introduction to voice alarm
TRANSCRIPT
![Page 1: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/1.jpg)
About Voice Evacuationan introduction
![Page 2: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/2.jpg)
Voice Evacuation• Research has proven that in an emergency people will react
without confusion or panic if they receive a clear, intelligible message.
• Bells and sounders only give a warning, they do not indicate the nature of the emergency.
• Phased evacuation using clear, easily understood, pre-recorded messages ensures that even untrained personnel are evacuated speedily and efficiently.
![Page 3: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/3.jpg)
Voice Evacuationwhat is it?
• An effective alternative to standard bells and sounders – using the spoken word for evacuating premises during an emergency.
• Often referred to as ‘voice alarm’, ‘VA’ or ‘VE’.
• Needs to be fully compliant with BS5839-8, BSEN54-16 and EN60849.
• Serves as a general public address system during normal circumstances.
• Provides companies with facilities such as advertisement injection, background music, timed message announcements – and much more.
![Page 4: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/4.jpg)
Voice Evacuationin brief
• A ‘building’ is ‘divided’ into separate areas (zones).• Zones can be ‘spoken to’ (broadcast to) individually, several at
once or as an ‘all call’.• During an emergency people are informed – via the spoken
word – what is happening and what to do.• Evacuation control is either via pre-recorded messages and/or
via emergency fire microphones.• The system is fully monitored (BS5839-8), with any faults
reported, so that it will work when needed – during an emergency.
![Page 5: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/5.jpg)
Voice Evacuationwhy do we need it?
• Those most at risk can be evacuated first.• Phased evacuation can be pre-planned.• Emergency messages can be stored on the system and
broadcast by automatic or manual means.• Fire officers/building management can broadcast ‘live’ at any
time.• Panic is reduced due to the controlled nature of the
evacuation.• Quite simply: voice alarm helps save lives during an
emergency.
![Page 6: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/6.jpg)
During an Emergency...
![Page 7: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/7.jpg)
..WITHOUT Voice Evacuation• A ‘break glass’ box or ‘fire detector’ is activated.
• An alarm is sounded – normally a bell/klaxon style alarm.
• Initially, it is usual for people to carry on as normal.
• Vital seconds – or minutes – are lost.
• After a while people become curious and eventually start to move.
• People habitually exit via the same route they entered – this may be the longest (or most dangerous) route.
• Unfortunately, such inaction can, and does, end in tragedy.
![Page 8: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/8.jpg)
A Standard Fire Alarm System
![Page 9: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/9.jpg)
..WITH Voice Evacuation• A ‘break glass’ box or ‘fire detector’ is activated.
• The fire alarm panel activates the voice alarm system messages.
• Emergency messages are broadcast to areas at risk.
• Areas of high risk are informed of any necessary action – ie ‘evacuate’.
• Areas of low risk are ‘alerted’ to the situation – ‘phased evacuation’.
• Real time information may be broadcast by the emergency services to prevent people moving into danger.
• Result – immediate action – calm, controlled and SAFE evacuation.
![Page 10: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/10.jpg)
Voice Evacuation System
![Page 11: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/11.jpg)
Centralised Voice Evacuation
• Usually offered for single building installations.
• All loudspeaker lines derived from a single location.
![Page 12: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/12.jpg)
Decentralised Voice Evacuation
• Usually offered on site wired installations where a number of buildings need to be covered.
![Page 13: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/13.jpg)
System Priorities• A voice alarm system has various inputs, which must be
prioritised. This ensures the most important input (ie fire officer’s microphone) overrides any other.
• Typical priorities are as follows:
Fire microphone 1 (all call)
Fire microphone 2 (zone select)
Evacuation message
Alert message
Other emergency message
Priority settings on VIGIL EVAS systems can be easily changed to suit individual requirements.
![Page 14: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/14.jpg)
Basic System Elements
![Page 15: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/15.jpg)
Fire Microphone• Weatherproof enclosure.• Fist microphone.• Has top priority – overrides all other
microphones and inputs to the voice evacuation system.
• Used by firemen/building control to override emergency broadcasts – either as a ‘zone select’ or ‘all call’.
• Any other messages being transmitted to zones will be interrupted when the fire microphone is activated.
![Page 16: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/16.jpg)
Microphone Controller• Operated by the designated person to
control the evacuation using voice announcements – live or recorded.
• Can also be used as a fire or paging microphone.
• Selects music source.• Ability to test the system via pre-
recorded ‘start’ and ‘end’ test messages.• During an emergency, assumes
‘emergency control mode’ and is given a higher priority.
![Page 17: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/17.jpg)
Router• The voice alarm router is connected to the
fire detection system of a building.• The fire detection system triggers the VA
system to evacuate and alert automatically.• Provides full system status monitoring and
fault reporting.• The router receives various inputs including
microphones, spot announcers, etc.• It outputs the ‘priority’ signal, via the
amplifier(s), to relevant loudspeaker circuits (zones).
![Page 18: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/18.jpg)
Amplifier• Receives the input from the microphone
(or other source) (via the router) and amplifies (broadcasts) it to the relevant zones.
• Several amplifiers will be built into a voice alarm rack, with each amplifier broadcasting to specific zones (circuits) within the building.
• Available in different power options to suit system requirements.
![Page 19: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/19.jpg)
Batteries• A voice evacuation system must work during an emergency –
even if the mains power has failed.
• Backup batteries included in the system must be of a suitable ‘size’.
• Calculations for battery sizes are made at the design stage of a system.
• Typically, the system is capable of being battery-backed for 24 hours quiescent and 30 minutes at full power (to meet the requirements of BS5839-8).
![Page 20: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/20.jpg)
Messages• Flash memory, recordable by client.
• Digital WAV files.
• CD quality.
• 57 second duration for each message.
• Constantly monitored.
• Triggered by fire panel or manually.
Alert
Evac
Test
![Page 21: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/21.jpg)
Music Input• A source of music which is installed in the voice alarm rack –
such as an MP3 or CD player.
• Used to broadcast background music to zones selected.
• Typically the lowest priority in a voice alarm system.
• Will be overridden in the event of an emergency.
![Page 22: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/22.jpg)
Phased Evacuation
![Page 23: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/23.jpg)
Typical Office Block or HotelROOF
7th floor
6th floor
5th floor
4th floor
3rd floor
2nd floor
1st floor
ground floor
BASEMENT 1
BASEMENT 2
EVACUATE
alert
alert
EVACUATE
EVACUATE
alert
alert
alert
EVACUATE
EVACUATE
EVACUATE
GROUND LEVEL
ROOF
7th floor
6th floor
5th floor
3rd floor
2nd floor
1st floor
ground floor
BASEMENT 1
BASEMENT 2
![Page 24: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/24.jpg)
The VIGIL2 Voice Evacuation System
![Page 25: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/25.jpg)
Fire Microphone
• Single, four or eight zone.• Lockable IP66 steel enclosure.• Zone status indicators.• Speak now indicator.• Speech volume indicator.• Option to fit ‘processor bypass’ hard-
wired press-to-talk switch.• Option to fit flip-top switches to
enable DVA (digital voice announcement) messages to be broadcast.
• Fully monitored.
BFM400 range
![Page 26: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/26.jpg)
Microphone Controller
• Available in eight versions – from 8-zone up to 64-zone.
• Performs as a paging or fire microphone with an optional ‘all call’ processor bypass facility.
• LCD displays showing zone name and status.• Red buttons for emergency messages –
operated by key switch.• Fault indicators.• Up to 30 messages available to operator
(stored on EVAS routers).• Five programmable function keys.• Fully monitored.• RJ45/CAT5 connection.
BVRD range
![Page 27: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/27.jpg)
Touchscreen Paging Station
• Operator selects options by simply touching the screen prompts.
• Graphics can be displayed as either virtual buttons or as a topographical layout (pictured).
• All functions: message selection, zone selection, paging, message recording, background music, etc – can be performed from the paging station.
• Industrial, solid state fan-less computer (no moving parts).
• High definition LCD display.
Unitouch
![Page 28: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/28.jpg)
Router
• Eight inputs and seven outputs.
• Inputs 1&2 with processor bypass.
• One failsafe emergency ‘all call’ message.
• Six messages stored in flash memory.
• USB2 port to configure unit/upload messages, etc.
• Realtime clock – fault logging, history, night time volume, etc.
• CANBUS ports to connect with modules, simple rack wiring.
• Parametric EQ on all inputs and outputs.
• Auto amplifier changeover (1 in 10).
DSP-controlled BVRD2M
![Page 29: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/29.jpg)
Expansion facilities
• 1U in height.• Up to five slave units can be added
to one BVRD2M master.• Each BVRD2S adds:• 12 audio inputs.• 16 audio outputs.• 12 messages.
• Each BVRD2SLT adds:• 6 audio inputs.• 8 audio outputs.• 6 messages.
• Mount directly on top of BVRD2M – connections are made using RJ45.
BVRD2S & BVRD2SLT slave units
![Page 30: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/30.jpg)
Mini Router
• Four inputs and four outputs.• One failsafe emergency ‘all call’
message.• Six messages stored in flash
memory.• Realtime clock – fault logging,
history, night time volume, etc.• Parametric EQ on all inputs and
outputs.• Fits alongside a VIGIL2 amplifier and
BVSMP power supply in one 19” frame.
• Fully monitored.
DSP-controlled BVRD2M4
![Page 31: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/31.jpg)
ECLIPSE3
• Wall-mountable, stand-alone system, complete with battery backup.
• All the facilities of the BVRD2M4.• Up to two VIGIL2 amplifiers can be
fitted (any combination):• BV225 – 225 Watt single amplifier.• BV125D – 125 Watt dual amplifier.• BV050Q – 50 Watt quad amplifier.
• Ideal for decentralised networking or tenant systems.
• Fully monitored.• Optional ‘all call’ fire microphone on
front panel.
VA/PA system
![Page 32: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/32.jpg)
Amplifiers
• Class D – 80% efficient.• Compact.• Sleep mode – automatically
reducing standby requirements to 50mA per amplifier when operating on batteries.
• Rated power obtainable from 22V battery supply.
• Over-temperature protection.• The BV225 can be paralleled. BV225, BV125D,
BV050Q
![Page 33: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/33.jpg)
DC line monitor/ isolator
• Enables dual loudspeaker circuits to connect to a single amplifier.
• Each BVRDADIS unit provides both A&B circuits for two amplifiers.
• Up to 10 spurs per loudspeaker line.
• The BVRDADIM master unit connects to the BVRD2M router.
• Up to five BVRDADIS can be connected to one BVRDADIM.
• Utilises DC line monitoring techniques, therefore, BEL1 end of line monitoring is not required.
BVRDADIM & BVRDADIS
![Page 34: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/34.jpg)
PSU Charger
• Switch mode power supplies.• Two individually protected outputs
at 24V (one on the BVSMPLT).• Built-in deep battery discharge cut
off.• Standby batteries are continually
‘float charged’.• A protected output is provided to
power a mixer or auxiliary circuit.• Several chargers may be paralleled
when used for larger systems.• Fully monitored.
BVSMP & BVSMPLT
![Page 35: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/35.jpg)
DSP Network
• Provides digital networking facilities for the VIGIL2 range.
• Connected in a loop configuration.• Continues to function in the event of
cabling damage at a single location.• The network can be copper, fibre or
a combination of both.• Two RS485 and up to fourteen
concurrent audio channels.• Network status indicators.• Up to 126 VIGIL2 EVAS systems can
be digitally networked.• Fully monitored.
BVRDNETBVRDCIF & BVRDFIF
![Page 36: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/36.jpg)
The Standards
![Page 37: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/37.jpg)
BS5839-8• At least two interleaved loudspeaker circuits are required in
order to ensure adequate coverage should one circuit fail (4,000m2/500 members of the public).
• Cabling for dual circuits must not be contained in one single sheath.
• Processor controlled system must:• Have restricted access for system configuration data.• Not use rotary discs or other moving parts.• Be monitored i.e. ‘watchdog’.• The network between subsystems must be monitored in
accordance with requirements (12.1).
![Page 38: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/38.jpg)
BS5839-8• System monitoring should include the following:
• Normal/standby power.• Battery chargers.• Fuses and protective devices.• Critical signal paths.• Emergency messages.• Loudspeaker circuits.• Main and standby amplifiers.• Select wires on a multi-zone emergency microphone.• All links between a decentralised system.• Detection of missing modules or amplifiers within the critical signal path.• Automatic level controllers must be monitored and should failsafe to a pre-
determined level, not mute.
![Page 39: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/39.jpg)
BS5839-8• The system should latch the input condition from the fire panel ensuring
that if a link is broken the alarm broadcast continues. Reset is achieved by a separate signal from the fire panel.
• After reset the system should be capable of producing a general evacuate broadcast within 30 seconds.
• The fire alarm interface and VACIE must be separated by no greater than 10m, unless duplicate circuits are used.
• Any fault should be indicated within 100 seconds.• Standby batteries to have capacity for 24hrs quiescent followed by 30
mins all zones evacuate.• 120 min enhanced fire resisting cables to be used in unsprinklered
buildings having a phased evacuation, or buildings over 30m high or where the risk assessment demands.
![Page 40: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/40.jpg)
• Many European countries adopted this standard in April 2011.• All voice alarm manufacturers need their products third party tested by an
accredited test house.• Specifiers, consultants, installers and end users need to ensure that the
voice alarm equipment supplied has full EN54-16 third party certification.• All manufacturers must have relevant factory production control
procedures in place – i.e. EN ISO9001-2000.• Power supplies need to meet EN54-4.• Loudspeakers need to meet EN54-24.• Annual inspections of the factory to be carried out by the test house.• All product enhancements need to be submitted for testing.
BS EN54-16:2008
![Page 41: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/41.jpg)
• VIGIL2 voice alarm products have full BSEN54-16:2008 certification (including BSEN54-4:2008 for power supplies).
• Our requirement for CE marking.
• Baldwin Boxall has all relevant EN54 certificates.
• Any Baldwin Boxall supplied system can be upgraded to meet EN54-16.
• The Construction Products Regulation (CPR) took effect on 1st July 2013. All voice alarm manufacturers were required to comply from this date for UK sales.
BS EN54-16:2008
![Page 42: Introduction to voice alarm](https://reader034.vdocuments.mx/reader034/viewer/2022051303/58a2eeab1a28ab0a518b99f8/html5/thumbnails/42.jpg)
www.baldwinboxall.co.uk