DRYCONTACTS
POWERRELAYS
CONTROLUNIT
120VAC
50-60 Hz
SENSOR PROBE
FAULT PUMP I
POWER RELAYS
HIGHWATER
120 VAC50-60 Hz
SUBMITTAL WLC-9100
Lead-Lag Duplex Pump Down with High Alarm(Total Dry Contacts)
PUMP II
POWERLOSS
HIGH WATER
POWERLOSS
HIGHWATER
PUMP I PUMP II
PUMP I PUMP II
Waterline ControlsP.O. Box 12544 Scottsdale, Arizona 85260Toll Free: 888-905-1892Email: [email protected]
LED INDICATORS(INTERNAL TO THE CONTROL UNIT)
DRY CONTACTS
FUNCTIONAL WIRING DIAGRAM
1
TO LOADS 120 VAC, 30 AMP, MAX.PUMP CONTACTORS,
AUDIBLE OR VISUAL ALARMS
60V MAX; 0.50AMP MAX.All others are 120 VAC 30AMPS Max.
9100 - 0405s16
-
POWERALARM
PUMP I HIGHALARM
PUMP II
TESTING
PRESS TO TEST
Green (Ground)
110 VACWhite
Black110VAC LOAD WIRING
WLC9100
MODEL BMS DRY CONTACTS POWER RELAYSELFTESTFAULT PUMP II PUMP I BASWIRES
HIGHALARM
X X X X X 8 X X X X X
LEADLAG
POWERLOSS
SUBMITTAL WLC 9100
HIGHALARM
PUMP II PUMP I
®
Waterline ControlsP.O. Box 12544 Scottsdale, Arizona 85260Toll Free: 888-905-1892Email: [email protected]
®
SENSORPROBE WIRES
{FAULT
FAU
LTB
LAC
KR
ED
WH
ITE
GR
EE
NB
RO
WN
COMMON
NO
NC
Red Pair
Pump II
COMMON
NO
NC
Brown Pair
Pump I
COMMON
NO
NC
High Alarm
Green Pair
PRODUCT FUNCTION TRUTH TABLE
Lead-Lag Duplex Pump Down with High Alarm
2 9100 - 040516
PUMPCONTACTORS
Bro
wn
PU
MP
IIB
row
n P
UM
P II
Gre
en
HIG
H A
LAR
MG
reen
H
IGH
ALA
RM
Red
PU
MP
IR
ed P
UM
P I
1 2 3 4 5 6 7
0.5 AMPS @ 60 VAC BUILDING AUTOMATION
LOW VOLTAGE DRY CONTACTS
RELAY RELAY RELAY
ALL RELAYS ARE TYPICALRELAY SPECIFICATIONSRated Load 30 A 250 VAC, 20 A 26 VDCCarry Current 30 A Max.Max.switching capacity 7,500 VA. 560 WAll Relay terminals are 1/4” male spade
220 VAC AVAILABLE UPON REQUEST
CONTROL UNIT RATINGS VOLTS: 110 VAC AMPS: 0.5 AMPS WATTS: 30W 50/60 HZ
-
50 ft. sensor wire
Sens
or L
ow V
olta
ge R
acew
ay
UP TO 8 WIRE DRYCONTACTSTO AUTOMATION SYSTEM - 2 for each function plus 2 for fault conditions. (see truth table for BAS wire quantities)
AC Power Input
Internal Relays (N.O.)are rated 30 amps at 250VAC.
Pump II
* See written specification for more details.
TESTING
PRESS TO TEST
* Contact the factory for Custom Sensor requirements.
Reference - BLACK
BROWNWHITE
RED
1. The 3" PVC Pipe needs to be at least 2" longer than the longest Sensor tip.2. Adjustment occurs by moving the 3" PVC Pipe up or down and tightening the
clamp so it rests on the Custom Fitting.
GREEN
High Level Alarm
SUBMITTAL WLC 9100
To Waste orReclaimed Tank
Pump to waste or reclaimed water
Relay in the Waterline Unit can be used as Pilot relaysto a 110 VAC coil for contactors properly rated for pump operation.
Pump Start II (Red)
Pump Stop II (White)
Sensor
5/8" Hole (2)
High Alarm (Green)
PUMP I
PUMP II
Pump II Control
®®
BLUE
3” Slip Coupler
3” PVC Pipe
Reference (Black) Pump Start I (Brown)
Pump Stop I (Blue)
3
POWERALARM
PUMP I HIGHALARM
PUMP II
9100 - 040516
Lead-Lag Duplex Pump Down with High Alarm
Waterline ControlsP.O. Box 12544 Scottsdale, Arizona 85260Toll Free: 888-905-1892Email: [email protected] • www.waterlinecontrols.com