introduction to simatic pdm and how to connect to a lr200 radar via hart

29
PDM & LR200 Webinar Automation and Drives PI5 James Powell 17.10.03 1 Setting a New Standard of Integration Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART Agenda: - Overview of PDM - Example of how to connect to a LR200 The objective of this web seminar is to give the viewer idea of what PDM is and how to use it to communicate to a LR200 Radar unit via HART communications.

Upload: lyneth

Post on 05-Jan-2016

82 views

Category:

Documents


4 download

DESCRIPTION

Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART. Agenda: - Overview of PDM - Example of how to connect to a LR200 The objective of this web seminar is to give the viewer an idea of what PDM is and how to use it to communicate to - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 1

Setting a New Standard

of Integration

Introduction to SIMATIC PDM And How to connect to a LR200 Radar via HART

Agenda:

- Overview of PDM - Example of how to connect to a LR200

The objective of this web seminar is to give the viewer anidea of what PDM is and how to use it to communicate to a LR200 Radar unit via HART communications.

Page 2: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 2

Setting a New Standard

of Integration

What is PDM?

Stands for Process Device Manager

A configuration tool Used for:- Commissioning field devices- Maintenance of field devices- Diagnosing field devices- Display field devices

Page 3: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 3

Setting a New Standard

of Integration

SIMATIC PDMA new, standardized approach

One piece of software for standardized operation of all field devices

Device Descriptions (DD)

Now Before PDM

Different programs for operation of the associated field devices and components

SIMATIC PDM for

operation of all field devices and components

based on EDD technology

Page 4: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 4

Setting a New Standard

of Integration

DD

Proper name is EDD = Electronic Device Descriptor

Describes:

All the parameters in the device

All the interactions between parameters in the device

How to read/write those parameters over the communication bus

Describes simple methods for performing functions (ie set address, quick start etc.)

Page 5: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 5

Setting a New Standard

of Integration

Electronic Device Descriptor Language EDDL

is a standard for Hart, PROFIBUS and Foundation Fieldbus (OPEN)

Stores information as a text file, therefore it is independent on PC operating system

Page 6: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 6

Setting a New Standard

of Integration

PDM is a DD interpreter

DD = Device Description

HART - device

HART - Device Description+

SIMATICPDM

Hand heldCommunicator

275

Page 7: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 7

Setting a New Standard

of Integration

SIMATIC PDMVersatile communication

Communication with PROFIBUS field devices

on PROFIBUS-DP on PROFIBUS-PA

via PA coupler or via PA link

HART field devices via SIMATIC ET200M remote I/O via SIMATIC ET200iS remote I/O via HART modem via HART multiplexer

Company-specific field devices on SIPART bus via isolated coupling to SIREC recorders

Page 8: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 8

Setting a New Standard

of Integration

CommunicationPROFIBUS

PROFIBUS DP

PROFIBUS PA

Page 9: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 9

Setting a New Standard

of Integration

CommunicationHART on PROFIBUS

PROFIBUS DP

Page 10: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 10

Setting a New Standard

of Integration

CommunicationHART via multiplexer

PROFIBUS DP

Page 11: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 11

Setting a New Standard

of Integration

CommunicationHART via HART modem

PROFIBUS DP

In the workshop

M

M

M M

Page 12: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 12

Setting a New Standard

of Integration

Communicationover Ethernet

Ethernet / Fast Ethernet

PROFIBUS DP

IE/PB LinkS7- 400

Page 13: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 13

Setting a New Standard

of Integration

SIMATIC PDM - Connection points in the automation system

Ethernet

Operator Station OS (e.g. Win CC)

RS232/ RS485

Engineering Station ES

.... .... ....

HART multiplexer / interface

Any device with any communication on the workbench

Possible SIMATIC PDM connection point

PROFIBUS PA

PROFIBUS DP

PROFIBUS DP 45.45 kBit/s

PROFIBUS PA

S7- 400H S7- 400 S7- 300

redundant

ET 200M DP/PA link ET 200iS

PROFIBUS DP

IE/PB Link

Page 14: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 14

Setting a New Standard

of Integration

A word about HART Protocol

Highway Addressable Remote Transducer Based on Bell 202 Frequency shift keying to superimpose

digital signal on top of a 4-20 mA signal Open standard (www.hartcomm.org)

Designed to: Replace 4-20 mA Remote configuration Remote diagnostics Can be multi-dropped (up to 15)

Analog and digital communications Analog is fast (continuous) Digital is slow - 1200 bits/sec (i.e. 2-3 updates/sec)

Page 15: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 15

Setting a New Standard

of Integration

HART devices on PROFIBUS DP networks

Use a ET200M remote I/O rack

Advantages:- Have ‘best in class’- Over 90% of fieldbus devices sold are HART- This solution is part of Totally IntegratedAutomation (TIA)- PDM will work fine- Main process variable is updated just as fast as PROFIBUS PA- HART can be Cheaper!

Page 16: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 16

Setting a New Standard

of Integration

HART on PROFIBUS - COSTS

PROFIBUS PA wire is 2.45 Euro/meterHART wire is 1.42 Euro/meter

Description:# of Devices 1 2 3 4 5 6 7 8 9 10PROFIBUS PA power 130 130 130 130 130 130 130 130 130 130link 496 496 496 496 496 496 496 496 496 496coupler 736 736 736 736 736 736 736 736 736 736PROFIBUS adder 256 512 768 1024 1280 1536 1792 2048 2304 2560total: 1618 1874 2130 2386 2642 2898 3154 3410 3666 3922

HARTpower 130 130 130 130 130 130 130 130 130 130ET200 326 326 326 326 326 326 326 326 326 326HART input card 302 302 604 604 906 906 1208 1208 1600 1600HART adder 0 0 0 0 0 0 0 0 0 0Total 758 758 1060 1060 1362 1362 1664 1664 2056 2056

Page 17: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 17

Setting a New Standard

of Integration

HART on PROFIBUS

Installation costs can remove the Hardware savings

Some installations, HART is cheaper

Some installations, PROFIBUS PA is cheaper

Point to Remember: YOU CAN CONNECT ANY HART DEVICE TO PROFIBUS

Page 18: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 18

Setting a New Standard

of Integration

HART Commands

HART commands are divided up into three types:Universal commandsCommon practice commandsDevice specific commands

You can connect to a HART device by:1. Using a ‘Generic’ DD that will give you just the

Universal commands and Common practice commands but not the Device specific commands

2. Using a DD that has been written for the device that will give you access to all the commands

Page 19: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 19

Setting a New Standard

of Integration

PDM uses HCF Library

This means:- PDM can connect to any HART device using a ‘Generic’ DD

- PDM can connect to any HART device using the device specific DD in the HCF Library

- PDM can connect to many devices that havehad a special DD written for it for PDM

All Siemens-Milltronics equipment that has HART can connect to PDM in all three way!

Page 20: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 20

Setting a New Standard

of Integration

HART Communicator 275 (Emerson)

Does not have all the HART Library in it (Library is too big)

HART Communicator 275 costs approx. 3000 Euro

PDM cost approx. 400 Euro for base unit

Page 21: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 21

Setting a New Standard

of Integration

AMS software (Emerson)

Competes with PDM

Works with HART and Foundation Fieldbus

Has some nice features

However:- AMS software not support straight use of the HCFlibrary - AMS software can connect to any device but only with Universal commands and the common

practice commands.- This is not enough to configure devices!

Device has to be made ‘AMSaware’ to use all HART commands

Page 22: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 22

Setting a New Standard

of Integration

SIMATIC PDMVariants

Stand alone Local installation

Local connection to the field bus, service bus or electric circuit

Local database with export option in XML

Integrated into SIMATIC Integrated in hardware

project

System-wide commu-nication (routing)

Optimum integration into SIMATIC S7 /PCS 7

Page 23: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 23

Setting a New Standard

of Integration

SIMATIC PDMUser interface (1) SIMATIC PDM has

Standardized displays and user interface Terminology and linguistics based on DIN V 19259 and

IEC 65/349/CD, and conforms to VDI/VDA GMA 2187 is Windows-compatible

Views of process devices Process devices – Network view Process devices – System view with status information Hardware project (integrated into SIMATIC S7 /PCS 7)

Page 24: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 24

Setting a New Standard

of Integration

SIMATIC PDMUser interface (2)

Documentation Online help and Getting

Started

Status of parameter values loaded, modified, invalid,

initial value, not supported

Automatic assignment: Device – Parameter data records

User interface in German English French Spanish Italian

Offline parameterization possible including consistency check

Page 25: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 25

Setting a New Standard

of Integration

SIMATIC PDMUser interface (3)

Parameterization / comparison Online with offline Device with device

Presentation of process values Curves Bar chart

Device diagnostics Status Quality

Commissioning aids Calibration Alignment Adjustment

Identification Bus scan (life list) Device identification HART multiplexer scan

Page 26: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 26

Setting a New Standard

of Integration

Ordering Information - PDM

Catalog sheet is on the web at www.fielddevices.comLinks to the product page on our websiteDifferent options available:

- Integrated into PCS7- Routing via S7-400- Hart Multiplexer

Base Software Gives you:- up to 4 tags per project (unlimited # of projects)- communications via HART modem- communications via RS232- communications via Profibus DP/PA

Siemens Internal use version (6ES7 658-3GA05-0YC0):- only for Siemens people and distributors - base software (100 EURO for two licenses)- pop up with ‘For Siemens internal use only’

Page 27: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 27

Setting a New Standard

of Integration

HART Modems

RS-232 to HART Modem (7MF49971DA) - made by MACTek

USB to HART Modem (ordered from MACTek)

MACTek can be found at www.mactekcorp.com

Page 28: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 28

Setting a New Standard

of Integration

ExampleLR200 HART connection

PLCRB

+

-

HART Modem

PC

HART Device

If the PLC internal resistance is < 250 ohms, then RB of 250 to 350 ohms needs to be added.

Page 29: Introduction to SIMATIC PDM  And  How to connect to a LR200 Radar via HART

PDM & LR200 Webinar

Automation and Drives

PI5 James Powell 17.10.03 29

Setting a New Standard

of Integration

ExampleLR200 HART connection

Live demonstation