johnson engineering, inc. tallahassee fort myers, …
TRANSCRIPT
GULF
OF
MEXICO
LEE COUNTY
COLLIER COUNTY
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
01
TALLAHASSEE
CHIPLEY
PANAMA CITY
KEY WEST
SARASOTA
FT MYERS
FT. PIERCE
DAYTONA BEACH
ST AUGUSTINE
GAINESVILLE
OCALA
BARTOW
TAMPA
ORLANDO
DELAND
LAKE CITYJACKSONVILLE
LAKEOKEECHOBEE
WEST PALM BEACH
FT. LAUDERDALE
PENSACOLA
LOCATION MAP
DESIGN CONSULTANT
CONSTRUCTION PLANSWASTEWATER PUMP STATION
REPAIR AND RENOVATIONPUMP STATION 312.27
COLLIER COUNTY UTILITIES
COLLIER COUNTY, FLORIDA
Cover
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
VICINITY MAP
*SEE PLAN SHEET NOTES AND ELECTRICAL PLAN
SHEET MATRIX ON SHEET 02 - Notes & Legends
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
Sheet List Table
Sheet Number Sheet Title
01 Cover
02
Notes & Legends
Site Plan
03
Existing
04 Demolition
05
Proposed
06
Offsite Improvements
Collier County Utility Detail: Pump Station Details
D-01 1 of 2
D-02 2 of 2
Electrical Plans
E-01
Electrical Improvements
ISSUED FOR CONSTURCTION
RE
VIS
IO
N P
ER
S
DP
I R
EV
IE
WE
R C
OM
ME
NT
S
1
1
1
2
3
RE
VIS
IO
N P
ER
S
DP
I R
EV
IE
WE
R C
OM
ME
NT
S
02
03/24/21
BID
A
DD
EN
DU
M #2
03
06/02/21
03/24/21
01
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
02
ABBREVIATIONS
COLLIER COUNTY UTILITIES STANDARD DETAIL NOTES: Notes & Legends
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
VICINITY MAP
PS 312.27
SEE SHEETS 03-05
EAGLE
FLAMINGO
GOLDFINCH
BOB WHITE
IBIS
LAY LN.
SU
NS
HIN
E B
LV
D.
S
U
N
S
H
I
N
E
B
L
V
D
.
LE
E B
UT
TS
B
LV
D.
BECK BLVD.
E
V
E
R
G
L
A
D
E
S
P
K
W
Y
(T
O
L
L
R
O
A
D
)
E
V
E
R
G
L
A
D
E
S
P
K
W
Y
W
H
IT
E
L
A
K
E
B
L
V
D
.
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
OFF SITE VALVE IMPROVEMENT
SEE SHEET 06
GENERAL NOTES:
1. ALL ELEVATIONS REFER TO NORTH AMERICA VERTICAL DATUM (N.A.V.D.) OF 1988. CONVERSION FROM N.A.V.D. TO N.G.V.D. FOR THIS
AREA, + 1.28 FT.
2. VEHICULAR AND PEDESTRIAN TRAFFIC SHALL BE MAINTAINED DURING CONSTRUCTION. THE CONTRACTOR SHALL SUBMIT A VEHICULAR
AND PEDESTRIAN MOT PLAN.
3. ALL COLLIER COUNTY UTILITY DEPARTMENT STANDARD DETAILS AND SPECIFICATIONS (UTILITY STANDARDS) ARE APPLICABLE TO
PROJECT AND ARE MADE A PART OF THE CONTRACT DOCUMENTS BY REFERENCE TO CURRENT 2015 COUNTY UTILITIES STANDARDS. IN
THE EVENT OF CONFLICT BETWEEN THE COUNTY UTILITIES STANDARD MANUAL AND THESE SPECIFICATIONS AND DRAWINGS, THE
MORE STRINGENT REQUIREMENT SHALL APPLY.
4. THE LOCATIONS OF EXISTING UTILITIES AND STORM SEWERS SHOWN ON THIS PLAN HAVE BEEN TAKEN FROM RECORD DRAWINGS AND
FIELD INFORMATION AND ARE APPROXIMATE ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THEIR EXACT LOCATION
PRIOR TO CONSTRUCTION AND PROVIDE IN WRITING ANY DISCREPANCIES TO THE ENGINEER.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY DURING CONSTRUCTION TO PROTECT ANY EXISTING UTILITIES.
6. THE CONTRACTOR IS REQUIRED TO CONTACT ALL UTILITY OWNERS PRIOR TO THE BEGINNING OF CONSTRUCTION AND COORDINATE WITH
UTILITY OWNERS DURING CONSTRUCTION.
7. EXISTING FACILITIES SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN WHAT EXISTED PRIOR TO COMMENCING
CONSTRUCTION, AT NO ADDITIONAL COST TO OWNER.
8. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REPLACE ANY EXISTING LANDSCAPING (I.E. SOD, BUSHES, TREES, PAVERS, ETC.),
SPRINKLER PIPING, SPRINKLER HEADS AND FENCING THAT MAY HAVE BEEN REMOVED OR HAS BEEN DAMAGED DURING CONSTRUCTION.
CONTRACTOR TO REPLACE OR REPAIR ANY DAMAGED PROPERTY OR IMPROVEMENTS TO A CONDITION EQUAL TO OR BETTER THAN
EXISTED PRIOR TO CONSTRUCTION.
9. ALL DRIVEWAYS, SIDEWALK, AND OTHER EXISTING FACILITIES, UTILITIES, AND IMPROVEMENTS SHALL BE RESTORED EQUAL TO
PRE-CONSTRUCTION CONDITIONS OR BETTER AND TO THE SATISFACTION OF THE OWNER.
10. ANY PROPERTY CORNER WITHIN THE LIMITS OF CONSTRUCTION IS TO BE PROTECTED. IF A CORNER MONUMENT IS IN DANGER OF BEING
DISTURBED THE CONTRACTOR SHALL PROPERLY REFERENCE ITS LOCATION TO BE RESET BY THE CONTRACTOR'S FLORIDA LICENSED
SURVEYOR, ANY SURVEY MONUMENTS AND PRIVATE PROPERTY CORNER DISTURBED BY CONSTRUCTION ACTIVITIES SHALL BE REPLACED
BY THE CONTRACTOR AT HIS OWN COST.
11. THE CONTRACTOR IS REQUIRED TO ADJUST ALL VALVE BOXES, MANHOLE RIMS, GRATES, ETC. AS NECESSARY TO MATCH PROPOSED
GRADES.
12. DAMAGE TO EXISTING UTILITIES AND PROPERTY DURING CONSTRUCTION SHALL BE REPAIRED AND/OR REPLACED AT CONTRACTOR
EXPENSE.
13. THE CONTRACTOR SHALL PROVIDE 72 HOURS WRITTEN NOTICE TO THE ENGINEER OF RECORD, OWNER'S CEI REPRESENTATIVE, AND
COLLIER COUNTY PROJECT MANAGER PRIOR TO THE FOLLOWING ACTIVITIES:
a. COMMENCEMENT
b. CHANGES TO APPROVED SCHEDULES, SUBCONTRACTORS, AND RESIDENT SUPERINTENDENT
c. TESTING AND COMMISSIONING OF BYPASS PUMP SYSTEM
d. TEMPORARY AND PERMANENT FORCEMAIN PRESSURE TESTS
e. PUMP STATION START-UP
14. THE CONTRACTOR SHALL NOTIFY COLLIER COUNTY UTILITIES DEPARTMENT AT LEAST THREE FULL WORK DAYS IN ADVANCE OF ALL
PLANNED SERVICE INTERRUPTIONS, AND RECEIVE COUNTY PROJECT MANAGER'S APPROVAL BEFORE PROCEEDING WITH PLANNED
INTERRUPTIONS.
15. SHOP DRAWINGS FOR ANY EQUIPMENT AND MATERIAL MUST BE APPROVED PRIOR TO FABRICATION AND INSTALLATION.
16. CONTRACTOR SHALL RETAIN, ON THE WORK SITE, COPIES OF ALL PERMITS NECESSARY FOR CONSTRUCTION.
17. CONTRACTOR IS REQUIRED TO OBTAIN FROM THE ENGINEER OF RECORD AND COUNTY PROJECT MANAGER WRITTEN APPROVAL FOR ANY
DEVIATIONS FROM THE PLANS AND/OR SPECIFICATIONS.
18. CONTRACTOR SHALL PROMPTLY REPORT ALL FIELD CHANGES TO THE ENGINEER OF RECORD AND CEI REPRESENTATIVE.
19. CONTRACTOR WILL BE RESPONSIBLE FOR STORING ALL MATERIALS FOR THE PROJECT INCLUDING ALL MATERIALS PURCHASED BY
COLLIER COUNTY IN SECURE STORAGE AREA.
20. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING UTILITY SERVICE AT ALL TIMES DURING CONSTRUCTION WITHIN THE PROJECT LIMITS.
THIS INCLUDES HAVING A SUPPLY OF REPAIR MATERIALS ONSITE THAT MATCHES EXISTING IN THE EVENT OF A BREAK.
21. CONTRACTOR WILL BE EXPECTED TO PROVIDE A TWO (2) WEEK LOOK AHEAD FOR ALL CONSTRUCTION ACTIVITIES AND ATTEND WEEKLY
OR BI-WEEKLY MEETINGS AT THE COUNTY'S DISCRETION.
22. CONTRACTOR SHALL NOT LEAVE TRENCHES OR HOLES OPEN OVERNIGHT OR OVER WEEKENDS.
23. ALL CONSTRUCTION DEBRIS AND OTHER WASTE MATERIAL SHALL BE DISPOSED OF OFFSITE IN ACCORDANCE WITH APPLICABLE
REGULATIONS.
24. WORK AREAS ARE TO BE CLEANED ON A DAILY BASIS.
25. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING RIGHT-OF-WAY, TREE REMOVAL, AND DEWATERING PERMITS IF REQUIRED.
26. ACCESS ONTO EXISTING STREETS AND DRIVES SHALL BE MAINTAINED TO LOCAL TRAFFIC AND PROPERTY OWNERS, RESPECTIVELY.
CONTRACTOR SHALL LIMIT CONSTRUCTION ACTIVITIES ON PUBLIC OR PRIVATE ROADWAYS.
27. THE CONTRACTOR SHALL FURNISH TO THE ENGINEER RECORD DRAWINGS CERTIFIED BY A FLORIDA LICENSED LAND SURVEYOR AND
MAPPER. THE INFORMATION SHALL DEPICT THE AS-BUILT LOCATION OF ALL IMPROVEMENTS, INCLUDING, BUT NOT LIMITED TO, CONDUITS,
PIPING, CONCRETE PAD LIMITS AND DIMENSIONS, BOLLARD POSTS, PANEL LIMITS AND DIMENSIONS, GRAVEL AND SOD LIMITS, EQUIPMENT
LIMITS AND DIMENSIONS, WIRING DIAGRAMS, ETC.
Site Plan
Existing
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
03
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
PICTURE #1 PICTURE #2 PICTURE #3
PICTURE #4 PICTURE #5 PICTURE #6
PICTURE #7
PICTURE #8
PICTURE #9 PICTURE #10
PICTURE #11 PICTURE #12
P
IC
#
1
P
IC
#2
P
IC
#
3
P
IC
#8
PIC
#4
P
IC
#5
P
IC
#6
PIC
#7
P
I
C
#
1
0
P
IC
#
1
1
P
I
C
#
1
2
S
U
N
R
IS
E
B
L
V
D
.
GOLDFITCH
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
1
RE
VIS
IO
N P
ER
S
DP
I R
EV
IE
WE
R C
OM
ME
NT
S01
03/24/21
1
1
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
04
Site Plan
Demolition
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
DEMOLITION NOTES:
1. CONTRACTOR TO DEMOLISH, REMOVE, AND DISPOSE OF HOOKS, SUBMERSIBLE PUMPS,
RAILS, DISCHARGE RISER PIPES, VALVE VAULT, VAULT PIPING AND VALVES, CHAINS AND
OTHER MISC. WET WELL COMPONENTS.
2. SAW CUT EXISTING CONCRETE PAD AND REMOVE PORTION SOUTH OF WET WELL. SAW
CUT TO HAVE TOOLED EDGE.
3. WET WELL TOP, HATCHES, PVC VENT PIPE, AND VERTICAL WET WELL CYLINDRICAL
SECTIONS TO REMAIN.
4. CONTROL PANEL AND ENCLOSURES TO REMAIN.
5. CONTRACTOR TO MAINTAIN WASTEWATER SERVICE VIA BYPASS PUMPING DURING ALL
DEMOLITION AND CONSTRUCTION.
6. CONTRACTOR SHALL REPLACE AND RESTORE ANY LANDSCAPE OR HARDSCAPE
DISTURBED DURING CONSTRUCTION.
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
2.50'
1
RE
VIS
IO
N P
ER
S
DP
I R
EV
IE
WE
R C
OM
ME
NT
S01
03/24/21
1
1
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
05
Site Plan
Proposed
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
PUMP STATION IMPROVEMENT NOTES:
1. PUMP STATION TO BE CONSTRUCTED PER THE CURRENT COLLIER
COUNTY UTILITIES DESIGN STANDARDS AND DETAILS.
2. ALL ABOVE GROUND PIPING TO BE HDPE DR 11 DIPS.
3. FUSION LOG SHALL BE PROVIDED FOR EVERY JOINT. SEE
TECHNICAL SPECIFICATIONS FOR JOINT FUSION LOG
REQUIREMENTS.
4. ABOVE GROUND CHECK VALVES AND PLUG VALVES TO BE PAINTED
GREEN.
5. BELOW GROUND VALVE CAPS TO BE PAINTED GREEN.
6. CONCRETE VALVE PADS FOR BELOW GROUND VALVES TO HAVE
TAGS PER CURRENT COUNTY STANDARDS.
7. SEE ELECTRICAL SHEETS FOR ELECTRICAL IMPROVEMENTS
8. NO FENCE OR GATE IS PROPOSED.
9. WET WELL FLOOR SHALL BE LEVEL AND FLAT USING WET WELL
PROTECTIVE LINER.
10. H-TECH ARV REQUIRED.
11. SEE OFF SITE IMPROVEMENTS SHEET 06.
BYPASS PUMPING NOTES:
1. CONTRACTOR TO PROVIDE BYPASS PUMPING WHILE PUMP
STATION IS OFF LINE.
2. CONTRACTOR MAY UTILIZE EXISTING MANHOLE FOR BYPASS
PUMPING.
3. REQUIRED CAPACITY FOR BYPASS PUMPING IS APPROXIMATELY
175 GPM @ 56 FT, NAVD HGL.
4. CONTRACTOR TO INSTALL PUMP OUT CONNECTION DOWNSTREAM
OF VALVE VAULT FOR BYPASS PUMPING.
SEE SHEETS D-01-D-02 FOR
PUMP STATION 312.27 DETAILS
PUMP NOTES:
1. CONTRACTOR TO FURNISH AND INSTALL FLYGT NP 3085 WITH AN
ADAPTIVE 255 IMPELLER 4-HP 230V 3-PHASE SUBMERSIBLE
WASTEWATER PUMP AND ASSOCIATED HARDWARE AND
ACCESSORIES.
*THE ELECTRICAL SERVICE TO THE CONTROL PANEL IS 1-PHASE AND
USES VFDS TO CONVERT TO 3-PHASE POWER. SEE ELECTRICAL
SHEETS.
PUMP NO. PUMP #1
EXISTING OR PROPOSED
PUMP MANUFACTURER
PUMP MODEL NO.
IMPELLER NO.
DESIGN PUMP HEAD
DESIGN PUMP RATE
DESIGN PUMP SPEED
PUMP POWER
PUMP VOLTAGE
PUMP PHASE
DISCHARGE SIZE
PUMP #2
(FT)
(GPM)
(RPM)
(HP)
(VOLTS)
(PH)
(IN)
PUMP INFORMATION
PROPOSED
FLYGT
NP 3085
ADAPTIVE 255
52
175
3395
4
230
3*
3
STATION INFORMATION
4
4
8
6
11.77
11.35
4.83
4.83
4.33
3.83
2.05
RISER PIPE DIAMETER
(IN)
PIPE DIAMETER AFTER RISER
WET WELL WALL THICKNESS
DIAMETER OF WET WELL (ID) (FT)
LEAD PUMP ON EL
HIGH WATER EL
PUMP OFF EL
LAG PUMP EL
TOP OF WET WELL EL
BOTTOM OF WET WELL EL
GRAVITY SEWER INVERT EL
BOTTOM OF CONTROL PANEL EL
(FT, NAVD)
(FT, NAVD)
(FT, NAVD)
(FT, NAVD)
(FT, NAVD)
(FT, NAVD)
(FT, NAVD)
(IN)
(IN)
0.55
(FT, NAVD)
8WET WELL TOP THICKNESS
(IN)
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
PROPOSED
FLYGT
NP 3085
ADAPTIVE 255
52
175
3395
4
230
3*
3
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING, ASSUMED)
CONTRACTOR TO
INSTALL PROTECTIVE LINER ON
MANHOLE INTERIOR SURFACE
CONTRACTOR TO
INSTALL PROTECTIVE LINER ON
WETWELL INTERIOR SURFACE.
WET WELL FLOOR TO BE MADE
LEVEL AND FLAT.
PROPOSED
ACCESS DRIVEWAY
11' RADIUS
PROPOSED
ACCESS DRIVEWAY
11' RADIUS
8.00'
26.74'
28.00'
PROPOSED
5 L.F. OF 4" FM - PVC C900 DR18
(BELOW GROUND)
PROPOSED
ACCESS DRIVEWAY
8' WIDE ASPHALT
PUMP STATION REHABILITATION
PER STANDARD DETAILS.
SEE SHEETS D-01 & D-02
NO. OF POLES 2 2
4" HDPE SUCTION PIPE
CORED INTO TOP OF
WET WELL LID
4" HDPE MJ-FLANGE ADAPTOR
4" STAINLESS STEEL QUICK
CONNECTION COUPLING
4" PLUG VALVE
CONNECT TO EX. 4" PVC FORCE MAIN
PROPOSED
ACCESS DRIVEWAY
27.1' ALONG EXISTING EOP
UTILITY DEVIATION
OBTAINED
1
RE
VIS
IO
N P
ER
S
DP
I R
EV
IE
WE
R C
OM
ME
NT
S01
03/24/21
1
1
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
06
Site Plan
Offsite Improvements
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
SEE SHEETS D-01-D-02 FOR
PUMP STATION 312.27 DETAILS
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
PS 312.27
SEE SHEETS 03-05
GOLDFINCH
BOB WHIT
E
SU
NS
HIN
E B
LV
D.
S
U
N
S
H
I
N
E
B
L
V
D
.
LE
E B
UT
TS
B
LV
D.
BECK BLVD.
EXISTING 4" PLUG VALVE
(NOT WORKING)
CONTRACTOR TO
INSTALL NEW 4" PLUG VALVE
ON EXISTING 4" FORCE MAIN
IN EXISTING GRASSY AREA
EDCBA
PIPE
301817
1
1
1
1
7
7
7
7
7
1
4 3/163
4 13/16
5 7/16
8 7/16
6 15/16
3
3
3
3
4
5
6
10
8
* ALL DIMENSIONS IN INCHES.
312 9 15/16
MINSIZE MAX
STEEL PLATE
1/2" 316 SS THICK SQUARE
1/4"
B
A
C
PROCESS PIPE
1" NON-SHRINK GROUT
(TYP OF 4)
LEVELING NUTS
ANCHORS WITH
5/8" 316 SST WEDGE
GRADE (DIMENSION "E")
REQUIRED PIPE
PIPE CUT TO MEET
SCHEDULE 40 316 SS
1/4" NEOPRENE PAD
316 SST U-BOLT
NOTES:
1. PIPE SUPPORT HEIGHT TO BE ADJUSTABLE.
2. SEE PLANS AND SECTIONS FOR PIPE GRADE
REQUIREMENT (DIMENSION "E").
3. PIPE SUPPORT TO BE COMPATIBLE WITH HDPE PIPE.
4. ALL MATERIALS AND HARDWARE TO BE 316 SS.
CONSTRUCT 18" x 18" x 6" CONC BASE WITH # 4
REINFORCING STEEL @ 5" OCEW IF SUPPORT IS
NOT LOCATED ON AN EXISTING SLAB.
STANCHION 316 SS
SADDLE
3018
3018
3018
3018
3018
E
D
SLATS
DETAIL
NOTE:
COLOR OF THE SLATS SHALL BE
GREEN OR BLACK TO MATCH VINYL
COATED PARTS
2"
GRADE
3000 PSI CONCRETE
TURNBUCKLE
TRUSS BARS
3/8" ROUND
BARS
STRETCHER
TOP RAIL
MIN
. 6'-0"
3'-0"
6" 6"
10'-0" TO CENTER (MAX)
CORNER
POST
GALV. POST CAP
SPACING
14" MAX.
#9 GALV. CLIPS
1'-0"
316 SS TENSION WIRE
LINE POST
12" O.C.
316 SS #9 TIE WIRES
STRETCHER
BARS
TRUSS BARS
AS REQUIRED
GALV. POST CAP
3" ±1"
ONE PIECE TRACK
AND TOP RAIL
ROLLER GUIDE
8.625" OD
(SCHDEULE 40 PIPE)
POST CAP
4'-0"
2"
2.0"
2.0"
2"
4'-0"
8.625" OD GALV.
STEEL POST
(SCHEDEULE 40 PIPE)
3'-0"
1'-0"
316 SS #9 TIE WIRES
12" O.C.
ASSEMBLY
GALV. STEEL POSTS
GRADE
ROLLER GUIDE
ASSEMBLY
FABRIC
NOTES:
1. ALL FENCING COMPONENTS SHALL BE VINYL COATED
GREEN OR BLACK AS APPLICABLE.
NOTES:
1. ALL FENCING COMPONENTS
SHALL BE VINYL COATED GREEN
OR BLACK AS APPLICABLE.
D-01
Collier County Utility
Pump Station Details
1 of 2
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
D-01
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
NOTES:
1. DETAIL WW-7 IS INTENDED FOR NEW PUMP STATION
CONSTRUCTION AND NOT ALL ITEMS WILL APPLY TO
THIS PROJECT.
2. WHERE CONFLICTS ARISE BETWEEN SHEETS 05
AND D-01, SHEET 05 WILL HOLD PRECEDENCE.
3. CONTRACTOR TO NOTIFY ENGINEER IN WRITING OF
ANY CONFLICTS OR DISCREPANCIES PRIOR TO
PERFORMING THAT WORK.
xxxxxxxxxxxxxxxxxxxxxxxxxxxx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xxxxxxxxxxxxxxxxxx
Wa
ste
wa
te
r P
um
p S
ta
tio
n
Re
pa
ir a
nd
R
en
ova
tio
n
Pu
mp
S
ta
tio
n 3
12
.2
7
Co
llie
r C
ou
nty, F
lo
rid
a
D-02
Collier County Utility
Pump Station Details
2 of 2
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
RE
VIS
IO
NS
NO
. D
ES
CR
IP
TIO
N D
AT
E
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
ELEVATIONS REFERENCE NAVD 1988.
CONVERSION TO NGVD 1929 IS:
NAVD1988 + 1.28 = NGVD 1929
2
RE
VIS
IO
N P
ER
S
DP
I R
EV
IE
WE
R C
OM
ME
NT
S
02
03/24/21
2
Electrical Plans
Electrical
Improvements
Wastew
ater Pum
p Station
Repair and Renovation
Pum
p Station 312.27
Collier County, Florida
E-01
DATE:
PROJECT NO.
FILE NO.
SCALE:
SHEET NUMBER
REVISIO
NS
NO
. D
ESCRIPTIO
N D
ATE
JOHNSON ENGINEERING, INC.
2122 JOHNSON STREET
P.O. BOX 1550
FORT MYERS, FLORIDA 33902-1550
PHONE: (239) 334-0046
FAX: (239) 334-3661
E.B. #642 & L.B. #642
APRIL 05, 2021
20203066-001
01-50-26
AS SHOWN
Electrical Improvement Notes:
1. Remove the (2) existing 3 HP Motortronics VFDs in the existing
pump control panel and furnish to County Wastewater Collections
staff.
2. Furnish and install (2) LSIS S100 MODEL 0040 EMC TYPE 7.5HP,
230V, 3-Phase VFDs.
3. A minimum vertical clearance of 4" shall be provided on the top and
bottom of the VFDs.
4. Contractor to adjust other components, if necessary, to maintain
appropriate clearance.
5. The existing electrical service, pump control panel, main breaker,
and VFD input breakers to remain.
Existing (2) 3 HP VFDs to be removed and furnish to Collier County Wastewater Collections staff.
Proposed (2) 7.5 HP VFDs to be installed in same location. Existing components to be adjusted, if necessary, to maintain required clearance.