4338.8508.21016.4
147.0293.9440.9881.8
126.8253.6380.4760.9
87.4174.9262.3524.6
55.5110.9166.4332.7
33.466.7100.1200.2
24.247.272.6145.1
19.038.157.1114.3
15.831.647.494.8
13.527.040.581.0
10.521.031.562.9
8.617.225.951.7
4.79.314.027.9
1.88 LS12-100LS6-200LS4-300LS2-600
216.1431.9616.21295.2
191.0382.3548.51148.3
161.5323.2467.9970.7
137.0273.9399.6820.2
93.0185.7273.0562.0
58.1113.5171.3350.9
34.869.7102.5208.0
25.250.474.3151.1
19.939.858.9119.5
16.533.049.099.1
14.228.342.184.7
11.022.132.965.8
9.118.127.153.9
4.89.714.428.3
1.85 LS12-100LS6-200LS4-300LS2-600
258.6517.1775.71551.4
224.2448.4672.61345.3
183.5367.0550.51100.9
151.9303.8455.8911.5
101.5203.0304.5609.0
62.4124.8187.3374.5
37.174.2111.3222.6
26.953.880.7161.4
21.242.463.6127.2
17.535.152.6105.3
15.030.044.989.9
11.623.234.869.6
9.519.028.456.9
5.09.914.929.7
1.84 LS12-100LS6-200LS4-300LS2-600
272.7545.4818.21636.4
233.9467.9701.81403.6
189.3378.6567.91135.8
155.8311.7467.5935.0
103.2206.5309.7619.4
63.3126.6189.8379.6
37.675.1112.9225.8
27.354.681.8163.6
21.643.264.4128.9
17.935.853.3106.6
15.330.645.590.9
11.923.835.270.4
9.719.528.757.4
5.110.215.030.0
1.80 LS12-100LS6-200LS4-300LS2-600
329.4658.8988.21976.5
272.4544.9817.31634.7
213.0426.0639.01278.0
171.7343.5515.21030.4
110.1220.1330.2660.3
67.0134.1201.1402.2
39.779.4119.2238.3
28.757.486.0172.1
22.545.167.6135.3
18.637.255.8111.6
15.831.747.595.1
12.224.536.773.5
10.020.029.959.9
5.210.415.631.2
1.78 LS12-100LS6-200LS4-300LS2-600
358.4716.51075.12149.6
284.2569.3852.51708.0
218.2435.1654.51305.3
175.3350.1525.91050.4
112.0224.5336.1673.4
68.0135.5204.0406.6
40.280.5120.7241.6
29.158.287.2174.6
22.845.768.5137.2
18.837.756.5113.2
16.132.148.296.4
12.424.837.274.4
10.120.230.360.6
5.310.515.831.5
1.75 LS12-100LS6-200LS4-300LS2-600
401.7803.51205.22410.4
302.2604.4906.51813.1
225.4450.7676.11352.2
180.3360.6540.91081.9
115.1230.1345.2690.4
69.4138.8208.2416.4
41.082.1123.1246.3
29.659.388.9177.8
23.346.669.9139.7
19.238.457.7115.3
16.432.749.198.2
12.625.037.575.0
10.320.630.961.9
5.410.716.132.2
Note:LibertySeries1000batteriesaretestedto95percentofpublishedratesattimeofshipmentat8hourrateto1.75VPC.AdditionalratingsandapplicationinformationisavailableintheBatterySelectionProgramatwww.cdstandbypower.net
12-373/0115/CD 3 www.cdtechno.com
RATINGS IN KW PER CELL AT 77°F (25°C)
Finalvoltspercell
ReserveTime
Models 1min 5min 10min 15min 20min 30min 1hr 3hr 5hr 8hr
1.95 LS12-100LS6-200LS4-300LS2-600
0.2400.4800.7201.440
0.2250.4510.6761.353
0.2070.4130.6201.239
0.1880.3750.5631.126
0.1700.3390.5091.017
0.1390.2790.4180.836
0.0910.1810.2720.544
0.0410.0830.1240.248
0.0280.0550.0830.165
0.0180.0370.0550.111
1.90 LS12-100LS6-200LS4-300LS2-600
0.3570.7131.0702.139
0.3240.6490.9731.946
0.2840.5680.8511.703
0.2470.4930.7401.480
0.2160.4310.6471.294
0.1720.3430.5151.030
0.1090.2190.3280.657
0.0480.0960.1440.289
0.0320.0630.0950.189
0.0210.0420.0630.126
1.85 LS12-100LS6-200LS4-300LS2-600
0.4790.9581.4362.873
0.4210.8421.2632.525
0.3490.6981.0472.094
0.2910.5810.8721.744
0.2490.4970.7461.492
0.1960.3920.5881.175
0.1220.2430.3650.729
0.0530.1060.1590.319
0.0350.0700.1050.209
0.0230.0460.0700.139
1.80 LS12-100LS6-200LS4-300LS2-600
0.5931.1861.7793.558
0.5021.0051.5073.015
0.3990.7991.1982.396
0.3240.6490.9731.946
0.2740.5480.8221.643
0.2110.4220.6331.265
0.1300.2600.3910.781
0.0560.1130.1690.338
0.0370.0730.1100.219
0.0240.0480.0720.145
1.75 LS12-100LS6-200LS4-300LS2-600
0.7031.4062.1094.218
0.5471.0941.6423.283
0.4160.8321.2492.497
0.3370.6731.0102.020
0.2840.5680.8531.705
0.2190.4380.6571.314
0.1340.2680.4020.804
0.0580.1160.1740.348
0.0380.0750.1130.226
0.0250.0500.0740.149
1.70 LS12-100LS6-200LS4-300LS2-600
0.8011.6022.4034.805
0.5751.1491.7243.448
0.4260.8531.2792.558
0.3430.6871.0302.060
0.2890.5790.8681.737
0.2220.4450.6671.335
0.1340.2680.4020.803
Notrecommendedtodischargelongerthan1hourbelow
1.75VPC.
1.67 LS12-100LS6-200LS4-300LS2-600
0.8571.7152.5715.143
0.5921.1861.7773.554
0.4360.8721.3092.618
0.3430.6871.0302.060
Notrecommendedtodischargelongerthan15min.below1.70VPC.
1.65 LS12-100LS6-200LS4-300LS2-600
0.8931.7872.6805.360
0.6031.2051.8083.615
0.4360.8731.3092.618
0.3440.6891.0332.067
1.63 LS12-100LS6-200LS4-300LS2-600
0.9291.8592.7885.576
0.6121.2231.8363.671
0.4370.8741.3102.620
0.3450.6911.0362.072
Note: LibertySeries1000batteriesaretestedto95percentofpublishedratesattimeofshipmentat8hourrateto1.75VPC.AdditionalratingsandapplicationinformationisavailableintheBatterySelectionProgramatwww.cdstandbypower.net
12-373/0115/CD 4 www.cdtechno.com
RACKSC&Disamajorsupplierofhigh-qualityVRLAbatteryrackstoTelecommunications,Switchgear&Control,andUPSmarkets.Bothstandardandmodularracksaredesignedandmanufacturedtosuitallcellconfigurations,includingmulti-rowandmulti-tierlayouts.C&Dracksmeetseismicloadingrequirements.ContactC&DTechnologiesforadditionalinformation.
Modular Rack
OPTIONAL ACCESSORIES
C&D’smodularracksprovideaflexible,efficientmethodforrackingLibertySeries1000batteries.Theseattractive,durableracksprovideaccessibilitytothebatteriesandareeasytoinstall.Racksareavailablein29inch(73.7cm)and43inch(109.2cm)lengthsandarestackable.Optionalpanelsareavailabletocompletelyencloseracks,providingacabinet-likeappearance.Pleasesee12-380formoreinformation.CompletestandbypowersystemsfromC&Dincludebatteries,racks,andelectronics.
Modular Rack with Panels
Steel JacketsFordemandingapplications,C&Dprovidesoptionalcomponentstoenhancebatterylife.Anoptionalsteeljacketisavailabletopreservejarshapeandmaintainelementcompressioninhigh-temperatureoperations.
Relay Rack Battery TraysC&Dmanufacturesawiderangeofbatterytraystomountin19inch(48.3cm)and23inch(58.4cm)relayracks.Pleasesee12-1064formoreinformation.
12-373/0115/CD 5 www.cdtechno.com
Copyright 2011 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-373 0115/CD
BATTERY CABINET SYSTEMSComplete,pre-packagedbatterycabinetsystemsareavailablefromC&DTechnologies.Systemsincludebatterybreakerorfuse,batterycablingandbatteries–allinstalledandreadytoconnecttoUPSuponinstallation.Optionsforbatterymonitoringwillalsobeavailable.
Powder-coatedsteelcabinetsareUL1778listedwithseismiczone4capabilityavailableasanoption.Fastactingfusesorcircuitbreakersareprovidedforsystemprotection.Batteriesaretestedtoassuresystemintegrity.
Mechanicalrobustness,approvedelectricaldisconnectsandhighqualityC&DbatteriesallcombinetoprovideaneasilyinstalledcompletebatterysystemwiththefinishedappearanceofaUPScabinet.