© ABB Group October 16, 2009 | Slide 1
ABB SACECommunication Capability PortfolioLow voltage Breakers
L.B.U. Breakers & Switches Product Management
© ABB Group October 16, 2009 | Slide 2
Nuevo Emax: La evolución continúa
© ABB Group October 16, 2009 | Slide 3
Las Gamas – Interruptores automáticos
MORE
Nivel de prestaciones B N B N S L N S H V L S H V H V
Corriente permanente [A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 3200
nominal Iu [A] 1000 1000 2000 1250 1000 1600 3200 1250 1000 1250 2500 4000 4000 5000 4000
[A] 1250 1250 1600 1250 1600 1250 1600 6300 5000
[A] 1600 1600 2000 1600 2000 1600 2000 6300
[A] 2000 2500 2000 2500
[A] 3200 2500 3200
[A] 3200
Poder de corte
Icu @ 415 V AC [kA] 42 50 42 65 85 130 65 75 100 130 130 75 100 150 100 150
Icu @ 690 V AC [kA] 42 50 42 55 65 85 65 75 100 100 85 75 85 100 100 100
Ics @ 415 V AC [kA] 42 50 42 65 85 130 65 75 85 100 130 75 100 150 100 125
Ics @ 690 V AC [kA] 42 50 42 55 65 65 65 75 85 85 65 75 85 100 100 100
Poder de cierre
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 286 143 165 220 286 286 165 220 330 220 330
Icm @ 690 V AC [kA] 75,6 75,6 88,2 121 143 187 143 165 187 220 187 165 186 220 220 220
Corriente de corta duraciòn
Icw @ 1 s [kA] 42 50 42 55 65 10 65 75 75 85 15 75 100 100 100 100
Icw @ 3 s [kA] 36 36 42 42 42 - 65 65 65 65 - 75 75 75 85 85
Categorìa de utilizaciòn B B B B B A B B B B A B B B B B
E6E1 E2 E3 E4
© ABB Group October 16, 2009 | Slide 4
Nuevo Emax: Prestaciones
E2S: Icu=85 kA
@440 V AC
E3V: Icu=130 kA
@ 440 V AC
Instalación simpleAhora el control es
también remoto
© ABB Group October 16, 2009 | Slide 5
Nuevo Emax: Inteligencia brillante
Reles de protección
completamente nuevosRating plug Modularidad
Fallas:
ningún problema
© ABB Group October 16, 2009 | Slide 6
Relés de Protección
© ABB Group October 16, 2009 | Slide 7
Dialogue - a world of advantages
Los rele electrónicos de ABB SACE pueden ser equipados con
modulos de comunicación
Comunicación en los diferentes protocolos industriales
Amplio rango de caracteristicas y variables.
Protocolo de base: Modbus RTU
Integration con otros protocolos de comunicación Profibus-DP,
DeviceNet
Posibilidad de comunicación Bluetooth
© ABB Group October 16, 2009 | Slide 8
Dialogue - a world of advantages
Las redes de comunicación pueden ser usadas para leer toda la información
disponible en el rele de protección, desde cualquier localidad conectado al bus y en
tiempo real
CB status: open/closed, opened by protection release trip
CB position: racked-in, test isolated, racked-out
measurements: currents, voltages, power, energy …
alarms and pre-alarms from the protection release
fault currents
complete settings of the protection releases
number of operations performed by the CB
estimate of the residual life of the CB
measurement history
trip history
© ABB Group October 16, 2009 | Slide 9
Dialogue - a world of advantages
Los CBs con opción de communication puede ser facilmente integrado con
sistemas de automatización y supervisión
Supervision of the installation with continuous data logging
Event logging (alarms, faults, trip logs)
Predictive maintenance based on number of operations,
interrupted currents and estimate of residual equipment life
Load schedding and demand side management
© ABB Group October 16, 2009 | Slide 10
Dialogue - New Emax
NEW Emax releases series
The new concept of modularity
More functions and more flexibility
PR122/P
PR123/P
PR120/D-M
© ABB Group October 16, 2009 | Slide 11
The ABB solution for bus communication
Air circuit breakers Emax E1-E6: PR122/P
PR120/D-M: Communication module for connetting Emax to Modbus network
YO: Shunt opening release
M: Motor for charging the closing springs
YC: Shunt closing release
© ABB Group October 16, 2009 | Slide 12
The ABB solution for bus communication
Air circuit breakers Emax E1-E6: PR122/P + PR120/V
PR120/V: Measurement module (installed in PR122/P-standard in PR123/P)
PR120/D-M: Communication module for connetting Emax to Modbus network
YO: Shunt opening release
M: Motor for charging the closing springs
YC: Shunt closing release
© ABB Group October 16, 2009 | Slide 13
The ABB solution for bus communication
Air circuit breakers Emax E1-E6: PR123/P
PR120/V: Measurement module (installed in PR122/P-standard in PR123/P)
PR120/D-M: Communication module for connetting Emax to Modbus network
YO: Shunt opening release
M: Motor for charging the closing springs
YC: Shunt closing release
© ABB Group October 16, 2009 | Slide 14
Dialogue - Modbus
PR122/P characteristicsCommunication functions
Protocol Modbus RTU
Physical layer RS485
Maximum baud-rate 19200 bps
Measuring functions
Phase currents
Neutral current
Ground current
Voltage (phase-phase, phase-neutral, residual)
Power (active, reactive, apparent)
Power factor
Frequency and peak factor
Energy (active, reactive, apparent)
Signalling functions
LED: auxiliary power supply, warning, alarm
Temperature
Indication for L, S, I, G and other protection
Available data
Circuit-breaker status (open, closed)
Circuit-breaker position (racked-in, racked-out)
Mode (local, remote)
Protection parameters set
Load control parameters
Events
Status changes in circuit-breaker, protections and
all alarms
Alarms
Protection L
Protection S
Protection I
Protection G
Protection T
Fault release mechanism failure
Undervoltage, overvoltage and residual voltage (timing
and trip) protection
Reverse power protection (timing and trip)
Directional protection (timing and trip)
Underfrequency/overfrequency protection (timing and trip)
Maintenance
Total number of operations
Total number of trips
Number of trip tests
Number of manual operations
Number of separate trips for each protection function
Contact wear (%)
Record data of last trip
Operating mechanisms
Circuit-breaker openi/close
Alarm reset
Setting of curves and protection thresholds
Synchronize system time
© ABB Group October 16, 2009 | Slide 15
Dialogue - Modbus
PR123/P characteristicsCommunication functions
Protocol Modbus RTU
Physical layer RS485
Maximum baud-rate 19200 bps
Measuring functions
Phase currents
Neutral current
Ground current
Voltage (phase-phase, phase-neutral, residual)
Power (active, reactive, apparent)
Power factor
Frequency and peak factor
Energy (active, reactive, apparent)
Harmonic analisys up to the 40th harmonic
Signalling functions
LED: auxiliary power supply, warning, alarm
Temperature
Indication for L, S, I, G and other protection
Available data
Circuit-breaker status (open, closed)
Circuit-breaker position (racked-in, racked-out)
Mode (local, remote)
Protection parameters set
Load control parameters
Events
Status changes in circuit-breaker, protections and
all alarms
Alarms
Protection L
Protection S
Protection I
Protection G
Protection T
Fault release mechanism failure
Undervoltage, overvoltage and residual voltage (timing
and trip) protection
Reverse power protection (timing and trip)
Directional protection (timing and trip)
Underfrequency/overfrequency protection (timing and trip)
Phases rotation
Maintenance
Total number of operations
Total number of trips
Number of trip tests
Number of manual operations
Number of separate trips for each protection function
Contact wear (%)
Record data of last trip
Operating mechanisms
Circuit-breaker openi/close
Alarm reset
Setting of curves and protection thresholds
Synchronize system time
© ABB Group October 16, 2009 | Slide 16
The ABB solution for bus communication
© ABB Group October 16, 2009 | Slide 30
Dialogue - EP010
For all new series
the universal evolution
To be open to all the protocols
EP010
© ABB Group October 16, 2009 | Slide 31
The FBP solution for Profibus DP and DeviceNet
The ABB solution for bus communication
© ABB Group October 16, 2009 | Slide 32
The ABB solution for bus communication
Air circuit breakers Emax E1-E6
EP010: Modbus/Field Bus Plug interface
PDP-22 FBP: PROFIBUS DP fieldbus interface
DNP-21 FBP: DeviceNet fieldbus interface
© ABB Group October 16, 2009 | Slide 36
BACK
Dialogue - Modbus
EP010 characteristics
No auxiliary supply needed - Real plug&play device
Communication functions
Protocol via FBP Profibus, Devicenet
Measuring functions
Phase currents
Neutral current
Ground current
Signaling functions
LED: auxiliary power supply, warning, alarm
Temperature
Indication for L, S, I, G and other protection
Available data
Circuit-breaker status (open, closed)
Operating mode (local, remote)
Protection parameters set
Events
Status changes in circuit-breaker, protections and all
alarms
Alarms
Protection L
Protection S
Protection I
Protection G
Release mechanism failure
Maintenance
Total number of operations
Total number of trips
Separate number of trips for each protection function
Record currents of last trip
Commands
Circuit-breaker open/close
Trip reset
Circuit-breaker reset
Setting of curves and protection thresholds (coming soon)
© ABB Group October 16, 2009 | Slide 37
Dialogue – Bluetooth/USB
ABB SACE SpA is the only manufacturer on the market that can provide the wireless
communication via Bluetooth for the electronic trip units.
Two version of Bluetooth module available
- Internal module PR120/D-BT WL
- External module BT030-USB
The Bluetooth Connection
© ABB Group October 16, 2009 | Slide 38
SD-TestBus2
“Ahora la configuración es remota”
Usted puede obtener grandes beneficios a través de los altos
niveles de conectividad posibles: El New Emax puede ser
comunicado a su Palm o Laptop utilizando la tecnología
Bluetooth
Full configuración
Diagnóstico
Estados de alarma
Estados de trip
Medidas
Histórico de medidas
Estadísticas de mantención
Comando
© ABB Group October 16, 2009 | Slide 39
SD-TestBus2
SD-TestBus2 ofrece una gran flexibilidad en la configuración de los parámetros de sus interruptores automáticos Tmax,
New Emax y Emax X1
Configurar las protecciones de un interruptor nunca ha sido tan fácil como hasta ahora. Usted tiene acceso a todos los
parámetros directamente.
© ABB Group October 16, 2009 | Slide 43