interior installation...2021/06/01  · spacing, typ.24" snap bar 'b' section...

12
INTERIOR INSTALLATION 1 1 2 " 1 1 4 " 3 1 2 " SYSTEM DEPTH 12" MAX CRC OVERHANG, TYP. 48" MAX HANGER WIRE SPACING, TYP. 12" MAX SNAP BAR OVERHANG, TYP. 48" MAX CRC SPACING, TYP. 24" SNAP BAR SPACING, TYP. 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6 AND A1.7* SNAP BAR CARRIER SPLICE SEE DETAIL A1.3 FIXTURE SPECIFICATIONS SEE DETAIL A1.8 AND A1.9 SUSPENSION REQUIREMENTS SEE DETAIL A1.2 WALL TRIM CONDITIONS SEE DETAIL A1.5 1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER) AT 48" O.C. MAX SPACING, BY OTHERS, TYP. SNAP-IN PANEL HEAVY-DUTY SNAP BAR (SECONDARY CARRIER) CROSS CONNECTOR CLAMP SECTION 'B' SCALE: 3" = 1'-0" 3 1 2 " SYSTEM DEPTH 1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER) AT 48" O.C. MAX SPACING, BY OTHERS, TYP. SNAP-IN PANEL HEAVY-DUTY SNAP BAR (SECONDARY CARRIER) CROSS CONNECTOR CLAMP *TRIM NOT SHOWN FOR CLARITY 12 GA HANGER WIRE, BY OTHERS, NOT BY CERTAINTEED SEE DETAIL A1.2 5015 Oakbrook Parkway, Suite 100 Norcross, GA 30093 O 800 366 4327 F 770 806 0214 www.certainteed.com/architectural SPECIFICATIONS (unless noted otherwise) MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL HEAVY-DUTY SNAP BAR SECONDARY CARRIER FINISH: PAINT | POWDER COAT | LUXACOTE PERFORATION: SEE DETAIL A1.1 OVERALL ISOMETRIC VIEW PROJECT: SNAP-IN PRODUCT SPECIFICATIONS DRAWING NUMBER: SNAP-IN-A1.0 SCALE: AS SHOWN DRAWN BY: CTA ENGINEERING DATE: 6/1/21 These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Upload: others

Post on 17-Aug-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

INTERIOR INSTALLATION

11 2"11 4"

31 2" SYS

TEM

DEPT

H 12" MAX CRC

OVERHANG, TYP.

48" MAX HANGER WIRE

SPACING, TYP.

12" MAX SNAP BAR

OVERHANG, TYP.

48" MAX CRC

SPACING, TYP.

24" SNAP BAR

SPACING, TYP.

'B'

SECTION 'A'SCALE: 3" = 1'-0"

PANEL SPECIFICATIONSSEE DETAIL A1.1

'A'

FLOATING TRIM CONDITIONSSEE DETAIL A1.6 AND A1.7*

SNAP BAR CARRIER SPLICESEE DETAIL A1.3

FIXTURE SPECIFICATIONSSEE DETAIL A1.8 AND A1.9

SUSPENSION REQUIREMENTSSEE DETAIL A1.2

WALL TRIM CONDITIONSSEE DETAIL A1.5

1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER)AT 48" O.C. MAX SPACING, BY OTHERS, TYP.

SNAP-IN PANEL

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

CROSS CONNECTOR CLAMP

SECTION 'B'SCALE: 3" = 1'-0"

31 2" SYS

TEM

DEPT

H

1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER)AT 48" O.C. MAX SPACING, BY OTHERS, TYP.

SNAP-IN PANEL

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

CROSS CONNECTOR CLAMP

*TRIM NOT SHOWN FOR CLARITY

12 GA HANGER WIRE, BY OTHERS,NOT BY CERTAINTEEDSEE DETAIL A1.2

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

OVERALL ISOMETRIC VIEW

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.0

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 2: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

PANEL MATERIAL

.032" OR .040" ALUMINUM

PANEL FINISHES

PAINTED & POWDER COATED

DECORATED WOOD FINISH (POWDER COATED)

LUXACOTE

PANEL CONFIGURATIONS

12"WIDTH UP TO 96" LONG

24" WIDTH UP TO 48" LONG

8 SQUARE FEET MAX PANEL SIZE

OTHER SIZES AVAILABLE, CONTACT CERTAINTEED

PERFORATION % OPEN103 20.0%106 16.0%115 12.0%119 8.0%132 20.0%201 19.6%

PERFORATIONS

MAX PANEL SIZE MAY BE LIMITED BASED ON PERFORATIONPATTERN, CONTACT CERTAINTEED

1. LIFT PANEL

2. SNAP PANEL DIMPLES INTO SNAP BAR

SNAP-IN PANEL DIMPLES

CROSS CONNECTOR CLAMP

HEAVY-DUTY SNAP BAR (SECONDARY CARRIER)

1/2" X 1-1/2" 16 GA CRC(PRIMARY CARRIER), BYOTHERS, TYP.

31 2" SYS

TEM

DEPT

H

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

PANEL SPECIFICATIONS

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.1

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 3: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

INTERIOR INSTALLATION

48" MAX HANGER WIRE SPACING (CRC SPAN)

12" MAX CRC

OVERHANG

12" MAX SNAP

BAR OVERHANG

48" MAX CRC SPACING (SNAP BAR SPAN)

24" X 24" SNAP-IN PANEL

24" SNAP BAR SPACING

(PANEL LENGTH)

1/2" X 1-1/2" 16 GA GALV. CRC (PRIMARY CARRIER)

CROSS CONNECTOR CLAMP

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

12 GA HANGER WIRE BY OTHERS'B' 'A'

SECTION 'A'SCALE: 3" = 1'-0"

SECTION 'B'SCALE: 3" = 1'-0"

11 2"11 4" 1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER)

AT 48" O.C. MAX SPACING, BY OTHERS, TYP.

SNAP-IN PANEL

HEAVY-DUTY SNAP BAR (SECONDARY CARRIER)

CROSS CONNECTOR CLAMP 1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER)AT 48" O.C. MAX SPACING, BY OTHERS, TYP.

SNAP-IN PANEL

CROSS CONNECTOR CLAMP

31 2"11 4"

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

117 32"

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

2'-0" X 2'-0" PANEL SUSPENSION SPECIFICATIONS

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.2

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 4: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

INTERIOR INSTALLATION

48" MAX HANGER WIRE SPACING (CRC SPAN)

12" MAX CRC

OVERHANG

12" MAX SNAP

BAR OVERHANG

48" MAX CRC SPACING (SNAP BAR SPAN) 48" SNAP BAR SPACING

(PANEL LENGTH)

1/2" X 1-1/2" 16 GA GALV. CRC (PRIMARY CARRIER)

CROSS CONNECTOR CLAMP

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

12 GA HANGER WIRE BY OTHERS

24" X 48" SNAP-IN PANEL

'B' 'A'

SECTION 'A'SCALE: 3" = 1'-0"

SECTION 'B'SCALE: 3" = 1'-0"

11 2"2" 1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER)

AT 48" O.C. MAX SPACING, BY OTHERS, TYP.

SNAP-IN PANEL

HEAVY-DUTY SNAP BAR (SECONDARY CARRIER)

CROSS CONNECTOR CLAMP 1/2" x 1-1/2" 16 GA CRC (PRIMARY CARRIER)AT 48" O.C. MAX SPACING, BY OTHERS, TYP.

SNAP-IN PANEL

CROSS CONNECTOR CLAMP

2"

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

117 32" 31 2"

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

2'-0" X 4'-0" PANEL SUSPENSION SPECIFICATIONS

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.3

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 5: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

'A'

'B' IF THE DESIRED HEAVY-DUTY SNAP BARLENGTH EXCEEDS THE MAXIMUM OF 16'-0",USE A SNAP-IN PROFILE SPLICE TO CONNECTTHE FACTORY SNAP-IN PROFILE ENDS.

THE SHEAR TABS WILL SECURE THE SPLICEAND ADDITIONAL FASTENERS ARE NOTREQUIRED.

24" X 24" SNAP-IN PANEL

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

SECTION 'A'SCALE: FULL

SECTION 'B'SCALE: 3" = 1'-0"

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

HEAVY-DUTY SNAP BAR SPLICE

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.4

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 6: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

CORRECT REMOVALSCALE: 3" = 1'-0"

VIEW FROM BELOWSCALE: NTS

SNAP-INDIMPLE SIDE

CORRECT LOCATION

HEAVY-DUTY

SNAP BAR DIRECTION 1/2" x 1-1/2"

16 GA CRC DIRECTION

TO FIND CORRECT LOCATION FOR ACCESS TOOL, INSERT ACCESSTOOL AT PANEL INTERSECTION. ALIGN EDGE OF BLADE WITHEDGE OF PANEL. IF INSERTED IN PROPER LOCATION, YOU SHOULDHEAR A "CLICK" SOUND AND THE WOODEN HANDLE WILL SEATFLUSH AGAINST THE PANEL FACE. IF NOT INSERTED IN PROPERLOCATION, BLADE WILL STOP BEFORE WOOD HANDLE SEATS. IFTHIS HAPPENS, REMOVE TOOL AND INSERT IN ADJACENT PANELEDGE. (AROUND THE CORNER).

ACCESS TOOL(PART # T63165)

NOTE: 5 BLADES INCLUDEDWITH TOOL HANDLE.

ADDITIONAL REPLACEMENTBLADES MAY BE ORDERED

CORRECT

INCORRECT

INCORRECT LOCATION

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

ACCESS TOOL SPECIFICATIONS

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.5

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 7: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

'B'

'A'

FIELD CUT PANEL SIDE

1" WALL ANGLE, USE ANGLE ABOVE ASHOLD DOWN FOR CUT PANEL EDGE

FIELD CUT PANEL END

1" WALL ANGLE, USE ANGLE ABOVE ASHOLD DOWN FOR CUT PANEL EDGE

12'-0" WALL ANGLE TRIM

1"1"1" WALL ANGLE

0.025" ALUMINUMFINISH TO MATCH, TYP.

SECTION 'A'SCALE: 3" = 1'-0"

SECTION 'B'SCALE: 3" = 1'-0"

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

24" X 24" SNAP-IN PANEL

*VERTICAL SUPPORT OMITTED FOR CLARITY

1/2" X 1-1/2" 16 GA GALV. CRC(PRIMARY CARRIER)

CROSS CONNECTOR CLAMP

1" WALL ANGLE TRIM

FIELD MITER TRIMSAT CORNERS

FIELD CUT ALL SNAP-INPANEL SIDES FOR WIDTH

AS REQUIRED, TYP.

FIELD CUT ALL SNAP-IN PANEL ENDSFOR LENGTH AS REQUIRED, TYP.

1" WALL ANGLE HOLD DOWN TO SECURE FIELDCUT PANEL SIDES AND ENDS. HOLD DOWNNOT REQUIRED AT FULL PANEL EDGES.

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

8" MAX CRC SPACING (SNAP BAR SPAN)

48" MAX CRC SPACING (SNAP BAR SPAN)

12" MAX OVERHANG

1/2" X 1-1/2" 16 GA CRC(PRIMARY CARRIER), BY OTHERS, TYP.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

WALL ANGLE TRIM

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.6

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 8: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

FIELD MITERTRIMS ATCORNERS

12 GA HANGER WIREBY OTHERS, TYP.

SECTION 'A'SCALE: 3" = 1'-0"

SECTION 'B'SCALE: 3" = 1'-0"

FIELD CUT PANEL END

SNAP-IN TRIM FOR FIELD CUT PANEL

1/2" X 1-1/2" 16 GA CRC(PRIMARY CARRIER), BY OTHERS, TYP.

12 GA HANGER WIRE BY OTHERS

FIELD CUT PANEL SIDE

SNAP-IN TRIM FOR FIELD CUT PANEL

HEAVY-DUTY SNAP BAR (SECONDARY CARRIER)

CROSS CONNECTOR CLAMP

1/2" X 1-1/2" 16 GA CRC (PRIMARY CARRIER), BY OTHERS, TYP.

SUPPLEMENTAL CRC & HANGER WIRE FOR TRIM SUPPORT BY OTHERS

CLIP ANGLE TO SECURE SUPPLEMENTALCRC TO PRIMARY CARRIER, BY OTHERS

12 GA HANGER WIRE BY OTHERS, TYP.

SUPPLEMENTAL CRC & HANGERWIRE FOR TRIM SUPPORT BY

OTHERS. SECURE TO PRIMARYCARRIER WITH CLIP ANGLE.

'A' 'B'

SNAP-IN FLOATING TRIM0.032" ALUMINUMFINISH TO MATCH, TYP.

POP RIVET BOX MOLD TO TRIM, BY OTHERS

HOLD DOWN CLIP

10'-0" SNAP-IN FLOATING

TRIM FOR FIELD CUT PANEL

3-1/

2" N

OM.

2" N

OM.

1-1/2"

1"

1/2" X 1-1/2" 16 GA GALV. CRC(PRIMARY CARRIER)

CROSS CONNECTOR CLAMP

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

24" X 24" SNAP-IN PANEL

BOX MOLD TRIM0.025" ALUMINUMFINISH TO MATCH, TYP.

10'-0" BOX MOLD TRIM

1-3/

4"

1"

11" CLIP PART LENGTH POP RIVET BOX MOLD TO TRIM, BY OTHERS

HOLD DOWN CLIP

48" MAX CRC SPACING (SNAP BAR SPAN)

12" MAX OVERHANG

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

FIELD CUT FLOATING TRIM

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.7

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 9: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

FULL PANEL END

SNAP-IN FLOATING TRIM

1/2" X 1-1/2" 16 GAGALV. CRC (PRIMARY

CARRIER)CROSS CONNECTOR

CLAMP

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

24" X 24" SNAP-IN PANEL'A'

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

1/2" X 1-1/2" 16 GA CRC (PRIMARYCARRIER), BY OTHERS, TYP.

12 GA HANGER WIRE BY OTHERS

CROSS CONNECTOR CLAMP

FULL PANEL SIDE

SNAP-IN FLOATING TRIM

POP RIVET PANEL TO TRIM, BY OTHERS

CROSS CONNECTOR CLAMP

1/2" X 1-1/2" 16 GA CRC (PRIMARY CARRIER), BY OTHERS, TYP.

SUPPLEMENTAL CRC & HANGER WIRE FOR TRIM SUPPORT BY OTHERS

CLIP ANGLE TO SECURE SUPPLEMENTALCRC TO PRIMARY CARRIER, BY OTHERS

12 GA HANGER WIRE BY OTHERS, TYP.

SECTION 'A'SCALE: 3" = 1'-0"

SECTION 'B'SCALE: 3" = 1'-0"

3-1/

2" N

OM.

1-1/

4" N

OM.

1-1/2"

2"

10'-0" SNAP-IN FLOATING

TRIM PART LENGTH

SNAP-IN FLOATING TRIM

SNAP-IN FLOATING TRIM0.032" ALUMINUMFINISH TO MATCH, TYP.

FIELD NOTCH TOP FLANGE OF TRIM TOCLEAR CROSS CONNECTOR CLAMP

FIELD MITERTRIMS ATCORNERS

SUPPLEMENTAL CRC & HANGERWIRE FOR TRIM SUPPORT BY

OTHERS. SECURE TO PRIMARYCARRIER WITH CLIP ANGLE.

'B'

12" MAX

OVERHANG

12 GA HANGER WIREBY OTHERS, TYP.

HEAVY-DUTYSNAP BAR(SECONDARYCARRIER)

FIELD NOTCHTOP FLANGE OFTRIM TO CLEAR CROSSCONNECTOR CLAMP, TYP.

48" MAX CRC SPACING (SNAP BAR SPAN)

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

FULL PANEL FLOATING TRIM

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.8

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 10: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

'B'

'B'

SECTION 'B'SCALE: 3" = 1'-0"

SECTION 'A'SCALE: 3" = 1'-0"

*HANGER WIRE OMITTED FOR CLARITY

TYPICAL ISOMETRICSCALE: NOT TO SCALE

INTERIOR INSTALLATION

'A'

'A'

NOTE:FIXTURE OR DIFFUSER MUST BEINDEPENDENTLY SUPPORTED INACCORDANCE WITH LOCAL BUILDING CODESAND MANUFACTURER'S INSTRUCTIONS

3/8"

3 8"

23'-14" CLEAR OPENING

24" SNAP BAR SPACING

1/2" X 1-1/2"16 GA GALV.CRC (PRIMARYCARRIER)

CROSSCONNECTORCLAMP"MT" FLANGE LIGHT

FIXTURE, BY OTHERS**

3/8"

24" X 24"SNAP-IN TILE

2" S

YSTE

MDE

PTH

24" CLEAR OPENINGCROSS

CONNECTORCLAMP

1/2" x 1-1/2"16 GA CRC

(PRIMARY CARRIER),BY OTHERS, TYP.

FULL 24" X 24"SNAP-IN

PANEL, TYP.

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

24" CLEAR OPENING23-1/4" CLEAR OPENING

31 2" SYS

TEM

DEPT

H

**RECOMMENDED MFG:LITHONIA: SERIES 2SP MT (OR EQUAL)

24" X 24"SNAP-IN TILE

HEAVY-DUTYSNAP BAR(SECONDARYCARRIER)

"MT" FLANGE LIGHTFIXTURE, BY OTHERS**

HEAVY-DUTYSNAP BAR(SECONDARYCARRIER)

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

2'-0" X 2'-0" FIXTURE OPENING

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.9

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 11: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

SECTION 'B'SCALE: 3" = 1'-0"

SECTION 'A'SCALE: 3" = 1'-0"

*HANGER WIRE OMITTED FOR CLARITY

TYPICAL ISOMETRICSCALE: NOT TO SCALE

INTERIOR INSTALLATION

NOTE:FIXTURE OR DIFFUSER MUST BEINDEPENDENTLY SUPPORTED INACCORDANCE WITH LOCAL BUILDING CODESAND MANUFACTURER'S INSTRUCTIONS

24" X 24"SNAP-IN TILE

24" CLEAROPENING

24" X 24"SNAP-IN TILE

HEAVY-DUTYSNAP BAR(SECONDARYCARRIER)

CROSSCONNECTOR

CLAMP

FULL 24" X 24"SNAP-IN

PANEL, TYP.

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

24" CLEAR OPENING

6" MAX FROMPANEL EDGE

6" MAX FROMPANEL EDGE

6" MAX FROMPANEL EDGE

6" MAX FROMPANEL EDGE

FIXTURE, BY OTHERS,SEE NOTE THIS SHEET

FIXTURE, BY OTHERS,SEE NOTE THIS SHEET

FLANGEDFIXTUREREQUIRED

FLANGED FIXTUREREQUIRED

1/2" x 1-1/2"16 GA CRC

(PRIMARY CARRIER),BY OTHERS, TYP.

'A' 'B''A''B'

6" MAX 6" MAX

2" S

YSTE

MDE

PTH

1/2" X 1-1/2"16 GA GALV.CRC (PRIMARYCARRIER)

31 2" SYS

TEM

DEPT

H

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

FIELD CUT PANEL OPENING

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.10

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.

Page 12: INTERIOR INSTALLATION...2021/06/01  · SPACING, TYP.24" SNAP BAR 'B' SECTION 'A' SCALE: 3" = 1'-0" PANEL SPECIFICATIONS SEE DETAIL A1.1 'A' FLOATING TRIM CONDITIONS SEE DETAIL A1.6

SPLAYED 12 GA HANGERWIRE, BY OTHERS, TYP.

COMPRESSIONSTRUT, BY OTHERS

45°

45°

SE

N45°

LATERAL BRACING: BRACE WITH HANGER WIRES AND STRUTS PER ASTM E-580 AND IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS.

(4) #12 GAUGE WIRES SPLAYED 90° FROM EACH OTHER AT ANGLE NOT EXCEEDING 45° FROMPLANE OF CEILING. A STRUT FASTENED TO MAIN RUNNER SHALL BE EXTENDED TO ANDFASTENED TO STRUCTURE ABOVE. SPLAYED WIRE AND STRUT BRACING TO BE PLACED NOTMORE THAN 12 FEET ON CENTER IN EACH DIRECTION, WITH THE FIRST POINT WITHIN 6 FEETFROM EACH WALL.

W45

°

N

SW

E

1/2" x 1-1/2" 16 GA CRC (PRIMARYCARRIER), BY OTHERS, TYP.

HEAVY-DUTY SNAP BAR(SECONDARY CARRIER)

(1) #10 X 1/2" TEK SCREW,BY OTHERS, TYP.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800 366 4327

F 770 806 0214

www.certainteed.com/architectural

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .032" | .040" ALUMINUM SNAP-IN PANEL | 24 GA GALV. STEEL

HEAVY-DUTY SNAP BAR SECONDARY CARRIER

FINISH: PAINT | POWDER COAT | LUXACOTE

PERFORATION: SEE DETAIL A1.1

SEISMIC SPECIFICATIONS

PROJECT: SNAP-IN PRODUCT SPECIFICATIONS

DRAWING NUMBER: SNAP-IN-A1.11

SCALE: AS SHOWN

DRAWN BY: CTA ENGINEERING

DATE: 6/1/21

These drawings show typical conditions for installing the CertainTeed product shown. They should not be construed as a substitute for an

architectural or engineering design and do not reflect the unique requirements of local codes, laws, statutes or regulations that may be applicable

for a specific installation. CertainTeed assumes no liability for the accuracy or completeness of the drawings for a specific installation or the

fitness of the drawings for a particular purpose. The user is advised to consult with local licensed design professionals in order to assure

compliance with all legal requirements. CertainTeed is not licensed to provide professional engineering or architectural services.