Electronic DATA Single Phase Inverter

Type INVERTRONIC/ 10 15 20 30 40 50 60

Inverter Data

Inverter Input Voltage 93.5 – 132 (110V Version)

107 – 150 (125V Version)

Nominal Input-Active-Power

(with Loads cos j = 0,8 ind) kW 8.9 13,4 17.8 26.7 35.6 44.4 53,5

Nominal Output-Active-Power

(cos j = 1) kW 8 12 16 24 32 40 48

Nominal Output-Current (cos j = 0.8) A 43,4 65,2 86,9 130,4 173,9 217,3 500

Nominal Output-Current (cos j = 1) A 34,7 52,2 69,5 104,3 139,1 173,9 400

Nominal Output Voltage 1x 120V (adjustable ± 5%)

Nominal Output Frequency Hz 50 / 60

Transformer galvanic isolated

Voltage tolerance

– static– 50% assymetric load– 100% assymetric load– dynamic with 100% load step

%

%

%

%

± 1

± 1

± 2< 4

Transient Time < 10 ms

Winkelabweichung– symetric load

– 50% assymetric load

– 100% assymetric load

< 1°< 2°< 3°

Frequency tolerance– Mains synchronic– Self synchronic

± 1% (Synchronisation band ±4%)

± 0,1 %

Distortion Factor (EN 62040-1)– linear load– non-linear load

< 1%< 5%

Crest factor ³ 3

Overload– 3ph– 1ph / N

150 % 60 s, 125 % 10 min220 % 60 s, 180 % 10 min

Short Circuit behaviour– 3ph– 1ph / N

200 % 3 s350 % 3 s

Page 6: Invertronic 110V englisch

Type INVERTRONIC/ 10 15 20 30 40 50 60

Inverter efficiency at nominal load(cos phi 0,8)

% > 90 > 91

Static Bypass

Nominal Voltage V 3 x 400 with neutral

(neutral is essential)

Nominal Frequency Hz 50

Overload capacity– 10 min– 100 ms

%

%

1501000

Switch-over limits U ± 10%; F ± 5%

Inverterr/Bypass switch-over-time– Inverter failure

– Overload or man. switch over

<1 ms<1 ms

interlocking if, the system became switched over5 times within 1 min.

Bypass/Inverter switch-over-time <1 ms

General Data

Power loss– 100% load

– 0% loadkW

kW

0.9

0.6

1,5

1,3

1,7

0.9

2.6

1,8

3.6

2.0

4.4

2,4

5,3

2,6

Needed volume air-stream /hm² 1500 2000

Acoustic level within 1m distance 63 dB(A) 64 dB(A)

Acceptable. ambiance temperature 0 – 40°C

daily middle £ 35°C

Relative humidity 5 % - 95 % without condensation

Max. installation height <1000 m over NN without power reduction

Power-reduction over 1000m Ca. 4,5% pro 500m

Humidity-class DIN/IEC 721 2-1-09/86

Cabinet Freistehendes Stahlblechstandgehäuse

Schutzart IP 20 (DIN/VDE 0470 Teil 11/92 IEC529)

Andere optional

Page 7: Invertronic 110V englisch

Type INVERTRONIC/ 10 15 20 30 40 50 60

Isolation class DIN/VDE 0110, Over voltage catergory 2,

Electromagnetic Compatibility EN 50091-2 Standard Klasse A

Dimensions in mm– width– depth– Height

800

800

2000

(optional 2200mm)

Cooling Forced-air-cooled with speed controlled,redundant and monitored fan. Fans can bereplaced from the front, Power block andtransformers are temperature controlled.

Weight app. kgkg 550 580 620 650 750 830 1020

Cable entrance from the bottom (optional from the top with anadded cabinet width 200mm)

Paint RAL 7035