TENDER DOCUMENT (TENDER No: NRO/CON/696/660) FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1 & 2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1, 2 &3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K) VOLUME III BOQ / PRICE BID PROJECT MANAGEMENT CONSULTANT: ENGINEERING PROJECTS (INDIA) LIMITED (A GOVT. OF INDIA ENTERPRISE) Northern Regional office 2 ND Floor, CORE-3, SCOPE COMPLEX, 7LODHI ROAD, NEW DELHI 110003. TEL. NO: 011- 24361666 FAX NO: 011- 24363426 E-Mail: [email protected]

Upload: others

Post on 25-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

TENDER DOCUMENT

(TENDER No: NRO/CON/696/660)

FOR

BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO.

11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1 & 2),

THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1, 2 &3) AND

OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE

CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K)

VOLUME – III

BOQ / PRICE BID

PROJECT MANAGEMENT CONSULTANT:

ENGINEERING PROJECTS (INDIA) LIMITED

(A GOVT. OF INDIA ENTERPRISE) Northern Regional office

2ND Floor, CORE-3, SCOPE COMPLEX, 7–LODHI ROAD, NEW DELHI – 110003.

TEL. NO: 011- 24361666 FAX NO: 011- 24363426

E-Mail: [email protected]

Page 2: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

In Figures In Words In Figures In Words

Annexure-X

1.0 A POWER SUPPLY PACKAGE FOR

SUBSTATION 1

1.1 POWER SUPPLY PACKAGE FOR

SUBSTATION 1 (As per DSR 2013) 1270208.00

1.2 POWER SUPPLY PACKAGE FOR

SUBSTATION 1 (As per Non DSR) 12748660.00

2.0 B POWER SUPPLY PACKAGE FOR

SUBSTATION II & COMPACT TYPE

SUBSTATION

2.1 POWER SUPPLY PACKAGE FOR

SUBSTATION II & COMPACT TYPE

SUBSTATION (As per DSR 2013)1714164.00

2.2 POWER SUPPLY PACKAGE FOR

SUBSTATION II & COMPACT TYPE

SUBSTATION (As per Non DSR)

22329210.00

3.0 C EXTERNAL LIGHTING

3.1 EXTERNAL LIGHTING WORK (As per

DSR 2013)22452.00

3.2 EXTERNAL LIGHTING WORK (As per

Non DSR)99480.00

4.0 D CIVIL WORK

4.1 CIVIL WORK (As per DSR 2013) 6552688.00

4.2 CIVIL WORK (As per Non DSR) 600.00

Annexure-Y

5.0 E MISC. CIVIL, ELECTRICAL & FIRE

FIGHTING WORK5.1 MISC. CIVIL, ELECTRICAL & FIRE

FIGHTING WORK (As per DSR 2013)931243.00

5.2 MISC. CIVIL, ELECTRICAL & FIRE

FIGHTING WORK (As per Non DSR)375668.40

I Total amount for DSR items 10490755.00

II Total amount for Non DSR items 35553618.40

III Total (I+II) 46044373

BIDDER FINANICIAL OFFER Rs:-( IN FIGURES)

Rs:-( IN WORDS)

Note:-

SEAL AND SIGNATURE OF BIDDER

ENGINEERING PROJECTS (INDIA) LTD.

NIT No. NRO/CON/696/660

Quoted rates shall be inclusive of all taxes & duties including GST.

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1&2),

THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE

PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

Bidder's Price

% Quote at Above/ PAR/ BelowS. No. DescriptionEstimated Cost

(Rs.)

Amount in Rs. After adding Percentage at

Above/ PAR/ BelowSection

PRICE BID FOR QUOTING SHEET

1 of 1

Page 3: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

DSR-2013 MR TOTAL

I. A POWER SUPPLY PACKAGE FOR SUBSTATION I 1270208.00 12748660.00 14,018,868.00

II. B

POWER SUPPLY PACKAGE FOR SUBSTATION II

& COMPACT TYPE SUBSTATIONS (CSS 1 TO

CSS 3)

1,714,164.00 22,329,210.00 24,043,374.00

III. C EXTERNAL LIGHTING 22,452.00 99,480.00 121,932.00

IV D Civil Work 6,552,688.00 600.00 6,553,288.00

V E Misc. Civil, Electrical & FF work 931,243.00 375,668.40 1,306,911.40

GRAND TOTAL 10,490,755.00 35,553,618.40 46,044,373.40

SAY Rs. ₹ 46,044,373.00

Annexure-Y

(Rupees four Crore sixty lacs forty four thousand three Hundred seventy three only)

GRAND SUMMARY OF POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1&2),

THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT

CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SUB-

HEADSECTION SH. DESCRIPTION

ESTIMATED COST IN RUPEES

SUMMARY SHEET

Annexure-X

Page 4: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

DSR-2013 MR TOTAL

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS 104,054.00 2,037,000.00 2,141,054.00

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING 611,750.00 3,254,000.00 3,865,750.00

III. DG SETS & ACCESSORIES 0.00 4,078,000.00 4,078,000.00

IV.MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-DISTRIBUTION

BOARDS0.00 3,313,000.00 3,313,000.00

V. LT CABLES 386,154.00 66,660.00 452,814.00

VI. EARTHING 168,250.00 0.00 168,250.00

TOTAL AMOUNT (In Rs.) 1,270,208.00 12,748,660.00 14,018,868.00

SAY Rs. ₹ 14,018,868.00

Annexure-X

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION

(ESS-1&2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL

WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION - A: ABSTRACT COST FOR BALANCE WORK OF POWER SUPPLY PACKAGE FOR SUBSTATION - I

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 5: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS

H.T. CABLE

1.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV

grade of following sizes direct in ground including excavation, sand cushioning,

protective covering and refilling the trench etc. as required.8.1

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 100 M 256.00 25,600.00 8.1.2

1.0A (Part

of sec.-B)

Laying of one number additional PVC insulated and PVC sheathed / XLPE power

cable of 11 KV grade of following size direct in ground in the same trench in one tier

horizontal formation including excavation, sand cushioning, protective covering and

refilling the trench etc as required. 8.2

(DSR-2013)

ii) Above 120sqmm and upto 400 sqmm. 100 M 182.00 18,200.00 8.2.2

2.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11

KV grade of following size in the existing RCC/HUME/ METAL pipe as required.8.3

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 40 M 53.00 2,120.00 8.3.2

3.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11

KV grade of following size in the existing masonry open duct as required.8.4

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 150 M 45.00 6,750.00 8.4.2

4.0 Supplying and making indoor cable end termination with heat shrinkable jointing kit

complete with all accessories including lugs suitable for following size of 3 core, XLPE

aluminium conductor cable of 11 KV grade as required :10.4

(DSR-2013)

i) 240 sq.mm 4 Set 7,007.00 28,028.00 10.4.3

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1&2), THREE NO. OUTDOOR TYPE

11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT

VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION - A: ABSTRACT COST FOR BALANCE WORK OF POWER SUPPLY PACKAGE FOR SUBSTATION - I

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

Item No. /

Sub-Head Description Qty.

Page 1 of 16

Page 6: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

ii) 400 sq.mm 2 Set 11,678.00 23,356.00 DR/DSR

5.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL (SUBSTATION - 1)

Supplying, installation, testing & commissioning of indoor type floor mounted metal

clad, 11KV VCB panel with 4 No. VCBs, totally enclosed and fully interlocked,

horizontal drawout, horizontal / vertical isolation type breaker as per IS 13118, as

amended up to date and additional specifications, having capacities as mentioned

below, single break, trip free mechanism, motorised / manually charged and auto /

manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C. supply with

short circuit fault level of 350 MVA, complete with self contained, fully interlocked,

rack in and rack out mechanism, air insulated but encapsulated copper bus bars of

800 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand

trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and

equipped with following switchgears and accessories i/c connections suitable for 3

core 400 sq.mm XLPE 11KV cable (cable entry from bottom / top / side), end

termination with heat shrinkable joint(6 metre length) including 80mm thick glass wool

insulation with aluminium cladding 26 guage aluminium sheet, electric starter,

batteries & ba

1 Set 2,037,000.00 2,037,000.00 (MR)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OF FOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker with motorised spring

charged and manual closing mechanism. Shunt trip coil shall operate in 110V DC

voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer 300/150/5/5Amp

epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ Ö3, 110V/ Ö3, 100VA burden of class 0.5 epoxy cast resin

type with 1 No. voltmeter (0-15KV), analog / digital type, selector switch with voltmeter

& protection mcb for H.T. Metering upto 12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/F protection. (over

load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

Page 2 of 16

Page 7: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

viii) 1 No. digital type Ammeter (0-300Amp) (96mm square) with selector switch.

ix) 1 No. electronic type digital energy analyser having minimum 30 days memory and

parameters of voltage, current, frequency, KW, KVA, KVAr, PF Power factor etc.

shall be suitable for BMS operation with 485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVA capacity for auxillary

supply for breaker closing coil, indicating lamps, space heaters etc. control

transformer shall be epoxy cast resin dry type and the connection for control

transformer shall be taken from the cable side before the circuit breaker tapping.

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPE aluminium armoured

cable.

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OF FOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker with motorised spring

charged and manual closing mechanism. Shunt trip coil shall operate on 110V DC

voltage derived through a power pack.

ii) 3 No. Single Phase double core current transformer 50/5 Amp epoxy cast insulated

class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

Page 3 of 16

Page 8: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/F protection. (Relay

shall be for highset instantaneous protection for over current & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. Auxiliary relay (VAA33) for transformer fault, alarm and trip suitable for 230 V

AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-50 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

x) 1 Set of fuses, ferrules, wiring etc. as required.

xi) 1 No. hooter.

xii) 1 No. master trip relay.

xiii) 1 No. power pack for trip coil operation.

xiv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminium armoured

cable.

- All metering and protection devices, interconnections, necessary control wiring and all

other accessories shall be provided as per specifications, technical requirement of

local electric supply authority.

TOTAL OF SUBHEAD I - HT CABLE & VACUUM CIRCUIT BREAKER CARRIED

OVER TO THE SUMMARY. 104,054.00 2,037,000.00

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING

1.0 DISTRIBUTION TRANSFORMER (OIL TYPE) (OLTC TYPE)

Page 4 of 16

Page 9: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

Supply, installation, testing & commissioning of 800 KVA 11KV/433V, 3 phase 50 Hz

outdoor copper wound oil type distribution transformer with OLTC (On Load Tap

Changer) with AVR and RTCC Panel. Vector group Dyn-11 ONAN cooled having

cable end box suitable for 3 core 240 sq.mm XLPE Aluminium conductor 11KV cable

on HV & multicore aluminium XLPE cable on L.T. side with all fittings &

accessories, bucholtz relay alarm & trip, WTI alarm & trip and oil temperature

alarm & trip control wiring, all civil work including foundation etc. complete as

per specifications & conforming to IS 2026-1977 and complying with specification

and requirement of local electric supply authority.

2 No. 1,557,000.00 3,114,000.00 (MR)

2.0 BUS TRUNKING

Supply, installation, testing & commissioning of following capacity / rating

prefabricated Air insulated bus trunking / Bus Duct suitable for 415 volts 3 phase, 4

wire 50Hz AC supply system (Between Transformer L.T. side and incomer of L.T.

Panel side) of aluminium busbars complete with bends, expansion joints, fire barriers,

copper fexible end connection at both ends, Earthing with 2 runs of copper /

aluminium earth of size 25mm x 5mm strip etc. including necessary support etc. as

per specification and as required.3.5

(DSR-2013)

a) Bus Trunking

i) 1250 Amp 50 M 12,235.00 611,750.00 3.5.3

b) Copper Flexible for Bus Trunking (Average length 320mm)

i) 1250 Amp 4 Set 35,000.00 140,000.00 (MR)

(Note: The bus trunking shall be measured along the length of enclosure. The

aluminium/ copper strips which will go inside LT panels & end termination box

of transformers shall not be taken into measurement of bus trunking quantity).

TOTAL OF SUBHEAD II - DISTRIBUTION TRANSFORMER & BUS TRUNKING

CARRIED OVER TO SUMMARY. 611,750.00 3,254,000.00

III. DG SETS & ACCESSORIES

Page 5 of 16

Page 10: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

1.0 Supply, installation, testing and commissioning of 200 KVA, 415 Volt, 3 phase, 1500

R.P.M, 0.8 PF radiator with fan cooled, floor mounted Diesel Generator set complete

with Alternator of 200 KVA, 415 Volt AC. Engine Coupled to Alternator housed in

acoustic enclosure conforming to latest environment protection regulations for

emmission and noise levels complete with Diesel Engine developing either 246 BHP

at 1500 RPM or actual BHP calculated considering de-rating factor if any whichever is

higher Alternator and all accessories including supply and installation of Engine

control panel with meters, CTs and transducers for all metering and protection, AMF

Panel suitable for auto start / stop of DG Set, Auto changeover of gird and DG supply,

interlocking with required switchgear, contactor (AC3 duty), Instrument, relay, timer

etc. complete, antivibration mountings, hospital type silencer, flexible pipe

connections, exhaust piping with bends etc. (6 metre length) including 80mm thick

glass wool insulation with aluminium cladding 26 guage aluminium sheets, electric

starter, batteries & battery charger, fuel tank of 990 ltrs.capacity with level indicator,

radiator, control wiring, first fill of lubricating oil, and Diesel for testing and

commissioning and all spares and accessories as required complete with necessary

civil work such as grouting, chipping, finishing etc.as required complete including

foundation (Foundation to be paid and measured under separate item) (Foundation to

be done by the Contractor based on DG Set manufacturer Shop Drawing). The work

should be as per Central Electrical Inspectorate/ Pollution control board standards.

(Refer Technical Specification)

1 No. 1,867,000.00 1,867,000.00 (MR)

Page 6 of 16

Page 11: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

2.0 Supply, installation, testing and commissioning of 250 KVA, 415 Volt, 3 phase, 1500

R.P.M, 0.8 PF water cooled, radiator type floor mounted Diesel Generator set

complete with Alternator of 250 KVA, 415 Volt AC. Engine Coupled to Alternator

housed in acoustic enclosure conforming to latest environment protection regulations

for emmission and noise levels complete with Diesel Engine developing either 310

BHP at 1500 RPM or actual BHP calculated considering de-rating factor if any

whichever is higher alternator considering de-rating factor if any whichever is higher

alternator and all accessories including supply and installation of Engine control panel

with meters, CTs and transducers for all metering and protection, AMF Panel suitable

for auto start / stop of DG Set, Auto changeover of gird and DG supply interlocking

with required switchgear, contactor (AC3 duty), Instrument, relay, timer etc. complete,

antivibration mountings, hospital type silencer, flexible pipe connections, exhaust

piping with bends etc. (6 metre length) including 80mm thick glass wool insulation

with aluminium cladding 26 guage aluminium sheet, electric starter, batteries & battery

charger, fuel tank of 990 ltrs. capacity with level indicator, radiator, control wiring,

first fill of lubricating oil, and Diesel for testing and commissioning and all spares and

accessories as required complete with necessary civil work such as grouting,

chipping, finishing etc.as required complete including foundation (Foundation to be

paid and measured under separate item) (Foundation to be done by the Contractor

based on DG Set manufacturer Shop Drawing). The work should be as per Central

Electrical Inspectorate/ Pollution control board standards. (Refer Technical

Specification)

1 No. 2,211,000.00 2,211,000.00 (MR)

TOTAL OF SUBHEAD III - DG SETS & ACCESSORIES CARRIED OVER TO THE

SUMMARY. 0.00 4,078,000.00

IV. MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-DISTRIBUTION

BOARDS

1.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS1/MLTP)

Page 7 of 16

Page 12: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

Supply, installation, testing & commissioning of Main L.T. Panel extensible type

suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supply totally enclosed

type with free standing floor mounted dust and vermin proof compartmentalised indoor

type fabricated from 2mm thick CRCA sheet steel complete with busbars, ammeter,

ammeter selector switch, voltmeter, voltmeter selector switch, indicating lamps,

protection relays, CT's, protection fuses, interconnections with suitable size of copper

leads/solid aluminium strips/rod and having following incoming and outgoing Air

Circuit Breakers, MCCB's as per the drawing and technical specifications complete

as required. (TOTAL OF A TO D)

1 Set 1,825,000.00 1,825,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 1250Amp FP Manually operated horizontal drawout type (MDO) Air Circuit

Breaker (50KA) with microprocessor release,O/L, S/C & E/F protection with

communication port RS485 port (Transformer Incomer).

B) BUSCOUPLER BREAKERS

● 1 No. 1250Amp FP Manually operated horizontal drawout type (MDO) Air Circuit

Breaker (50KA) as buscoupler with interlocking arrangement with incomers ACB.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

C) BUSBARS

● 1600 Amp TPN busbars of aluminium alloy (Bus-Section I & II).

D) OUTGOING BREAKERS WITH INSTRUMENTS

● 6 Nos. 800 Amp Three Pole Manually operated horizontal drawout type (MDO) Air

Circuit Breaker (50KA) with thermal magnetic release, with O/L, S/C & E/F protection

& neutral link.

● 4 Nos. 630 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection & neutral link.

● 2 No. 400 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection & neutral link.

E) INSTRUMENTS & RELAYS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mm square) (one for

each incoming breaker).

Page 8 of 16

Page 13: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

● 2 Nos. 0 to 1250 Amp digital ammeter (96mm square) with CT's (one for each

incoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one set for each

incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

● 2 Sets trip circuit healthy indicating lamp (one set for each incoming breaker).

● 2 Sets auto trip indicating lamp (one set for each incoming breaker).

● 2 Nos. of Dual ratio CT's of 1250/300/5/5Amp ratio each for APFC Relay (one for

each incoming breaker).

● 2 Nos. trip circuit supervision relay (one for each incoming breaker).

● 2 Nos. electronic type Digital energy analyser having 30 day memory and parameters

of KW, KWH, power factor, frequency etc. (one for each incoming breaker).

● 2 Nos. Phase squence relay (one for each incoming breaker).

● 2 Nos. master trip relay (one for each incoming breaker).

● 2 Set of O/V & U/V relay (one for each incoming breaker).

2.0 CAPACITOR BANK PANEL (200 KVAR)

Supply, installation, testing & commissioning of Capacitor Panel suitable for 415 volts

(nominal) 3 phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with free standing

floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA

sheet steel complete with busbars, ammeter, ammeter selector switch, voltmeter,

voltmeter selector switch, indicating lamps, protection relays, CT's protection fuses,

interconnections with suitable size of copper leads/solid aluminium strips/rod auto /

manual selector switch for operation of capacitor units, push buttons for manual

operation capacitor duty, contractors capacitor bank, APFC relay, power factor meter

etc. complete and having following incoming and outgoing Circuit Breakers etc. as per

the drawing and specifications complete as required. (TOTAL OF A TO C)

2 Set 351,000.00 702,000.00

A) INCOMER

● 1 No. 630 Amp FP Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection.

● 1 No. 0-630A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch.

Page 9 of 16

Page 14: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

● 1 Set of phase indicating lamps

B) BUSBARS

● 700A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 4 Nos. 63 Amp TP Moulded Case Circuit Breaker (25KA Ics Value) with neutral link.

● 10 Nos. 32 Amp TP Moulded Case Circuit Breaker (25KA Ics Value) with neutral link.

● 14 Nos. Capacitor duty contactor (one for each 25KVAR / 10KVAR) Capacitor unit.

● 4 Nos. 25 KVAR Capacitor Bank.

● 10 Nos. 10 KVAR Capacitor Bank.

● 14 sets of push button stations Red and Green for manual operation of capacitor units

with auto/manual selector switches.

● 1 No. Indicating lamp for each 25 KVAR / 10 KVAR capacitor unit to indicate that the

unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation of capacitor units.

● 1 No. Power factor meter.

3.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS1/EMLTP)

Supply, installation, testing & commissioning of Main L.T. Panel (Essential Supply)

extensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supply

totally enclosed type with free standing floor mounted dust and vermin proof

compartmentalised indoor type fabricated from 2mm thick CRCA sheet steel complete

with busbars, ammeter, ammeter selector switch, voltmeter,

Page 10 of 16

Page 15: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

voltmeter selector switch, indicating lamps, protection relays, CT's protection fuses,

interconnections with suitable size of copper leads/solid aluminium strips/rod. PLC

shall be provided for monitering power supply on various bus section and closing /

opening of incomer & bus coupler breakers and interlocking of incomer and bus

coupler breakers and having following incoming and outgoing Air Circuit Breakers,

MCCB's as per the drawing and technical specifications complete as required.

(TOTAL OF A TO E)

1 Set 679,000.00 679,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 400Amp FP Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection.

● 2 Nos. 400Amp FP contactor (AC 3 Duty) with timer switch.

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

i) Load management through Micro PLC shall be provided to achieve the following

functions.

ii) Auto changeover between incomer breakers.

iii) Buscoupler switching.

iv) Signal to AMF Panel for status of 'Load' to ensure auto stop / auto start of DG Set by

AMF Panel.

v) Interlocking of incomer and bus coupler breakers.

vi) Necessary hardware shall be provided to achieve above functions including micro

PLC with real time clock, digital inputs / outputs, MMI with 2 line display, power

supply, auxillary relays, push buttons, LED indication lamp, window announciation

facia etc. & software for the above. All items required for complete operation whether

or not list in BOQ shall deemed to be included in quoted rates.

vii) Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

- 1 No. 400Amp FP Contactor as buscoupler.

- 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

i) 600 Amp TPN busbars of aluminium alloy in Bus Section - I & II.

E) OUTGOING BREAKERS WITH INSTRUMENTS

Page 11 of 16

Page 16: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

i) 2 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection and neutral link.

ii) 2 Nos. 200 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

thermal magnetic release, O/L, S/C & E/F protection and neutral link.

iii) 2 Nos. 125 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

thermal magnetic release, O/L, S/C & E/F protection and neutral link.

iv) 2 Nos. 63 Amp Three Pole Moulded Case Circuit Breaker (25KA Ics Value) with

thermal magnetic release, O/L, S/C & E/F protection and neutral link.

F) INSTRUMENTS ON INCOMER BREAKERS

i) 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mm square) (one for

each incoming breaker).

ii) 2 Nos. 0 to 400 Amp digital ammeter (96mm square) with CT's and selector switch.

iii) 2 Sets of phase indicating lights (RYB) with protection mcb's (one set for each

incoming breaker).

iv) 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

v) 2 Nos. electronic type Digital energy analyser having 30 day memory and parameters

of KW, KWH, power factor, frequency etc. (one for each incoming breaker).

4.0 SDB - DISTRIBUTION BOARDS

Supply, installation, testing & commissioning of cubicle type tollally enclosure free

standing type moistue, dust and vermin proof Sub Distribution Boards (SDB) made

out of 2mm thick CRCA sheet steel complete with following equipments, including

ammeter, ammeter selector switch, voltmeter, voltmeter selector switch, indicating

lamps, CT's internal wiring with suitable size wires / cable, interconnection, pointing

etc. as per drawing and specification complete as required.

4.1 ESDB/SS1 (TOTAL OF A TO D) 1 Set 107,000.00 107,000.00 (MR)

A) INCOMING

● 1 No. 125Amp FP Moulded Case Circuit Breaker of (35KA Ics Value) with thermal

magnetic release and O/L, S/C & E/F protection.

Page 12 of 16

Page 17: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

B) INSTRUMENTS

● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selector switch.

● 1 No. 0 to 125 Amp digital ammeter (96mm square) with selector switch & CT's.

● 1 Set of phase indicating lights (RYB) with protection MCB.

C) BUSBARS

● 150Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 2 Nos. 100 Amp TP Moulded Case Circuit Breaker of (25KA Ics Value) with thermal

magnetic release, O/L & S/C protection and neutral link.

● 3 Nos. 32-63 Amp TP Moulded Case Circuit Breaker of (25KA Ics Value) with thermal

magnetic release, O/L & S/C protection and neutral link.

TOTAL OF SUBHEAD IV - MAIN LT PANELS, CAPACITOR BANK PANELS &

SUB-DISTRIBUTION BOARDS CARRIED OVER TO THE SUMMARY. 0.00 3,313,000.00

V. LT CABLES

1.0 Supply of following size of 1.1KV grade multicore aluminium conductor XLPE /

PVC insulated & PVC sheathed armoured cable as per IS: 7098 (Part-1) 1988

complete as required.

i) 3.5 core, 50 Sq.mm.220 M. 303.00 66,660.00 (MR)

2.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable

of 1.1 KV grade of following size direct in ground including excavation, sand

cushioning, protective covering and refilling the trench etc as required.7.1

(DSR-2013)

i) Upto 35 sq. mm 200 M. 181.00 36,200.00 7.1.1

(Part of sec.-

B)

ii)

Above 35 sq. mm and upto 95 sq. mm 220 M. 188.00 41,360.00 7.1.2

Page 13 of 16

Page 18: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

ii) Above 95 sq. mm and upto 185 sq. mm 50 M. 195.00 9,750.00 7.1.3

iii) Above 185 sq. mm and upto 400 sq. mm150 M. 215.00 32,250.00 7.1.4

3.0 Laying of one number additional PVC insulated and PVC sheathed / XLPE

power cable of 1.1 KV grade of following size direct in ground in the same

trench in one tier horizontal formation including excavation, sand cushioning,

protective covering and refilling the trench etc as required.7.2

(DSR-2013)

i) Upto 35 sq. mm 250 M. 124.00 31,000.00 7.2.1

ii) Above 95 sq. mm and upto 185 sq. mm 100 M. 138.00 13,800.00 7.2.3

iii) Above 185 sq. mm and upto 400 sq. mm 300 M. 159.00 47,700.00 7.2.4

4.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. 7.5

(DSR-2013)

i) Upto 35 sq. mm 36 M. 15.00 540.00 7.5.1

ii) Above 95 sq. mm and upto 185 sq. mm 20 M. 30.00 600.00 7.5.3

iii) Above 185 sq. mm and upto 400 sq. mm 48 M. 53.00 2,544.00 7.5.4

5.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size in the existing masonry open duct as required. 7.6

(DSR-2013)

i) Upto 35 sq. mm 20 M. 11.00 220.00 7.6.1

ii) Above 35 sq. mm and upto 95 sq. mm 20 M. 18.00 360.00 7.6.2

iii) Above 95 sq. mm and upto 185 sq. mm 20 M. 25.00 500.00 7.6.3

iv) Above 185 sq. mm and upto 400 sq. mm 30 M. 45.00 1,350.00 7.6.4

6.0 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power

cable of 1.1 KV grade of following size on wall surface / cable Tray as required. 7.7

(DSR-2013)

i) Upto 35 sq. mm (clamped with 1mm thick saddle) 60 M. 22.00 1,320.00 7.7.1

ii) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)100 M. 77.00 7,700.00 7.7.3

iii) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)220 M. 107.00 23,540.00 7.7.4

Page 14 of 16

Page 19: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

7.0 Suppling and making indoor end termination with brass compression gland and

aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE

aluminium conductor cable of 1.1 KV grade as required. 9.1

(DSR-2013)

i) 3.5 core, 400 Sq.mm. 12 Set 1,203.00 14,436.00 9.1.31

ii) 3.5 core, 300 Sq.mm. 12 Set 940.00 11,280.00 9.1.30

iii) 3.5 core, 150 Sq.mm. 4 Set 501.00 2,004.00 9.1.26

iv) 3.5 core, 50 Sq.mm. 4 Set 286.00 1,144.00 9.1.22

v) 4 core, 16 Sq.mm. 2 Set 208.00 416.00 9.1.33

8.0 Supply and installing following size of perforated M.S. cable trays with perforation not

more than 17.5% in convenient sections, joints with connectors suspended from the

ceiling with M.S. suspenders and including bolts & nuts, painting suspenders etc. as

per specification and as required.4.1

(DSR-2013)

i) 150 mm width X 50 mm depth X 1.6 mm thickness 30 M. 523.00 15,690.00 4.1.2

ii) 300 mm width X 50 mm depth X 1.6 mm thickness 40 M. 756.00 30,240.00 4.1.4

(Part of sec.-

B)

iii) 600 mm width X 50 mm depth X 2.0 mm thickness 45 M. 1,338.00 60,210.00 4.1.7

TOTAL OF SUBHEAD V - LT CABLES CARRIED OVER TO THE SUMMARY. 386,154.00 66,660.00

VI. EARTHING

1.0 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth

electrode including connection with brass nut, bolt, spring, washer excavation and re-

filling etc. as required.60 M. 1,019.00

61,140.00 5.10

(DSR-2013)

2.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth

electrode including connection with G.I. nut, bolt, spring, washer excavation and re-

filling etc. as required.80 M. 391.00

31,280.00 5.11

(DSR-2013)

Page 15 of 16

Page 20: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Unit

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per

NON DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty.

3.0 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for

connections etc. as required. 70 M. 812.0056,840.00

5.14

(DSR-2013)

4.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections

etc. as required. 130 M. 133.0017,290.00

5.15

(DSR-2013)

5.0 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as

required. 50 M. 34.001,700.00

5.16

(DSR-2013)

TOTAL OF SUBHEAD VI - EARTHING CARRIED OVER TO THE SUMMARY. 168,250.00 0.00

Page 16 of 16

Page 21: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

DSR-2013 MR TOTAL

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS 626,948.00 2,029,000.00 2,655,948.00

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING 0.00 6,540,000.00 6,540,000.00

III. DG SETS & ACCESSORIES 0.00 2,211,000.00 2,211,000.00

IV.MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-

DISTRIBUTION BOARDS0.00 4,361,000.00 4,361,000.00

V. COMPACT TYPE SUBSTATION & DISTRIBUTION FEEDER PILLARS 0.00 7,167,000.00 7,167,000.00

VI. L.T. CABLES 612,996.00 21,210.00 634,206.00

VII. EARTHING 474220.00 0.00 474,220.00

TOTAL 1,714,164.00 22,329,210.00 24,043,374.00

SAY ₹ 24,043,374.00

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION

(ESS-1&2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS

FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION - B: ABSTRACT COST FOR BALANCE WORK OF POWER SUPPLY PACKAGE FOR SUBSTATION II & COMPACT TYPE SUBSTATION (CSS)

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 22: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS

1.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of

11KV grade of following sizes direct in ground including excavation, sand

cushioning, protective covering and refilling the trench etc. as required. 8.1

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 750 M 256.00 192,000.00 8.1.2

2.0 Laying of one number additional PVC insulated and PVC sheathed / XLPE power

cable of 11 KV grade of following size direct in ground in the same trench in one tier

horizontal formation including excavation, sand cushioning, protective covering and

refilling the trench etc as required. 8.2

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 1200 M 182.00 218,400.00 8.2.2

3.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11

KV grade of following size in the existing RCC/HUME/ METAL pipe as required. 8.3

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 80 M 53.00 4,240.00 8.3.2

4.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11

KV grade of following size in the existing masonry open duct as required. 8.4

(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 1500 M 45.00 67,500.00 8.4.2

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1&2), THREE NO.

OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE

CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION - B: ABSTRACT COST FOR BALANCE WORK OF POWER SUPPLY PACKAGE FOR SUBSTATION II & COMPACT TYPE SUBSTATION (CSS)

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

Page 1 of 21

Page 23: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

5.0 Supplying and making indoor cable end termination with heat shrinkable jointing kit

complete with all accessories including lugs suitable for following size of 3 core,

XLPE aluminium conductor cable of 11 KV grade as required : 10.4

(DSR-2013)

i) 240 sq.mm 4 Set 7,007.00 28,028.00 10.4.3

ii) 400 sq.mm 10 Set 11,678.00 116,780.00 DR/DSR

6.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL (SUBSTATION

- 2)

Supplying, installation, testing & commissioning of indoor type floor mounted metal

clad, 11KV VCB panel with 4 No. VCBs, totally enclosed and fully interlocked,

horizontal drawout, horizontal / vertical isolation type breaker as per IS 13118, as

amended up to date and additional specifications, having capacities as mentioned

below, single break, trip free mechanism, motorised / manually charged and auto /

manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C. supply with

short circuit fault level of 350 MVA, complete with self contained, fully interlocked,

rack in and rack out mechanism, air insulated but encapsulated copper bus bars of

800 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand

trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and

equipped with following switchgears and accessories i/c connections suitable for 3

core 400 sq.mm XLPE 11KV cable (cable entry from bottom / top / side), end

termination with heat shrinkable jointing material etc. and complete as per

specification as required. (Note :- Cost of end termination not included in this item)

(TOTAL OF A & B)

1 Set 2,029,000.00 2,029,000.00 (MR)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OF FOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker with motorised spring

charged and manual closing mechanism. Shunt trip coil shall operate in 110V DC

voltage derived through a power pack.

Page 2 of 21

Page 24: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

ii) 3 No. Single Phase double core double ratio current transformer 300/150/5/5Amp

epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ 3, 110V/ 3, 100VA burden of class 0.5 epoxy cast resin

type with 1 No. voltmeter (0-15KV), analog / digital type, selector switch with

voltmeter & protection mcb for H.T. Metering upto 12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/F protection. (over

load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-300Amp) (96mm square) with selector switch.

ix) 1 No. electronic type digital energy analyser having minimum 30 days memory and

parameters of voltage, current, frequency, KW, KVA, KVAr, PF Power factor etc.

shall be suitable for BMS operation with 485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVA capacity for

auxillary supply for breaker closing coil, indicating lamps, space heaters etc. control

transformer shall be epoxy cast resin dry type and the connection for control

transformer shall be taken from the cable side before the circuit breaker tapping.

xiii) 1 No. hooter.

Page 3 of 21

Page 25: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPE aluminium armoured

cable.

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OF FOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker with motorised spring

charged and manual closing mechanism. Shunt trip coil shall operate on 110V DC

voltage derived through a power pack.

ii) 3 No. Single Phase double core current transformer 90/5 Amp epoxy cast insulated

class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/F protection. (Relay

shall be for highset instantaneous protection for over current & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. auxiliary relay (VAA33) for transformer fault, alarm and trip suitable for 230 V

AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-100 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

xi) 1 Set of fuses, ferrules, wiring etc. as required.

xii) 1 No. hooter.

Page 4 of 21

Page 26: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

xiii) 1 No. master trip relay.

xiv) 1 No. power pack for trip coil operation.

xv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminium armoured

cable.

- All metering and protection devices, interconnections, necessary control wiring and all

other accessories shall be provided as per specifications, technical requirement of local

electic supply authority.

TOTAL OF SUBHEAD I - HT CABLE & VACUUM CIRCUIT BREAKER

CARRIED OVER TO THE SUMMARY. 626,948.00 2,029,000.00

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING

DISTRIBUTION TRANSFORMER (OIL TYPE) (OLTC TYPE)

1.0 Supply, installation, testing & commissioning of 1600 KVA 11KV/433V, 3 phase 50

Hz indoor copper wound oil type distribution transformer with OLTC (On Load Tap

Changer) with AVR and RTCC Panel. Vector group Dyn-11 ONAN cooled having

cable end box suitable for 3 core 240 sq.mm XLPE Aluminium conductor 11KV

cable on HV & Aluminium Bus Trunding / Bus Duct on L.T side with all fittings &

accessories, bucholtz relay alarm & trip, WTI alarm & trip and oil temperature

alarm & trip control wiring, all civil work including foundation etc. complete as

per specifications & conforming to IS 2026-1977 and complying with specification

and requirement of local electric supply authority.

2 No. 2,302,000.00 4,604,000.00 (MR)

2.0 BUS TRUNKING

Page 5 of 21

Page 27: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

Supply, installation, testing & commissioning of following capacity / rating

prefabricated Air insulated bus trunking / Bus Duct suitable for 415 volts 3 phase, 4

wire 50Hz AC supply system (Between Transformer L.T. side and incomer of L.T.

Panel side) of aluminium busbars complete with bends, expansion joints, fire barriers,

copper fexible end connection at both ends, Earthing with 2 runs of copper /

aluminium earth of size 25mm x 5mm strip etc. including necessary support etc. as

per specification and as required.

3.5

(DSR-2013)

a) Bus Trunking

ii 2500 Amp 50 M 32,000.00 1,600,000.00 (MR)

b) Copper Flexible for Bus Trunking (Average length 320mm)

i) 2500 Amp 4 Set 84,000.00 336,000.00 (MR)

(Note: The bus trunking shall be measured along the length of enclosure. The

aluminium/ copper strips which will go inside LT panels & end termination box

of transformers shall not be taken into measurement of bus trunking quantity).

TOTAL OF SUBHEAD II - DISTRIBUTION TRANSFORMER & BUS

TRUNKING CARRIED OVER TO SUMMARY. 0.00 6,540,000.00

III. DG SETS & ACCESSORIES

Page 6 of 21

Page 28: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

1.0 Supply, installation, testing and commissioning of 250 KVA, 415 Volt, 3 phase, 1500

R.P.M, 0.8 PF radiator with fan cooled, floor mounted Diesel Generator set complete

with Alternator of 250 KVA, 415 Volt AC. Engine Coupled to Alternator housed in

acoustic enclosure conforming to latest environment protection regulations for

emmission and noise levels complete with Diesel Engine developing either 310 BHP at

1500 RPM or actual BHP calculated considering de-rating factor if any whichever is

higher Alternator and all accessories including supply and installation of Engine control

panel with meters, CTs and transducers for all metering and protection, AMF Panel

suitable for auto start / stop of DG Set, Auto changeover of gird and DG supply,

interlocking with required switchgear, contactor (AC3 duty), Instrument, relay, timer etc.

complete, antivibration mountings, hospital type silencer, flexible pipe connections,

exhaust piping with bends etc. (6 metre length) including 80mm thick glass wool

insulation with aluminium cladding 26 guage aluminium sheets, electric starter, batteries

& battery charger, fuel tank of 990 ltrs. capacity with level indicator, radiator, control

wiring, first fill of lubricating oil, and Diesel for testing and commissioning and all

spares and accessories as required complete with necessary civil work such as grouting,

chipping, finishing etc.as required complete including foundation (Foundation to be paid

and measured under separate item) (Foundation to be done by the Contractor based on

DG Set manufacturer Shop Drawing). The work should be as per Central Electrical

Inspectorate/ Pollution control board standards. (Refer Technical Specification)

1 No. 2,211,000.00 2,211,000.00 (MR)

TOTAL OF SUBHEAD III - DG SETS & ACCESSORIES CARRIED OVER

TO THE SUMMARY. 0.00 2,211,000.00

IV. MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-

DISTRIBUTION BOARDS

1.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS2/MLTP-1)

Page 7 of 21

Page 29: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

Supply, installation, testing & commissioning of Main L.T. Panel extensible type

suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supply totally enclosed

type with free standing floor mounted dust and vermin proof compartmentalised

indoor type fabricated from 2mm thick CRCA sheet steel complete with busbars,

ammeter, ammeter selector switch, voltmeter, voltmeter selector switch, indicating

lamps, protection relays, CT's, protection mcb's, interconnections with suitable size of

copper leads/solid aluminium strips/rod having following incoming and outgoing Air

Circuit Breakers, MCCB's as per the drawing and technical specifications complete

as required. (TOTAL OF A TO E)

1 Set 2,586,000.00 2,586,000.00 (MR)

A) INCOMER BREAKERS

● 2 No. 2500Amp FP Manually operated horizontal drawout type (MDO) Air Circuit

Breaker (50KA) with microprocessor release, O/L, S/C & E/F protection with

communication port RS485 port (Transformer Incomer).

B) BUSCOUPLER BREAKERS

● 1 No. 2500Amp FP Manually operated horizontal drawout type (MDO) Air Circuit

Breaker (50KA) as buscoupler with interlocking arrangement with incomers.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

C) BUSBARS

● 3000 Amp TPN busbars of aluminium alloy (Bus-Section I & II).

D) OUTGOING BREAKERS WITH INSTRUMENTS

i) 8 Nos. 1250 Amp Three Pole Manually operated horizontal drawout type (MDO) Air

Circuit Breaker (50KA) complete with thermal magnetic release, O/L, S/C & E/F

protection & neutral link.

ii) 2 Nos. 800 Amp Three Pole Manually operated horizontal drawout type (MDO) Air

Circuit Breaker with thermal magnetic release, O/L, S/C & E/F protection & neutral

link.

Page 8 of 21

Page 30: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

iii) 2 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker (50KA) complete with

microprocessor release, O/L, S/C & E/F protection & neutral link.

E) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mm square) (one for

each incoming breaker).

● 2 Nos. 0 to 2500 Amp digital ammeter (96mm square) with CT's (one for each

incoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one set for each

incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

● 2 Sets trip circuit healthy indicating lamp (one set for each incoming breaker).

● 2 Sets auto trip indicating lamp (one set for each incoming breaker).

● 2 No. of Dual ratio CT's of 2500/500/5/5Amp ratio for APFC Relay (one for each

incomer breaker).

● 2 Nos. trip circuit supervision relay (one for each incoming breaker).

● 2 Nos. electronic type Digital energy analyser having 30 day memory and parameters

of KW, KWH, power factor, frequency etc. (one for each incoming breaker).

● 2 Nos. master trip relay (one for each incoming breaker).

● 2 Set of O/V & U/V relay (one for each incoming breaker).

● 2 Nos. Phase squence relay (one for each incoming breaker).

2.0 CAPACITOR BANK PANEL (SS-2)

Page 9 of 21

Page 31: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

Supply, installation, testing & commissioning of Capacitor Panel suitable for 415

volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with free

standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick

CRCA sheet steel complete with busbars, ammeter, ammeter selector switch,

voltmeter, voltmeter selector switch, indicating lamps, protection relays, CT's

protection fuses, interconnections with suitable size of copper leads/solid aluminium

strips/rod, auto / manual selector switch for operation of capacitor units, push buttons

for manual operation, capacitor duty contractors, capacitor bank, APFC relay, power

factor meter etc. complete and having following incoming and outgoing Circuit

Breakers etc. as per the drawing and specifications complete as required.

2.1 Capacitor Bank Panel (400 KVAR) 2 Set 518,000.00 1,036,000.00 (MR)

A) INCOMER

● 1 No. 1250 Amp FP Moulded Case Circuit Breaker (50KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection.

● 1 No. 0-1250A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch

● 1 Set of phase indicating lamps

B) BUSBARS

● 1500A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 4 Nos. 100 Amp TP Moulded Case Circuit Breaker (25KA Ics Value) with thermal

magnetic release and neutral link.

● 6 Nos. 63 Amp TP Moulded Case Circuit Breaker (25KA Ics Value) with thermal

magnetic release and neutral link.

● 4 Nos. 40 Amp TP Moulded Case Circuit Breaker (25KA Ics Value) with thermal

magnetic release and neutral link.

● 14 Nos. Capacitor duty contactor (one for each 50KVAR / 25KVAR/12.5KVAR)

Capacitor unit.

Page 10 of 21

Page 32: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

● 4 Nos. 12.5 KVAR Capacitor Bank.

● 4 Nos. 50 KVAR Capacitor Bank.

● 6 Nos. 25 KVAR Capacitor Bank.

● 14 Sets of push button stations Red and Green for manual operation of capacitor units

with auto/manual selector switches.

● 1 No. Indicating lamp for each 50 KVAR / 25 KVAR / 12.5KVAR capacitor unit to

indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation of capacitor units.

● 1 No. Power factor meter.

3.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS2/EMLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panel (Essential Supply)

extensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supply

totally enclosed type with free standing floor mounted dust and vermin proof

compartmentalised indoor type fabricated from 2mm thick CRCA sheet steel

complete with busbars, ammeter, ammeter selector switch, voltmeter, voltmeter

selector switch, indicating lamps, protection relays, CT's protection fuses,

interconnections with suitable size of copper leads/solid aluminium strips/rod . PLC

shall be provided for monitering power supply on various bus section and closing /

opening of incomer & bus coupler breakers and interlocking, auto / manual selector

switch, and having following incoming and outgoing Air Circuit Breakers, MCCB's

as per the drawing and technical specifications complete as required. (TOTAL OF A

TO F)

1 Set 634,000.00 634,000.00 (MR)

A) INCOMER BREAKERS

● 1 No. 800Amp FP Electrical operated horizontal drawout type (EDO) Air Circuit

Breaker (50KA) with microprocessor release, O/L, S/C & E/F protection.

Page 11 of 21

Page 33: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

● 1 No. 400Amp FP Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection.

● 1 No. 400Amp FP contactor (AC 3 Duty) with timer switch.

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

● Load management through Micro PLC shall be provided to achieve the following

functions.

● Auto changeover closing & opening incomer breakers.

● Buscoupler switching.

● Signal to AMF Panel for status of load to ensure Auto stop / Auto start of DG Sets by

AMF Panel. (Both DG Set)

● Interlocking.

● Necessary hardware shall be provided to achieve above functions including PLC with

real time clock, digital inputs / outputs, MMI with 2 line display, power supply,

auxillary relays, push buttons, LED indication lamp etc. and software for the above.

All items required for complete operation whether or not list in BOQ shall deemed to

be included in quoted rates.

● Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

● 1 No. 400Amp FP Contactor (AC 3 Duty) for closing & opening through PLC.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

● 1000 Amp TPN busbars of aluminium alloy in Bus Section - I.

● 500 Amp TPN busbars of aluminium alloy in Bus Section - II.

E) OUTGOING BREAKERS WITH INSTRUMENTS

● 2 Nos. 500 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection and neutral link.

● 3 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KA Ics Value) with

microprocessor release for O/L, S/C & E/F protection and neutral link.

Page 12 of 21

Page 34: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

● 2 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA Ics Value) with

thermal magnetic release for O/L, S/C & E/F protection and neutral link.

F) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mm square) (three for

each incoming breaker).

● 1 No. 0 to 800 Amp digital ammeter (96mm square) with CT's (for DG incoming

breaker) and selector switch.

● 1 No. 0 to 400 Amp digital ammeter (96mm square) with CT's (for DG incoming

breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one set for each

incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

● 2 Set trip circuit healthy indicating lamp (for incomer ACB Breaker).

● 2 Set auto trip indicating lamp (for incomer ACB Breaker).

● 2 No. electronic type Digital energy analyser having 30 day memory and parameters

of KW, KWH, power factor, frequency etc. (for each incomer).

● 2 No. master trip relay (for incomer ACB Breaker).

● 2 No. O/V & U/V relay (for incomer ACB Breaker).

● 2 No. of reverse power relay (for incomer ACB Breaker).

4.0 SDB - DISTRIBUTION BOARDS

Supply, installation, testing & commissioning of cubicle type tollally enclosure free

standing type moistue, dust and vermin proof Sub Distribution Boards (SDB) made

out of 2mm thick CRCA sheet steel complete with following equipments, including

ammeter, ammeter selector switch, voltmeter, voltmeter selector switch, indicating

lamps, CT's internal wiring with suitable size wires / cable, interconnection, pointing

etc. as per drawing and specification complete as required.

Page 13 of 21

Page 35: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

4.1 ESDB/SS2 (TOTAL OF A TO D)

1 Set 105,000.00 105,000.00 (MR)

A) INCOMING

● 1 No. 100Amp FP Moulded Case Circuit Breaker of (25KA Ics Value) with thermal

magnetic release and O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selector switch.

● 1 No. 0 to 100 Amp digital ammeter (96mm square) with selector switch & CT's.

● 1 Set of phase indicating lights (RYB) with protection MCB.

C) BUSBARS

● 150Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 5 Nos. 32-63 Amp TP Moulded Case Circuit Breaker of (25KA Ics Value) with

thermal magnetic release, O/L, S/C & E/F protection and neutral link.

TOTAL OF SUBHEAD IV - MAIN LT PANELS, CAPACITOR BANK

PANELS & SUB-DISTRIBUTION BOARDS CARRIED OVER TO THE

SUMMARY.

0.00 4,361,000.00

V. COMPACT TYPE SUBSTATION & DISTRIBUTION FEEDER PILLARS

1.0 COMPACT TYPE SUBSTATIONS (CSS - 1) [TYPICAL FOR CSS2]

.

Supply, Installation, Testing & Commissioning of Compact type substation consisting of

following equipments mounted in outdoor enclosure fabricated out of galvanised sheet steel

complete as per specifications complete as required. (TOTAL OF A TO C):

2 Set 2,149,000.00 4,298,000.00 (MR)

.

A) THREE WAY 11KV RING MAIN UNIT

.

Page 14 of 21

Page 36: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated in steel vessel with SF6 Gas

Insulated with self powered IDMT relay type VIP 35 for protection against phase to phase &

phase to earth protection and 2 Nos. 630 Amp TP Load Break Switch with earth switch

complete as required (Three Way RMU with One No. VCB for transformer Protection & 2 Nos.

Load break switches).

.

B) TRANSFORMER (OIL TYPE)

1 No. 400 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oil type, ONAN cooled,

hermitically sealed, copper wound Distribution transformer with off load tap changer of range

+5% to -5% insteps of 2.5%, cable end boxes on HV & LT side with all fittings & accessories,

WTI alarm & trip and oil temperature alarm & trip control wiring, complete as per

specifications & conforming to IS 2026-1977.

.

C) LT PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz AC supply, cubicle type dust

and vermin proof compartmentalised indoor type febricated from 2mm thick CRCA sheet steel

complete with busbars, Ammeter, Ammeter selector switch, voltmeter, voltmeter selector switch,

indicating lamp, interconnection and having follwing incoming and outgoing breakers as per

drawing and specification.

.

i) INCOMING

● 1 No. 630 Amp FP manually operated Fixed type (MF) Air Circuit Breaker (50KA) with

microprocessor release, with O/L, S/C & EF protection and ON/ OFF Indicating LED lights

complete as per specifications.

.

ii) INSTRUMENTS

● 1 No. 0 to 630 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 800Amp TPN aluminium busbar.

Page 15 of 21

Page 37: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

.

iv) TIE BREAKER

● 1 No. 250 Amp FP Moulded Case Circuit Breakers (35KA Ics Value) with microprocessor

release for O/L, S/C & EF protection and ON/ OFF Indicating LED lights complete as per

specifications.

v) OUTGOING

● 2 Nos. 300Amp TP Moulded Case Circuit Breaker (35KA Ics Value) with microprocessor

release and neutral link.

● 2 Nos. 200Amp TP Moulded Case Circuit Breaker (35KA Ics Value) with thermal magnetic

release and neutral link.

2.0 COMPACT TYPE SUBSTATIONS (CSS - 3)

Supply, Installation, Testing & Commissioning of Compact type substation consisting of

following equipments mounted in outdoor enclosure fabricated out of galvanised sheet steel

complete as per specifications complete as required. (TOTAL OF A TO C):

1 Set 2,149,000.00 2,149,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated in steel vessel with SF6 Gas

Insulated with self powered IDMT relay type VIP 35 for protection against phase to phase &

phase to earth protection and 2 Nos. 630 Amp TP Load Break Switch with earth switch

complete as required (Three Way RMU with One No. VCB for transformer Protection & 2 Nos.

Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 400 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oil type, ONAN cooled,

hermitically sealed, copper wound Distribution transformer with off load tap changer of range

+5% to -5% insteps of 2.5%, cable end boxes on HV & LT side with all fittings & accessories,

WTI alarm & trip and oil temperature alarm & trip control wiring, complete as per

specifications & conforming to IS 2026-1977.

Page 16 of 21

Page 38: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz AC supply, cubicle type dust

and vermin proof compartmentalised indoor type febricated from 2mm thick CRCA sheet steel

complete with busbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeter selector

switch, indicating lamp, interconnection and having follwing incoming and outgoing breakers as

per drawing and specification.

i) INCOMING

● 1 No. 630 Amp FP manually operated Fixed type (MF) Air Circuit Breaker (50KA) with

thermal magnetic release, with O/L, S/C & EF protection and ON/ OFF Indicating LED lights

complete as per specifications.

ii) INSTRUMENTS

● 1 No. 0 to 800 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 1000Amp TPN aluminium busbar.

.iv) TIE BREAKER

● 1 No. 500 Amp FP Moulded Case Circuit Breakers (35KA Ics Value) with microprocessor

release for O/L, S/C & EF protection and ON/ OFF Indicating LED lights complete as per

specifications.

v) OUTGOING

● 6 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value) with thermal magnetic

release and neutral link.

● 2 Nos. 100Amp TP Moulded Case Circuit Breaker (25KA Ics Value) with thermal magnetic

release and neutral link.

3.0 DISTRIBUTION FEEDER PILLAR

Page 17 of 21

Page 39: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

Supply, installation, testing & commissioning of Double door type with slanting top

dust, damp, vermin proof, weather proof type Distribution Feeder Pillars fabricated

from 2mm thick CRCA sheet including opening handle,locking arrangement

complete with incomer MCCB, busbar, indicating lights, protection mcbs, including

all civil works like excavation, PCC, bricks work, plastering, refilling, providing PVC

sleeves in foundation (Feeder Pillar foundation shall be of brick work minimum

600mm above from Ground level) etc. including epoxy painting of feeder pillar,

interconnection etc complete as per specifications as required.

3.1 I/FP-1 TYPICAL FOR II/FP-1, II/FP-2, III/FP-1 (TOTAL A TO D).4 Set 180,000.00 720,000.00

(MR)

A) INCOMING

● 1 No. 200Amp Four Pole Moulded Case Circuit Breaker of (35KA Ics Value) with

thermal magnetic release, O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1No. 0-200 Ammeter with selector switch and CT's.

● 1No. 0 -500 Volt voltmeter with selector switch.

● 1Set of phase indicating lamps with SP MCB.

C) BUSBARS

● 250Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 9 Nos. 40-63Amp Three Pole Moulded Case Circuit Breaker (25KA Ics Value) with

thermal magnetic release, O/L, S/C & E/F protection and neutral link.

TOTAL OF SUBHEAD V - COMPACT TYPE SUBSTATION &

DISTRIBUTION FEEDER PILLARS CARRIED OVER TO THE

SUMMARY.

0.00 7,167,000.00

VI. L.T. CABLES

Page 18 of 21

Page 40: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

1.0 Supply of following size of 1.1KV grade multicore aluminium conductor XLPE /

PVC insulated & PVC sheathed armoured cable as per IS: 7098 (Part-1) 1988

complete as required.

i) 3.5 core, 50 Sq.mm. 70 M. 303.00 21,210.00 (MR)

2.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size direct in ground including excavation, sand cushioning,

protective covering and refilling the trench etc as required. 7.1

(DSR-2013)

i) Upto 35 sq. mm 200 M. 181.00 36,200.00 7.1.1

ii) Above 35 sq. mm and upto 95 sq. mm 320 M. 188.00 60,160.00 7.1.2

iii) Above 95 sq. mm and upto 185 sq. mm 600 M. 195.00 117,000.00 7.1.3

iv) Above 185 sq. mm and upto 400 sq. mm 250 M. 215.00 53,750.00 7.1.4

3.0 Laying of one number additional PVC insulated and PVC sheathed / XLPE power

cable of 1.1 KV grade of following size direct in ground in the same trench in one tier

horizontal formation including excavation, sand cushioning, protective covering and

refilling the trench etc as required. 7.2

(DSR-2013)

i) Upto 35 sq. mm 300 M. 124.00 37,200.00 7.2.1

iii) Above 95 sq. mm and upto 185 sq. mm 500 M. 138.00 69,000.00 7.2.3

iv) Above 185 sq. mm and upto 400 sq. mm 250 M. 159.00 39,750.00 7.2.4

4.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. 7.5

(DSR-2013)

i) Upto 35 sq. mm 30 M. 15.00 450.00 7.5.1

ii) Above 35 sq. mm and upto 95 sq. mm 30 M. 23.00 690.00 7.5.2

iii) Above 95 sq. mm and upto 185 sq. mm 35 M. 30.00 1,050.00 7.5.3

iv) Above 185 sq. mm and upto 400 sq. mm 35 M. 53.00 1,855.00 7.5.4

5.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size in the existing masonry open duct as required. 7.6

(DSR-2013)

i) Upto 35 sq. mm 50 M. 11.00 550.00 7.6.1

ii) Above 35 sq. mm and upto 95 sq. mm 50 M. 18.00 900.00 7.6.2

Page 19 of 21

Page 41: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

iii) Above 95 sq. mm and upto 185 sq. mm 50 M. 25.00 1,250.00 7.6.3

iv) Above 185 sq. mm and upto 400 sq. mm 500 M. 45.00 22,500.00 7.6.4

6.0 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power

cable of 1.1 KV grade of following size on cable Tray as required.7.8

(DSR-2013)

i) Upto 35 sq. mm (clamped with 1mm thick saddle) 60 M. 19.00 1,140.00 7.8.1

ii) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)

60 M. 44.00 2,640.00 7.8.2

iii) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)

120 M. 54.00 6,480.00 7.8.3

iv) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

250 M. 84.00 21,000.00 7.8.4

7.0 Suppling and making indoor end termination with brass compression gland and

aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE

aluminium conductor cable of 1.1 KV grade as required. 9.1

(DSR-2013)

i) 3.5 core, 400 Sq.mm. 4 Set 1,203.00 4,812.00 9.1.31

ii) 3.5 core, 300 Sq.mm. 2 Set 940.00 1,880.00 9.1.30

iii) 3.5 core, 240 Sq.mm. 2 Set 824.00 1,648.00 9.1.29

iv) 3.5 core, 150 Sq.mm. 2 Set 501.00 1,002.00 9.1.26

v) 3.5 core, 120 Sq.mm. 10 Set 417.00 4,170.00 9.1.25

vi) 3.5 core, 95 Sq.mm. 1 Set 401.00 401.00 9.1.24

vii) 3.5 core, 50 Sq.mm. 2 Set 286.00 572.00 9.1.22

viii) 3.5 core, 35 Sq.mm. 4 Set 245.00 980.00 9.1.21

ix) 4 core, 400 Sq.mm. 4 Set 1,203.00 4,812.00 9.1.31

x) 4 core, 25 Sq.mm. 28 Set 211.00 5,908.00 9.1.34

xi) 4 core, 16 Sq.mm. 2 Set 208.00 416.00 9.1.33

8.0 Supply and installing following size of perforated M.S. cable trays with perforation

not more than 17.5% in convenient sections, joints with connectors suspended from

the ceiling with M.S. suspenders and including bolts & nuts, painting suspenders etc.

as required.4.1

(DSR-2013)

Page 20 of 21

Page 42: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)

DSR -2013 /

MR

Item No. /

Sub-Head Description Qty. Unit

Rate as per

DSR

(In Rs.)

i) 150 mm width X 50 mm depth X 1.6 mm thickness 30 M. 523.00 15,690.00 4.1.2

ii) 300 mm width X 50 mm depth X 1.6 mm thickness 40 M. 756.00 30,240.00 4.1.4

iii) 600 mm width X 50 mm depth X 2.0 mm thickness 50 M. 1,338.00 66,900.00 4.1.7

TOTAL OF SUBHEAD VI - SUBMAIN CABLES CARRIED OVER TO THE

SUMMARY. 612,996.00 21,210.00

VII. EARTHING

1.0 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including

accessories, and providing masonry enclosure with cover plate having locking

arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as

required.14 Set 8,939.00 125,146.00

5.6

(DSR-2013)

2.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including

accessories, and providing masonry enclosure with cover plate having locking

arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as

required. 22 Set 4,367.00 96,074.00

5.4

(DSR-2013)

3.0 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth

electrode including connection with brass nut, bolt, spring, washer excavation and re-

filling etc. as required. 100 M. 1,019.00 101,900.00

5.10

(DSR-2013)

4.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth

electrode including connection with G.I. nut, bolt, spring, washer excavation and re-

filling etc. as required. 120 M. 391.00 46,920.00

5.11

(DSR-2013)

5.0 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for

connections etc. as required. 100 M. 812.00 81,200.00

5.14

(DSR-2013)

6.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections

etc. as required. 160 M. 133.00 21,280.00

5.15

(DSR-2013)

7.0 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as

required. 50 M. 34.00 1,700.00

5.16

(DSR-2013)

TOTAL OF SUBHEAD VII - EARTHING CARRIED OVER TO THE

SUMMARY. 474,220.00 0.00

Page 21 of 21

Page 43: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

DSR-2013 MR TOTAL

I. EXTERNAL LIGHTING WORKS 22,452.00 99,480.00 121,932.00

TOTAL OF EXTERNAL ELECTRICAL

WORKS121,932.00

SAY ₹ 121,932.00

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC

SUBSTATION (ESS-1&2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL

ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA

(J&K).

SECTION - C: ABSTRACT COST FOR BALANCE WORK OF EXTERNAL ELECTRICAL WORKS

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 44: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

1.0 FEEDER PILLARS (EXTERNAL LIGHTING)

Supply, installation, testing & commissioning of dust, damp, vermin proof, weather

proof type fabricated from 2mm thick CRCA sheet steel including locking

arrangement complete with incomer MCCB, busbar, ammeter, ammeter selector

switch, voltmeter, voltmeter selector switch, CT's, indicator lights, protection mcb

including all civil works (Feeder Pillar foundation) like excavation, PCC, bricks

work, plastering, refilling, providing PVC sleeves in foundation etc. including epoxy

painting of feeder pillar, interconnection etc complete as per specifications as

required. (Note : Feeder Pillar-I - Not in scope of this contract)

1.1 FEEDER PILLAR-(EXTERNAL LIGHTING - 2) TYPICAL FOR [FEEDER

PILLAR EXT/L4] 1 Set 94,000.00 94,000.00 (MR)

A) INCOMING

● 1 No. 63 Amp FP Moulded Case circuit Breaker of 25KA (Ics Value) with O/L, S/C

& E/F protection.

● 1 Set of 3 pole 70Amp power contactor , Astronomical Timer switch DIN mounting

& Toggle switch for auto / manual operation of Road lighting complete as required.

B) INSTRUMENTS WITH INCOMER

● 1 No. 0 to 500Volt voltmeter with selector switch.

● 1No. 0 to 63Amp ammeter with selector switch & CT's.

● 1 Sets of ON / OFF indicating lamps

● 1 Sets of RYB indicating lamps with SP MCB.

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per

DSR

(In Rs.)

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1&2), THREE NO.

OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE

CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION - C: ABSTRACT COST FOR BALANCE WORK OF EXTERNAL ELECTRICAL WORKS

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

Amount as per NON

DSR

(In Rs.)DSR -2013 /

MR

Item No. /

Sub-HeadDescription Qty. Unit

Page 1 of 3

Page 45: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per

DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)DSR -2013 /

MR

Item No. /

Sub-HeadDescription Qty. Unit

C) BUSBARS

● 1 Set of 100Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 12 Nos. 10-32 Amp four pole Miniature Circuit Breaker (10KA).

● 9 Nos. 10-32 Amp double pole Miniature Circuit Breaker (10KA).

2.0 Supply of following size of 1.1KV grade multicore aluminium conductor XLPE

insulated & PVC sheathed armoured cable as per IS:7098 (Part-I) 1988.

i) 4 Core 10 Sq.mm. 40 M 137.00 5,480.00 (MR)

3.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size direct in ground including excavation, sand cushioning,

protective covering and refilling the trench etc as required. 7.1

(DSR-2013)

i) Upto 35 sq.mm 30 M 181.00 5,430.00 7.1.1

4.0 Laying of one number additional PVC insulated and PVC sheathed / XLPE power

cable of 1.1 KV grade of following size direct in ground in the same trench in one

tier horizontal formation including excavation, sand cushioning, protective covering

and refilling the trench etc as required. 7.2

(DSR-2013)

i) Upto 35 sq. mm 10 M 124.00 1,240.00 7.2.1

5.0 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1

KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. 7.5

(DSR-2013)

i) Upto 35 sq. mm 10 M 15.00 150.00 7.5.1

6.0 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground

complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand)

including trenching (75 cm deep) and refilling etc as required.14.14

(DSR-2013)

i) 150 mm dia 10 M 357.00 3,570.00 14.14.2

Page 2 of 3

Page 46: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Rate as per

DSR

(In Rs.)

Rate as per

NON-DSR

(In Rs.)

Amount as per

DSR

(In Rs.)

Amount as per NON

DSR

(In Rs.)DSR -2013 /

MR

Item No. /

Sub-HeadDescription Qty. Unit

7.0 Supply & making end termination with brass compression gland & aluminium lugs

for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor

cable of 1.1KV grade as required. 9.1

(DSR-2013)

i) 4 Core 10 Sq.mm. 2 Set 163.00 326.00 9.1.32

9.0 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and

providing masonry enclosure with cover plate having locking arrangement and

watering pipe etc. with charcoal/ coke and salt as required.

2 Set 3,753.00 7,506.00

5.2

(DSR-2013)

10.0 Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for

conductor earth electrode, including connection/ termination with GI thimble etc. as

required (from pole to pole) 10 M 25.00 250.00

5.7

(DSR-2013)

11.0 Providing and laying earth connection from earth electrode with 6 SWG dia G.I.

Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I.

thimble excavation and re-filling required. 10 M 136.00 1,360.00

5.12

(DSR-2013)

12.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth

electrode including connection with G.I. nut, bolt, spring, washer excavation and re-

filling etc. as required. 5 M 391.00 1,955.00

5.11

(DSR-2013)

13.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections

etc. as required. 5 M 133.00 665.00

5.15

(DSR-2013)

TOTAL OF EXTERNAL ELECTRICAL WORKS CARRIED OVER TO THE

SUMMARY.22,452.00 99,480.00

Page 3 of 3

Page 47: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

S.No. Sub Head DSR Amount ( Rs) Non DSR Amount (

Rs) )

1 EARTH WORK : Rs. 64250.00 0.00

2 CONCRETE WORK : Rs. 569210.75 0.00

3 REINFORCEMENT CEMENT CONCRETE : Rs. 951552.00 0.00

4 BRICK WORK : Rs. 1078500.25 0.00

5 FLOORING : Rs. 1337296.90 0.00

6 FINISHING : Rs. 747426.25 600.00

7 STEEL WORK : Rs. 1460451.20 0.00

8 ROOFING : Rs. 21201.90 0.00

9 WATERPROOFING WORK : Rs. 322799.00 0.00

Sub Total : Rs. 6552688.25 600.00

Amount of DSR items 6552688.25

say : Rs. 6552688.00

Amount of Non DSR items 600.00

say : Rs. 600.00

Grand Total (DSR + Non DSR) Say Rs. 6553288.00

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION

(ESS-1&2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS

FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION D: ABSTRACT COST FOR BALANCE WORK OF CIVIL WORK

(CIVIL WORKS)

SUMMARY SHEET

Page 48: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

DSR Non DSR

1 2 6 7 3 4

Note: This BOQ to be read in conjunction with

generel conditions, special conditions, LEED/

GRIHA conditions and other tender document.

1.00SUB-HEAD : I : EARTH WORK :-

1.1 2.6.1

Earth work in excavation by mechanical means

(Hydraulic excavator) / manual means over areas

(exceeding 30cm in depth. 1.5m in width as

well as 10 sqm on plan) including disposal of

excavated earth, lead upto 50m and lift upto 1.5m,

disposed earth to be levelled and neatly dressed.All

kinds of soil including river pebbles.

300.00 Cum 146.5 43950.00

1.2 2.25

Filling available excavated earth (excluding rock) in

trenches, plinth, sides of foundations etc. in layers

not exceeding 20 cm in depth, consolidating each

deposited layer by ramming and watering, lead up

to 50 m & lift upto 1.5 m.

200.00 Cum 101.50 20300.00

Total :- 64250 0

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-1&2),

THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT

CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION D: ABSTRACT COST FOR BALANCE WORK OF CIVIL WORK

(CIVIL WORKS)

S.No.

Ref.

Code

DSR-

2013/

MR

Description. BOQ Qty Unit.Rate (In Rs.) as

per DSR-2013

Rate (In Rs.) as

per Non DSR

Amount (In Rs.)

Page 1 of 10

Page 49: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

2.00 SUB-HEAD : II : CONCRETE WORK :-

2.1

Providing and laying in position cement concrete of

specific grade excluding the cost of centring and

shuttering-All work upto plinth level

2.1.1 4.1.3

a) 1:2:4 (1 Cement : 2 coarse sand : 4 graded

stone aggregate 20 mm nominal size) 50.00 cum 4921.70 246085.00

2.1.2 4.1.8

b) 1:4:8 ( 1 cement: 4 coarse sand:8 graded stone

aggregate 40mm nominal size ) 80.00 cum 3920.65 313652.00

2.2 4.17

Making plinth protection 50mm thick of cement

concrete 1:3:6 ( 1 cement: 3 coarse sand : 6

graded stone aggregate 20 mm nominal size ) over

75mm thick bed of dry brick ballast 40 mm nominal

size,well rammed and consolidated and grouted

with fine sand,including finishing th etop smooth.

25.00 sqm 378.95 9473.75

Total :- 569210.75 0.00

3.00SUB-HEAD : III : REINFORCEMENT CEMENT

CONCRETE :-

3.1

Providing and laying in position machine bayched

and machine mixed design mix M-25 grade cement

concrete for reinforced cement concrete work,using

cement content as per approved design

mix,including pumping of ceonctrete to site of

laying but excluding the cost of

centring,shuttering,finishing and

reinforcement,includingadmixtures in

recommednded proportions as per IS: 9103 to

accelerate , retard setting of concrete,improve

workability without impairing strenth andduability

as per direction of Engineer-in-Charge.

( Note: Cement content considered in this item is

330 Kg/cum.Excess/less cement used as per

design mix is payable /recoverable seperately )

Page 2 of 10

Page 50: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

3.1.1 5.33.1a) All works upto plinth level.

40.00 cum 5704.45 228178.00

3.1.2 5.33.2b) All works above plinth level upto floor V level.

20.00 cum 6353.00 127060.00

3.2Extra for providing richer mixes at all floor levels.

Note: Excess /less cement over the specified

cement content used is payable/recoverable

seperately )

5.34.1

a) Providing M-30 grade concrete instead of M-25

grade BMC/RMC. ( Note ; Cement content

cosidered in M-30 is @ 340 Kg/cum )20.00 cum 64.15 1283.00

3.3

Centring and shuttering including

strutting,propping etc. and removal of form for:

3.3.1 5.9.1a) Foundation ,footing,bases of columns ,etc. for

mass concrete.140.00 sqm 186.40 26096.00

3.3.2 5.9.2

b) Walls ( Any thickness ) including attached

pilasters,butteresses,plinth and string courses etc. 10.00 sqm 334.50 3345.00

3.3.3 5.9.5d) Lintels, beams, plinth beams, girders,

bressuners and cantilevers.50.00 sqm 309.8 15490.00

3.3.4 5.9.6e) Columns,Pillars,Piers,Abutments,Posts and

struts.200.00 sqm 423.00 84600.00

3.4

Steel reinforcement for RCC work includng

straightening,cutting,bending,placing in position

and binding all complete for all works i.e below

/above plinth level.

5.22.6 Thermo-Mechanically Treated bars 7000.00 Kilogram 66.50 465500.00

Total :- 951552 0

4.00 SUB-HEAD : IV : BRICK WORK :-

4.1

Brick work with common burnt clay F.P.S (non

modular) bricks of class designation 7.5

foundations and plinth in :-

4.1.1 6.1.2a) Cement mortar 1:6 ( 1 cement: 6 coarse sand )

10.00 cum 4646.50 46465.00

Page 3 of 10

Page 51: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

4.2

Brick work with non modular fly ash lime bricks (

FALG Bricks ) conforming to IS: 12894,class

designation 10 average compressive strength in

super structure above plinth level upto floor V level

in :

6.34.1a) Cement mortar 1:4 ( 1 cement: 4 coarse sand )

185.00 cum 5301.25 980731.25

4.3

Half brick masonry with non modular fly ash lime

Gypsum bricks (FALG Bricks ) of class designation

10,conforming to IS: 12894,in super structure

above plinth and upto floor V level.

6.45.2a) Cement mortar 1:4 ( 1 cement: 4 coarse sand )

80.00 sqm 641.30 51304.00

Total :- 1078500.25 0.00

5.00 SUB-HEAD: VIII: FLOORING:-

5.1 11.5

62 mm thick cement concrete flooring with

concrete hardener topping under layer 50 mm thick

cement concrete 1:2:4 (1 Cement : 2 coarse sand :

4 graded stone aggregate 20 mm nominal size)

and top layer 12 mm thick Hardcrete cement

hardener consisting of mix 1:2 (1 cement hardener

mix : 2 graded stone aggregate 6mm nominal size)

by volume hardening compound is mixed @ 2 litre

per 50 kg of cement or as per manufacturers

specificationss. This included cost of cement

slurry, but excluding the cost of nosing of steps

etc. complete.

750.00 sqm 528.25 396187.50

5.2

Cement concrete flooring 1:2:4 (1 cement : 2

coarse sand : 4 graded stone aggregate) finished

with floating coat of neat cement including cement

slurry, but excluding the cost of nosing of steps

etc. complete.

11.3.1a) 40mm thick with 20mm nominal size stone

aggregate5.00 sqm 316.80 1584.00

Page 4 of 10

Page 52: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

5.3

Cement plaster skirting upto 30 cm height with

cement mortar 1:3 (1 Cement: 3 coarse sand)

finished with a floating coat of neat cement.

11.6.1 a) 18 mm thick 2.00 sqm 299.20 598.40

5.4 11.26.1

Kota stone slab flooring over 20mm (average) thick

base laid over and jointed with grey cement slurry

mixed with pigment to match the shade of the slab

including rubbing and polishing complete with

base of cement mortar 1 : 4 ( 1 cement : 4 coarse

sand) :

80.00 sqm 1071.70 85736.00

25 mm thick

5.5 11.27

Kota stone slabs 20 mm thick in risers of steps,

skirting, dado and pillars laid on 12 mm (average)

thick cement mortar 1:3 (1 cement 3 coarse sand)

and jointed with grey cement slurry mixed with

pigment to match the shade of the slabs, including

rubbing and polishing complete.

30.00 sqm 1100.85 33025.50

5.6 11.36

Providing and fixing Ist quality ceramic glazed wall

tiles conforming to IS : 15622 (thickness to be

specified by the manufacture ) of approved make

in all colours, shades except burgundy, bottle

green, black of any size as approved by Engineer-in-

Charge in skirting, risers of steps and dados over

12 mm thick bed of cement Mortar 1:3 (1 cement :

3 coarse sand) and jointing with grey cement slurry

@ 3.3kg per sum including pointing in white

cement mixed with pigment of matching shade

complete.

40.00 sqm 793.60 31744.00

Page 5 of 10

Page 53: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

5.7 11.37

Providing and laying Ceramic glazed floor tiles

300x300 mm (thickness to be specified by the

manufacturer) of 1st quality conforming to IS :

15622 of approved make in colours such as White,

Ivory, Grey, Fume Red Brown, laid on 20 mm thick

Cement Mortar 1:4 (1 Cement : 4 Coarse sand)

including pointing the joints with white cement and

matching pigment etc., complete.

15.00 sqm 822.10 12331.50

5.8 12.55

Providing and fixing Heat resistant terrace tile (

300x 300mm x 20mm ) with SRI ( solar refractive

index )>78, solar reflection > 0.70 and initial

emmitance > 0.75 on waterproof and sloped

roofed surface of terrace,laid on 20mm thick

cement sand mortar in theratio of 1: 4 ( 1 cement:

coarse sand ) and grouting the joints with mix of

white cement & marble powder in ratio of 1:

1,including rubbing and polishing of the surface

upto 3 cuts complete,including providing skirting

upto 150 mm heights along the parapet walls in

the same manner.

700.00 sqm 1108.70 776090.00

Total :- 1337296.90 0.00

6.00SUB-HEAD: IX : FINISHING:-

6.1 12mm cement plaster of mix :-

13.4.1 a) 1:4 ( 1 cement : 4 coarse sand) 750.00 sqm 153.85 115387.50

6.215mm cement plaster on the rough side of single

or half brick wall of mix

a) 13.5.1 1:4 (1 cement : 4 coarse sand) 750.00 sqm 178.60 133950.00

6.3 6mm cement plaster to ceiling of mix :-

13.16.1 a) 1:3 (1 cement : 3 fine sand) 675.00 sqm 120.35 81236.25

6.4White washing with lime to give an even shade

13.37.1 a) New work ( three or more coats ) 350.00 sqm 14.35 5022.50

6.5Finishing walls with textured exterior paint of

required shade:

Page 6 of 10

Page 54: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

13.45.1

a) New work ( two or more coats allpied @ 3.28

ltr/10 sqm) over and including priming coat of

exterior primer applied 2.20 kg/10 sqm900.00 sqm 127.10 114390.00

6.6 13.12

18 mm cement plaster in two coats under layer

12mm thick cement plaster 1:5 ( 1cement : 5

coarse sand) and a top layer 6mm thick cement

plaster 1:3 (1 cement : 3 coarse sand) finished

with rough with sponge.

600.00 sqm 231.20 138720.00

6.7

Distempering with 1st quality acrylic

distemper,having VOC ( Volatile Organic Compound

) Content less than 50grams/litre,of approved

brand and manufacture,including applying

additional coats wherever required,to achieve even

shade and colour

13.81.2 a) Two or more coats 3240.00 sqm 41.75 135270.00

6.8

Painting with synthetic enamel paint ,having VOC (

Volatile Organic Compound ) content less than 150

gms/litre,of approved brand and

manufacture,including applying additional coats

wherever required to achieve even shade colour.

13.84.2 Two or more coats 350.00 sqm 67.00 23450.00

6.9 MR

Extra for Making 15 x 15 mm grooves in the

plastering work as shown in the drawing or as

directed by the Engineer-in-Charge.

50.00 metre 12.00 600.00

Total :- 747426.25 600.00

7.00 SUB-HEAD: X : STEEL WORK :-

7.1

Steel work welded in built up sections/framed

,including cutting,hopisting,fixing in position and

applying a priming coat of approved steel primer

using structural steel etc. as required.

Page 7 of 10

Page 55: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

10.25.2

In gratings, frames, guard bar, ladders,

railings,louvers, brackets, gates & similar works. 14000.00 Kg 86.50 1211000.00

7.2

Supplying and fixing rolling shutters of approved

make, made of required size M.S. laths interlocked

together through their entire length and jointed

together at the end by end locks mounted on

specially designed pipe shaft with brackets, side

guides and arrangements for inside and outside

locking with push and pull operation complete

including the cost of providing and fixing necessary

27.5cm long wire springs grade No. 2 and M.S. top

cover of required thickness for rolling shutters.

10.6.2a) 80 x 1.20mm M.S. laths with 1.20mm thick top

cover45.00 sqm 1831.20 82404.00

7.3 10.7Providing and fixing ball bearing for rolling

shutters.30.00 each 436.45 13093.50

7.4 10.9

Extra for providing grilled rolling shutters

manufactured out of 8mm dia M.S. Bar instead of

laths as per design approved by Engineer-in-Charge

(Area of grill to be measured).

7.00 sqm 313.60 2195.20

7.5

Extra for providing mechnical device chain and

cranks operation for operating rolling shutters

10.8.1a) Excedding 10 sqm and upto 16.80 sqm in the

area7.00 sqm 665.50 4658.50

7.6

Providing and fixing 1mm thick M.S. sheet door

with frame of 40x40x6mm angle iron and 3mm

M.S. gusset plates at the junction and corners , all

necessary fittings complete, including applying a

priming coat of approved steel primer.

10.5.1Using M.S angles 40x40x6mm for diagonal braces.

50.00 sqm 2942.00 147100.00

Total :- 1460451.2 0

8.00 SUB-HEAD: XI: ROOFING :-

Page 8 of 10

Page 56: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

8.1

Providing gola 75 x 75 mm in cement concrete 1: 2

:4 (1 cement:2 coarse sand:4 stone aggregate

10mm and down gauge) ,including finishing with

cement mortar 1: 3 ( 1 cement: 3 fine sand) as

perstandard design.

12.21.1 a) 75 x 75mm deep chase. 150.00 metre 127.95 19192.50

8.2 12.22

Making khurras 45 x 45 cm with average minimum

thickness of 5cm cement concrete 1: 2 :4 ( 1

cement:2 coarse sand:4 graded stone aggregate

of 20mm nominal size ) overP.V.C. sheet 1mx 1mx

400 micron,finished with 12mm cement plaster 1;3

( 1 cement: 3 coarse sand) and a coat of neat

cement,rounding the edges and making and

finishing the outlet complete

12.00 each 167.45 2009.40

Total :- 21201.9 0

9.00 SUB-HEAD: XIII: WATERPROOFING WORKS :-

9.1

Providing and laying water proofing treatment to

vertical and horizontal surfaces of depressed

portions of W.C ,kitchen and the like consisiting of

:

i) 1st course of applying cement slurry @ 4.4

kg/sqm mixed with waterproofing compound

conforming to IS:2645 in recommended

proportions including rounding off junction of

vertical and horizontal surface.

ii) 2nd course of 20mm cement plaster 1:3 ( 1

cement: 3 coarse sand) mixed with water rpoofing

compound in recommended proportion including

rounding off junctionsof vertical and horizontal

surface.

iii) 3rd surface of applying blown or residual

bitumen applied hot at 1.7 kgper sqm of area.

Page 9 of 10

Page 57: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

22.3

iv) 4th course of 400 micron thick PVC sheet (

Overlaps at joints of PVC sheet should be 100mm

wide and pasted to each other with bitumen @ 1.7

kg/sqm.

20.00 sqm 449.45 8989.00

9.2

Providing and laying APP ( Atactic Polypropylene

Polymer ) modified prefabricated five layer 3mm

thick waterproofing mambrane,black finished

reinforced with non woven polyster matt consisting

of a coat of bitumen primer for bitumen membrane

@ 0.40 litre/sqm by the same membrane

manufacture of density at 250 C,0.87 - 0.89 kg/litre

and viscocity 70-160 cps.Over the primer coat the

layer of membrane shall be laid using butane torch

and sealing all joints etc, and preparing the surface

complete.The cital physical and chemical

parametres of the membrane shall be as

under:Joint strength in longitudinal and trensverse

direction at 230 C as 650/450 N/5 cm.Tear strength

in longitudinal and transverse direction as 300/250

N. Softening point of membrane not lessthan 1500

C.Cold flexibility shall be upto -20 C when tested in

accordance with ASTM, D-5147.The laying of

membrane shall be got done through the authorised

applicator of the manufacture of membrane:

22.20.1 3mm thick 700.00 sqm 448.30 313810.00

Total :- 322799 0

Grant Total 6552688.25 600.00

Page 10 of 10

Page 58: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

DSR-2013 MR TOTAL

A MISC. CIVIL WORKS 507,139.00 3,088.40 510,227.40

B MISC. ELECTRICAL WORKS 424,104.00 221,160.00 645,264.00

C MISC. FIRE FIGHTING WORKS 0.00 151,420.00 151,420.00

TOTAL OF EXTERNAL ELECTRICAL

WORKS (A+B+C)931,243.00 375,668.40 1,306,911.40

SAY Rs. ₹ 1,306,911.00

Annexure-Y

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC

SUBSTATION (ESS-1&2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL

ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA

(J&K).

SECTION E: ABSTRACT COST FOR BALANCE MISC. CIVIL, ELECTRICAL & FIRE-FIGHTING WORK

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 59: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

Ref. code

DSR-2013/

MRDSR-2013 Non-DSR DSR-2013 Non-DSR

1 2 3 4 5 6 7 8 9 10

A Civil

1 5.35

Add for using extra cement in the

items of design mix over and above

the specified cement content therein. 20 Qtl. 619.65 12393.00

2 6.15

Extra for providing and placing in

position 2 Nos 6mm dia. M.S. bars at

every third course of half brick

masonry.

80 M2 69.50 5560.00

3 12.41.2

Providing and fixing on wall face

unplasticised Rigid PVC rain water

pipes conforming to IS : 13592 Type

A, including jointing with seal ring

conforming to IS : 5382, leaving 10

mm gap for thermal expansion, (i)

Single socketed pipes. - 110 mm

diameter

25 Mtr 218.60 5465.00

TENDER FOR BALANCE WORK OF SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF TWO NO. 11/0.433KV INDOOR ELECTRIC SUBSTATION (ESS-

1&2), THREE NO. OUTDOOR TYPE 11/0.433KV COMPACT SUB-STATION (CSS-1,2&3) AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE

PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K).

SECTION E: ABSTRACT COST FOR MISC. CIVIL, ELECTRICAL & FIRE-FIGHTING WORK

(MISC. CIVIL, ELECTRICAL & FIRE FIGHTING WORKS)

S. No. Description of Item

Total Qty (02

nos sub-

stations)

Unit Remarks

Rate (In Rs.)Amount (In Rs.)

Page 1 of 21

Page 60: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

4 12.42.6.2

Providing and fixing on wall face

unplasticised - PVC moulded fittings/

accessories for unplasticised Rigid

PVC rain water pipes conforming to

IS : 13592 Type A, including jointing

with seal ring conforming to IS : 5382,

leaving 10 mm gap for thermal

expansion. - Shoe (Plain) - 110 mm

shoe

6 Nos 290.35 1742.10

5 12.42.5.2

Providing and fixing on wall face

unplasticised - PVC moulded fittings/

accessories for unplasticised Rigid

PVC rain water pipes conforming to

IS : 13592 Type A, including jointing

with seal ring conforming to IS : 5382,

leaving 10 mm gap for thermal

expansion. - Bend - 110 mm bend

6 Nos 160.25 961.50

6 12.43.2

Providing and fixing unplasticised -

PVC pipe clips of approved design to

unplasticised - PVC rain water pipes

by means of 50x50x50 mm hard

wood plugs, screwed with M.S.

screws of required length, including

cutting brick work and fixing in

cement mortar 1:4 (1 cement : 4

coarse sand) and making good the

wall etc. complete.

- 110 mm

15 Nos 173.25 2598.75

Page 2 of 21

Page 61: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

7 12.44

Providing and fixing to the inlet mouth

of rain water pipe cast iron grating 15

cm diameter and weighing not less

than 440 grams.

6 Nos 37.25 223.50

8 17.65.1

Painting sand cast iron / centrifugally

cast (spun) iron soil, waste vent pipes

and fittings with two coats of synthetic

enamel paint of any color such as

chocolate grey, or buff etc. over a

coat of primer (of aproved quality) for

new work. - 100 mm diameter pipe.

40 M 33.85 1354.00

9 19.1.3

Providing, laying and jointing glazed

stoneware pipes class SP-1 with stiff

mixture of cement mortar in the

proportion of 1:1 (1 cement : 1 fine

sand) incl. testing of joints etc.

complete.

- 200 mm diameter pipe.

25 M 447.25 11181.25

10 19.2.3

Providing and laying cement concrete

1:5:10 (1 cement : 5 coarse sand : 10

graded stone aggregate 40 mm

nominal size) all-round S.W. pipes

including bed concrete as per

standard design : -

- 200 mm diameter SW pipe

25 M 774.95 19373.75

Page 3 of 21

Page 62: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

11 19.4.2.1

Providing and fixing square-mouth

S.W. gully trap class SP-1 complete

with C.I. grating brick masonry

chamber with water tight C.I. cover

with frame of 300 x300 mm size

(inside) the weight of cover to be not

less than 4.50 kg and frame to be not

less than 2.70 kg as per standard

design. - 150 x 100 mm size P type.

- With common burnt clay F.P.S.

(non modular) bricks of class

designation 7.5

3 Nos 1546.95 4640.85

Page 4 of 21

Page 63: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

12 19.7.1.1

Constructing brick masonry manhole

in cement mortar 1:4 ( 1 cement : 4

coarse sand ) with R.C.C. top slab

with 1:2:4 mix (1 cement : 2 coarse

sand : 4 graded stone aggregate 20

mm nominal size), foundation

concrete 1:4:8 mix (1 cement : 4

coarse sand : 8 graded stone

aggregate 40 mm nominal size),

- inside plastering 12 mm thick with

cement mortar 1:3 (1 cement : 3

coarse sand) finished with floating

coat of neat cement and making

channels in cement concrete 1:2:4 (1

cement : 2 coarse sand : 4 graded

stone aggregate 20 mm nominal

size) finished with a floating coat of

neat cement complete as per

standard design. Inside size 90x80

cm and 45 cm deep including C.I

cover with frame (light duty) 455x610

mm internal dimentions, total weight

of cover and frame to be not less

than 38 kg (weight of cover 23 kg and

weight of frame 15 kg)

- with common burnt clay F.P.S. (non

modular) bricks of class designation

7.5

6 Nos 8062.70 48376.20

13 19.8.1.1

Extra for depth for manholes. - With

common burnt clay F.P.S. (non

modular) bricks of class designation

7.5

3 M 5481.40 16444.20

14 17.35.1.2

Providing and fixing soil, waste and

vent pipes - 100 mm

- Centrifugally cast (spun) iron socket

& spigot (S&S) pipe as per IS: 3989.20 M 950.15 19003.00

Page 5 of 21

Page 64: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

15 17.37.1

Providing and fixing M.S. holder-bat

clamps of approved design toSand

Cast iron/cast iron (spun) pipe

embedded in and includingcement

concrete blocks 10x10x10 cm of

1:2:4 mix (1 cement : 2coarse sand :

4 graded stone aggregate 20 mm

nominal size),including cost of cutting

holes and making good the walls etc.

: - For 100 mm dia pipe

5 Nos 140.65 703.25

16 17.38.1.2

Providing and fixing bend of required

degree with access door, insertion

rubber washer 3 mm thick, bolts and

nuts complete. - 100 mm diameter

- Sand cast iron S&S as per IS - 3989

6 Nos 384.45 2306.70

17 17.39.1.2

Providing and fixing plain bend of

required degree. - 100 mm diameter.

- Sand cast iron S&S as per IS : 3989 6 Nos 334.50 2007.00

18 17.40.1.2

Providing and fixing heel rest sanitary

bend. - 100 mm diameter

- Sand cast iron S&S as per IS - 3989 3 Nos 370.50 1111.50

19 17.56.1.2

Providing and fixing terminal guard : -

100 mm diameter

- Sand cast iron S&S as per IS - 39896 Nos 433.20 2599.20

20 17.57.1.2

Providing and fixing collar : - 100 mm

diameter

- Sand cast iron S&S as per IS - 39896 Nos 317.05 1902.30

Page 6 of 21

Page 65: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

21 17.58.1

Providing lead caulked joints to sand

cast iron/centrifugally cast (spun) iron

pipes and fittings of diameter : - 100

mm

16 Nos 232.30 3716.80

22 10.11.1

Providing and fixing factory made ISI

marked steel glazed doors, windows

and ventilators, side /top /centre

hung, with beading and all members

such as F7D, F4B, K11 B and K12 B

etc. complete of standard rolled steel

sections, joints mitred and flash butt

welded and sash bars tenoned and

riveted, including providing and fixing

of hinges, pivots, including priming

coat of approved steel primer, but

excluding the cost of other fittings,

complete all as per approved design,

(sectional weight of only steel

members shall be measured for

payment).

- Fixing with 15x3 mm lugs 10 cm

long embedded in cement concrete

block 15x10x10 cm of C.C. 1:3:6 (1

Cement : 3 coarse sand : 6 graded

stone aggregate 20 mm nominal

size)

240 Kg 105.10 25224.00

23 10.12

Extra for providing and fixing steel

beading of size 10x10x1.6 mm (box

type), approved shape and section

with screws instead of glazing clips

and metal sash putty, in steel doors,

windows, ventilators and composite

units.

150 M 35.90 5385.00

Page 7 of 21

Page 66: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

24 11.13.1

Providing and fixing glass strips in

joints of terrazo/ cement concrete

floors.

- 40 mm wide and 4 mm thick

5500 M 33.80 185900.00

25 18.10.2

Providing and fixing G.I. pipes

complete with G.I. fittings and

clamps, i/c cutting and making good

the walls etc.

Internal work - Exposed on wall

- 20 mm dia nominal bore

21 M 221.50 4651.50

26 18.8.1

Providing and fixing Chlorinated

Polyvinyl Chloride (CPVC) pipes,

having thermal stability for hot & cold

water supply, including all CPVC

plain & brass threaded fittings, i/c

fixing the pipe with clamps at 1.00 m

spacing. This includes jointing of

pipes & fittings with one step CPVC

solvent cement and the cost of

cutting chases and making good the

same including testing of joints

complete as per direction of Engineer

in Charge.

Concealed work, including cutting

chases and making good the walls

etc.

- 15 mm nominal outer dia Pipes

10 M 254.95 2549.50

Page 8 of 21

Page 67: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

27 18.12.2

Providing and fixing G.I. pipes

complete with G.I. fittings including

trenching and refilling etc.

External work

- 20 mm dia nominal bore

45 M 186.25 8381.25

28 18.40.2

Painting G.I. pipes and fittings with

two coats of anti-corrosive bitumastic

paint of approved quality :

- 20 mm dia nominal bore

25 M 6.15 153.75

29 18.40.4

Painting G.I. pipes and fittings with

two coats of anti-corrosive bitumastic

paint of approved quality :

- 32 mm dia nominal bore

10 M 9.35 93.50

30 18.40.6

Painting G.I. pipes and fittings with

two coats of anti-corrosive bitumastic

paint of approved quality :

- 50 mm dia nominal bore

5 M 12.65 63.25

31 18.18.2

Providing and fixing ball valve (brass)

of approved quality, High or low

pressure, with plastic floats complete

- 20 mm nominal bore

2 Nos 407.40 814.80

32 18.38.2

Painting G.I. pipes and fittings with

synthetic enamel white paint with two

coats over a ready mixed priming

coat, both of approved quality for new

work :

- 20 mm diameter pipe

40 M 10.10 404.00

Page 9 of 21

Page 68: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

33 18.46.2

Providing and fixing G.I. Union in G.I.

pipe including cutting and threading

the pipe and making long screws etc.

complete (New work)

- 20 mm nominal bore

10 Nos 178.85 1788.50

34 18.48

Providing and placing on terrace (at

all floor levels) polyethylene water

storage tank, ISI : 12701 marked,

with cover and suitable locking

arrangement and making necessary

holes for inlet, outlet and overflow

pipes but without fittings and the base

support for tank.

2000 Ltr 6.30 12600.00

35 17.1

Providing and fixing water closet

squatting pan (Indian type W.C. pan )

with 100 mm sand cast Iron P or S

trap, 10 litre low level white P.V.C.

flushing cistern, including flush pipe,

with manually controlled device

(handle lever) conforming to IS :

7231, with all fittings and fixtures

complete, including cutting and

making good the walls and floors

wherever required :

-White Vitreous china Orissa pattern

W.C. pan of size

580x440 mm with integral type foot

rests

2 Nos 3265.25 6530.50

Page 10 of 21

Page 69: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

36 17.31

Providing and fixing 600x450 mm

beveled edge mirror of superior glass

(of approved quality) complete with 6

mm thick hard board ground fixed to

wooden cleats with C.P. brass

screws and washers complete.

2 Nos 762.55 1525.10

37 17.7.4

Providing and fixing wash basin with

C.I. brackets, 15 mm C.P. brass pillar

taps, 32 mm C.P. brass waste of

standard pattern, including painting of

fittings and rackets, cutting and

making good the walls wherever

require :

- White Vitreous China Flat back

wash basin size 550x

400 mm with single 15 mm C.P.

brass pillar tap

2 Nos 1699.95 3399.90

38 MR

Providing and fixing CP brass towel

ring square fixed to PVC cleats with

CP brass screws including cutting

and making good the walls wherever

required:

2 Nos 534.80 1069.60

39 18.49

Providing and fixing C.P. brass bib

cock of approved quality conforming

to IS:8931 :

-15 mm nominal bore

4 Nos 458.40 1833.60

Page 11 of 21

Page 70: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

40 18.51

Providing and fixing C.P. brass long

body bib cock of approved quality

conforming to IS standards and

weighing not less than 690 gms.

- 15 mm nominal bore

4 Nos 609.40 2437.60

41 18.53

Providing and fixing C.P. brass angle

valve for basin mixer and geyser

points of approved quality conforming

to IS:8931 a) 15 mm nominal bore.

- 15mm nominal bore

2 Nos 506.70 1013.40

42 17.28.1.1

Providing and fixing P.V.C. waste

pipe for sink or wash basin including

P.V.C. waste fittings complete.

-32 mm dia2 Nos 74.90 149.80

43 MR

Providing and fixing CP grating with

frame and SS screw casted heavy

duty 125 mm dia including cutting

and making good wall & floor where

required in all respect.

4 Nos 504.70 2018.80

44 17.60.1.1

Providing and fixing trap of self

cleansing design with screwed down

or hinged grating with or without vent

arm complete, including cost of

cutting and making good the walls

and floors :

- Sand cast iron S&S as per IS: 3989

4 Nos 938.05 3752.20

Page 12 of 21

Page 71: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

45 10.13.1

Providing and fixing T-iron frames for

doors, windows and ventilators of

mild steel Tee-sections, joints mitred

and welded, including fixing of

necessary butt hinges and screws

and applying a priming coat of

approved steel primer.

- Fixing with 15x3 mm lugs 10 cm

long embedded in cement concrete

block 15x10x10 cm of C.C. 1:3:6 (1

Cement : 3 coarse sand : 6 graded

stone aggregate 20 mm nominal

size)

400 Kg 81.95 32780.00

46 16.70.1

Providing and fixing G.I. chain link

fabric fencing of required width in

mesh size 50x50 mm including

strengthening with 2 mm dia wire or

nuts, bolts and washers as required

complete as per the direction of

Engineer-in-charge.

- Made of G.I. wire of dia 4 mm

80 Sqm 525.55 42044.00

507139.00 3088.40

B Electrical Work

Sub Total - A

Total-A 510227

Page 13 of 21

Page 72: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

1 1.10.3

Wiring for light point/ fan point/

exhaust fan point/ call bell point with

1.5 sq.mm FRLS PVC insulated

copper conductor single core cable in

surface / recessed medium class

PVC conduit, with modular switch,

modular plate, suitable GI box and

earthing the point with 1.5 sq.mm.

FRLS PVC insulated copper

conductor single core cable etc as

required.

(i) Group-C (as per DSR-2013)

114 Point 727.00 82878.00

2 1.11

Wiring for twin control light point with

1.5 sq.mm FRLS PVC insulated

copper conductor single core cable in

surface / recessed medium class

PVC conduit, 2 way modular switch,

modular plate, suitable GI box and

earthing the point with 1.5 sq.mm.

FRLSPVC insulated copper

conductor single core cable etc as

required. (As per DSR-2013)

2 Point 782.00 1564.00

3 1.14.1

Wiring for circuit/ submain wiring

alongwith earth wire with the

following sizes of FRLS PVC

insulated copper conductor, single

core cable in surface/ recessed

medium class PVC conduit as

required.

(i) 2 x 1.5 Sq.mm. + 1 x 1.5Sq.mm

earth wire (As per DSR-2013)

1500 Mtr 116.00 174000.00

Page 14 of 21

Page 73: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

4 1.12

Wiring for light/ power plug with 2X4

sq. mm FRLS PVC insulated copper

conductor single core cable in

surface/ recessed medium class

PVC conduit alongwith 1 No 4 sq.

mm FRLS PVC insulated copper

conductor single core cable for loop

earthing as required. (As per DSR-

2013)

600 Mtr 171.00 102600.00

5 1.32

Supplying and fixing suitable size GI

box with modular plate and cover in

front on surface or in recess,

including providing and fixing 6 pin

5/6 & 15/16 amps modular socket

outlet and 15/16 amps modular

switch, connection etc. as required.

(As per DSR-2013)

18 Nos 411.00 7398.00

6 2.7.6

Supplying and fixing following way

prewired TP&N MCB distribution

board of steel sheet for 415 volts on

surface/ recess complete with loose

wire box, terminal connectors for all

incoming and outgoing circuits, duly

prewired with suitable size FRLS

PVC insulated copper conductor up

to terminal blocks, tinned copper bus

bar, neutral link, earth bar, din bar,

detachable gland plate,

interconnections, powder painted

including earthing etc. as

required.(But without MCB/ RCCB/

Isolator). (i) 8 way (4 + 24), Double

door (As per DSR-2013)

2 Nos 9899.00 19798.00

Page 15 of 21

Page 74: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

7 2.14.2

Supplying and fixing following rating,

double pole, (single phase and

neutral), 240 volts, residual current

circuit breaker (RCCB), having a

sensitivity current upto 300

milliamperes in the existing MCB DB

complete with connections, testing

and commissioning etc. as required.

(i) 40 Amp rating (As per DSR-2013)

6 Nos 1510.00 9060.00

8 2.12.1

Supplying and fixing following rating,

four pole, 415 volts, isolator in the

existing MCB DB complete with

connections, testing and

commissioning etc. as required. (i) 40

Amp rating (As per DSR-2013)

2 Nos 604.00 1208.00

9 2.10.1

Supplying and fixing 5 amps to 32

amps rating, 240/415 volts, “C” curve,

miniature circuit breaker suitable for

inductive load of following poles in

the existing MCB DB complete with

connections, testing and

commissioning etc. as required. (i)

Single pole. (As per DSR-2013)

36 Nos 146.00 5256.00

Page 16 of 21

Page 75: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

10 1.41

Installation, testing and

commissioning of pre-wired,

fluorescent fitting / compact

fluorescent fitting of all types,

complete with all accessories and

tube etc. directly on ceiling/ wall,

including connection with 1.5 sq. mm

FRLS PVC insulated, copper

conductor, single core cable and

earthing etc. as required. (As per

DSR-2013)

104 Nos 82.00 8528.00

11 1.50.1

Installation of exhaust fan in the

existing opening, including making

good the damage, connection,

testing, commissioning etc. as

required. (i) Upto 450 mm sweep (As

per DSR-2013)

12 Nos 189.00 2268.00

12 1.21.2

Supplying and fixing of following sizes

of medium class PVC conduit along

with accessories in surface/recess

including cutting the wall and making

good the same in case of recessed

conduit as required. (i) 25mm dia. (As

per DSR-2013)

100 Mtr 72.00 7200.00

13 1.24.6

Supplying and fixing of following

modular switch / socket on the

existing modular plate & switch box

including connections but excluding

modular plate etc. as required. (i)

Telephone socket outlet. (As per

DSR-2013)

2 Nos 92.00 184.00

Page 17 of 21

Page 76: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

14 1.27.1

Supplying and fixing following size /

modules, GI box alongwith modular

base & cover plate for modular

switches in recess etc. as required. (i)

1 or 2 Module (75mm x 75mm). (As

per DSR-2013)

2 Nos 159.00 318.00

15 1.18.2

Supplying and drawing following pair

0.5 mm dia FRLS PVC insulated

annealed copper conductor,

unarmored telephone cable in the

existing surface/ recessed steel/ PVC

conduit as required. (i) 2 Pair (As per

DSR-2013)

50 Mtr 17.00 850.00

16 MR

Supply of 1 x 28 W T5 suface / wall

mounted fluorescent light fixtures

complete with lamp, electronic

ballast & all accessories as required

of approved make.

32 Nos 760.00 24320.00

17 MR

Supply of 2 x 28 watt T5 surface

mounted Industrial type light fixture

complete with lamp, electronic

ballast & all accessories as required

of approved make.

40 Nos 2650.00 106000.00

18 MR

Supply of 1 x 14 watt surface

mounted T5 light fixture complete

with with lamp, electronic ballast & all

accessories as required of approved

make. (above mirror for toilet area)2 Nos 720.00 1440.00

Page 18 of 21

Page 77: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

19 MR

Supply of 1 x 9 watt CFL wall

mounted bulkhead light fixtures

complete with lamp, electronic

ballast & all accessories as required

of approved make.

22 Nos 940.00 20680.00

20 MR

Supply of 1 x 18W CFL surface

mounted downlighter outdoor type

light fixture with lamp, electronic

ballast complete with all accessories

as required of approved make.

6 Nos 1310.00 7860.00

21 MR

Supply of 1x18W Decorative type

wall bracket light fixture complete

with lamp & all accessories as

required of approved make.

2 Nos 1230.00 2460.00

22 MR

Supply of following sizes of energy

saver ( 5 star rated) ceiling fan

without regulator complete with

double ball bearing, motor, blades,

downrod, canopy, capacitor etc.

complete as required.

(i) 1200 mm Sweep.

2.00 Nos 2200.00 4400.00

23 1.25

Supplying and fixing stepped type

electronic fan regulator on the

existing modular plate switch box

including connections but excluding

modular plate etc. as required. (As

per DSR-2013)

2.00 Nos 362.00 724.00

Page 19 of 21

Page 78: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

24 1.44 & 1.46

Installation of ceiling fan with

regulator complete with double pole

ball bearing. motor, blades. down

rod, canopy capacitor etc. including

connection with 1.5 sq.mm FRLS

PVC insulated copper conductor

single core cable as required. (As

per DSR-2013)

2.00 Nos 135.00 270.00

25 MR

Supply of Exhaust fan of 450 mm

sweep size suitable for operation on

single phase 230 Volt AC 50 Hz

supply complete with ceiling rose &

all fixing accessories as required.

12 Nos 4500.00 54000.00

424104.00 221160.00

C FIRE FIGHTING

1 MR

CO2 type cylindrical shape fire

extinguisher with fixing hangers,

hose, brackets, screws to required

size etc.,complete as per IS:15683 -

wall mounted type. (i) 4.5 Kg.

Capacity

10 Nos 5650.00 56500.00

2 MR

9 litres capacity water Stored

pressure type extinguishers with

CO2 cartridge with fixing hangers,

hose, brackets, screws to required

size etc., complete as per IS:15683 -

Wall mounted type

10 Nos 2185.00 21850.00

Sub Total - B

Total-A 645264

Page 20 of 21

Page 79: INSTITUTE OF CHARTERED FINANCIAL ANALYSTS OF INDIA AT ...engineeringprojects.com/Tender/UploadFiles/3612_Vol-III.pdf · cable of 11 KV grade of following size direct in ground in

NRO/CON/696/660

3 MR

ABC' stored pressure type Dry

Chemical Powder (Mono-Ammonium

Phosphate ) fire extinguisher with

fixing hangers, hose, brackets,

screws to required size etc.,

complete as per IS:15683. (i)

Capacity 6 Kg.

10 Nos 3420.00 34200.00

4 MR

CO2 type cylindrical shape fire

extinguisher with hose and all

required accessories, complete as

per IS:2878 - trolley mounted type for

portable use.

(i) 22.5 Kg. Capacity

2 Nos 17845.00 35690.00

5 MR

Providing and Fixing 3 Nos. G.I. Sand

bucket painted red color complete

with G.I. Stand duly painted red color

of suitable size to hang three buckets

at a time as per required specification

(The weight of sand with bucket not

less then 9 Kg)

2 Set 1590.00 3180.00

0.00 151420.00

Grand total - (A+B+C) 1306911.40