    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 2of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    FIRST PART _ ICL009.1

    0. ITP SCOPE

    SpecialSpecifications.

    Section 10General

    SpecificationsSection 10

    This Section covers requirements for supplying andinstalling cast in-situ concrete and steel piles by boring.

    1. PRELIMINARY

    Special

    Specifications.Sub-section10.1.3.1General

    SpecificationsSub-section

    10.1.3.1

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1H H H H H 100%

    Shop drawings approvedMethod Statement approvedWork program approvedITP approvedConcrete trial mixes approved

    2.

    SETTING OUTAND WORK

    PLATFORM

    SpecialSpecifications.

    Section 10General

    SpecificationsSection 10

    2.1 Work platformavailability

    SpecialSpecifications.

    Section 10GeneralSpecifications

    Section 10

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    H H W W 100% In accordance to approved drawings

    2.2Temporary bench

    mark location

    SpecialSpecifications.

    Section 10General

    SpecificationsSection 10

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Survey report

    H H H W W 100% In accordance to approved drawings

  • 8/10/2019 ITP for Piling

    3/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 3of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    2.3Pile location and

    numbering

    SpecialSpecifications.

    Section 10General

    SpecificationsSection 10

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Survey reportPile Record Sheet

    H H H H W 100%As per approved drawings and work program.Tolerances: Position: 75 mm in any direction at the pile head

    3.FOLLOW-UP

    ACTIVITIES

    SpecialSpecifications.

    Section 10

    GeneralSpecifications

    Section 10

    3.1 Piling rig setting up

    SpecialSpecifications.

    Subsection10.1.3.2General

    SpecificationsSub-section

    10.1.3.2

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Pile record Sheet

    S S W W 100%In accordance to approced shop drawing.

    Approved equipment is used

    3.2Casing verticalityand position for

    Bucket & Auger pile

    SpecialSpecifications.Sub-section

    5.3.3.9. Item

    16a

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Pile record Sheet

    S S W W 100% Verticali ty: 1 in 75 deviation

  • 8/10/2019 ITP for Piling

    4/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 4of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    3.3

    Pile diameter,length, bottomcleaning and

    concreterequirement

    checking

    SpecialSpecifications.Sub-section

    10.1.3.2General

    SpecificationsSub-section

    10.1.3.3

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Pile record Sheet

    H H S W 100%

    Pile diameter an length per drawings.On completion of boring, the base of the pile shall becleaned thoroughly with a cleaning bucket to ensure thatthere is no loose material in the baseDrilling fluid shall be tested and results in accordance tomanufacturer recommendations. If bentonite is isuedproperties will be: Density less 1.20 g/cm3 Fluid loss less than 40 mils (1.016 mm)

    Marsh viscosity less than 60 s Plastic viscosity less than20 cP Sand content less tha 3% Shear Strength 4 to 25 N/m2 pH: 9.5 to 11.7

    Approved class 40 concrete mix design

    3.4 Reinforcement cage

    SpecialSpecifications.Sub-section 5.2

    GeneralSpecifications

    Sub-section 5.2

    KAS-CCJV/BS2P2/ICL/QA/0

    07.1Daily report

    Pile record Sheet

    H H H H 100%In accordance to drawings and ITP No. KAS-CCJV/BS2P2/ITP/QA/007

    3.5 Concrete placement

    SpecialSpecifications.Sub-section 5.2

    GeneralSpecifications

    Sub-section 5.2

    KAS-CCJV/BS2P2/ICL/QA/0

    07.1

    Daily reportPile record SheetConcrete

    Placement Record

    S S W W 100% In accordance to ITP No. KAS-CC JV/BS2P2/ITP/QA/007

    3.6 Concrete level

    SpecialSpecifications.

    Section 10General

    SpecificationsSection 10

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Pile record Sheet

    S S W W 100% As per drawings

  • 8/10/2019 ITP for Piling

    5/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 5of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    3.7 Pile as built position

    SpecialSpecifications.

    Section 10General

    SpecificationsSection 10

    KAS-CCJV/BS2P2/ICL/QA/0

    09.1Daily report

    Pile record SheetSurvey report

    H H H W W 100%As per drawings.Tolerances 75 mm in any direction at the pile head.

    FIRST PART _ ICL009.2

    4. TESTING

    Special

    Specifications.Section 10General

    SpecificationsSection 10

    4.1

    Drilling fluid testing.

    Density

    (To be made onpolymer if

    recommended bymanufacturer) (*)

    SpecialSpecifications.Sub-section

    10.1.2General

    SpecificationsSub-section

    10.1.3.2

    API RP 138 B-1ASTM D 4380

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    Once aday as

    suppliedto drillingprocess

    Each pilefrom top

    andbottom ofthe pileprior

    concreting

    If polymer: as per technical data sheet of themanufacturerIf bentonite: During drilling, 1.10 g/cm3; fromexcavation prior concreting, 1.20 g/cm3

  • 8/10/2019 ITP for Piling

    6/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 6of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    4.2

    Drilling fluid testing.

    Viscosity(To be made on

    polymer ifrecommended bymanufacturer) (*)

    SpecialSpecifications.Sub-section

    10.1.2General

    SpecificationsSub-section

    10.1.3.2

    API RP 138 B-1ASTM D 6910

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    Once aday as

    suppliedto drillingprocess

    Each pilefrom top

    andbottom of

    the pileprior

    concreting

    If polymer: as per technical data sheet of themanufacturerIf bentonite: During drilling, 30 to 40 s; from excavationprior concreting, 60 s

    4.3

    Drilling fluid testing.

    Plastic Viscosity

    (To be made onpolymer if

    recommended bymanufacturer) (*)

    SpecialSpecifications.Sub-section

    10.1.2General

    SpecificationsSub-section

    10.1.3.2

    API RP 138 B-1

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    Once aday as

    suppliedto drillingprocess

    Each pilefrom top

    andbottom ofthe pileprior

    concreting

    If polymer: as per technical data sheet of themanufacturerIf bentonite: During drilling, 10 cP; from excavationprior concreting, 20 cP

  • 8/10/2019 ITP for Piling

    7/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 7of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    4.4

    Drilling fluid testing.Shear Strength

    (To be made onpolymer if

    recommended bymanufacturer) (*)

    SpecialSpecifications.Sub-section

    10.1.2General

    SpecificationsSub-section

    10.1.3.2

    API RP 138 B-1

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    Once aday as

    suppliedto drillingprocess

    Each pilefrom top

    andbottom of

    the pilepriorconcreting

    If polymer: as per technical data sheet of themanufacturerIf bentonite: During drilling, 4 to 25 N/m2; fromexcavation prior concreting, 4 to 25 N/m2

    4.5

    Drilling fluid testing.

    Sand Content

    (To be made onpolymer if

    recommended bymanufacturer) (*)

    SpecialSpecifications.Sub-section

    10.1.2General

    SpecificationsSub-section

    10.1.3.2

    API RP 138 B-1ASTM D 4381

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    Once aday as

    suppliedto drillingprocess

    Each pilefrom top

    andbottom ofthe pileprior

    concreting

    If polymer: as per technical data sheet of themanufacturerIf bentonite: During drilling, 1%; from excavation priorconcreting, 3%

  • 8/10/2019 ITP for Piling

    8/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 8of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    4.6

    Drilling fluid testing.pH

    (To be made onpolymer if

    recommended bymanufacturer) (*)

    SpecialSpecifications.Sub-section

    10.1.2General

    SpecificationsSub-section

    10.1.3.2

    API RP 138 B-1ASTM D 4381

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    Once aday as

    suppliedto drillingprocess

    Each pilefrom top

    andbottom of

    the pilepriorconcreting

    If polymer: as per technical data sheet of themanufacturerIf bentonite: During drilling, 1%; from excavation priorconcreting, 3%

    4.7

    Caliper logging teston the entire lengthof bored hole prior

    to concreting

    SpecialSpecifications.Sub-section

    10.1.3.2ASTM D 6167

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H W W

    5 No inthe firstweek

    Provisionally 10 Nothereafter, equallyspacedthrough

    theworks.

    Acceptance in accordance to test result interpretarion

    4.8

    Low strain dynamic

    test, sonic eco testor

    High straindynamic testing

    or

    Cross-hole soniclogging

    Special

    Specifications.Sub-section

    10.2General

    SpecificationsSub-section

    10.2

    ASTM D 5882

    ASTM D 4945

    ICE-Section 9

    KAS-CCJV/BS2P2/ICL/QA/0

    09.2Daily report

    Pile Record SheetTest report

    H H H H 1% Acceptance in accordance to test result interpretarion

  • 8/10/2019 ITP for Piling

    9/9

    EMPLOYER ENGINEER CONTRACTOR

    Ministry of Transport & CommunicationsDirectorate General of Roads & Land Transport

    P.O.Box27, P.C.114Sultanate of Oman

    COWI & Partners LLC

    P.O.Box2115, P.C.112

    Sultanate of Oman

    Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV

    Al Azaiba

    P.O. Box723, P.C.130

    Sultanate of Oman

    Contract No.: 95/2012 BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2DOC No: KAS-CCJV/SB2P2/ITP/QA/009 Rev.00

    INSPECTION AND TEST PLAN PILING Date: 16/11/2014

    (*) When the results show consistent behaviour, the tests for shear strength and pH value may be discontinued, and tests to determine density and viscosity shall be carried out as agreed with the Engineer.

    INSPECTION CODE: HHold Point WWitness Point S - Surveillance NIRNo Inspection Requested

    Form No.: KAS-CC/SB2P2/OP/QA/01.06 Page 9of 9

    ITEM OFINSPECTION

    REFERENCE DOCUMENTSFOLLOW-UPDOCUMENTS

    TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY

    NOTES/ACCEPTANCE CRITERIA

    SPEC. STANDARDSIndustPark

    Subcont Product Survey Quality Engineer Frequency

    4.9 Static Load Test

    SpecialSpecifications.

    Sub-section10.2General

    SpecificationsSub-section

    10.2

    In accordance toSpecial

    Specification,

    Tables 10.2.3.1and 10.2.3.2ASTM D 1143

    orASTM D 5882

    Approved MethodStatement

    KAS-CC

    JV/BS2P2/ICL/QA/009.2Daily report

    Pile Record SheetTest report

    H H H H

    2preliminarypile testsshall be

    undertakenat eachbridge

    location oragreed with

    theEngineer

    At least onepercent ofworkingpile testsshall be

    undertakenon piles

    agreed withthe

    Engineer,or as

    shown onthe

    Drawings

    A preliminary test pile shall be considered to have failedwhen any of the following conditions apply: Any of the above criteria apply at working loads The maximum load specified has not been achieved

    A working pile shall be considered to have failed when

    any of the following conditions apply: On completion of a load test, the residual settlement

    after rebound exceeds 6 mm. The test load as specified in the contract shall not

    have been achieved. The maximum settlement under 1.5 working load

    specified on the drawings exceeds 10mm or 1% ofthe least lateral dimension of the pile, whichever isthe greater.