k:1 jobjob 40412dc1416 unlv bhs cadaver labmg1.01 g1.01 (1) · 2019. 12. 21. · 125v. grounded...
TRANSCRIPT
E0.01
ELECTRICAL
LEGEND
AND
SPECIFICATIONS
E0.01 ELECTRICAL LEGEND AND SPECIFICATIONS
E1.01 ELECTRICAL FLOOR PLANS AND DETAILS
E1.02 ELECTRICAL ROOF PLANS AND DETAILS
1. DIMENSIONS INDICATED ARE TO CENTERLINE OF DEVICE
OR OUTLET FROM FINISHED FLOOR OR FINISHED GRADE.
2. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT.
AAMPERE(S)
GROUND FAULT CIRCUIT INTERRUPTER
HORSEPOWER
RECEPTACLE
THERMOSTAT
SWITCHBOARD
NORMALLY CLOSED
SINGLE POLE DOUBLE THROW
WEATHERPROOF
JUNCTION BOX
NATIONAL ELECTRICAL CODE
NORMALLY OPEN
TRANSFORMER
AIR CONDITIONING
AMERICAN WIRE GAUGE
CIRCUIT BREAKER
DOUBLE POLE DOUBLE THROW
COPPERCU
EXISTINGEXIST
4W
F
FUT
FOUR WIRE
FUTURE
FUSE
EF
ELEC
EM
EQUIP
CW
DN
DPDT
EXHAUST FAN
ELECTRIC
EQUIPMENT
EMERGENCY
COLD WATER
DOWN
AWG
CAB
CKT BKR
CLG
C
BC
BKBD
BLDG
CABINET
CEILING
CONDUIT
BARE COPPER
BACKBOARD
BUILDING
ANN
AUTO
AMP
ABV
A/C
AL
ANNUNCIATOR
AUTOMATIC
AMPERE
ABOVE
ALUMINUM
VOLT(S)
W
WP
WATT(S)
SWBD
T-STAT
TEL
V
XFMR
RM
SPDT
STR
TELEPHONE
ROOM
STARTER
J-BOX
RECEPT
NO
NEC
PNL
LTG
NC
MTR
PANEL
LIGHTING
MOTOR
GFCI
HP
GRD GROUND
PANEL BOARD OR CABINET
FUSIBLE SWITCH
CIRCUIT BREAKER
COMPUTER/DATA OUTLET @ +18"
TELEPHONE OUTLET @ +18"
TRANSFORMER, TYPE AND SIZE
AS NOTED (DIAGRAMMATIC)
THERMOSTAT
TIME CLOCK
ELECTRIC MOTOR, HP SCRIBED INSIDE
TRANSFORMER (IN PLAN)
CIRCUIT HOMERUN
SELF CONTAINED SMOKE DETECTOR
DUCT SMOKE DETECTOR
MECHANICAL EQUIPMENT DESIGNATION
SHUNT TRIP ELEMENT
JUNCTION BOX, MOUNTING AS REQUIRED, SIZE PER NEC.
NO SLASHES = 2#12, NUMBER OF SLASHES = NUMBER OF
CONDUCTORS OTHER THAN 2
WIRING IN FLOOR SLAB OR UNDERGROUND
WIRING CONCEALED IN WALL OR CEILING
JUNCTION BOX WALL MOUNTED, SIZE PER NEC.
SWITCHBOARD OR MOTOR CONTROL CENTER
COMBINATION MOTOR STARTER AS NOTED ON PLANS.
CONTACTOR, DESCRIPTION AS NOTED ON PLANS
SAFETY SWITCH, F SCRIBED INSIDE INDICATES FUSIBLE
BOX AROUND SYMBOL INDICATES FLUSH FLOOR OUTLET
COMBINATION VOICE/DATA OUTLET @ +18"
COMBINATION EXIT SIGN/EMERGENCY LIGHTING UNIT
EMERGENCY LIGHTING UNIT WITH TWIN HEADS
WITH TWIN HEADS
EXIT SIGN, SHADED QUADRANT INDICATES LIGHTED FACE
POLE MOUNTED LIGHT FIXTURE
UPPER CASE LETTER INDICATES FIXTURE TYPE, LOWER CASE
LETTER INDICATES SWITCHING GROUP
WALL MOUNT LIGHT FIXTURE
RECESSED WALL WASHER OR DIRECTIONAL LIGHT FIXTURE
RECESSED LIGHT FIXTURE
FLUORESCENT STRIP FIXTURE
PLUGMOLD MULTIOUTLET SYSTEM, WIRING AND OUTLET
CONFIGURATION AS NOTED ON PLANS.
BOX AROUND SYMBOL INDICATES FLUSH FLOOR OUTLET
HALF-SWITCHED OR TWO CIRCUIT
SPECIAL PURPOSE RECEPTACLE AS NOTED
50A, 250V RANGE RECEPTACLE
GFCI TYPE DUPLEX RECEPTACLE
SPLIT-WIRED DUPLEX RECEPTACLE @ +18"
SINGLE RECEPTACLE, CLOCKHANGER TYPE @ +78"
ISOLATED GROUND TYPE DUPLEX RECEPTACLE
FLUORESCENT LIGHT FIXTURE
ON PLANS
@ +18"
T
C
H
M
D
D
PC
T
S
TC
S
T
PHOTOCELL
PUSHBUTTON SWITCH
DOUBLE DUPLEX RECEPTACLE @ +18"
DUPLEX RECEPTACLE @ +18"
TIME CYCLE WITH OWNER
DUAL SLIDE TYPE FAN SPEED/LIGHT
LEVEL CONTROL SWITCH
AUTO SHUT-OFF TIMER SWITCH, VERIFY
SWITCH WITH OVERLOAD ELEMENT
SINGLE POLE MANUAL MOTOR STARTER
AND LOAD TYPE AS REQUIRED OR INDICATED
SINGLE POLE LOCK TYPE SWITCH @ +46"
FOUR WAY WALL SWITCH @ +46
SINGLE POLE SWITCH WITH PILOT LIGHT @ +46"
THREE WAY WALL SWITCH @ +46
SINGLE POLE WALL SWITCH @ +46"
SINGLE POLE SLIDE TYPE DIMMER, RATING
J
J
0
0
0
0
Approved By
File Name:
Drawn By
Date:
Checked By
Consultant Project No.
-
DRAWING TITLE :
REVISIONS :
SEAL:
CONSULTANT:
NO. DATE ISSUE
PR
OJE
CT
:
SIGMA'S Project No.
412DC1416
187 E
. W
arm
S
prings R
oad, S
uite A
Las V
egas, N
V 89119 (702) 315-4272
En
gin
ee
rin
g C
on
su
lta
nts
Sig
ma
M
ec
ha
nic
al
UN
LV
B
HS
C
AD
AV
ER
LA
B E
XP
AN
SIO
N
CONSTRUCTION
10.20.2016
NR NRHM
UNLESS OTHERWISE SPECIFIED, ALL WIRE SHALL BE TYPE THWN, THHN, OR XHHW.
ALL WIRING SHALL BE COPPER.
THE WIRES SHALL BE MARKED WITH COLOR TO SIMPLIFY CIRCUIT IDENTIFICATION.
UNLESS OTHERWISE REQUIRED BY LOCAL ORDINANCES EQUIPMENT GROUND CONDUCTORS SHALL
BE GREEN. GROUNDED CONDUCTOR SHALL BE WHITE (120V) AND GREY (277V) AND UNGROUNDED
CONDUCTORS SHALL BE BLACK (PHASE A), RED PHASE B), AND BLUE (PHASE C) FOR 208Y/120V.
SYSTEM; AND BROWN (PHASE A), ORANGE (PHASE B) AND YELLOW (PHASE C) FOR 480Y/277V.
SYSTEM.
THE WIRE SHALL BE #12 AWG UNLESS OTHERWISE INDICATED.
NO WIRE SHALL BE INSTALLED IN THE CONDUIT SYSTEM UNTIL THE CONDUIT SYSTEM IS COMPLETE.
USE MINERALAC #100 OR EQUIVALENT AS A LUBRICANT TO FACILITATE THE INSTALLATION OF THE
CONDUCTORS IN THE CONDUIT SYSTEM.
FUSES SHALL BE OF THE TYPE, SIZE, AND RATING AS INDICATED ON THE DRAWINGS.
ALL FUSES SHALL BE BY BUSSMAN MFG. COMPANY, OR GOULD SHAWMUT.
VERIFY FUSE AND SWITCH REQUIREMENTS WITH THE EQUIPMENT SUPPLIED.
SAFETY SWITCHES, UNLESS OTHERWISE INDICATED ON THE DRAWINGS, SHALL BE HEAVY DUTY TYPE,
600 OR 240 VOLT, OF THE NUMBER OF POLES REQUIRED. SAFETY SWITCHES FOR AIR CONDITIONING
USE SHALL BE OF THE FUSIBLE TYPE WHERE RECOMMENDED BY EQUIPMENT MANUFACTURER. THE
SWITCH
SIZE SHALL BE AS REQUIRED BY CODE AND AS INDICATED ON THE DRAWINGS. WHERE OUTSIDE THE
BUILDING, THE SWITCHES SHALL BE RAINTIGHT TYPE NEMA 3R. ALL SWITCHES SHALL BE LOCKABLE.
ALL SAFETY SWITCHES SHALL HAVE A PROVISION, BY THE MANUFACTURER, FOR AN EQUIPMENT
GROUNDING CONDUCTOR SO THAT ALL NON CURRENT CARRYING METAL IS BONDED.
ALL SAFETY SWITCH ENCLOSURES OR COVERS SHALL BE IDENTIFIED BY A PERMANENT MEANS,
APPROVED BY THE JURISDICTION. SPECIFYING SOURCE PANEL, BREAKER, AND SYSTEM VOLTAGE.
SWITCHES: WALL SWITCHES SHALL BE COMMERCIAL SPECIFICATION GRADE AC SILENT TYPE
SWITCHES,
20A. 120/277 VOLTS. SINGLE POLE SWITCHES SHALL BE HUBBELL CS120I OR APPROVED EQUAL. 3-WAY
SWITCHES SHALL BE HUBBELL CS320I OR APPROVED EQUAL.
RECEPTACLES: SHALL BE INDUSTRIAL SPECIFICATION GRADE, DUPLEX TYPE, NEMA 5-20R, 20 AMPERE,
125V. GROUNDED TYPE. OUTLETS SHALL BE HUBBELL 5362I OR APPROVED EQUAL. SPECIAL
APPLICATION RECEPTACLES SHALL BE AS INDICATED ON PLANS.
GFCI RECEPTACLES: SHALL BE INDUSTRIAL SPECIFICATION GRADE, NEMA 5-20R, HUBBELL GFR5362.
WEATHERPROOF RECEPTACLES: SHALL BE HUBBELL WP26 WITH GFCI RECEPTACLE OUTLET OR
EQUAL.
DEVICE PLATES SHALL BE SMOOTH IVORY NYLON.
ALL WIRING DEVICES SHALL HAVE A PROVISION, BY THE MANUFACTURER, FOR AN EQUIPMENT
GROUNDING CONDUCTOR SO THAT ALL NON CURRENT CARRYING METAL IS BONDED TO THE GROUND
ELECTRODE SYSTEM.
FURNISH AND INSTALL A COMPLETELY WIRED AND OPERATIONAL ELECTRICAL SYSTEM AS SHOWN ON THE
DRAWINGS AND SPECIFIED HEREIN, INCLUDING BUT NOT LIMITED TO, THESE MAJOR ITEMS.
1. DISCONNECT AND REMOVE EXISTING EXHAUST FAN DISCONNECT SWITCH, RECEPTACLES AND DATA
OUTLET.
2. ELECTRICAL CONTROLS, DISCONNECTS, CONDUIT, WIRING, ETC. FOR INSTALL NEW EXHAUST FANS,
RECEPTACLES AND DATA OUTLETS.
3. PROVIDE CONNECTION TO FIRE SMOKE DAMPERS.
THE INSTALLATION SHALL COMPLY WITH APPLICABLE LOCAL AND STATE CODES AND ORDINANCES, WITH
THE REGULATIONS OF THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE AND WITH THE
REQUIREMENTS OF THE POWER AND TELEPHONE COMPANIES FURNISHING SERVICES TO THIS
INSTALLATION.
THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS AND CODES ARE MINIMUM REQUIREMENTS:
1. THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION STANDARDS.
2. THE NATIONAL ELECTRICAL CODE, LATEST ADOPTED EDITION.
3. UNDERWRITER LABORATORIES INCORPORATED STANDARDS.
4. AMERICAN NATIONAL STANDARDS INSTITUTE.
5. THE INTERNATIONAL BUILDING CODE, LATEST ADOPTED EDITION.
KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS, OR RUBBISH CAUSED BY
EMPLOYEES OR WORK UNDER THIS DIVISION OF THE SPECIFICATIONS. AT THE COMPLETION OF THE
WORK, REMOVE ALL SURPLUS MATERIALS, TOOLS, ETC., AND LEAVE THE PREMISES "BROOM-CLEAN" AND DUST
FREE.
DELIVER MATERIALS AND EQUIPMENT TO THE PROJECT IN THE MANUFACTURER'S ORIGINAL, UNOPENED,
LABELED CONTAINERS. PROTECT AGAINST MOISTURE, TAMPERING, OR DAMAGE FROM IMPROPER
HANDLING OR STORAGE. CONTRACTOR SHALL PROTECT AND BE RESPONSIBLE FOR ANY DAMAGE TO WORK
OR MATERIALS UNTIL FINAL ACCEPTANCE BY THE OWNER AND SHALL MAKE GOOD WITHOUT COST TO THE
OWNER ANY DAMAGE OR LOSS THAT MAY OCCUR DURING THIS PERIOD.
ARRANGE FOR TIMELY DELIVERY OF MATERIALS AND EQUIPMENT TO THE JOB SITE IN ORDER TO
MINIMIZE THE LENGTH OF TIME BETWEEN DELIVERY AND INSTALLATION.
COVER AND PROTECT ANY MATERIAL WHICH MAY BE AFFECTED BY THE WEATHER WHILE IN TRANSIT OR
STORED AT THE PROJECT SITE. ANY MATERIAL FOUND DEFECTIVE OR NOT INSTALLED IN ACCORDANCE
WITH THE CONTRACT DOCUMENTS MAY BE REJECTED BY THE ENGINEER.
PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK THE CONTRACTOR SHALL VISIT THE SITE OF THE
PROPOSED CONSTRUCTION AND SHALL THOROUGHLY ACQUAINT HIMSELF WITH EXISTING UTILITIES AND
WORKING CONDITIONS, ETC. TO BE ENCOUNTERED. ALLOWANCE WILL NOT BE MADE FOR NONCOMPLIANCE
WITH THIS CONDITION AFTER BIDDING.
GUARANTEE ALL MATERIAL FURNISHED AND ALL WORKMANSHIP PERFORMED FOR A PERIOD OF ONE
YEAR
FROM THE DATE OF FINAL ACCEPTANCE OF THE WORK. ANY DEFECTS DEVELOPING WITHIN THIS
PERIOD, TRACEABLE TO MATERIAL FURNISHED AS A PART OF THIS SECTION OR WORKMANSHIP
PERFORMED HEREUNDER, SHALL BE MADE GOOD AT NO EXPENSE TO THE OWNER.
ALL EQUIPMENT SHALL BE WIRED TO CONFORM WITH MANUFACTURERS RECOMMENDATIONS AND
WITH
APPLICABLE CODES. REVIEW MANUFACTURER'S WIRING DIAGRAMS AND PROVIDE ALL NECESSARY
WIRING, CONDUIT, FITTINGS, DISCONNECT SWITCHES/FUSES, MOTOR STARTER, CONTROL WIRING
ETC. FOR A COMPLETE AND OPERATIONAL SYSTEM. VERIFY EQUIPMENT LOCATION AND ELECTRICAL
REQUIREMENTS WITH THE TRADE SUPPLYING THE EQUIPMENT BEFORE INSTALLING THE CONDUIT
AND WIRING.
CONTRACTOR SHALL BE RESPONSIBLE FOR THE FOLLOWING REQUIREMENTS AS THEY RELATE TO THE
WORK
PERFORMED UNDER THIS SECTION OF THE SPECIFICATION.
1. ALL FIRE-RATED ASSEMBLY PENETRATIONS SHALL COMPLY WITH IBC REQUIREMENTS..
2. ALL THRU AND MEMBRANE FIRE-RATED ASSEMBLY PENETRATIONS SHALL UTILIZE LISTED
FIRESTOP
SYSTEMS THAT MAINTAIN THE RATING OF THE WALL, FLOOR OR CEILING PENETRATED. FIRESTOP
SYSTEMS SHALL BE PROPERLY INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
RMC AND IMC MAY BE USED IN ALL AREAS. EMT MAY BE USED IN INDOOR LOCATIONS NOT IN CONTACT
WITH EARTH, NOT IN CONCRETE SLAB OR WALLS AND NOT SUBJECT TO DAMAGE. UNDERGROUND CONDUIT
SHALL BE SCHEDULE 40 PVC WITH PROPERLY CEMENTED JOINTS. FMC SHALL BE USED FOR FINAL
CONNECTION TO MECHANICAL EQUIPMENT NOT TO EXCEED 36" AND TO RECESSED REMOVABLE LIGHTING
FIXTURES NOT TO EXCEED 72". FMC SHALL NOT BE USED EXCEPT AS NOTED. LIQUIDTITE FMC SHALL BE
USED FOR FINAL CONNECTION TO MOTORS IN OUTDOOR LOCATIONS. MC CABLE MAY NOT BE USED IN THIS
PROJECT. EMT FITTINGS SHALL BE OF THE COMPRESSION TYPE, RMC AND IMC FITTINGS SHALL BE
THREADED TYPE (NO EXCEPTION). ALL CONDUIT RUNS SHALL BE INSTALLED PARALLEL AND
PERPENDICULAR TO BUILDING STRUCTURES. ALL EMPTY CONDUIT SYSTEMS SHALL HAVE 200 LB. TEST
PULL CORD TO FACILITATE INSTALLATION OF WIRE IN FUTURE. CONDUITS AND OUTLETS SHALL BE
CONCEALED WITHIN THE BUILDING STRUCTURE; EXCEPT THAT CERTAIN MOTOR AND LIGHTING FEEDER
CONDUITS MAY BE RUN EXPOSED IN CERTAIN AREAS AS INDICATED ON THE DRAWINGS. CONDUIT SHOWN
TO BE INSTALLED IN CABINETS, COUNTERS, AND CASEWORK SHALL BE INSTALLED AS DIRECTED BY THE
ARCHITECT.
ALL MATERIALS SHALL BE NEW AND OF QUALITY AS SPECIFIED ON THE PLANS OR SPECIFICATIONS AND
MUST CARRY THE UNDERWRITER'S LABORATORIES APPROVAL COVERING THE PURPOSE FOR WHICH THEY
ARE USED, IN ADDITION TO MEETING ALL REQUIREMENTS OF THE CURRENT APPLICABLE CODES AND
REGULATIONS.
COOPERATE WITH THE OTHER TRADES SO THAT THE INSTALLATION OF THE ELECTRICAL OUTLETS AND
EQUIPMENT WILL BE PROPERLY COORDINATED. CONDUIT, FIXTURES, AND OTHER EQUIPMENT LOCATIONS
SHALL BE CHECKED WITH THE OTHER TRADES TO AVOID CONFLICT WITH THE PIPING, DUCTWORK,
STEEL, BEAMS, OR OTHER OBSTRUCTIONS.
CAREFULLY CHECK THE LOCATIONS OF THE OUTLET BOXES AND DETERMINE THAT THEY HAVE NOT BEEN
DISTURBED DURING THE INSTALLATION OF MATERIALS OF OTHER TRADES.
COORDINATE THE LOCATION OF TRENCHES AND CONDUITS FOR ELECTRIC AND TELEPHONE UTILITY
SERVICES WITH THE GENERAL CONTRACTOR.
PERFORM THE CUTTING, FITTING, REPAIRING AND FINISHING OF THE WORK NECESSARY FOR THE
INSTALLATION OF THE EQUIPMENT OF THIS SECTION. HOWEVER, NO CUTTING OF THE WORK OF OTHER
TRADES OR OF ANY STRUCTURAL MEMBER SHALL BE DONE WITHOUT THE CONSENT OF THE ARCHITECT.
EACH SWITCH, LIGHT, RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED WITH A CODE GAUGE,
GALVANIZED STEEL OUTLET BOX. JUNCTION BOXES SHALL BE CODE GAUGE, GALVANIZED STEEL.
OUTLET BOXES SHALL BE OF THE ONE PIECE, KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER
RING. PLASTER RINGS SHALL BE SET TO PROVIDE NOT MORE THAN 1/8" FROM WALL SURFACE TO
RING. IN NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE OF WALL. SINGLE GANG RINGS
SIMILAR TO STEEL CITY 52050 SHALL BE USED FOR 4" BOXES IN UNFINISHED BRICK. #180 BOXES
MAY BE USED FOR UNFINISHED MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK
COURSE. ALL BOXES SHALL BE IDENTIFIED BY A PERMANENT MEANS, APPROVIED BY THE JURISDICTION.
SPECIFY SOURCE PANEL, BREAKER, AND SYSTEM VOLTAGE.
THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT AND LOCATIONS OF THE ELECTRICAL WORK. DATA
PRESENTED ON THESE DRAWINGS ARE AS ACCURATE AS PLANNING CAN DETERMINE, BUT FIELD
VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC, TO SUIT FIELD CONDITIONS IS
REQUIRED. REVIEW ALL ARCHITECTURAL, STRUCTURAL AND MECHANICAL DRAWINGS AND ADJUST ALL
WORK TO MEET THE REQUIREMENTS OF CONDITIONS SHOWN. THE ARCHITECTURAL DRAWINGS SHALL TAKE
PRECEDENCE OVER ALL OTHER DRAWINGS. DISCREPANCIES BETWEEN DIFFERENT PLANS, OR BETWEEN
DRAWINGS AND SPECIFICATION, OR REGULATIONS AND CODES GOVERNING THE INSTALLATION SHALL BE
BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE THE DATE OF BID OPENING. IF
DISCREPANCIES ARE NOT REPORTED, THE CONTRACTOR SHALL BID THE GREATER QUANTITY OR BETTER
QUALITY, AND APPROPRIATE ADJUSTMENTS WILL BE MADE AFTER CONTRACT AWARD. CONTRACTOR SHALL
BE RESPONSIBLE TO FIELD MEASURE AND CONFIRM MOUNTING HEIGHTS AND LOCATION OF ELECTRICAL
EQUIPMENT WITH RESPECT TO COUNTERS, RADIATION, ETC. DO NOT SCALE DISTANCES OFF THE
ELECTRICAL DRAWINGS. USE ACTUAL BUILDING DIMENSIONS.
IN ALL CASES SWITCHES CONTROLLING LIGHTING ARE TO BE LOCATED ON THE STRIKE SIDE OF DOORS.
LOCATION INDICATED FOR SWITCHES AND OUTLETS ARE APPROXIMATE. OWNER MAY MAKE MINOR
RELOCATIONS AT NO ADDITIONAL CHARGE.
Approved By
File Name:
Drawn By
Date:
Checked By
Consultant Project No.
-
DRAWING TITLE :
REVISIONS :
SEAL:
CONSULTANT:
NO. DATE ISSUE
PR
OJE
CT
:
SIGMA'S Project No.
412DC1416
187 E
. W
arm
S
prings R
oad, S
uite A
Las V
egas, N
V 89119 (702) 315-4272
En
gin
ee
rin
g C
on
su
lta
nts
Sig
ma
M
ec
ha
nic
al
UN
LV
B
HS
C
AD
AV
ER
LA
B E
XP
AN
SIO
N
CONSTRUCTION
10.20.2016
NR NRHMApproved By
File Name:
Drawn By
Date:
Checked By
Consultant Project No.
-
DRAWING TITLE :
REVISIONS :
SEAL:
CONSULTANT:
NO. DATE ISSUE
PR
OJE
CT
:
SIGMA'S Project No.
412DC1416
187 E
. W
arm
S
prings R
oad, S
uite A
Las V
egas, N
V 89119 (702) 315-4272
En
gin
ee
rin
g C
on
su
lta
nts
Sig
ma
M
ec
ha
nic
al
UN
LV
B
HS
C
AD
AV
ER
LA
B E
XP
AN
SIO
N
CONSTRUCTION
10.20.2016
NR NRHM
EXISTING TO REMAIN(E)
EXISTING TO BE RELOCATED(R)
EXISTING TO BE REMOVED(X)
HALF SHADE FIXTURE INDICATES EMERGENCY LIGHT
FIXTURE OR UNSWITCHED NIGHT LIGHT
CHIME
1
2
( EMERGENCY RED)
3
4
( EMERGENCY RED)
( EMERGENCY RED)
5
4
3
FSD
FSD
FSD
FSD FSD
FSD
6
6
6
Approved By
File Name:
Drawn By
Date:
Checked By
Consultant Project No.
-
DRAWING TITLE :
REVISIONS :
SEAL:
CONSULTANT:
NO. DATE ISSUE
PR
OJE
CT
:
SIGMA'S Project No.
412DC1416
187 E
. W
arm
S
prings R
oad, S
uite A
Las V
egas, N
V 89119 (702) 315-4272
En
gin
ee
rin
g C
on
su
lta
nts
Sig
ma
M
ec
ha
nic
al
UN
LV
B
HS
C
AD
AV
ER
LA
B E
XP
AN
SIO
N
CONSTRUCTION
10.20.2016
NR NRHM
E1.01
ELECTRICAL DEMOLITION PLAN- 2ND FLOOR
SCALE: 1/8" = 1'-0"
1
E1.01
KEY NOTES:
#
ELECTRICAL
FLOOR
PLANS AND
DETAILS
GENERAL NOTES:
ELECTRICAL PLAN- 2ND FLOOR
SCALE: 1/8" = 1'-0"
2
E1.01
1. REMOVE RECEPTACLES AND PORTION WIRING TO ABOVE CEILING
AND PREPARE FOR EXTEND TO NEW LOCATION.
2. REMOVE DATA WIRING BACK TO SOURCE. REMOVE PORTION OF
CONDUIT TO ABOVE CEILING AND PREPARE FOR EXTENSION TO
NEW LOCATION.
3. PROVIDE NEW RECEPTACLES ABOVE COUNTER AND CONNECT TO
EXISTING CIRCUITS AS SHOWN.
4. PROVIDE NEW DATA OUTLET ABOVE COUNTER. PROVIDE NEW CAT
6 CABLE FROM EXISTING IDF ROOM. VERIFY LOCATION.
5. PROVIDE NEW RECEPTACLE IN WALL FOR COMPUTER MONITOR.
MATCH MOUNTING HEIGHT WITH MONITOR IN ROOM 214. CONNECT
TO EXISTING RECEPTACLE CIRCUIT IN ROOM. VERIFY FIELD
LOCATION WITH OWNER'S REPRESENTATIVE.
6. PROVIDE CONNECTION TO FIRE SMOKE DAMPERS (FSD) . SEE
MECHANICAL PLANS FOR EXACT QUANTITIES AND LOCATIONS.
INTERCONNECT TO EXISTING FIRE ALARM PANEL. EXISTING FIRE
ALARM PANEL IS NOTIFIER AND IS LOCATED IN LOBBY AT 1
ST
FLOOR. ALL WORK RELATED TO FIRE ALARM SYSTEM SHALL BE
PERFORMED BY LICENSED FIRE ALARM CONTRACTOR AUTHORIZED
TO WORK ON THE EXISTING SYSTEM.
1. CONTRACTOR SHALL VISIT THE BUILDING SITE, TAKE HIS OWN MEASUREMENTS
AND OBTAIN SUCH OTHER INFORMATION AS MAY BE NECESSARY FOR HIS WORK.
NO ALLOWANCES WILL SUBSEQUENTLY BE MADE FOR ANY ERROR OR OMISSION
ON THE PART OF THE CONTRACTOR IN THIS REGARD.
2. FURNISH ALL MATERIALS AND TEMPORARY LIGHTS AND WIRING REQUIRED
DURING CONSTRUCTION OF THE PROJECT FOR ALL TRADES THAT REQUIRE
POWER. COMPLY WITH OSHA AND NEC REQUIREMENTS.
3. REMOVE ALL ABANDONED OR UNUSED OUTLETS, CONDUIT AND CONDUCTORS
THAT RESULT FROM THE WORK OF THIS PROJECT. WHERE SUCH CONDUITS AND
OUTLETS CAN NOT BE REMOVED, PULL OUT CONDUCTORS AND PROVIDE BLANK
COVERS FOR OUTLET BOXES. PROVIDE KNOCKOUT CLOSURES OR SHEET METAL
COVERS FOR ALL UNUSED BOX OR EQUIPMENT OPENINGS.
4. CONTRACTOR SHALL COORDINATE ALL POWER OUTAGES WITH OWNER'S
REPRESENTATIVE. OBTAIN PERMISSION AT LEAST SEVEN (7) DAYS BEFORE
PARTIAL OR COMPLETE POWER OUTAGES.
5. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT EQUIPMENT LOCATIONS PRIOR
TO BEGINNING WORK.
6. IN THE EVENT OF CONFLICTS BETWEEN THE DRAWINGS AND THE
SPECIFICATIONS, CONTRACTOR SHALL BID THE SUPERIOR QUALITY AND
GREATER QUANTITY.
7. CONTRACTOR SHALL REFER TO THE PROJECT MANUAL, ARCHITECTURAL,
MECHANICAL AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS FOR THIS PROJECT.
8. CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS AND FOR THE SCHEDULING OF WORK.
9. PROVIDE NEW NAMEPLATES FOR ELECTRICAL EQUIPMENT FEEDING NEW
EQUIPMENT THAT RESULTS FROM THE WORK OF THIS PROJECT. NAMEPLATES
SHALL BE ENGRAVED MICARTA AND SHALL BE MECHANICALLY SECURED USING
RIVET ATTACHMENT, NOT GLUED.
10. FINAL CONNECTIONS TO ALL EQUIPMENT SHALL BE PER MANUFACTURER'S
APPROVED WIRING DIAGRAMS, DETAILS AND INSTRUCTIONS. IT SHALL BE THE
CONTRACTORS RESPONSIBILITY TO VERIFY REQUIREMENTS AND PROVIDE
MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY
SUPPLIED.
11. THE CONTRACTOR SHALL PATCH AND PAINT DAMAGED AREAS AS REQUIRED TO
MATCH EXISTING SURFACES. THE CONTRACTOR SHALL REPLACE ANY CEILING
TILES THAT ARE DAMAGED DURING CONSTRUCTION.
12. NO CONDUIT SHALL BE INSTALLED ON ROOF. ALL CONDUITS SHALL BE
INSTALLED BELOW ROOF AND PENETRATE THRU ROOF WITHIN EQUIPMENT
CURB. NO EXCEPTION.
(E)ACID PERCHLORIC - FAN
(E)EF-2
(E)EF-3
(E)EF-5
(E)EF-4
EF
1
(E) MOTOR CONTROL
CENTER "EMCCB"
1
11
(E)EF-2
(E)EF-3
(E)EF-5
(E)EF-4
6
(E)ACID PERCHLORIC - FAN
EF
1-1
EF
1-2
6
(E) MOTOR CONTROL
CENTER "EMCCB"
(N) VFDs
8
(N) CTRL CAB
9
(E) CTRL CAB
11
10
EMCCB
11
EMCCB
11
( ALT. BID-1)
(BASE BID)
12
12
Approved By
File Name:
Drawn By
Date:
Checked By
Consultant Project No.
-
DRAWING TITLE :
REVISIONS :
SEAL:
CONSULTANT:
NO. DATE ISSUE
PR
OJE
CT
:
SIGMA'S Project No.
412DC1416
187 E
. W
arm
S
prings R
oad, S
uite A
Las V
egas, N
V 89119 (702) 315-4272
En
gin
ee
rin
g C
on
su
lta
nts
Sig
ma
M
ec
ha
nic
al
UN
LV
B
HS
C
AD
AV
ER
LA
B E
XP
AN
SIO
N
CONSTRUCTION
10.20.2016
NR NRHM
E1.02
ELECTRICAL DEMOLITION PLAN- ROOF
SCALE: 1/8" = 1'-0"
2
E1.02
KEY NOTES:
#
ELECTRICAL
ROOF
PLANS AND
DETAILS
GENERAL NOTES:
ELECTRICAL PLAN- ROOF
SCALE: 1/8" = 1'-0"
3
E1.02
1. DISCONNECT AND REMOVE EXISTING EXHAUST FAN DISCONNECT
SWITCH IN PREPARATION FOR REMOVAL OF EQUIPMENT BY
OTHERS.
2. REMOVE EXISTING MI CABLE AND ALL ASSOCIATED SPLICES
SUPPORTS ETC COMPLETE.
3. REMOVE ALL WIRING (POWER AND CONTROL) FROM MOTOR
STARTER. REMOVE ALL IDENTIFICATION LABELS AND PROVIDE NEW
LABEL READING "SPARE" .
4. PROVIDE NEW 2-HR FIRE RESISTIVE RATED WIRING SYSTEM
CONSISTING OF TYPE RHW/RHH CABLE AND CONDUIT INSTALLED IN
ACCORDANCE WITH CABLE MANUFACTURER'S STRICT
INSTALLATION REQUIREMENTS TO ACHIEVE THE 2-HR FIRE
RESISTIVE RATING. INSTALLATION SHALL COMPLY WITH NEC
ARTICLE 700.
5. EXISTING SPARE FUSIBLE SWITCH. PROVIDE NEW FRSR TYPE
FUSES AS SHOWN. PROVIDE NEW LABEL IDENTIFYING EQUIPMENT
SERVED.
6. CONNECT TO NEW EXHAUST FANS THRU VENDOR PROVIDED
DISCONNECT SWITCH. ROOF PENETRATION SHALL BE WITHIN
EQUIPMENT ROOF CURB. NO EXCEPTION.
7. ENTIRE WIRING SHALL BE INSTALLED IN INTERSTITIAL SPACE
ABOVE CEILING. FINAL CONNECTION TO EQUIPMENT SHALL BE
DONE WITHIN EQUIPMENT ROOF CURB. DO NOT INSTALL ANY
CONDUIT ON ROOF TOP. NO EXCEPTION.
8. VFD PROVIDED BY MECHANICAL CONTRACTOR. INSTALLED AND
WIRED BY ELECTRICAL CONTRACTOR. FIELD VERIFY EXACT
LOCATION WITH OWNER'S REPRESENTATIVE PRIOR TO ROUGH IN.
9. NEW CONTROLS CABINET. CONNECT TO SAME CIRCUIT FEEDING
EXISTING CONTROL CABINETS. VERIFY LOCATION WITH
CONTROLS/MECHANICAL CONTRACTOR.
10. PROVIDE 3/4"C FOR CONTROL WIRING FOR MOTORIZED DAMPERS.
VERIFY REQUIREMENTS WITH CONTROLS/MECHANICAL
CONTRACTOR.
11. SEE ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.
12. PROVIDE PRICING FOR BASE BID AND ALT. BID-1. REFER TO
MECHANICAL PLANS FOR ADDITIONAL INFORMATION.
1. CONTRACTOR SHALL VISIT THE BUILDING SITE, TAKE HIS OWN MEASUREMENTS
AND OBTAIN SUCH OTHER INFORMATION AS MAY BE NECESSARY FOR HIS WORK.
NO ALLOWANCES WILL SUBSEQUENTLY BE MADE FOR ANY ERROR OR OMISSION
ON THE PART OF THE CONTRACTOR IN THIS REGARD.
2. FURNISH ALL MATERIALS AND TEMPORARY LIGHTS AND WIRING REQUIRED
DURING CONSTRUCTION OF THE PROJECT FOR ALL TRADES THAT REQUIRE
POWER. COMPLY WITH OSHA AND NEC REQUIREMENTS.
3. REMOVE ALL ABANDONED OR UNUSED OUTLETS, CONDUIT AND CONDUCTORS
THAT RESULT FROM THE WORK OF THIS PROJECT. WHERE SUCH CONDUITS AND
OUTLETS CAN NOT BE REMOVED, PULL OUT CONDUCTORS AND PROVIDE BLANK
COVERS FOR OUTLET BOXES. PROVIDE KNOCKOUT CLOSURES OR SHEET METAL
COVERS FOR ALL UNUSED BOX OR EQUIPMENT OPENINGS.
4. CONTRACTOR SHALL COORDINATE ALL POWER OUTAGES WITH OWNER'S
REPRESENTATIVE. OBTAIN PERMISSION AT LEAST SEVEN (7) DAYS BEFORE
PARTIAL OR COMPLETE POWER OUTAGES.
5. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT EQUIPMENT LOCATIONS PRIOR
TO BEGINNING WORK.
6. IN THE EVENT OF CONFLICTS BETWEEN THE DRAWINGS AND THE
SPECIFICATIONS, CONTRACTOR SHALL BID THE SUPERIOR QUALITY AND
GREATER QUANTITY.
7. CONTRACTOR SHALL REFER TO THE PROJECT MANUAL, ARCHITECTURAL,
MECHANICAL AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS FOR THIS PROJECT.
8. CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS AND FOR THE SCHEDULING OF WORK.
9. PROVIDE NEW NAMEPLATES FOR ELECTRICAL EQUIPMENT FEEDING NEW
EQUIPMENT THAT RESULTS FROM THE WORK OF THIS PROJECT. NAMEPLATES
SHALL BE ENGRAVED MICARTA AND SHALL BE MECHANICALLY SECURED USING
RIVET ATTACHMENT, NOT GLUED.
10. FINAL CONNECTIONS TO ALL EQUIPMENT SHALL BE PER MANUFACTURER'S
APPROVED WIRING DIAGRAMS, DETAILS AND INSTRUCTIONS. IT SHALL BE THE
CONTRACTORS RESPONSIBILITY TO VERIFY REQUIREMENTS AND PROVIDE
MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY
SUPPLIED.
11. THE CONTRACTOR SHALL PATCH AND PAINT DAMAGED AREAS AS REQUIRED TO
MATCH EXISTING SURFACES. THE CONTRACTOR SHALL REPLACE ANY CEILING
TILES THAT ARE DAMAGED DURING CONSTRUCTION.
12. NO CONDUIT SHALL BE INSTALLED ON ROOF. ALL CONDUITS SHALL BE
INSTALLED BELOW ROOF AND PENETRATE THRU ROOF WITHIN EQUIPMENT
CURB. NO EXCEPTION.
EF
1
30/3
9 AF
SIZE 1
(E) MOTOR CONTROL CENTER 'EMCCB', 480V, 3PH, 3W,
EF
1-1
30/3
15 AF
PARTIAL ONE-LINE DIAGRAM
SCALE: NONE
1
E1.02
30/3
15 AF
(E) EF-1
(5 HP)
(N) EF-1-1
(7.5 HP)
2
3
3#12,
1#12,
(RHW/RHH)
3/4"C.
4
5
(N) EF-1-2
(7.5 HP)
EF
1-2
1
7
(E) 12/4
MI CABLE
6 6
5
(N) VFD
3#12,
1#12,
(RHW/RHH)
3/4"C.
4
8
3#12,
1#12,
(RHW/RHH)
3/4"C.
4 7
(N) VFD
3#12,
1#12,
(RHW/RHH)
3/4"C.
4
8
(BASE BID) (ALT. BID-1)
12 12