instruction manual smoke inlet 10-year battery smoke …

1
11-16 12-16 9-16 7-16 8-16 5-16 6-16 Install at a distance of at least 50cm from fluorescent light sources. 50 cm Fig.8 smoke alarm Fig.7 Install at a distance of at least 61cm from the corner of the wall. To mount the smoke alarm, proceed as follows: Use the screws to fix the base plate in the chosen position. Pay attention to the figure above (Fig.4-Fig.8). Gently tighten the alarm onto the base plate. Mount the alarm in the center of the ceiling of the room. Do not mount the alarm in a place that is difficult to reach. Do not paint the alarm. Fig.9 Twist to tighten Twist to loose SCREWS SCREWS Bracket INSTRUCTION MANUAL 10-YEAR BATTERY SMOKE ALARM FS-MINI Read the instruction manual before use. 1. General This smoke alarm device uses photoelectric technology. It is designed for detecting smoke in the air, not for sensing heat, gas or flame. If the smoke alarm is properly mounted and maintained, it will be activated at the very start. The smoke alarm is designed to detect smoke, it can not prevent a fire. Please read the instruction manual carefully before you use this smoke alarm. The “device” hereinafter stands for “smoke alarm device”. 2. Device & Spare parts 1 2 3 1-Main unit 2-User manual 3-Screws and dowels ( 2 sets) Fig.1 2-16 3. General figure 4. Power on Fig.2 LED indicator Test/Hush button Smoke inlet Back cover Fig.3 3-16 To switch to power ON, unscrew the bottom cover and remove the small magnet (Fig.3). CAUTION: The built-in Lithium battery of the product can not be replaced. Standby time is 10 years at normal use condition. The device is working if the LED indicator is flashing and a continuous "Beep" alarm sounds when pressing the Test/Hush button. Note: To switch the device OFF, put the small magnet back into place. If there is no LED light flashing and a successive "Beep" alarm signal is given when the Test/Hush button is pressed, the device has been switched OFF. 5. Device specificationsDimensionØ 45x42 mm Weight50g Operate Temperature0- 50Working Voltage: 3V Standby current: 7uA Humidity10% - 90% Service environment: house supply Designed life: 10 years 4-16 15-16 6. Mounting The smoke alarm should be mounted in the following places: at least one in each room one on each floor, if the floor is large, two or more smoke alarms should be installed in the hallway and staircase in the living room in each bedroom in the storage room or spaces with electric equipment The alarm should not be mounted in the following places: a room in which the temperature can drop below 0˚C or rise above 50˚C in damp rooms in front of doors or windows near a ventilator or radiator. Smoke alarm for minimal protection Smoke alarm for extra protection Fig.4 1. Bedroom 2. Bedroom 3. Staircase 4. Bedroom 5. Livingroom 6. Kitchen 7. Entrance 8. Hobby area 9.Guest bathroom 10. Bathroom 11. Storage 12. Garage Fig.5 Do not install in the tip of a 30-50 cm from the tip is to be observed. If the slope is up to 45° the smoke alarm can be installed on the slope. Fig.6 sloping ceiling as smoke-free air can collect in these areas. If the ceiling slopes over 30° and has a total height of 30° up to 6 m, a distance of 30 - 50 cm 6 m 7. Functionality The device goes into standby mode once powered on, with the LED blinking once every 344 seconds. Fig.10 7.1 This device is capable of self-regulating to long term drift of photoelectric chamber to ensure long-time stability of the device 7.2 Standby mode 7.3 Test Fig.11 ~ To test the device, press and hold the Test/Hush button until the device gives a continuous audible alarm, and the LED starts blinking. When the Test/ Hush button is released, the audible and visible alarm stops. Meanwhile, the device goes into Hush mode. Repeat the above steps to exit Hush mode. 7.4 Hush mode 1. In Standby mode, press the Test/Hush button to enter Hush mode. 2. In the state of an alarm, press the Test/Hush button to enter Hush mode. 3. The whole process of the Hush mode lasts for 9 minutes. 4. In the Hush mode, hold the Test/Hush button until 10-16 Fig.12 acoustic alarm signal is emitted. The device exits the Hush mode and returns to Standby mode. Attention: 1. In Standby mode or during an alarm, press the Test/Hush button to enter Hush mode. The LED indicator will flash once every 10 seconds. Hold the Test/Hush button until the acoustic alarm signal is emitted and the device will exit Hush mode. 2. The device will not enter Hush mode if the Test/ Hush button is pressed with a long hold. It will enter Hush mode only with a short press of the button. 3. When the device is in Standby mode or Hush mode, please pay close attention to the time interval of the flashing LED. If the LED flashes once every 10 seconds, it’s in Hush mode. If the LED flashes once every 344 seconds, it’s in Standby mode. 4. On Hush mode, the device gives a normal alarm when the smoke concentration in the ambiance is more than 4 times of alarming value. every 10 seconds 7.5 Low battery When the device is in low-battery condition, it will sound a Beep” once every 43 seconds. 7.6 Malfunction or end-of-life When the device malfunctions or reaches its end of life, it will sound a continuously “Beep” every 43 seconds. Fig.13 Fig.14 Please replace device under conditions of malfunction, end of life or low-battery warning. 8. Precautions for use Test regularly Do not paint Do not use this device in dusty or smoky ambiance. Both designed device lifetime and battery standby time is 10 years. The sealed Lithium battery is not replaceable. This device is not designed to prevent a fire. Hence, it is necessary to take precautions against a fire such as allocating extinguishers, emergency ladders and fire blankets. Users with a hearing disorder may not be made aware of the audible alarm when this device is used. WE will not be made liable for loss and / or damage , including incidental and/ or if device was not used according to the instructions and/ or consequential loss, arising from the fact that the signal from the smoke alarm did not sound during smoke or fire. 13-16 IMPORTANT When the device is alarming or in standby mode, press the Test/Hush button once to enter Hush mode. Press the Test/Hush button again to exit Hush mode. 14-16 Imported and distributed by Harkness & Young Ltd. PO BOX 11-344, Ellerslie, Auckland 1542, New Zealand www.harco.co.nz 0086-CPR-550646 Beep x 1 Beep x 3 INSTRUCTION MANUAL 10-YEAR BATTERY SMOKE ALARM FS-MINI

Upload: others

Post on 30-May-2022

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTRUCTION MANUAL Smoke inlet 10-YEAR BATTERY SMOKE …

11-16 12-169-16

7-16 8-165-16 6-16

Install at a distance of at least 50cm from fluorescent light sources.

50 cmFig.8

smoke alarmFig.7

Install at a distance of at least 61cm from the corner of the wall.

To mount the smoke alarm, proceed as follows:

– Use the screws to fix the base plate in the chosen

position. Pay attention to the figure above (Fig.4-Fig.8).

– Gently tighten the alarm onto the base plate.

– Mount the alarm in the center of the ceiling of the room.

– Do not mount the alarm in a place that is difficult to

reach.

– Do not paint the alarm.

Fig.9

Twist to tighten

Twist to loose

SCREWS

SCREWS

Bracket

INSTRUCTION MANUAL10-YEAR BATTERY SMOKE ALARM

FS-MINI

Read the instruction manual before use.

1. GeneralThis smoke alarm device uses photoelectric technology. It is designed for detecting smoke in the air, not for sensing heat, gas or flame. If the smoke alarm is properly mounted and maintained, it will be activated at the very start. The smoke alarm is designed to detect smoke, it can not prevent a fire. Please read the instruction manual carefully before you use this smoke alarm.The “device” hereinafter stands for “smoke alarm device”.2. Device & Spare parts

1

23

1-Main unit2-User manual3-Screws and dowels ( 2 sets)

Fig.1

2-16

3. General figure

4. Power on

Fig.2

LED indicator

Test/Hush button

Smoke inlet

Back cover

Fig.3

3-16

To switch to power ON, unscrew the bottom cover and remove the small magnet (Fig.3).

CAUTION: The built-in Lithium battery of the product can not be replaced. Standby time is 10 years at normal use condition.

The device is working if the LED indicator is flashing and a continuous "Beep" alarm sounds when pressing the Test/Hush button.

Note: To switch the device OFF, put the small magnet back into place. If there is no LED light flashing and a successive "Beep" alarm signal is given when the Test/Hush button is pressed, the device has been switched OFF.

5. Device specifications:Dimension:ΦØ 45x42 mmWeight:50gOperate Temperature:0℃ - 50℃Working Voltage: 3VStandby current: ≤7uAHumidity:10% - 90%Service environment: house supplyDesigned life: 10 years

4-16

15-16

6. MountingThe smoke alarm should be mounted in the

following places:

• at least one in each room

• one on each floor, if the floor is large, two

or more smoke alarms should be installed

• in the hallway and staircase

• in the living room

• in each bedroom

• in the storage room or spaces withelectric equipment

The alarm should not be mounted in the following places:

• a room in which the temperature

can drop below 0˚C or rise above 50˚C

• in damp rooms

• in front of doors or windows

• near a ventilator or radiator.

Smoke alarm for minimal protectionSmoke alarm for extra protection

Fig.4

1. Bedroom2. Bedroom3. Staircase4. Bedroom5. Livingroom6. Kitchen7. Entrance8. Hobby area9.Guest bathroom10. Bathroom11. Storage12. Garage

Fig.5

Do not install in the tip of a

30-50 cm from the tipis to be observed. If the slope is up to 45° the smoke alarm can be installed on the slope.

Fig.6

sloping ceiling as smoke-free air can collect in these areas. If

the ceiling slopes over 30° and has a total height of

30° up to 6 m, a distance of

30 - 50 cm

6 m

7. Functionality

The device goes into standby mode once powered on, with the LED blinking once every 344 seconds.

Fig.10

7.1 This device is capable of self-regulating to long term drift of photoelectric chamber to ensure long-time stability of the device

7.2 Standby mode

7.3 Test

Fig.11

~

To test the device, press and hold the Test/Hush button until the device gives a continuous audible alarm, and the LED starts blinking. When the Test/Hush button is released, the audible and visible alarm stops. Meanwhile, the device goes into Hush mode. Repeat the above steps to exit Hush mode.

7.4 Hush mode

1. In Standby mode, press the Test/Hush button to enter Hush mode.2. In the state of an alarm, press the Test/Hush button to enter Hush mode.3. The whole process of the Hush mode lasts for 9 minutes.4. In the Hush mode, hold the Test/Hush button until

10-16

Fig.12

acoustic alarm signal is emitted. The device exits the Hush mode and returns to Standby mode.

Attention:

1. In Standby mode or during an alarm, press the Test/Hush button to enter Hush mode. The LED indicator will flash once every 10 seconds. Hold the Test/Hush button until the acoustic alarm signal is emitted and the device will exit Hush mode.2. The device will not enter Hush mode if the Test/Hush button is pressed with a long hold. It will enter Hush mode only with a short press of the button.3. When the device is in Standby mode or Hush mode, please pay close attention to the time intervalof the flashing LED. If the LED flashes once every 10 seconds, it’s in Hush mode. If the LED flashes once every 344 seconds, it’s in Standby mode.4. On Hush mode, the device gives a normal alarm when the smoke concentration in the ambiance is more than 4 times of alarming value.

every 10 seconds

7.5 Low battery

When the device is in low-battery condition, it will sound a “Beep” once every 43 seconds.7.6 Malfunction or end-of-life

When the device malfunctions or reaches its end of life, it will sound a continuously “Beep” every 43 seconds.

Fig.13

Fig.14

Please replace device under conditions of malfunction, end of life or low-battery warning.8. Precautions for use

• Test regularly

• Do not paint

• Do not use this device in dusty or smoky ambiance.

• Both designed device lifetime and battery standby time is 10 years. The sealed Lithium battery is not replaceable.

• This device is not designed to prevent a fire. Hence, it is necessary to take precautions against a fire such as allocating extinguishers, emergency ladders and fire blankets.

• Users with a hearing disorder may not be made aware of the audible alarm when this device is used.

• WE will not be made liable for loss and / or damage , including incidental and/ or if device was not used according to the instructions and/ or consequential loss, arising from the fact that the signal from the smoke alarm did not sound during smoke or fire.

13-16

IMPORTANT

When the device is alarming or in standby mode, press the Test/Hush button once to enter Hush mode. Press the Test/Hush button again to exit Hush mode.

14-16

Imported and distributed by Harkness & Young Ltd.

PO BOX 11-344,Ellerslie, Auckland 1542,

New Zealand

www.harco.co.nz

0086-CPR-550646

Beep x 1

Beep x 3

INSTRUCTION MANUAL