Installer manual

LEK

NIBE™ F1226Ground source heat pump

IHB GB 1127-2031796

Page 2: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

A detailed explanation of the button functions can be found on page 33.

How to scroll through menus and make different settings is described on page 35.

The mode for setting the indoor temperature is reached, when in the start mode in the main menu, by pressing theOK button twice. Read more about the settings on page 37.

To temporarily increase the amount of hot water, first turn the control knob to mark menu 2 (water droplet) and thenpress the OK button twice. Read more about the settings on page 41.

In event of disturbances in comfort

If a disturbance in comfort of any type occurs there are some measures that can be taken before you need to contactyour installer. See page 55 for instructions.

Page 3: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Table of Contents1 Important information 2

Safety information 2

2 Delivery and handling 5Transport 5

Assembly 5

Supplied components 6

Removing the covers 6

Removing parts of the insulation 7

3 The heat pump design 8General 8

Electrical cabinets 9

Cooling section 11

4 Pipe connections 12General 12

Dimensions and pipe connections 13

Brine side 13

Heating medium side 14

Hot water heater 14

Docking alternatives 15

5 Electrical connections 17General 17

Connections 19

Settings 20

Optional connections 22

Connecting accessories 23

6 Commissioning and adjusting 24Preparations 24

Filling and venting 24

Start guide 25

Post adjustment and venting 30

7 Control - Introduction 33Display unit 33

Menu system 34

8 Control - Menus 37Menu 1 - INDOOR CLIMATE 37

Menu 2 - HOT WATER 41

Menu 3 - INFO 42

Menu 4 - HEAT PUMP 43

Menu 5 - SERVICE 45

9 Service 49Service actions 49

10 Disturbances in comfort 55Info-menu 55

Manage alarm 55

Troubleshooting 55

11 Accessories 57

12 Technical data 58Dimensions and setting-out coordinates 58

Technical specifications 59

Electrical circuit diagram 62

Item register 72

1Table of Contents |NIBE™ F1226

Page 4: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Safety informationThis manual describes installation and service proceduresfor implementation by specialists.

This appliance is not intended for use by persons (includ-ing children) with reduced physical, sensory or mentalcapabilities, or lack of experience and knowledge, unlessthey have been given supervision or instruction concern-ing use of the appliance by a person responsible for theirsafety.Children should be supervised to ensure that they do notplay with the appliance.Rights to make any design or technical modifications arereserved.©NIBE 2011.

Symbols

NOTE

This symbol indicates danger to machine orperson.

Caution

This symbol indicates important informationabout what you should observe when maintain-ing your installation.

TIP

This symbol indicates tips on how to facilitateusing the product.

Marking

F1226 is CE marked and fulfils IP21.

The CE marking means that NIBE ensures that the productmeets all regulations that are placed on it based on relev-ant EU directives. The CE mark is obligatory for mostproducts sold in the EU, regardless where they are made.

IP21 means that the product can be touched by hand,that objects with a diameter larger than or equivalent to12.5 mm cannot penetrate and cause damage and thatthe product is protected against vertically falling drops.

Serial number

The serial number can be found at the bottom right ofthe front cover and in the info menu (menu 3.1).

Caution

Always give the product's serial number whenreporting a fault.

Country specific information

Installer manual

This installer manual must be left with the customer.

NIBE™ F1226Chapter 1 | Important information2

1 Important information

Page 5: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Inspection of the installation

Current regulations require the heating installation to be inspected before it is commissioned. The inspection must becarried out by a suitably qualified person. Fill in the page for information about installation data in the User manual.

DateSignatureNotesDescription✔

Brine (page 13)

System flushed

System vented

Antifreeze

Level/Expansion vessel

Particle filter

Safety valve

Shut off valves

Circulation pump setting

Heating medium (page 14)

System flushed

System vented

Expansion vessel

Particle filter

Safety valve

Shut off valves

Circulation pump setting

Electricity (page 17)

Fuses heat pump

Fuses property

Outside sensor

Safety breaker

Earth circuit-breaker

Setting of emergency mode thermostat

Miscellaneous

Guarantee submitted

3Chapter 1 | Important informationNIBE™ F1226

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.

Page 6: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Contact informationKNV Energietechnik GmbH, Gahberggasse 11, 4861 SchörflingAT

Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: [email protected] www.knv.atNIBE Wärmetechnik AG, Winterthurerstrasse 710, CH-8247 FlurlingenCH

Tel: (52) 647 00 30 Fax: (52) 647 00 31 E-mail: [email protected] www.nibe.chDruzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad JizerouCZ

Tel: +420 326 373 801 Fax: +420 326 373 803 E-mail: [email protected] www.nibe.czNIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleDE

Tel: 05141/7546-0 Fax: 05141/7546-99 E-mail: [email protected] www.nibe.deVølund Varmeteknik A/S, Member of the Nibe Group, Brogårdsvej 7, 6920 VidebækDK

Tel: 97 17 20 33 Fax: 97 17 29 33 E-mail: [email protected] www.volundvt.dkNIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaFI

Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: [email protected] www.nibe.fiNIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QGGB

Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: [email protected] www.nibe.co.ukNIBE Energietechniek B.V., Postbus 2, NL-4797 ZG WILLEMSTAD (NB)NL

Tel: 0168 477722 Fax: 0168 476998 E-mail: [email protected] www.nibenl.nlABK AS, Brobekkveien 80, 0582 Oslo, Postadresse: Postboks 64 Vollebekk, 0516 OsloNO

Tel. sentralbord: +47 02320 E-mail: [email protected] www.nibeenergysystems.noNIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKPL

Tel: 085 662 84 90 Fax: 085 662 84 14 E-mail: [email protected] www.biawar.com.pl© "EVAN" 17, per. Boynovskiy, Nizhny NovgorodRU

Tel./fax +7 831 419 57 06 E-mail: [email protected] www.nibe-evan.ruNIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydSE

Tel: +46-(0)433-73 000 Fax: +46-(0)433-73 190 E-mail: [email protected] www.nibe.se

For countries not mention in this list, please contact NibeSweden or check www.nibe.eu for more information.

NIBE™ F1226Chapter 1 | Important information4

Page 7: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

TransportF1226 should be transported and stored vertically in adry place. When being moved into a building, F1226 maybe leant back 45 °. Note! Can be tail heavy.

R

0

R0

Pulling out the cooling module

To simplify transport and service, the heat pump can beseparated by pulling the cooling module out from thecabinet.

See page 51 for instructions about the separation.

AssemblyPosition the heat pump on a firm base that can bearits weight, preferably on a concrete floor or founda-tion. Use the heat pump’s adjustable feet to obtaina horizontal and stable set-up.

30 - 50 mm

The area where the heat pump is located must beequipped with floor drainage.

Install with its back to an outside wall, ideally in aroom where noise does not matter, in order to elim-inate noise problems. If this is not possible, avoidplacing it against a wall behind a bedroom or otherroom where noise may be a problem.

Wherever the unit is located, walls to sound sensitiverooms should be fitted with sound insulation.

Route pipes so they are not fixed to an internal wallthat backs on to a bedroom or living room.

Installation area

Leave a space of 800 mm in front of the heat pump.Approx 50 mm free space is required in order to openthe side hatches. The hatches do not need to be openedduring service, all service on F1226 can be carried outfrom the front. Leave space between the heat pump andwall behind (and any routing of supply cables and pipes)to reduce the risk reproduction of any vibration.

(50) (50)

* A normal installation needs 300 - 400 mm (any side) for connec-tion equipment, i.e. level vessel, valves and electrical equipment.

5Chapter 2 | Delivery and handlingNIBE™ F1226

2 Delivery and handling

Page 8: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Supplied components

LEK

Particle filterLevel vesselOutside sensor

LEK

O-ringsSafety valve(0.3 MPa) (3 bar)

Conex connectors

5-8 kW

2 x (ø28 x G25)

2 x (ø22 x G20)

11 kW

4 x (ø28 x G25)

Location

The kit of supplied items is placed in packaging on topof the heat pump.

Removing the coversFront cover

1

2

LE

K

LE

K

1. Remove the screws from the lower edge of the frontcover.

2. Lift the cover out at the bottom edge and up.

Side covers

LE

K

LE

K

LE

K

The side covers can be removed to facilitate the installa-tion.

1. Remove the screws from the upper and lower edges.

2. Twist the cover slightly outward.

3. Move the cover backwards and slightly to the side.

4. Pull the cover to one side.

5. Pull the cover forwards.

NIBE™ F1226Chapter 2 | Delivery and handling6

Page 9: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Removing parts of the insula-tionParts of the insulation can be removed to facilitate theinstallation.

Insulation, top1. Disconnect the cable from the motor and remove

the motor from the shuttle valve as illustrated.

LEK

LEK

A

B

LEK

2. Grip the handle and pull straight out as illustrated.

LEK

Insulation, immersion heater

NOTE

Electrical installation and service must be carriedout under the supervision of a qualified electri-cian. Electrical installation and wiring must becarried out in accordance with the stipulationsin force.

1. Remove the cover of the junction box according tothe description on page 18.

2. Grip the handle and pull the insulation carefully to-wards you as illustrated.

LEK

7Chapter 2 | Delivery and handlingNIBE™ F1226

Page 10: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

General

View from above

Pipe connectionsConnection, heating medium flowXL 1Connection, heating medium returnXL 2Connection, cold waterXL 3Connection, hot waterXL 4Connection, HWC*XL 5Connection, brine inXL 6Connection, brine outXL 7

* Only applies to stainless steel vessels.

HVAC componentsVenting, coilQM 22Shut off valve, heating medium returnQM 32Shut off valve, brine outQM 33Shut-off valve, brine inQM 34Shuttle valve, climate system/water heaterQN 10Pipe connection, heating medium flowWP 4

Sensors etc.Outside sensorBT 1Temperature sensors, heating medium flowBT 2Temperature sensor, hot water chargingBT 6Temperature sensor, hot water topBT 7

Electrical componentsDisplay unitAA 4

AA4-XJ3 USB outlet (no function)

AA4-XJ4 Service outlet (No function)Immersion heaterEB 1SwitchSF 1

MiscellaneousRating platePF 1Type plate, cooling sectionPF 2Serial number platePF 3Cable gland, incoming electricityUB 1Cable glandUB 2Cable gland, rear side, sensorUB 3

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

NIBE™ F1226Chapter 3 | The heat pump design8

3 The heat pump design

Page 11: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Electrical cabinets

Electrical componentsImmersion heater cardAA 1Base cardAA 2Miniature circuit-breakerFA 1Motor cut-out*FB 1Temperature limiter/Emergency mode thermostatFD 1Terminal blockX 1

* 5 kW has auxiliary switch for motor cut-out.

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

9Chapter 3 | The heat pump designNIBE™ F1226

Page 12: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

3x400 V 5 kW

3x400 V 6-11 kW

Electrical componentsSoft-start cardAA 10CapacitorCA 1Motor cut-out*FB 1Soft-starterQA 30Terminal blockX 301Terminal blockX 302

* 5 kW has auxiliary switch for motor cut-out.

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

NIBE™ F1226Chapter 3 | The heat pump design10

Page 13: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Cooling section Pipe connectionsService connection, high pressureXL 20Service connection, low pressureXL 21

HVAC componentsCirculation pumpGP 1Brine pumpGP 2Drainage, climate systemQM 1Draining, brine sideQM 2

Sensors etc.High pressure pressostatBP 1Low pressure pressostatBP 2Temperature sensors, heating medium returnBT 3Temperature sensor, brine inBT 10Temperature sensor, brine outBT 11Temperature sensor, condenser supply lineBT 12Temperature sensor, hot gasBT 14Temperature sensor, fluid pipeBT 15Temperature sensor, suction gasBT 17

Electrical componentsJoint cardAA 100Compressor heaterEB 10

Cooling componentsEvaporatorEP 1CondenserEP 2CompressorGQ 10Drying filterHS 1Expansion valveQN 1

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

11Chapter 3 | The heat pump designNIBE™ F1226

Page 14: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

GeneralPipe installation must be carried out in accordance withcurrent norms and directives. F1226 can operate with areturn temperature of up to 56 °C and an outgoingtemperature from the heat pump of 70 (63 °C with onlythe compressor).

F1226 is not equipped with external shut off valves; thesemust be installed to facilitate any future servicing.

NOTE

The pipe system needs to be flushed out beforethe heat pump is connected so that debris can-not damage component parts.

Symbol key

MeaningSymbol

Venting valve

Shut-off valve

Non-return valve

Shunt / shuttle valve

Safety valve

Trim valve

Temperature sensor

Level vessel

Pressure gaugeP

Circulation pump

Particle filterAuxiliary relay

Fan

Compressor

Heat exchanger

System diagram

F1226 consists of a heat pump, water heater, electricalmodule, circulation pumps and a control system. F1226is connected to the brine and heating medium circuits.

In the heat pump evaporator, the brine (water mixed withanti-freeze, glycol or ethanol) releases its energy to therefrigerant, which is vaporised in order to be compressedin the compressor. The refrigerant, of which the temper-ature has now been raised, is passed to the condenserwhere it gives off its energy to the heating medium circuitand, if necessary, to the water heater. If there is a greaterneed for heating/hot water than the compressor canprovide there is an integrated immersion heater.

Connection, heating medium flowXL 1Connection, heating medium returnXL 2Connection, cold waterXL 3Connection, hot waterXL 4Connection, brine inXL 6Connection, brine outXL 7

NIBE™ F1226Chapter 4 | Pipe connections12

4 Pipe connections

Page 15: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Dimensions and pipe connec-tions

62

0

600

560 440

70

17

75

65

0*

25

-50

25

50

130

210

390

470

525

65

0*

Pipe dimensions

11kW

5-8kW

Connection

28(mm)(XL6)/(XL7) Brine in/out ext Ø

2822(mm)(XL1)/(XL2) Heating mediumflow/return ext Ø

22(mm)(XL3)/(XL4) Cold/hot water Ø

Brine sideCollector

Rock heat, recom-mended active

drilling depth (m)

Surface soil heat,recommended col-lector length (m)

Type

70-90200-3005 kW90-110250-4006 kW

120-145325-2x2508 kW180-2102x250-2x35011 kW

Applies to PEM hose 40x2.4 PN 6.3.

These are rough example values. At installation the correctcalculations must be made according to local conditions.

Caution

The length of the collector hose varies depend-ing on the rock/soil conditions, climate zone andon the climate system (radiators or underfloorheating).

Max length per coil for the collector should not exceed400 m.

In those cases where it is necessary to have several collect-ors, these should be connected in parallel with the pos-sibility for adjusting the flow of the relevant coil.

For surface soil heat, the hose should be buried at a depthdetermined by local conditions and the distance betweenthe hoses should be at least 1 metre.

For several bore holes, the distance between the holesmust be determined according to local conditions.

Ensure the collector hose rises constantly towards theheat pump to avoid air pockets. If this is not possible,airvents should be used.

As the temperature of brine system can fall below 0 °Cit must be protected against freezing down to -15 °C. 1litre of ready mixed brine per meter of collector hose(applies when using PEM-hose 40x 2.4 PN 6.3) is used asa guide value when making the volume calculation.

Side connection

It is possible to angle the brine connections, for connec-tion to the side instead of top connection.

To angle out a connection:

1. Disconnect the pipe at the top connection.

2. Angle the pipe in the desired direction.

3. If necessary, cut the pipe to the desired length.

Connecting the brine sideInsulate all indoor brine pipes against condensation.

* Can be angled for side connection.

13Chapter 4 | Pipe connectionsNIBE™ F1226

Page 16: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

The level vessel must be installed as the highest pointin the brine system on the incoming pipe before thebrine pump (Alt. 1).

If the level vessel cannot be placed at the highest pointan expansion vessel must be used (Alt. 2).

NOTE

Note that condensation may drip from the levelvessel. Position the vessel so that this does notharm other equipment.

Details of the antifreeze used must be shown on thelevel vessel.

Install the supplied safety valve under the level vesselas illustrated. The entire length of the overflow waterpipe from the safety valves must be inclined to preventwater pockets and must also be frost proof.

Install shut off valves as close to the heat pump aspossible.

Fit the supplied particle filter on the incoming pipe.

In the case of connection to an open groundwater system,an intermediate frost-protected circuit must be provided,because of the risk of dirt and freezing in the evaporator.This requires an extra heat exchanger.

P

Heating medium sideConnecting the climate system

A climate system is a system that regulates indoor comfortwith the help of the control system in F1226 and for ex-ample radiators, underfloor heating/cooling, fan con-vectors etc.

Install all required safety devices, shut-off valves (asclose to the heat pump as possible), and suppliedparticle filter.

The safety valve must have a maximum 0.25 MPa (2.5bar) opening pressure and be installed on the heatingmedium return as illustrated. The entire length of theoverflow water pipe from the safety valves must beinclined to prevent water pockets and must also befrost proof.

When connecting to a system with thermostats onall radiators, a relief valve must be fitted, or some ofthe thermostats must be removed to ensure sufficientflow.

P

Hot water heaterConnecting the hot water heater

The hot water heater in the heat pump must be sup-plied with necessary set of valves.

The mixing valve must be installed if the setting ischanged so that the temperature can exceed 60 °C.The setting is made in menu 5.1.1 (page 45)

The safety valve must have a maximum 1.0 MPa (10.0bar) opening pressure and be installed on the incom-ing domestic water line as illustrated. The entire lengthof the overflow water pipe from the safety valves mustbe inclined to prevent water pockets and must alsobe frost proof.

NIBE™ F1226Chapter 4 | Pipe connections14

Page 17: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Docking alternativesF1226 can be connected in several different ways, someof which are shown below.

Further option information is available at www.nibe.euand in the respective assembly instructions for the ac-cessories used. See page 57 for a list of the accessoriesthat can be used with F1226.

Extra electric hot water heater

The heat pump should be supplemented with an electricwater heater, for example NIBE COMPACT, if a whirlpoolor other significant consumer of hot water is installed.

The valve connection on COMPACT can be separated.The mixing valve remains on COMPACT and the re-maining valve connector can be used for incomingcold water in F1226.

VV

KV

Buffer vessel

If the climate system volume is too small for the heatpump output, the radiator system can be supplementedwith a buffer vessel, for example NIBE UKV.

UKV

P

Ventilation recovery

The installation can be supplemented with the exhaustair module FLM to provide ventilation recovery.

Pipes and other cold surfaces must be insulated withdiffusion-proof material to prevent condensation.

The brine system must be supplied with a pressureexpansion vessel (CM3). If there is a level vessel (CM2)this should be replaced.

Frånluft Ø 160

Avluft Ø 160

P

Free cooling

The installation can be supplemented with fan convectors,for example, in order to allow connections for free cool-ing.

Pipes and other cold surfaces must be insulated withdiffusion-proof material to prevent condensation.

Where the cooling demand is high, fan convectorswith drip trays and drain connection are needed.

The brine system must be supplied with a pressureexpansion vessel (CM3). If there is a level vessel (CM2)this should be replaced.

P

Fläktkonvektor

15Chapter 4 | Pipe connectionsNIBE™ F1226

Page 18: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Under floor heating systems

The external circulation pump is dimensioned for theunder floor heating system’s demand.

If the climate system volume is too small for the heatpump output, the underfloor heating system can besupplemented with a buffer vessel, for example NIBEUKV.

UKV

P

Ground water system

An intermediate heat exchanger is used to protect theheat pump's exchanger from dirt. The water is releasedinto a buried filtration unit or a drilled well. This dockingalternative requires the EXC 40 accessory.

NIBE™ F1226Chapter 4 | Pipe connections16

Page 19: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

GeneralAll electrical equipment except for the outdoor temperat-ure sensors has been connected at the factory.

Disconnect the heat pump before insulation testingthe house wiring.

If the building is equipped with an earth-fault breaker,F1226 should be equipped with a separate one.

If a miniature circuit breaker is used this should haveat least motor characteristic “C”. See page 59 forfuse size.

For the heat pump wiring diagram, see page 62.

Communication and sensor cables to external connec-tions must not be laid close to high current cables.

The minimum area of communication and sensorcables to external connections must be 0.5 mm² upto 50 m, for example EKKX or LiYY or equivalent.

When cable routing in F1226, cable grommets (e.g.UB1-UB3, marked in image) must be used. In UB1-UB3the cables are inserted through the heat pump fromthe back to the front.

NOTE

The switch (SF1) must not be moved to "" or

" " until the boiler has been filled with water.Otherwise the temperature limiter, thermostat,compressor and the immersion heater can bedamaged.

NOTE

Electrical installation and service must be carriedout under the supervision of a qualified electri-cian. Cut the current with the circuit breakerbefore carrying out any servicing. Electrical in-stallation and wiring must be carried out in ac-cordance with the stipulations in force.

Miniature circuit-breaker

The heat pump and a large proportion of its internalcomponents are internally fused by a miniature circuitbreaker (FA1).

Temperature limiter

The temperature limiter (FD1) cuts the current supply tothe electrical addition if the temperature rises between90 and 100°C and can be manually reset.

Resetting

The temperature limiter (FD1) is accessible behind thefront cover. Reset the temperature limiter by pressing thebutton (FD1-SF2) using a small screwdriver.

Motor cut-out

Motor protection breaker (FB1) cuts the power to thecompressor if the current is too high.

Resetting

The motor protection breaker (FB1) is accessible behindthe front cover. The breaker is reset by twisting the con-trol knob to horizontal position.

Caution

Check the miniature circuit-breaker, temperaturelimiter and motor protection breaker. They mayhave tripped during transportation.

17Chapter 5 | Electrical connectionsNIBE™ F1226

5 Electrical connections

Page 20: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Accessibility, electrical connection

The plastic cap of the electrical boxes is opened using ascrewdriver.

NOTE

The cover for the terminal block for soft inputsis opened without a tool.

Removing the cover, terminal block

LEK

1

2

1. Push the catch down.

2. Angle out the cover and remove it.

Removing the cover, immersion heater circuitboard

LEK

1

2

A

B

1. Insert the screwdriver (A) and pry the catch carefullydownwards (B).

2. Angle out the cover and remove it.

Removing the cover, base board

Caution

To remove the cover for the base board, thecover for the terminal block for soft inputs mustfirst be removed.

LEK

LEK

1

A

B

2

1. Disconnect the switches using a screwdriver.

2. Insert the screwdriver (A) and pry the catch carefullydownwards (B).

3. Angle out the cover and remove it.

NIBE™ F1226Chapter 5 | Electrical connections18

Page 21: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Cable lock

Use a suitable tool to release/lock cables in the heat pumpterminal blocks.

2

1

2

3

LEK

3

4

1

2

Connections

NOTE

To prevent interference, unscreened communic-ation and/or sensor to external connectionscables must not be laid closer than 20 cm tohigh voltage cable when cable routing.

Power connection

F1226 must be installed via an isolator switch with aminimum breaking gap of 3mm. Minimum cable areamust be dimensioned according to the fuse rating used.Supplied cable for incoming electricity is connected toterminal block X1 on the immersion heater card (AA1).

Connection 3x400V

PE1

L1 1 L2 L3PE0N

NOTE

F1226-11 contains scroll compressor, whichmeans that it is important that electrical connec-tions are made with the correct phase sequence.With the incorrect phase sequence, the com-pressor does not start and an alarm is displayed.

If separate supply to the compressor and immersionheater is required, see section "Switch for externalblocking of addition and/or compressor" on page 22.

Tariff control

If the voltage to the immersion heater and/or the com-pressor disappears during a certain period, there mustalso be blocking via the AUX-input, see "Connectionoptions- Possible selection for AUX inputs".

Connecting external operating voltage forthe control system

NOTE

Mark up any junction boxes with warnings forexternal voltage.

If you wish to connect external operating voltage for thecontrol system to F1226 on the immersion heater circuitboard (AA1) the edge connector at AA1:X2 must bemoved toAA1:X9 (as illustrated).

Operating voltage (1x230V+N+PE) is connected toAA1:X11 (as illustrated).

1 2

3

4

5

6

ON

L1 1 L2 L3PE

PE

0N

NL

19Chapter 5 | Electrical connectionsNIBE™ F1226

Page 22: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Outside sensor

Install the outside temperature sensor (BT1) in the shadeon a wall facing north or north-west, so it is unaffectedby themorning sun.

Connect the sensor to terminal block X1:1 and X1:2. Usea 2 core cable of at least 0.5 mm² cable area.

If a conduit is used it must be sealed to prevent condens-ation in the sensor capsule.

56

42

31

56

42

31

Settings

Electrical addition - maximum output

On delivery the immersion heater is connected for amaximum of 7 kW (switchable to 9 kW).

The immersion heater's output is split into seven steps(four steps if the immersion heater is switched to maxim-um 9 kW), according to the table below.

Setting max electrical output

Setting maximum output in the electrical addition is donein menu 5.1.12.

The tables display the total phase current for the immer-sion heater.

Switching to maximum electrical output

If more than the maximum output for the immersionheater connected on delivery is needed, the heat pumpcan be switched to maximum 9 kW.

Move the white cable from terminal block X7:23 to ter-minal block X3:13 (the seal on the terminal block mustbe broken) on the immersion heater card (AA1).

3x400V (maximum electrical output, connectedupon delivery 7 kW)

Max phasecurrentL3(A)

Max phasecurrentL2(A)

Max phasecurrentL1(A)

Max elec-trical addi-tion (kW)

00004.300108.702

4.38.7038.78.7044.38.78.758.78.78.76138.78.77

NIBE™ F1226Chapter 5 | Electrical connections20

Page 23: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

3x400V (maximum electrical output, switched to9 kW)

Max phasecurrentL3(A)

Max phasecurrentL2(A)

Max phasecurrentL1(A)

Max elec-trical addi-tion (kW)

000008.702

8.78.7048.78.78.7616.216.28.79

Emergency mode

When the heat pump is set to emergency mode (SF1 isset to ) only the most necessary functions are activated.

The compressor is off and heating is managed by theimmersion heater.

Hot water is not produced.

NOTE

Switch (SF1) must not be moved to "" or " "until F1226 has been filled with water. Other-wise the temperature limiter, thermostat, com-pressor and the immersion heater can be dam-aged.

Power in emergency mode

The immersion heater’s output in emergency mode is setwith the dipswitch (S2) on the immersion heater circuitboard (AA1) according to the table below. Factory settingis 6 kW.

When installing according to current building regulations(BBR) the immersion heater's power in emergency modemust be set to the maximum permitted electrical output.

3x400V (maximum electrical output, connectedupon delivery 7 kW)

654321

onoffoffoffoffoff1 kWoffoffoffonoffoff2 kWonoffoffonoffoff3 kWoffonoffonoffoff4 kWonoffoffonoffon5 kWoffonoffonoffon6 kWononoffonoffon7 kW

3x400V (maximum electrical output, switched to9 kW)

654321

offonoffoffoffoff2 kWoffonoffonoffoff4 kWoffonoffonoffon6 kWononononoffon9 kW

3x400V

1 2

3 4

5 6

ON

The image shows the dip-switch (AA1-SF2) in the factorysetting, that is 6 kW.

Emergency mode thermostat

The supply temperature is set in emergency mode usinga thermostat (FD1-BT30). It can be set to 35 (pre-set, forexample underfloor heating) or 45 °C (for example radi-ators).

LEK

21Chapter 5 | Electrical connectionsNIBE™ F1226

Page 24: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Optional connectionsExternal connection options

On the terminal block (X1) F1226 has software controlledinputs for connecting the external switch function orsensor. This means that when an external switch functionor sensor is connected to one of two special connections,the correct function must be selected to the correct con-nection in the software in F1226.

Caution

If an external switch function or sensor is connec-ted to F1226, the function for use input mustbe selected in menu 5.4, see page 47.

Selectable inputs on the input card for these functionsare AUX1 (X1:3-4) and AUX2 (X1:5-6)

56

78

42

31

B

A

56

42

31

The example above uses the inputs AUX1 (X1:3-4) and AUX2 (X1:5-6) on the terminal block (X1).

Caution

Some of the following functions can also be ac-tivated via menu settings.

Possible selection for AUX inputs

Room temperature sensor (accessory)

F1226 can be supplemented with the accessory RTS 40(room temperature sensor).

The room temperature sensor is connected to the selectedinput (menu 5.4, see page 47) on terminal block X1 and

installed in the building according to the installer hand-book.

Temperature sensor, external flow line

If temperature sensor, external flow line (BT25) needs tobe used, connect it to selected input (menu 5.4, see page47) on terminal block X1. Use a 2 core cable of at least0.5 mm² cable area.

Switch for external blocking of addition and/orcompressor

In those cases external blocking of addition and/or com-pressor is wanted, this can be connected to terminal blockX1, which is positioned behind the front cover.

The additional heat and/or the compressor are disconnec-ted by connecting a potential free switch function to theinput selected in menu 5.4, see page 47.

External blocking of addition and compressor can becombined.

A closed contact results in the electrical output beingdisconnected.

Switch for external blocking of heating

In those cases external blocking of heat is used, this canbe connected to terminal block X1, which is positionedbehind the front cover.

Heating operation is disconnected by connecting a poten-tial free switch function to the input selected in menu5.4, see page 47.

A closed switch results in blocked heating operation.

Contact for activation of “temporary lux"

An external contact function can be connected to F1226for activation of the hot water function“temporary lux".The switch must be potential free and connected to theselected input (menu 5.4, see page 47) on terminal blockX1.

"temporary lux" is activated for the time that the contactis connected.

Contact for activation of “external adjustment"

An external contact function can be connected to F1226to change the supply temperature and the room temper-ature.

When the switch is closed the temperature changes in°C (if the room sensor is connected and activated). If aroom sensor is not connected or not activated, the desiredoffset of "temperature" (heating curve offset) is set withthe number of steps selected. The value is adjustablebetween -10 and +10.

climate system 1

The switch must be potential free and connected tothe selected input (menu 5.4, see page 47) on termin-al block X1.

NIBE™ F1226Chapter 5 | Electrical connections22

Page 25: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

The value for the change is set in menu 1.9.2, "extern-al adjustment".

Connecting accessoriesInstructions for connecting accessories are in the installa-tion instructions provided for the respective accessory.See page 57 for the list of the accessories that can beused with F1226.

23Chapter 5 | Electrical connectionsNIBE™ F1226

Page 26: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Preparations1. Check that the switch (SF1) is in position " ".

2. Check that the temperature limiter FD1 has nottripped.

3. Check for water in the hot water heater and climatesystem.

Caution

Check the temperature limiter, motor protectionand miniature circuit-breaker. They may havetripped during transportation.

Filling and ventingFilling and venting the climate system

Filling1. Open the venting valve (QM22).

2. When the water that exits the venting valve (QM22)is not mixed with air, close the valve. After a whilethe pressure starts to rise.

3. Close the filling valve when the correct pressure isobtained.

Venting1. Bleed the heat pump via the bleed valve (QM22) and

the rest of the climate system via the relevant bleedvalves.

2. Keep topping up and venting until all air has beenremoved and the pressure is correct.

TIP

If the heating medium pump (GP1) must be runduring venting, it can be started via the startguide.

NOTE

The pipe from the coil in the container must bedrained of water before air can be released. Thismeans that the system is not necessarily venteddespite the flow of water when the venting valve(QM22) is opened.

Filling the hot water heater

1. Open a hot water tap in the house.

2. Fill the hot water heater through the cold waterconnection (XL3).

3. When the water that comes out of the hot water tapis no longer mixed with air, the water heater is fulland the tap can be closed.

Filling and venting the brine system

When filling the brine system, mix the water with anti-freeze in an open container. The mixture should be pro-tected against freezing down to about -15 °C. The brineis filled by connecting a filling pump.

1. Check the brine system for leakage.

2. Connect the filling pump and return line on the brinesystem's filler connector as illustrated.

3. If alternative 1 (level vessel) is used, close the valveunder the level vessel (CM2).

4. Close the three way valve in the filler connector (ac-cessory).

5. Open the valves on the filler connector.

6. Start the filling pump.

7. Fill until liquid enters the return pipe.

8. Vent the brine system with venting valve on F1226.

9. Close the valves on the filler connector.

10. Open the three way valve in the filler connector.

11. If alternative 1 (level vessel) is used, open the valveunder the level vessel (CM2).

TIP

If the brine pump (GP2) must be run duringventing, it can be started via the start guide.

VVKV

KBin

VBf VBr

KBut

BK / JK

Stängs

P

NIBE™ F1226Chapter 6 | Commissioning and adjusting24

6 Commissioning and adjusting

Page 27: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Connection, heating medium flowXL 1Connection, heating medium returnXL 2Connection, cold waterXL 3Connection, hot waterXL 4Connection, brine inXL 6Connection, brine outXL 7

Symbol key

MeaningSymbol

Shut-off valve

Safety valve

Level vessel

Expansion vessel

Pressure gaugeP

Particle filter

Start guide

NOTE

There must be water in the climate system be-fore the switch is set to " ".

1. Turn the heat pump's switch (SF1) to "".

2. Follow the instructions in the start guide in the heatpump display. If the start guide does not start whenyou start the heat pump, start it manually in menu5.7.

Commissioning

The first time the heat pump is started a start guide isstarted. The start guide instructions state what needs tocarried out at the first start together with a run throughof the heat pump’s basic settings.

The start guide ensures that the start-up is carried outcorrectly and cannot be bypassed. The start guide can bestarted later in menu 5.7.

Operation in the start guide

1. Turn the control knob until one of the arrows in thetop left corner (at the page number) has beenmarked.

2. Press the OK button to skip between the steps in thestart guide.

See page 33 for a more in-depth introduction to the heatpump’s control system.

The start guide will be described under the followingpoints step-by-step.

1 Selection of language

Choose the language that you want the information tobe displayed in here.

Change language as follows:

1. Turn the control knob until the language you requireis marked.

2. Press the OK button.

3. Turn the control knob until the arrow in the top leftcorner (at the page number) has been marked.

4. Press the OK button to access the next step in thestart guide.

2 Information

Information about the start guide for the heat pump isshown here.

25Chapter 6 | Commissioning and adjustingNIBE™ F1226

Page 28: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

3 Setting "operating mode brine pump"

op. mode

Setting range: intermittent, continuous, 10 days con-tinuous

Default value: intermittent

Set the operating mode of the brine pump here.

intermittent: The brine pump starts 20 seconds beforeand stops at the same time as the compressor.

continuous: Continuous operation.

10 days continuous: Continuous operation for 10 days.Then the pump shifts to intermittent operation.

TIP

You can use “10 days continuous" at start-upto obtain continuous circulation during a start-up time in order to make it easier to bleed thesystem.

5 Setting "op. mod heat med pump"

op. mode

Setting range: auto, intermittent, continuous

Default value: auto

Set the operating mode of the heating medium pumphere.

auto: The heating medium pump runs according to thecurrent operating mode for F1226.

intermittent: The heating medium pump starts 20seconds before and stops at the same time as the com-pressor.

continuous: Continuous operation.

6 Setting "internal electrical addition"

max connected el. add.

Setting range: 7 / 9 kW

Default values: 7 kW

set max electrical add.

Setting range: 0 - 9 kW

Default values: 6 kW

Here you set the max. electrical output of the internalelectrical addition in F1226 and the fuse size for the in-stallation.

NIBE™ F1226Chapter 6 | Commissioning and adjusting26

Page 29: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

8 Room sensor settings

factor system

Setting range: 0.2 - 3.0

Default value: 2.0

Room sensors to control the room temperature can beactivated here.

Here you can set a factor that determines how much thesupply temperature is to be affected by the differencebetween the desired room temperature and the actualroom temperature. A higher value gives a greater changeof the heating curve's set offset.

22 Checking the measurement values fromsensor

Check here whether the selected externally mountedsensor shows permitted values for the installation.

23 Setting time and date

Set time and date and display mode here.

24 Setting min. flow line temp.

climate system

Setting range: 15-50 °C

Default values: 15°C

Set the minimum temperature on the supply temperatureto the climate system. This means that F1226 never cal-culates a temperature lower than that set here.

TIP

The value can be increased if you have, for ex-ample, a cellar that you always want to heat,even in summer.

You may also need to increase the value in "stopheating" menu 4.9.2 "auto mode setting".

25 Setting max. flow line temp.

climate system

Setting range: 15-80 °C

Default value: 60 °C

Set the maximum supply temperature for the climatesystem here.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max floor temperature with your floorsupplier.

27Chapter 6 | Commissioning and adjustingNIBE™ F1226

Page 30: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

26 Setting the heat curve

At basic setting the climate system "heating curve" and"temperature" (heating curve offset) must be changed.

Further information on how to set the heating curve canbe found on page 38.

Setting automatic heating controls with diagram

The diagrams are based on the dimensioned outdoortemperature in the area and the dimensioned supplytemperature of the climate system. When these two val-ues "meet", the heating control's curve slope can beread. This is set under "heating curve“ in menu 1.9.1.

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

- 40 °C

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70°C

FR

AM

LED

NIN

GS

TE

MP

ER

ATU

R

- 20 - 30

FÖRSKJUTNINGVÄRMEKURVA (-2)

VÄRMEKURVA

30

40

50

60

70°C

FR

AM

LED

NIN

GS

TE

MP

ER

ATU

R

- 40 °C

UTETEMPERATUR

- 10010 - 20 - 30

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

VÄRMEKURVA

- 5

+ 5

FÖRSKJUTNINGVÄRMEKURVA (0)

1514 13 12 11 108

7

6

5

4

3

2

1

- 40 °C

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70°C

FR

AM

LED

NIN

GS

TE

MP

ER

ATU

R

- 20 - 30

FÖRSKJUTNINGVÄRMEKURVA (+2)

9

VÄRMEKURVA

27 Setting operating mode

op. mode

Setting range: auto, manual, add. heat only

Default value: auto

functions

Setting range: compressor, addition, heating

The heat pump operating mode is usually set to "auto".It is also possible to set the heat pump to "add. heatonly", but only when an addition is used, or "manual"and select yourself what functions are to be permitted.

Change the operating mode by marking the desired modeand pressing the OK button. When an operating modeis selected it shows what in the heat pump is permitted(crossed out = not permitted) and selectable alternativesto the right. To select selectable functions that are permit-ted or not you mark the function using the control knoband press the OK button.

Operating mode auto

In this operating mode you cannot select which functionsare to be permitted because it is handled automaticallyby the heat pump.

Operating mode manual

In this operating mode you can select what functions arepermitted. You cannot deselect "compressor" in manualmode.

NIBE™ F1226Chapter 6 | Commissioning and adjusting28

Page 31: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Operating mode add. heat only

Caution

If you choose mode "add. heat only" the com-pressor is deselected and there is a higher oper-ating cost.

In this operating mode the compressor is not active andonly additional heating is used.

Functions

"compressor" is that which produces heating and hotwater for the accommodation. If "compressor" isdeselected, a symbol in the main menu on the heat pumpsymbol is displayed. You cannot deselect "compressor"in manual mode.

"addition" is what helps the compressor to heat theaccommodation and/or the hot water when it cannotmanage the whole requirement alone.

"heating" means that you get heat in the accommoda-tion. You can deselect the function when you do notwish to have heating running.

Caution

If you deselect "addition" it may mean thatsufficient heating in the accommodation is notachieved.

28 Dealing with alarms

Select how you want the heat pump to alert you thatthere is an alarm in the display here.

The different alternatives are that the heat pump stopsproducing hot water (default setting) and/or reduces theroom temperature.

Caution

If no alarm action is selected, it can result inhigher energy consumption in the event of analarm.

29 Filling in the checklist

Do not forget to fill in the checklist on page 3 and inthe user manual.

30 Complete the start guide

Here you select whether to start the start guide the nexttime the heat pump is restarted.

Caution

If you choose "yes" this means that the nexttime the heat pump is started (e.g. after a powercut) it will not produce heat or hot water for 60minutes.

29Chapter 6 | Commissioning and adjustingNIBE™ F1226

Page 32: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Post adjustment and ventingPump capacity diagrams, collector side

To set the correct flow in the brine system the correctspeed must be set for the brine pump.

The flow must have a temperature difference betweenbrine out (BT11) and brine in (BT10) of 2 - 5 °C when thesystem is balanced (suitably 5 minutes after compressorstart). Check these temperatures in menu 3.1 "serviceinfo" and adjust the brine pump (GP2) speed until thetemperature difference is achieved. A high difference in-dicates a low brine flow and a low difference indicates ahigh brine flow.

Read off what speed the brine pump should have fromthe diagrams below.

EleffektTillgängligt tryck

P

F1226 5 kW

0

10

20

30

40

50

60

70

80

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,40

20

40

60

80

100

120

140

160

Flödel/s

P3P2

P1

1

2

3

Eleffekt, WTillgängligt tryck, kPa

F1226 6 kW

0

10

20

30

40

50

60

70

80

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,40

20

40

60

80

100

120

140

160

P3

P1

P2

3

1

2

Flödel/s

Eleffekt, WTillgängligt tryck, kPa

F1226 8 kW

0

10

20

30

40

50

60

70

80

0 0,1 0,2 0,3 0,4 0,50

20

40

60

80

100

120

140

160

P3

P2P1

1

2 3

Flödel/s

Eleffekt, WTillgängligt tryck, kPa

F1226 11 kW

0

20

40

60

80

100

120

0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,80

40

80

120

160

200

240

P4P3

P2

P1

4

32

1

Flödel/s

Eleffekt, WTillgängligt tryck, kPa

NIBE™ F1226Chapter 6 | Commissioning and adjusting30

Page 33: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Pump capacity diagrams, heating mediumside

To set the correct flow in the climate system the correctspeed must be set for the heating medium pump in thedifferent operating conditions.

The flow must have a suitable temperature difference forthe operation (heating operation: 5 - 10 °C, hot waterregeneration: 8 - 10 °C, pool heating: approx. 15 °C)between flow temperature (BT2) and the return temper-ature (BT3). Check these temperatures in menu 3.1"service info" and adjust the heating medium pump (GP1)speed until the temperature difference is achieved. A highdifference indicates a low heating medium flow and alow difference indicates a high heating medium flow.

EleffektTillgängligt tryck

P

F1226 5 kW

0

10

20

30

40

50

60

70

80

0 0,05 0,1 0,15 0,2 0,25 0,3 0,350

10

20

30

40

50

60

70

80

Flödel/s

P3P2

P1

12

3

Eleffekt, WTillgängligt tryck, kPa

F1226 6 kW

0

10

20

30

40

50

60

70

80

0 0,05 0,1 0,15 0,2 0,25 0,3 0,350

10

20

30

40

50

60

70

80P3

P1

P2

3

12

Flödel/s

Eleffekt, WTillgängligt tryck, kPa

F1226 8 kW

0

10

20

30

40

50

60

70

80

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,40

10

20

30

40

50

60

70

80P3

P2

P1

1

23

Flödel/s

Eleffekt, WTillgängligt tryck, kPa

F1226 11 kW

0

10

20

30

40

50

60

70

80

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,40

20

40

60

80

100

120

140P3

P2

P13

2

1

Flödel/s

Eleffekt, WTillgängligt tryck, kPa

31Chapter 6 | Commissioning and adjustingNIBE™ F1226

Page 34: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Readjusting, venting, heat medium side

Air is initially released from the hot water and ventingmay be necessary. If gurgling sounds can be heard fromthe heat pump or climate system, the entire system willrequire additional venting.

Readjusting, venting, collector side

Level vessel

2/3

LE

K

Check the fluid level in the level vessel(CM2). If the fluid level has dropped, top upthe system.

1. Close the valve under the vessel.

2. Disconnect the connection on top of thevessel.

3. Fill with brine until approx 2/3 of thevessel is full.

4. Reconnect the connector at the top ofthe vessel.

5. Open the valve under the vessel.

The pressure is raised by closing the valve on the incomingmain line when the brine pump (GP2) is running and thelevel vessel (CM2) is open, so that liquid is drawn downfrom the vessel.

Expansion vessel

LEK

If a pressure expansion vessel (CM3) is usedinstead of a level vessel, the pressure levelis checked. If the pressure drops, the systemshould be replenished.

Post adjusting the room temperat-ure

If the required room temperature is not obtained, read-justment may be necessary.

Cold weather conditionsIf the room temperature is too low, increase "heatingcurve" in menu 1.9.1, one step.

If the room temperature is too high, reduce "heatingcurve" in menu 1.9.1, one step.

Warm weather conditionsIf the room temperature is too low, increase "temper-ature" (heating curve offset) in menu 1.1, one step.

If the room temperature is too high, reduce "temper-ature" (heating curve offset) in menu 1.1, one step.

NIBE™ F1226Chapter 6 | Commissioning and adjusting32

Page 35: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Display unit

DisplayInstructions, settings and operational informationare shown on the display. The easy-to-read dis-play and menu system, facilitates navigationbetween the different menus and options to setthe comfort or obtain the information you re-quire.

A

Status lampThe status lamp indicates the status of the heatpump. It:

lights green during normal operation.lights yellow in emergency mode.lights red in the event of a deployed alarm.

B

OK buttonThe OK button is used to:

confirm selections of sub menus/options/setvalues/page in the start guide.

C

Back buttonThe back button is used to:

go back to the previous menu.change a setting that has not been con-firmed.

D

Control knobThe control knob can be turned to the right orleft. You can:

scroll in menus and between options.increase and decrease the values.change page in multiple page instructions(for example help text and service info).

E

Switch (SF1)The switch assumes three positions:

On ( )

Standby ( )

Emergency mode ( )

Emergency mode must only be used in the eventof a fault on the heat pump. In this mode, thecompressor switches off and the immersionheater engages. The heat pump display is not il-luminated and the status lamp illuminates yellow.

F

33Chapter 7 | Control - IntroductionNIBE™ F1226

7 Control - Introduction

Page 36: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu systemWhen the door to the heat pump is opened, the menusystem’s four main menus are shown in the display aswell as certain basic information.

Menu 1 - INDOOR CLIMATE

Setting the indoor climate. See page 37.

Menu 2 - HOT WATER

Setting the hot water production. See page 41.

Menu 3 - INFO

Display of temperature and other operating informationand access to the alarm log. See page 42.

Menu 4 - HEAT PUMP

Setting time, date, language, display, operating modeetc. See page 43.

Menu 5 - SERVICE

Advanced settings. These settings are not available to theend user. The menu is visible by pressing the Back buttonfor 7 seconds. See page 45.

NIBE™ F1226Chapter 7 | Control - Introduction34

Page 37: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Operation

To move the cursor, turn the control knobto the left or the right. The marked positionis brighter and/or has a light frame.

Selecting menu

To advance in the menu system select a main menu bymarking it and then pressing the OK button. A newwindow then opens with sub menus.

Select one of the sub menus by marking it and thenpressing the OK button.

Selecting options

In an options menu the current selected option isindicated by a green tick.

To select another option:

Mark the applicable option. One of the optionsis pre-selected (white).

1.

Press the OK button to confirm the selectedoption. The selected option has a green tick.

2.

35Chapter 7 | Control - IntroductionNIBE™ F1226

Page 38: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Setting a value

To set a value:

Mark the value you want to set using thecontrol knob.

1.

Press the OK button. The background ofthe value becomes green, which meansthat you have accessed the setting mode.

2.

Turn the control knob to the right to in-crease the value and to the left to reducethe value.

3.

Press the OK button to confirm the valueyou have set. To change and return to theoriginal value, press the Back button.

4.

Scroll through the windows

A menu can consist of several windows. Turn the controlknob to scroll between the windows.

Scroll through the windows in the start guide

1. Turn the control knob until one of the arrows in thetop left corner (at the page number) has beenmarked.

2. Press the OK button to skip between the steps in thestart guide.

Help menu

In many menus there is a symbol that indicates thatextra help is available.

To access the help text:

1. Use the control knob to select the help symbol.

2. Press the OK button.

The help text often consists of several windows that youcan scroll between using the control knob.

NIBE™ F1226Chapter 7 | Control - Introduction36

Page 39: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 1 - INDOOR CLIMATE Overview

1.1 - temperature1 - INDOOR CLIMATE

1.9.1 - heating curve1.9 - advanced

1.9.2 - external adjustment

1.9.3 - min. flow line temp.

1.9.4 - room sensor settings

1.9.7 - own curve

1.9.8 - point offset

Sub-menus

For the menu INDOOR CLIMATE there are several sub-menus. Status information for the relevant menu can befound on the display to the right of the menus.

temperature Setting the temperature for the climatesystem. The status information shows the set values forthe climate system. Tab for cooling system is only dis-played if accessory for cooling are present or if the heatpump has the integrated cooling function.

advanced Setting of heat curve, adjusting with externalcontact, minimum value for supply temperature and roomsensor.

Menu 1.1 - temperature

If the house has several climate systems, this is indicatedon the display by a thermometer for each system.

Set the temperature (with room sensors installedand activated):

Setting range: 5 - 30 °C

Default value: 20

The value in the display appears as a temperature in °Cif the heating system is controlled by a room sensor.

To change the room temperature, use the control knobto set the desired temperature in the display. Confirmthe new setting by pressing the OK button. The newtemperature is shown on the right-hand side of thesymbol in the display.

Setting the temperature (without room sensorsactivated):

Setting range: -10 to +10

Default value: 0

The display shows the set values for heating (curve offset).To increase or reduce the indoor temperature, increaseor reduce the value on the display.

Use the control knob to set a new value. Confirm thenew setting by pressing the OK button.

The number of steps the value has to be changed toachieve a degree change of the indoor temperature de-pends on the heating unit. One step for under floorheating whilst radiators may require three.

Setting the desired value. The new value is shown on theright-hand side of the symbol in the display.

Caution

An increase in the room temperature can beslowed by the thermostats for the radiators orunder floor heating. Therefore, open the thermo-stat valves fully, except in those rooms where acooler temperature is required, e.g. bedrooms.

TIP

Wait 24 hours before making a new setting, sothat the room temperature has time to stabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope in menu1.9.1 by one increment.

If it is cold outdoors and the room temperatureis too high, lower the curve slope menu 1.9.1by one increment.

If it is warm outdoors and the room temperatureis too low, increase the value in menu 1.1 byone increment.

If it is warm outdoors and the room temperatureis too high, reduce the value in menu 1.1 by oneincrement.

Menu 1.9 - advanced

Menu advanced is intended for the advanced user. Thismenu has several sub-menus.

heating curve Setting the heating curve slope.

external adjustment Setting the heat curve offset whenthe external contact is connected.

37Chapter 8 | Control - MenusNIBE™ F1226

8 Control - Menus

Page 40: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

min. flow line temp. Setting minimum permitted flowline temperature.

room sensor settings Settings regarding the room sensor.

own curve Setting own heat curve.

point offset Setting the offset of the heating curve at aspecific outdoor temperature.

Menu 1.9.1 - heating curve

heating curve

Setting range: 0 - 15

Default value: 9

In the menu heating curve the so-called heating curvefor your house can be viewed. The task of the heatingcurve is to give an even indoor temperature, regardlessof the outdoor temperature, and thereby energy efficientoperation. It is from this heating curve that the heatpump’s control computer determines the temperature ofthe water to the heating system, flow line temperature,and therefore the indoor temperature. You can selectheating curve and read off how the flow line temperaturechanges at different outdoor temperatures here.

Curve coefficient

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Brantare kurvlutning

The slope of the heating curve indicates how many de-grees the supply temperature is to be increased/reducedwhen the outdoor temperature drops/increases. A

steeper slope means a higher supply temperature at acertain outdoor temperature.

The optimum slope depends on the climate conditionsin your location, if the house has radiators or under floorheating and how well insulated the house is.

The heating curve is set when the heating installation isinstalled, but may need adjusting later. Thereafter theheating curve should not need further adjustment.

Caution

In the event of making fine adjustments for theindoor temperature, the heat curve must beoffset up or down instead, this is done in menu1.1 temperature .

Curve offset

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Förskjuten värmekurva

An offset of the heating curve means that the supplytemperature changes as much for all the outdoor temper-atures, e.g. that a curve offset of +2 steps increases thesupply temperature by 5 °C at all outdoor temperatures.

Flow line temperature– maximum and minimumvalues

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Maximivärde

Minimivärde

Because the flow line temperature cannot be calculatedhigher than the set maximum value or lower than the setminimum value the heating curve flattens out at thesetemperatures.

NIBE™ F1226Chapter 8 | Control - Menus38

Page 41: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max temperature for your floor withyour installer/floor supplier.

The figure at the end of the curve indicates the curveslope. The figure beside the thermometer gives the curveoffset. Use the control knob to set a new value. Confirmthe new setting by pressing the OK button.

Curve 0 is an own heating curve created in menu 1.9.7.

To select another heat curve (slope):1. Press the OK button to access the setting mode

2. Select a new heating curve. The heat curves arenumbered from 0 to 15, the greater the number, thesteeper the slope and the greater the supply temper-ature. Heating curve 0 means that own curve (menu1.9.7) is used.

3. Press the OK button to exit the setting.

To read off a heating curve:1. Turn the control knob so that the ring on the shaft

with the outdoor temperature is marked.

2. Press the OK button.

3. Follow the grey line up to the heat curve and out tothe left to read off the value for the supply temperat-ure at the selected outdoor temperature.

4. You can now select to take read outs for differentoutdoor temperatures by turning the control knobto the right or left and read off the correspondingflow temperature.

5. Press the OK or Back button to exit read off mode.

TIP

Wait 24 hours before making a new setting, sothat the room temperature has time to stabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope by one incre-ment.

If it is cold outdoors and the room temperatureis too high, lower the curve slope by one incre-ment.

If it is warm outdoors and the room temperatureis too low, increase the curve offset by one incre-ment.

If it is warm outdoors and the room temperatureis too high, lower the curve offset by one incre-ment.

Menu 1.9.2 - external adjustment

climate system

Setting range: -10 to +10 or desired room temperatureif the room sensor is installed.

Default value: 0

Connecting an external contact, for example, a roomthermostat or a timer allows you to temporarily or period-ically raise or lower the room temperature. When thecontact is on, the heat curve offset is changed by thenumber of steps selected in the menu. If a room sensoris installed and activated the desired room temperature(°C) is set.

Menu 1.9.3 - min. flow line temp.

climate system

Setting range: 15-50 °C

Default values: 15°C

Set the minimum temperature on the supply temperatureto the climate system. This means that F1226 never cal-culates a temperature lower than that set here.

TIP

The value can be increased if you have, for ex-ample, a cellar that you always want to heat,even in summer.

You may also need to increase the value in "stopheating" menu 4.9.2 "auto mode setting".

Menu 1.9.4 - room sensor settings

factor system

Setting range: 0.2 - 3.0

Default value: 2.0

Room sensors to control the room temperature can beactivated here.

Here you can set a factor that determines how much thesupply temperature is to be affected by the differencebetween the desired room temperature and the actualroom temperature. A higher value gives a greater changeof the heating curve's set offset.

Menu 1.9.7 - own curve

supply temperature

Setting range: 15 – 70 °C

39Chapter 8 | Control - MenusNIBE™ F1226

Page 42: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

You can create your own heating curve here, if there arespecial requirements, by setting the desired supply tem-peratures for different outdoor temperatures.

Caution

Curve 0 in menu 1.9.1 must be selected for thiscurve to apply.

Menu 1.9.8 - point offset

outdoor temp. point

Setting range: -40 – 30 °C

Default value: 0 °C

change in curve

Setting range: -10 – 10 °C

Default value: 0 °C

Select a change in the heating curve at a certain outdoortemperature here. A one degree change in room temper-ature requires one increment for underfloor heating andapproximately two to three increments for the radiatorsystem.

The heat curve is affected at ± 5 °C from set outdoortemp. point.

It is important that the correct heating curve is selectedso that the room temperature is experienced as even.

TIP

If it is cold in the house, at, for example -2 °C,"outdoor temp. point" is set to "-2" and"change in curve" is increased until the desiredroom temperature is maintained.

Caution

Wait 24 hours before making a new setting, sothat the room temperature has time to stabilise.

NIBE™ F1226Chapter 8 | Control - Menus40

Page 43: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 2 - HOT WATER Overview

2.1 - temporary lux2 - HOT WATER

2.2 - comfort mode

2.9.1 - periodic increases2.9 - advanced

Sub-menus

For the menu HOT WATER there are several sub-menus.Status information for the relevant menu can be foundon the display to the right of the menus.

temporary lux Activation of temporary increase in thehot water temperature. Status information displays “off"or what length of time of the temporary temperature in-crease remains.

comfort mode Setting hot water comfort. The statusinformation displays what mode is selected, "economy","normal" or "luxury".

advanced Setting periodic increase in the hot watertemperature.

Menu 2.1 - temporary lux

Setting range: 3, 6 and 12 hours and mode "off"

Default value: "off"

When hot water requirement has temporarily increasedthis menu can be used to select an increase in the hotwater temperature to lux mode for a selectable time.

Caution

If comfort mode "luxury" is selected in menu2.2 no further increase can be carried out.

The function is activated immediately when a time periodis selected and confirmed using the OK button. The timeto the right displays the remaining time at the selectedsetting.

When the time has run out F1226 returns to the modeset in menu 2.2.

Select “off" to switch off temporary lux .

Menu 2.2 - comfort mode

Setting range: economy, normal, luxury

Default value: normal

The difference between the selectable modes is thetemperature of the hot tap water. Higher temperaturemeans that the hot water lasts longer.

economy: This mode gives less hot water than the other,but is more economical. This mode can be used in smallerhouseholds with a small hot water requirement.

normal: Normal mode gives a larger amount of hot waterand is suitable for most households.

luxury: Lux mode gives the greatest possible amount ofhot water. In this mode the immersion heater may bepartially used to heat hot water, which may increase op-erating costs.

Menu 2.9 - advanced

Menu advanced is intended for the advanced user. Thismenu has several sub-menus.

Menu 2.9.1 - periodic increases

period

Setting range: 1 - 90 days

Default value: 14 days

start time

Setting range: 00:00 - 23:00

Default value: 00:00

To prevent bacterial growth in the water heater, thecompressor and the immersion heater can increase hotwater temperature at regular intervals.

The length of time between increases can be selectedhere. The time can be set between 1 and 90 days. Factorysetting is 14 days. Untick "activated" to switch off thefunction.

41Chapter 8 | Control - MenusNIBE™ F1226

Page 44: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 3 - INFO Overview

3.1 - service info3 - INFO

3.2 - compressor info

3.3 - add. heat info

3.4 - alarm log

3.5 - indoor temp. log

Sub-menus

For the menu INFO there are several sub-menus. Nosettings can be made in these menus, it is just display ofinformation. Status information for the relevant menucan be found on the display to the right of the menus.

service info shows temperature levels and settings inthe heat pump.

compressor info shows operating times, number of startsetc for the compressor.

add. heat info displays information about the addition’soperating times etc.

alarm log displays the latest alarm and information aboutthe heat pump when the alarm occurred.

indoor temp. log the average temperature indoors weekby week during the past year.

Menu 3.1 - service info

Information about the heat pump’s actual operatingstatus (e.g. current temperatures etc.) can be obtainedhere. No changes can be made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Symbols in this menu:

HeatingCompressor

Hot waterAddition

Heating mediumpump

Brine pump

Menu 3.2 - compressor info

Information about the compressor’s operating status andstatistics can be obtained here. No changes can be made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Menu 3.3 - add. heat info

Information about the additional heat settings, operatingstatus and statistics can be obtained here. No changescan be made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Menu 3.4 - alarm log

To facilitate fault-finding the heat pump operating statusat alarm alerts is stored here. You can see informationfor the 10 most recent alarms.

To view the run status in the event of an alarm, mark thealarm and press the OK button.

Menu 3.5 - indoor temp. log

Here you can see the average temperature indoors weekby week during the past year. The dotted line indicatesthe annual average temperature.

The average outdoor temperature is only shown if a roomtemperature sensor/room unit is installed.

To read off an average temperature1. Turn the control knob so that the ring on the shaft

with the week number is marked.

2. Press the OK button.

3. Follow the grey line up to the graph and out to theleft to read off the average indoor temperature atthe selected week.

4. You can now select to take read outs for differentweeks by turning the control knob to the right or leftand read off the average temperature.

5. Press the OK or Back button to exit read off mode.

NIBE™ F1226Chapter 8 | Control - Menus42

Page 45: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 4 - HEAT PUMP Overview

4.2 - op. mode4 - HEAT PUMP

4.4 - time & date

4.6 - language

4.9.1 - op. prioritisation4.9 - advanced

4.9.2 - auto mode setting

4.9.3 - degree minute setting

4.9.4 - factory setting user

Sub-menus

For the menu HEAT PUMP there are several sub-menus.Status information for the relevant menu can be foundon the display to the right of the menus.

plus functions Settings applying to any installed extrafunctions in the heating system.

op. mode Activation of manual or automatic operatingmode. The status information shows the selected operat-ing mode.

time & date Setting current time and date.

language Select the language for the display here. Thestatus information shows the selected language.

advanced Setting heat pump work mode.

Menu 4.2 - op. mode

op. mode

Setting range: auto, manual, add. heat only

Default value: auto

functions

Setting range: compressor, addition, heating

The heat pump operating mode is usually set to "auto".It is also possible to set the heat pump to "add. heatonly", but only when an addition is used, or "manual"and select yourself what functions are to be permitted.

Change the operating mode by marking the desired modeand pressing the OK button. When an operating modeis selected it shows what in the heat pump is permitted(crossed out = not permitted) and selectable alternativesto the right. To select selectable functions that are permit-ted or not you mark the function using the control knoband press the OK button.

Operating mode auto

In this operating mode you cannot select which functionsare to be permitted because it is handled automaticallyby the heat pump.

Operating mode manual

In this operating mode you can select what functions arepermitted. You cannot deselect "compressor" in manualmode.

Operating mode add. heat only

Caution

If you choose mode "add. heat only" the com-pressor is deselected and there is a higher oper-ating cost.

In this operating mode the compressor is not active andonly additional heating is used.

Functions

"compressor" is that which produces heating and hotwater for the accommodation. If "compressor" isdeselected, a symbol in the main menu on the heat pumpsymbol is displayed. You cannot deselect "compressor"in manual mode.

"addition" is what helps the compressor to heat theaccommodation and/or the hot water when it cannotmanage the whole requirement alone.

"heating" means that you get heat in the accommoda-tion. You can deselect the function when you do notwish to have heating running.

Caution

If you deselect "addition" it may mean thatsufficient heating in the accommodation is notachieved.

Menu 4.4 - time & date

Set time and date and display mode here.

Menu 4.6 - language

Choose the language that you want the information tobe displayed in here.

43Chapter 8 | Control - MenusNIBE™ F1226

Page 46: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 4.9 - advanced

Menu advanced is intended for the advanced user. Thismenu has several sub-menus.

Menu 4.9.1 - op. prioritisation

op. prioritisation

Setting range: 0 to 180 min

Default value: 20 min

Choose here how long the heat pump should work witheach requirement if there are two or more requirementsat the same time. If there is only one requirement theheat pump only works with that requirement.

The indicator marks where in the cycle the heat pump is.

If 0 minutes is selected it means that requirement is notprioritised, but will only be activated when there is noother requirement.

Menu 4.9.2 - auto mode setting

stop heating

Setting range: -20 – 40 °C

Default values: 20

stop additional heat

Setting range: -20 – 40 °C

Default values: 15

filtering time

Setting range: 0 – 48 h

Default value: 24 h

When operating mode is set to "auto“ the heat pumpselects when start and stop of additional heat and heatproduction is permitted, dependent on the average out-door temperature.

Select the average outdoor temperatures in this menu.

You can also set the time over which (filtering time) theaverage temperature is calculated. If you select 0, thepresent outdoor temperature is used.

Caution

It cannot be set "stop additional heat" higherthan "stop heating".

Menu 4.9.3 - degree minute setting

current value

Setting range: -3000 – 3000

start compressor

Setting range: -1000 – -30

Default value: -60

start addition

Setting range: -2000 – -30

Default value: -400

diff. between additional steps

Setting range: 0 – 1000

Default value: 100

Degree minutes are a measurement of the current heatingrequirement in the house and determine when the com-pressor respectively additional heat will start/stop.

Caution

Higher value on "start compressor" gives morecompressor starts, which increases wear in thecompressor. Too low value can give uneven in-door temperatures.

Menu 4.9.4 - factory setting user

All settings that are available to the user (including ad-vanced menus) can be reset to default values here.

Caution

After factory setting, personal settings such asheating curves must be reset.

NIBE™ F1226Chapter 8 | Control - Menus44

Page 47: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 5 - SERVICE Overview

5.1.1 - hot water settings5.1 - operating settings5 - SERVICE

5.1.2 - max flow line temperature

5.1.3 - max diff flow line temp.

5.1.4 - alarm actions

5.1.7 - br pmp al set.

5.1.8 - operating mode brine pump

5.1.10 - op. mod heat med pump

5.1.12 - internal electrical addition

5.1.13 - max inst. el.pwr (BBR)

5.2 - system settings

5.4 - soft in/outputs

5.5 - factory setting service

5.6 - forced control

5.7 - start guide

5.8 - quick start

5.10 - change log

Hold the Back button in for 7 seconds to access the Ser-vice menu.

Sub-menus

Menu SERVICE has orange text and is intended for theadvanced user. This menu has several sub-menus. Statusinformation for the relevant menu can be found on thedisplay to the right of the menus.

operating settings Operating settings for the heat pump.

system settings System settings for the heat pump, ac-tivating accessories etc.

soft in/outputs Setting software controlled inputs onthe terminal block (X1).

factory setting service Total reset of all settings (includingsettings available to the user ) to default values.

forced control Forced control of the different compon-ents in the heat pump.

start guide Manual start of the start guide which is runthe first time the heat pump is started.

quick start Quick starting the compressor.

NOTE

Incorrect settings in the service menus candamage the heat pump.

Menu 5.1 - operating settings

Operating settings can be made for the heat pump in thesub menus.

Menu 5.1.1 - hot water settings

start temp. economy / normal / lux

Setting range: 5 – 70 °C

Factory setting (°C):

luxurynormaleco-nomy

kW

4845425Copper4845425Stainless4744416Copper4744416Stainless4643408Copper4643408Stainless43403711Copper43403711Stainless

45Chapter 8 | Control - MenusNIBE™ F1226

Page 48: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

stop temp. economy / normal / lux

Setting range: 5 – 70 °C

Factory setting (°C):

luxurynormaleco-nomy

kW

5249465Copper5249465Stainless5148456Copper5148456Stainless5047448Copper5047448Stainless47444111Copper47444111Stainless

stop temp. per. increase

Setting range: 55 – 70 °C

Default values: 55 °C

Here you set the start and stop temperature of the hotwater for the different comfort options in menu 2.2 aswell as the stop temperature for periodic increase in menu2.9.1.

Menu 5.1.2 - max flow line temperature

climate system

Setting range: 15-80 °C

Default value: 60 °C

Set the maximum supply temperature for the climatesystem here.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max floor temperature with your floorsupplier.

Menu 5.1.3 - max diff flow line temp.

max diff compressor

Setting range: 1 – 25 °C

Default value: 10 °C

max diff addition

Setting range: 1 – 24 °C

Default value: 7 °C

Here you set the maximum permitted difference betweenthe calculated and actual supply temperature duringcompressor respectively add. heat mode.

max diff compressor

When the current supply temperature deviates from theset value compared to that calculated, the heat pump isforced to stop irrespective of the degree-minute value.

If the calculated flow temperature exceeds the calculatedflow with set value, the degree minute value is set to 0.The compressor stops when there is only a heating re-quirement.

max diff addition

If "addition” is selected and activated in menu 4.2 andthe present supply temp exceeds the calculated with setvalue, the additional heat is forced to stop.

Menu 5.1.4 - alarm actions

Select how you want the heat pump to alert you thatthere is an alarm in the display here.

The different alternatives are that the heat pump stopsproducing hot water (default setting) and/or reduces theroom temperature.

Caution

If no alarm action is selected, it can result inhigher energy consumption in the event of analarm.

Menu 5.1.7 - br pmp al set.

min. brine out

Setting range: -12 – 15 °C

Default value: -8 °C

max brine in

Setting range: 10 – 40 °C

Default value: 30 °C

min. brine out

Set the temperature at which the heat pump is to activatethe alarm for low temperature in outgoing brine.

If "automatic reset" is selected, the alarm resets whenthe temperature has increased by 1 °C below the setvalue.

max brine in

Set the temperature at which the heat pump is to activatethe alarm for high temperature in incoming brine.

Select “alarm activated" to activate the alarm.

NIBE™ F1226Chapter 8 | Control - Menus46

Page 49: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 5.1.8 - operating mode brine pump

op. mode

Setting range: intermittent, continuous, 10 days con-tinuous

Default value: intermittent

Set the operating mode of the brine pump here.

intermittent: The brine pump starts 20 seconds beforeand stops at the same time as the compressor.

continuous: Continuous operation.

10 days continuous: Continuous operation for 10 days.Then the pump shifts to intermittent operation.

TIP

You can use “10 days continuous" at start-upto obtain continuous circulation during a start-up time in order to make it easier to bleed thesystem.

Menu 5.1.10 - op. mod heat med pump

op. mode

Setting range: auto, intermittent, continuous

Default value: auto

Set the operating mode of the heating medium pumphere.

auto: The heating medium pump runs according to thecurrent operating mode for F1226.

intermittent: The heating medium pump starts 20seconds before and stops at the same time as the com-pressor.

continuous: Continuous operation.

Menu 5.1.12 - internal electrical addition

max connected el. add.

Setting range: 7 / 9 kW

Default values: 7 kW

set max electrical add.

Setting range: 0 - 9 kW

Default values: 6 kW

Here you set the max. electrical output of the internalelectrical addition in F1226 and the fuse size for the in-stallation.

Menu 5.1.13 - max inst. el.pwr (BBR)

max installed el.pwr (only this machine)

Setting range: 0.000 - 30.000 kW

Default values: 15.000 kW

In order to meet certain building regulations, it is possibleto lock the device's maximum power output. In this menuyou can set the value corresponding to the heat pump'smaximum power connection for heating, hot water andcooling, if applicable Note whether there are also externalelectrical components that are to be included. After thevalue has been locked, a weeks cooling-off period starts.After this period, parts in the machine must be replacedin order to obtain greater power. If the above buildingregulations are not applicable, do not use this setting.

Menu 5.4 - soft in/outputs

Here you can select which input on the terminal block(X1) the external contact function (page 22) is to beconnected to.

Selectable inputs on terminal block AUX1-1 (X1:3-6).

Menu 5.5 - factory setting service

All settings can be reset (including settings available tothe user) to default values here.

NOTE

When resetting, the start guide is displayed thenext time the heat pump is restarted.

Menu 5.6 - forced control

You can force control the different components in theheat pump here.

Menu 5.7 - start guide

When the heat pump is started for the first time the startguide starts automatically. Start it manually here.

For more information about the different parts of thestart guide, see page 25.

47Chapter 8 | Control - MenusNIBE™ F1226

Page 50: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 5.8 - quick start

It is possible to start the compressor from here.

Caution

There must be a heating or hot water demandto start the compressor.

Caution

Do not quick start the compressor too manytimes in succession over a short period of timeas this may damage the compressor and its an-cillary equipment.

Menu 5.10 - change log

Read off any previous changes to the control system here.

The date, time and ID no. (unique to certain settings) andthe new set value is shown for every change.

NOTE

The change log is saved at restart and remainsunchanged after factory setting.

NIBE™ F1226Chapter 8 | Control - Menus48

Page 51: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Service actions

NOTE

Servicing should only be carried out by personswith the necessary expertise.

When replacing components on F1226 only re-placement parts from NIBE may be used.

Emergency mode

NOTE

Switch (SF1) must not be moved to "" or " "until F1226 has been filled with water. Other-wise the temperature limiter, thermostat, com-pressor and the immersion heater can be dam-aged.

Emergency mode is used in event of operational interfer-ence and in conjunction with service. Hot water is notproduced in this mode.

Emergency mode is activated by setting switch (SF1) to

” ”. This means that:

The status lamp illuminates yellow.

The display is not lit and the control computer is notconnected.

The temperature at the immersion heater is controlledby the thermostat (FD1-BT30). It can be set either to35 or 45 °C.

The compressor and the brine system are off and onlythe heating medium pump and the electrical additionare active. The addition power in emergency mode isset in the immersion heater card (AA1). See page 21for instructions.

Draining the water heater

The siphon principle is used to empty the hot waterheater. This can be done either via the drain valve on theincoming cold water pipe or by inserting a hose into thecold water connection.

Draining the climate system

In order to carry out service on the climate system, it maybe easier to drain the system first. This can be done indifferent ways depending on what needs doing:

NOTE

There may be some hot water when drainingthe heating medium side/climate system. Thereis a risk of scalding.

49Chapter 9 | ServiceNIBE™ F1226

9 Service

Page 52: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Draining the heating medium side in the coolingmodule

If, for example, the heating medium pump requires repla-cing or the cooling module requires servicing, drain theheating medium side as follows:

1. Close the shut-off valve for the heating medium side(QM32).

2. Connect a hose to the bleed valve (QM1) and openthe valve. Some liquid will run out.

3. Air must get into the system for the remaining liquidto run out. Do this by slightly slackening off theconnection at the shut-off valve (QM32) that joinsthe heat pump to the cooling module.

When the heating medium side is drained, the requiredservice can be performed and/or replacement of anycomponents carried out.

Draining the heating medium system in the heatpump

If the heat pump requires servicing, drain the heatingmedium side as follows:

1. Close the shut-off valves outside the heat pump forthe heating medium side (return and flow line).

2. Connect a hose to the bleed valve (QM1) and openthe valve. Some liquid will run out.

3. Air must get into the system for the remaining liquidto run out. Do this by slightly slackening off theconnection at the shut-off valve that joins the climatesystem and the heat pump at the connection (XL2).

When the heating medium side is empty the requisiteservice can be carried out.

Draining the entire climate system

If the entire climate system requires draining, do this asfollows:

1. Connect a hose to the bleed valve (QM1) and openthe valve. Some liquid will run out.

2. Air must get into the system for the remaining liquidto run out. This is done by unscrewing the bleedscrew on the highest radiator in the house.

When the climate system is empty the requisite servicecan be carried out.

Emptying the brine system

In order to service the brine system it may be easier todrain the system first. This can be done in different waysdepending on what needs doing:

Draining the brine system in the cooling module

If, for example, the brine pump requires replacing or thecooling module requires servicing, drain the brine systemby:

1. Close the shut-off valves to brine system (QM33) and(QM34).

2. Connect a hose to the drain valve (QM2), place theother opening of the hose in a container and openthe valve. A small amount of brine will flow into thecontainer.

3. Air must get into the system for the remaining brineto run out. Do this by slightly slackening off theconnection at the shut-off valve (QM33) that joinsthe heat pump with the cooling module.

When the brine side is empty the requisite service can becarried out.

Draining the brine system in the heat pump

If the heat pump requires servicing, drain the brine systemby:

1. Close the shut-off valve outside the heat pump forthe brine system.

2. Connect a hose to the drain valve (QM2), place theother opening of the hose in a container and openthe valve. A small amount of brine will flow into thecontainer.

3. Air must get into the system for the remaining brineto run out. Do this by slightly slackening off theconnection at the shut-off valve that joins the brineside and the heat pump at the connection (XL7).

When the brine side is empty the requisite service can becarried out.

Helping the circulation pump to start

1. Shut off F1226 by setting the switch (SF1) to " ".

2. Open the service cover.

3. Remove the cover for the cooling module.

4. Loosen the venting screw (QM5) with a screwdriver.Hold a cloth around the screwdriver blade as a smallamount of water may run out.

5. Insert a screwdriver and turn the pump motoraround.

6. Screw in the venting screw (QM5).

7. Start F1226 by setting the switch (SF1) to "" andcheck whether the circulation pump works.

It is usually easier to start the circulation pump with F1226running, switch (SF1) set to " ". Helping the circulationpump to start is performed with F1226 running, be pre-pared for the screwdriver to jerk when the pump starts.

NIBE™ F1226Chapter 9 | Service50

Page 53: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Luftningsskruv

16

LE

K

GR

UN

DF

OS

Typ

eU

PS

25

- 6

01

30

P/N

:59

52

64

47

23

0V

-

HE

JS

AN

PC

;00

17

NIB

DK

50

Hz

IP

44

TF

1

10

Cla

ss

HM

ax. 1

0b

ar

2.5

uF

45

0.2

06

50

.30

90

0.4

0

1m(A

)P,

(W)

The image shows an example of what a circulation pump can looklike.

Temperature sensor data

Voltage (VDC)Resistance(kOhm)

Temperature(°C)

3.256351.0-403.240251.6-353.218182.5-303.189133.8-253.15099.22-203.10574.32-153.04756.20-102.97642.89-52.88933.0202.78925.6152.67320.02102.54115.77152.39912.51202.24510.00252.0838.045301.9166.514351.7525.306401.5874.348451.4263.583501.2782.968551.1362.467601.0072.068650.8911.739700.7851.469750.6911.246800.6071.061850.5330.908900.4690.779950.4140.672100

Pulling out the cooling module

The cooling module can be pulled out for service andtransport.

Caution

The cooling module is easier to remove if it isdrained first (see page 49).

Weight of the cooling module

Weight (kg)Type (kW)

10851126120813011

NOTE

Shut off the heat pump and turn off the currenton the safety breaker.

Caution

Remove the front cover according to the descrip-tion on page 6.

Close the shut-off valves (QM32), (QM33) and(QM34). Drain the cooling module according to theinstructions on page 49.

1

Pull off the lock catches.2

LEK

Disconnect the pipe connection at the pipe coupling(WP4).

3

51Chapter 9 | ServiceNIBE™ F1226

Page 54: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Remove the two screws.4

LEK

Remove the connections from the base card (AA2)using a screwdriver.

5

LEK

Disconnect the connectors (A) and (B) from the un-derside of the base card cabinet.

6

Disconnect the connector (C) from the immersionheater circuit board (AA1) using a screwdriver.

7

Disconnect the connector (D) from the joint circuitboard (AA100).

8

Carefully pull out the cooling module.9

LEK

TIP

The cooling module is installed in reverse order.

NOTE

At reinstallation, the supplied O-rings must re-place the existing ones at the connections to theheat pump (see image).

NIBE™ F1226Chapter 9 | Service52

Page 55: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

USB service outlet

LE

K

F1226 is equipped with a USB socket in the display unit.This USB socket can be used to connect a USB memoryto update the software, save logged information andhandle the settings in F1226.

When a USB memory is connected a new menu (menu7) appears in the display.

Menu 7.1 - update firmware

This allows you to update the software in F1226.

NOTE

For the following functions to work the USBmemory must contain files with software forF1226 from NIBE.

The fact box at the top of the display shows information(always in English) of the most probable update that theupdate software has selected form the USB memory.

This information states which product the software is in-tended for, the software version and general informationabout them. If you wish to select another file than theone selected, the correct file can be selected by "chooseanother file".

start updating

Select “start updating" if you want to start the update.You are asked whether you really want to update thesoftware. Respond "yes" to continue or "no" to undo.

If you responded"yes" to the previous question the up-date starts and you can now follow the progress of theupdate on the display. When the update is completeF1226 restarts.

NOTE

A software update does not reset the menusettings in F1226.

NOTE

If the update is interrupted before it is complete(for example power cut etc.) the software canbe reset to the previous version if the OK buttonis held in during start up until the green lampstarts to illuminate (takes about 10 seconds).

53Chapter 9 | ServiceNIBE™ F1226

Page 56: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

choose another file

Select “choose another file" if you do not want to usethe suggested software. When you scroll through thefiles, information about the marked software is shownin a fact box just as before. When you have selected afile with the OK button you will return to the previouspage (menu 7.1) where you can choose to start the up-date.

Menu 7.2 - logging

Setting range: 1 s – 60 min

Default setting range: 5 s

Set whether the present measurement values from F1226are to be saved in a log on the USB memory.

Log for longer periods1. Set the desired interval between loggings.

2. Tick “activated".

3. Mark “read log settings" and press the OK button.

4. The present values from F1226 are saved in a file inthe USB memory at the set interval until “activated"is unticked.

Caution

Untick "activated" before removing the USBmemory.

Menu 7.3 - manage settings

Here you can manage (save as or retrieve from) all themenu settings (user and service menus) in F1226 with aUSB memory.

Via "save settings" you save the menu settings to theUSB memory in order to restore them later or to copy thesettings to another F1226.

NOTE

When you save the menu settings to the USBmemory you replace any previously saved set-tings on the USB memory.

Via "recover settings" you reset all menu settings fromthe USB memory.

NOTE

Reset of the menu settings from the USBmemory cannot be undone.

NIBE™ F1226Chapter 9 | Service54

Page 57: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

In most cases, the heat pump notes operational interfer-ence (operational interference can lead to disturbance incomfort) and indicates this with alarms and shows actioninstructions in the display.

Info-menuAll the heat pump measurement values are gatheredunder menu 3.1 in the heat pump menu system. Lookingthrough the values in this menu can often simplify findingthe fault source. See page 42 for more information aboutmenu 3.1.

Manage alarm

In the event of an alarm, some kind of malfunction hasoccurred, which is indicated by the status lamp changingfrom green continuously to red continuously. In addition,an alarm bell appears in the information window.

Alarm

In the event of an alarm with a red status lamp a malfunc-tion has occurred that the heat pump cannot remedy it-self. In the display, by turning the control knob andpressing the OK button, you can see the type of alarm itis and reset it. You can also choose to set the heat pumpto aid mode.

info / action Here you can read what the alarm meansand receive tips on what you can do to correct the prob-lem that caused the alarm.

reset alarm In most cases it is enough to select "resetalarm" to correct the problem that caused the alarm. Ifa green light illuminates after selecting "reset alarm" thealarm has been remedied. If a red light is still visible anda menu called ”alarm” is visible in the display, the prob-lem that caused the alarm remains. If the alarm disappearsand then returns, see the troubleshooting section (page55).

aid mode ”aid mode” is a type of emergency mode. Thismeans that the heat pump produces heat and/or hotwater despite there being some kind of problem. Thiscan mean that the heat pump's compressor is not run-ning. In this case the immersion heater produces heatand/or hot water.

Selecting "aid mode” is not the same as correcting theproblem that caused the alarm. The status lamp willtherefore continue to be red.

TroubleshootingIf the operational interference is not shown in the displaythe following tips can be used:

Basic actions

Start by checking the following possible fault sources:

The switch's (SF1) position.

Group and main fuses of the accommodation.

The property's earth circuit breaker.

The heat pump's miniature circuit breaker (FA1).

The heat pump's temperature limiter (FD1).

Correctly set load monitor (if installed).

Low hot water temperature or a lack of hotwater

Heat pump in incorrect operating mode.

If mode "manual" is selected, select "addition".

Large hot water consumption.

Wait until the hot water has heated up. Tempor-arily increased hot water capacity (temporary lux)can be activated in menu 2.1.

Too low hot water setting.

Enter menu 2.2 and select a higher comfort mode.

Too low or no operating prioritisation of hot water.

Enter menu 4.9.1 and increase the time for whenhot water is to be prioritised.

Closed or choked filling valve for the hot water heater.

Open the valve.

Low room temperatureClosed thermostats in several rooms.

Set the thermostats to max in as many rooms aspossible. Adjust the room temperature via menu1.1 instead of choking the thermostats.

Heat pump in incorrect operating mode.

Enter menu 4.2. If mode "auto" is selected, selecta higher value on "stop heating“ in menu 4.9.2.

If mode "manual" is selected, select "heating".If this is not enough, select "addition".

Too low set value on the automatic heating control.

Enter menu 1.1 (temperature) and adjust the heatcurve offset of the heat curve. If the room temper-ature is only low in cold weather the curve slopein the menu 1.9.1 (heating curve) needs to beadjusted up.

Too low or no operating prioritisation of heat.

55Chapter 10 | Disturbances in comfortNIBE™ F1226

10 Disturbances in comfort

Page 58: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Enter menu 4.9.1 and increase the time for whenheating is to be prioritised.

External switch for changing the room heating activ-ated.

Check any external switches.

Circulation pump(s) (GP1 and/or GP2) stopped.

See section "Helping the circulation pump tostart" on page 50.

Air in the climate system.

Vent the climate system (see page 24).

Closed valves (QM20), (QM32)to the climate system.

Open the valves.

High room temperatureToo high set value on the automatic heating control.

Enter menu 1.1 (temperature) and adjust the heatcurve offset downwards. If the room temperatureis only high in cold weather the curve slope inmenu 1.9.1 (heating curve) needs to be adjusteddown.

External switch for changing the room heating activ-ated.

Check any external switches.

Low system pressureNot enough water in the climate system.

Top up the water in the climate system (see page24).

The compressor does not startThere is no heating requirement.

The heat pump does not call on heating nor hotwater.

Minimum time between compressor starts has notbeen reached.

Wait 30 minutes and check if the compressor hasstarted.

Alarm tripped.

Follow the display instructions.

NIBE™ F1226Chapter 10 | Disturbances in comfort56

Page 59: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Auxiliary relay HR 10

Part no. 089 423

Buffer vessel UKV

UKV 100

Part no. 088 207

UKV 200

Part no. 088 300

Exhaust air module FLM

FLM is an exhaust air module specially designed to com-bine recovery of mechanical exhaust air with an energycollector in rock.

Bracket pack FLM

Part no. 067 083

FLM

Part no. 067 011

Extra relay card EXC 40

Extra relay card required if ground heat pump and/or hotwater circulation pump is to be connected to F1226.

The extra relay card is installed inside the heat pump.

Part no. 067 072

Filling valve kit KB R25

Filling valve kit for filling brine in the collector hose forrock heat pumps. Includes dirt filter and insulation.

KB R25 (max 12 kW)

Part no. 089 368

Level monitor NV 10

Part no. 089 315

Load monitor EBV 200

Part no. 418 346

Room sensor RTS 40

Part no. 067 065

57Chapter 11 | AccessoriesNIBE™ F1226

11 Accessories

Page 60: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Dimensions and setting-out coordinates

62

0

600

560 440

70

17

75

65

0*

25

-50

25

50

130

210

390

470

525

65

0*

* This dimension applies at 90° angle on the brine pipes (side connection). The dimension can vary approx. ±100 mm inheight as the brine pipes partially consist of flexible pipes.

NIBE™ F1226Chapter 12 | Technical data58

12 Technical data

Page 61: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Technical specifications IP 21

3x400V118653x400V

Output data at nom flow Refers to performance of heat pump excl. circulation pumps

0/3511.017.635.564.60kWRated output8.596.014.333.51kWCooling output2.421.621.241.09kWElectrical output4.554.714.504.22-COP

0/5010.326.324.453.63kWRated output7.144.443.062.42kWCooling output3.181.881.391.21kWElectrical output3.253.363.203.01-COP

Output data according to EN 145110/35

10.657.335.344.41kWRated output2.621.701.311.14kWElectrical output4.064.314.093.87-COPEN14511

0/4510.146.744.583.77kWRated output3.111.861.381.20kWElectrical output3.263.623.313.14-COPEN14511

1/2/3/4/5/6/7 (switchable to 2/4/6/9)kWAdditional powerElectrical data

400V 3NAC 50 HzRated voltage9.06.64.69.5(1-phase)ArmsMax operating current, compressor

(Including Control system and Circulation pumps)29231823ArmsStarting current

----ohmMax permitted impedance at connection point 1)

18(20)15(16)13(16)18(20)ArmsMax operating current heat pump incl. 1 – 2 kW immersion heater

(Recommended fuse rating)18(20)15(16)13(16)18(20)ArmsMax operating current heat pump incl. 3 – 4 kW immersion heater

(Recommended fuse rating)18(20)15(16)13(16)18(20)ArmsMax operating current heat pump incl. 5 – 6 kW immersion heater

(Recommended fuse rating)23(25)21(25)19(20)18(20)ArmsMax operating current heat pump including 7 kW immersion heater, connec-

ted upon delivery

(Recommended fuse rating)24(25)22(25)19(20)24(25)ArmsMax operating current heat pump including 9 kW immersion heater, requires

switching

(Recommended fuse rating)130 – 25080 – 14080 – 14080 – 140WOutput, Brine pump80 – 14050 – 8050 – 8050 – 80WOutput, Heating medium pump

IP 21IP classRefrigerant circuit

R407CType of refrigerant1.51.51.41.1kgVolume

2.9 (29 bar)MPaCut-out value pressostat HP

59Chapter 12 | Technical dataNIBE™ F1226

Page 62: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

118653x400V

-0.7 (-7 bar)MPaDifference pressostat HP0.15 (1.5 bar)MPaCut-out value pressostat LP0.15 (1.5 bar)MPaDifference pressostat LP

Brine circuit0.3 (3 bar)MPaMax system pressure brine

0.430.300.220.18l/sMin flow0.640.420.300.22l/sNominal flow57394957kPaMax external avail. press at nom flow

see diagram°CMax/Min incoming Brine temp-10°CMin. outgoing brine temp.

Heating medium circuit0.4 (4 bar)MPaMax system pressure heating medium

0.180.120.090.07l/sMin flow0.250.160.130.09l/sNominal flow57475354kPaMax external avail. press at nom flow

see diagram°CMax/Min heating medium temp44444343dB(A)Noise output (LWA) according to EN 12102 at 0/35

29292828dB(A)Sound pressure level (LPA) calculated values according to EN ISO 11203 at 0/35 and

a distance of 1 m

Pipe connections28mmBrine ext diam. CU pipe

2822mmHeating medium ext diam. CU pipes22mmHot water connection external diam22mmCold water connection external diam

Miscellaneous11865Miscellaneous

Water heater180lVolume water heater

0.9 (9 bar)MPaMax pressure in water heaterDimensions and weight

600mmWidth620mmDepth

1800mmHeight1950mmRequired ceiling height 2)

330320307303kgWeight complete heat pump130120112108kgWeight only cooling module

065 265065 263065 262-Part no. 3x400V, Stainless steel065 225065 223065 222065 221Part no. 3x400V, Copper

1)Max. permitted impedance in the mains connected point in accord-ance with EN 61000-3-11. Start currents can cause short voltagedips that could affect other equipment in unfavourable conditions.If the impedance in the mains connection point is higher than thatstated it is possible that interference will occur. If the impedance inthe mains connection point is higher than that stated check withthe power supplier before purchasing the equipment.2)With feet dismantled the height is approx. 1930 mm.

NIBE™ F1226Chapter 12 | Technical data60

Page 63: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Working range heat pump, compressor oper-ation

The compressor provides a flow temperature up to 63°C, the remainder (up to 70 °C) is obtained using theadditional heat.

5-8 kW

0

10

20

30

40

50

60

70

-15 -10 -5 0 5 10 15 20 25 30 35

°Cp

°C

11 kW

0

10

20

30

40

50

60

70

-15 -10 -5 0 5 10 15 20 25 30 35

°Cp

°C

61Chapter 12 | Technical dataNIBE™ F1226

Page 64: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Electrical circuit diagram3x400V 5 kW

NIBE™ F1226Chapter 12 | Technical data62

Page 65: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

63Chapter 12 | Technical dataNIBE™ F1226

Page 66: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

NIBE™ F1226Chapter 12 | Technical data64

Page 67: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

65Chapter 12 | Technical dataNIBE™ F1226

Page 68: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

NIBE™ F1226Chapter 12 | Technical data66

Page 69: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

3x400V 6-11 kW

67Chapter 12 | Technical dataNIBE™ F1226

Page 70: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

NIBE™ F1226Chapter 12 | Technical data68

Page 71: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

69Chapter 12 | Technical dataNIBE™ F1226

Page 72: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

NIBE™ F1226Chapter 12 | Technical data70

Page 73: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

71Chapter 12 | Technical dataNIBE™ F1226

Page 74: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Item registerAAccessibility, electrical connection, 18Accessories, 57Assembly, 5

BBack button, 33Brine side, 13

CCable lock, 19Commissioning and adjusting, 24

Filling and venting, 24Post adjustment and bleeding, 30Preparations, 24Start guide, 25

Connecting accessories, 23Connecting external operating voltage for the control system, 19Connecting the climate system, 14Connecting the hot water heater, 14Connections, 19Contact for activation of “external adjustment", 22Contact for activation of “temporary lux", 22Contact information, 4Control, 33, 37

Control - Introduction, 33Control - Menus, 37

Control - Introduction, 33Display unit, 33Menu system, 34

Control knob, 33Control - Menus, 37

Menu 1 - INDOOR CLIMATE, 37Menu 2 - HOT WATER, 41Menu 3 - INFO, 42Menu 4 - HEAT PUMP, 43Menu 5 - SERVICE, 45

Cooling section, 11

DDelivery and handling, 5

Assembly, 5Drawing out the cooling module, 5Installation area, 5Removing parts of the insulation, 7Removing the covers, 6Supplied components, 6Transport, 5

Dimensions and pipe connections, 13Dimensions and setting-out coordinates, 58Display, 33Display unit, 33

Back button, 33Control knob, 33Display, 33OK button, 33Status lamp, 33Switch, 33

Disturbances in comfort, 55Manage alarm, 55Troubleshooting, 55

Docking alternatives, 15Extra electric hot water heater, 15Free cooling, 15Ground water system, 16Neutralization vessel, 15Under floor heating systems, 16Ventilation recovery, 15

Draining the climate system, 49

Draining the hot water heater, 49Drawing out the cooling module, 5, 51

EElectrical addition - maximum output, 20

Setting max electrical output, 20Switching to maximum electrical output, 20

Electrical cabinets, 9Electrical circuit diagram, 62

3x400V 5 kW, 623x400V 6-11 kW, 67

Electrical connections, 17Accessibility, electrical connection, 18Cable lock, 19Connecting accessories, 23Connecting external operating voltage for the control system, 19Connections, 19Electrical addition - maximum output, 20External connection options, 22General, 17Miniature circuit-breaker, 17Motor cut-out, 17Optional connections, 22Outdoor sensor, 20Power connection, 19Removing the cover, base board, 18Removing the cover, immersion heater circuit board, 18Removing the hatch, input circuit board, 18Settings, 20Standby mode, 21Temperature limiter, 17

Emptying the brine system, 50External connection options, 22

Contact for activation of “external adjustment", 22Contact for activation of “temporary lux", 22Possible selection for AUX inputs, 22Switch for external blocking of addition and/or compressor, 22Switch for external blocking of heating, 22Temperature sensor, external flow line, 22Temperature sensor, hot water top, 22

FFilling and venting, 24

Filling and venting the brine system, 24Filling and venting the climate system, 24Filling the hot water heater, 24Symbol key, 25

Filling and venting the brine system, 24Filling and venting the climate system, 24Filling the hot water heater, 24

HHeating medium side, 14

Connecting the climate system, 14Helping the circulation pump to start, 50Help menu, 36Hot water heater, 14

Connecting the hot water heater, 14

IImportant information, 2

Safety information, 2Inspection of the installation, 3Installation area, 5

MManage alarm, 55Marking, 2Menu 1 - INDOOR CLIMATE, 37Menu 2 - HOT WATER, 41

NIBE™ F1226Chapter 13 | Item register72

13 Item register

Page 75: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

Menu 3 - INFO, 42Menu 4 - HEAT PUMP, 43Menu 5 - SERVICE, 45Menu system, 34

Help menu, 36Operation, 35Scroll through the windows, 36Selecting menu, 35Selecting options, 35Setting a value, 36

Miniature circuit-breaker, 17Motor cut-out, 17

Resetting, 17

OOK button, 33Operation, 35Optional connections, 22Outdoor sensor, 20

PPipe connections, 12

Brine side, 13Dimensions and pipe connections, 13Docking alternatives, 15General, 12Heating medium side, 14Hot water heater, 14Pipe dimensions, 13Symbol key, 12System diagram, 12

Pipe dimensions, 13Possible selection for AUX inputs, 22Post adjusting the room temperature, 32Post adjustment and bleeding, 30

Post adjusting the room temperature, 32Pump capacity diagrams, collector side, 30Pump capacity diagrams, heating medium side, 31Readjusting, venting, heat medium side, 32

Power connection, 19Preparations, 24Pump capacity diagrams, collector side, 30Pump capacity diagrams, heating medium side, 31

RReadjusting, venting, heat medium side, 32Removing parts of the insulation, 7Removing the cover, base board, 18Removing the cover, immersion heater circuit board, 18Removing the covers, 6Removing the hatch, input circuit board, 18

SSafety information, 2

Contact information, 4Inspection of the installation, 3Marking, 2Serial number, 2Symbols, 2

Scroll through the windows, 36Selecting menu, 35Selecting options, 35Serial number, 2Service, 49

Service actions, 49Service actions, 49

Draining the climate system, 49Draining the hot water heater, 49Drawing out the cooling module, 51Emptying the brine system, 50Helping the circulation pump to start, 50Standby mode, 49

Temperature sensor data, 51USB service outlet, 53

Setting a value, 36Settings, 20Standby mode, 49

Power in emergency mode, 21Start guide, 25Status lamp, 33Supplied components, 6Switch, 33Switch for external blocking of addition and/or compressor, 22Switch for external blocking of heating, 22Symbol key, 12, 25Symbols, 2System diagram, 12

TTechnical data, 58

Dimensions and setting-out coordinates, 58Electrical circuit diagram, 62Technical Data, 59

Technical Data, 59Working range heat pump, 61

Temperature limiter, 17Resetting, 17

Temperature sensor, external flow line, 22Temperature sensor, hot water top, 22Temperature sensor data, 51The heat pump design, 8

Component list cooling section, 11Component list electrical cabinets, 9Component location cooling section, 11Component location electrical cabinets, 9Component locations, 8List of components, 8

Transport, 5Troubleshooting, 55

UUSB service outlet, 53

WWorking range heat pump, 61

73Chapter 13 | Item registerNIBE™ F1226

Page 76: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

NIBE™ F1226Chapter 13 |74

Page 77: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

75Chapter 13 |NIBE™ F1226

Page 78: Installer manual InstallerManual.pdf · 2019. 4. 24. · FI NIBE Energy Systems OY, Juurakkotie 3, 01510 Vantaa Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi GB NIBE Energy

NIBE™ F1226Chapter 13 |76