INSTRUCTIONS FOR THE INSTALLATION, OPERATION AND MAINTENANCE OF TYPES 1125A/1128 & 1125/1127 DIFFERENTIAL PRESSURE GAUGES 1. Type 1125A/1128 – Gauge has a dial with zero at top center. When the pointer is to the right of the zero it indi- cates that the pressure at the right hand socket connection is greater than that exerted at the left and vice-versa. The gauge will not be damaged if the highest pressure should shift from left to right or vice-versa. 2. Type 1125/1127 – Gauge has the usual type dial, such as 0/30, 0/100, etc., with the zero at the bottom left. Pressure must be applied to the high pressure connection before the low pressure is applied. It is important that the high pressure line be connected to the right hand socket, (marked “H”). 3. General Information – The pres- sure gauge contains two bourdon tubes, the free ends of which move when subjected to pressure. A gear movement transmits the motion of the bourdon tubes to the pointer. A pres- sure gauge must not be subjected to a pressure higher than the maximum working pressure shown on the dial. If higher pressures are applied, perma- nent distortion of the bourdon tube and inaccurate readings may result. For best service the gauge should operate at approximately one half of the maxi- mum working pressure. (Example: A gauge with a dial range of 0-200 psi should operate at a working pressure of about 150 lbs. or less.) 4. Installation – Pressure gauges should be mounted in a vertical posi- tion and free from vibration. The gauge socket is equipped with standard size wrench flats. These wrench flats should be used exclusively when installing the gauge. Under no circum- stances should any force be applied to the gauge case directly. Twisting of the case may result in disturbing the cali- bration of the gauge. 5. Applica tions – For steam pressure applications use a siphon. If the gauge is installed above the point of measure- ment, install the siphon in the pressure line to the gauge. Install a shut-off cock between the siphon and the gauge. The siphon should be filled with water to prevent steam from entering the gauge, otherwise the high steam tem- perature may damage the instrument. If the gauge is located below the point of measurement, the bourdon tube will be filled with condensate and no siphon is required. If the gauge is installed on a liquid pressure line, lay the piping so as to avoid vapor entrap- ment, otherwise readings may be incorrect. If possible, arrange for vents at high points in the line to bleed off entrappe d vapors. 6. Gauge Protectors and Dampeners – On installations which are subject to severe pressure fluctuati on, pulsati ons and/or line shock, the use of snubbers or orifice pulsation dampeners is rec- ommended. The snubber is placed in the line just before the pressure gauge. The pointer moves across the gauge scale at a rate which is proportional to the pressure differential across the ele- ment. A moderate but smooth action is obtained, free from shock and pulsa- tion. Gauge failure due to pressure shock is eliminated. A simpler but less effective protective dampening device consists of a restrictive orifice screw. The screw is available as an accessory when ordering the gauge. 7. Zero Adjustment – First remove the bezel or retaining ring and glass face in order to reset the pointer. There are two types of adjustable pointers. The micrometer type is adjusted by holding the pointer firmly with one hand and rotating the adjustment screw with a small screw driver. The friction type adjustable pointer is reset by holding the pointer firmly and rotating the slot- ted hub with a screw driver. Plain point- ers must be removed with a hand jack. On gauges equipped with plain point- ers, minor adjustments can be made by rotating the slotted scale. When resetting pointers to zero, it is impor- tant that there be no pressure in both inlets.  © 2007 Ashcroft, Inc., 250 East. Main Street., Stratford, CT 06614-5145, USA, Tel: 203-378-8281 • www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M008-10158 (84A493-01) 1 1/99 06/10

Upload: sunilkumar2685

Post on 07-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation of P.G

8/3/2019 Installation of P.G

http://slidepdf.com/reader/full/installation-of-pg 1/1

INSTRUCTIONS FOR THE INSTALLATION, OPERATIONAND MAINTENANCE OF TYPES 1125A/1128 &

1125/1127 DIFFERENTIAL PRESSURE GAUGES

1. Type 1125A/1128 – Gauge has adial with zero at top center. When thepointer is to the right of the zero it indi-

cates that the pressure at the righthand socket connection is greater thanthat exerted at the left and vice-versa.The gauge will not be damaged if thehighest pressure should shift from leftto right or vice-versa.

2. Type 1125/1127 – Gauge has theusual type dial, such as 0/30, 0/100,etc., with the zero at the bottom left.Pressure must be applied to the highpressure connection before the lowpressure is applied. It is important thatthe high pressure line be connected tothe right hand socket, (marked “H”).

3. General Information – The pres-sure gauge contains two bourdontubes, the free ends of which movewhen subjected to pressure. A gearmovement transmits the motion of thebourdon tubes to the pointer. A pres-sure gauge must not be subjected to apressure higher than the maximumworking pressure shown on the dial. Ifhigher pressures are applied, perma-nent distortion of the bourdon tube andinaccurate readings may result. Forbest service the gauge should operate

at approximately one half of the maxi-mum working pressure.(Example: A gauge with a dial range of 0-200 psi should operate at a working pressure of about 150 lbs. or less.) 

4. Installation – Pressure gaugesshould be mounted in a vertical posi-tion and free from vibration. The gaugesocket is equipped with standard sizewrench flats. These wrench flatsshould be used exclusively wheninstalling the gauge. Under no circum-stances should any force be applied to

the gauge case directly. Twisting of thecase may result in disturbing the cali-bration of the gauge.

5. Applications – For steam pressureapplications use a siphon. If the gaugeis installed above the point of measure-ment, install the siphon in the pressureline to the gauge. Install a shut-off cockbetween the siphon and the gauge.The siphon should be filled with waterto prevent steam from entering thegauge, otherwise the high steam tem-

perature may damage the instrument.If the gauge is located below the pointof measurement, the bourdon tube will

be filled with condensate and nosiphon is required. If the gauge isinstalled on a liquid pressure line, laythe piping so as to avoid vapor entrap-ment, otherwise readings may beincorrect. If possible, arrange for ventsat high points in the line to bleed offentrapped vapors.

6. Gauge Protectors and Dampeners– On installations which are subject tosevere pressure fluctuation, pulsationsand/or line shock, the use of snubbersor orifice pulsation dampeners is rec-ommended. The snubber is placed inthe line just before the pressure gauge.The pointer moves across the gaugescale at a rate which is proportional tothe pressure differential across the ele-ment. A moderate but smooth action isobtained, free from shock and pulsa-tion. Gauge failure due to pressureshock is eliminated. A simpler but lesseffective protective dampening deviceconsists of a restrictive orifice screw.The screw is available as an accessorywhen ordering the gauge.

7. Zero Adjustment – First remove the

bezel or retaining ring and glass face inorder to reset the pointer. There aretwo types of adjustable pointers. Themicrometer type is adjusted by holdingthe pointer firmly with one hand androtating the adjustment screw with asmall screw driver. The friction typeadjustable pointer is reset by holdingthe pointer firmly and rotating the slot-ted hub with a screw driver. Plain point-ers must be removed with a hand jack.On gauges equipped with plain point-ers, minor adjustments can be madeby rotating the slotted scale. When

resetting pointers to zero, it is impor-tant that there be no pressure in bothinlets.