infrared flame detectors - bosch security...

4
Fire Alarm Systems | Infrared Flame Detectors Infrared Flame Detectors are used to detect open flames in rooms or outdoors. They are especially suitable for smokeless liquid and gas fires as well as for fires of materials that contain carbon with strong smoke development. Typical areas of application are: large industrial warehouses, airplane hangars, chemical facilities, oil refineries, machine rooms, ferries and freight ships, power plants, printing plants, wood warehouses, subway tunnels. The DF1101A‑Ex is an inherently safe Infrared Flame Detector for use in explosive areas of the zones 1 and 2, e. g. in high warehouse halls for flammable liquids, where liquid fires could occur in an explosive atmosphere. System Overview FLM-420/4-CON EOL22(Ex) DM 1103 B-Ex DM 1103 B-Ex DO1101A-Ex DCA1192 SB3 DCA1192 SB3 DFA1101A-Ex DO1101A-Ex 1 2 Pos. Description 1 Non-Ex area 2 Ex area zone 1 or 2 Functions The detection element of the Infrared Flame Detector consists of two pyroelectric sensors (sensor 1 and 2) and a silicon photo diode (sensor 3). Infrared Flame Detectors Compact, robust and nearly maintenance-free Suitable for outdoor use under extreme conditions Optimal adjustment to the environmental conditions with 10 DIP switches Two sensitivity levels Easy-to-see red individual display For room heights from 1.50 m to 20 m www.boschsecurity.com

Upload: dotuyen

Post on 17-Mar-2019

239 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Infrared Flame Detectors - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1283095307.pdf · consists of two pyroelectric sensors (sensor 1 and 2) and a

Fire Alarm Systems | Infrared Flame Detectors

Infrared Flame Detectors are used to detect open flamesin rooms or outdoors.

They are especially suitable for smokeless liquid and gasfires as well as for fires of materials that contain carbonwith strong smoke development.

Typical areas of application are:

large industrial warehouses, airplane hangars, chemicalfacilities, oil refineries, machine rooms, ferries and freightships, power plants, printing plants, wood warehouses,subway tunnels.

The DF1101A‑Ex is an inherently safe Infrared FlameDetector for use in explosive areas of the zones 1 and 2,e. g. in high warehouse halls for flammable liquids, whereliquid fires could occur in an explosive atmosphere.

System Overview

FLM-420/4-CON

EOL22(Ex)

DM 1103 B-Ex DM 1103 B-Ex

DO1101A-Ex

DCA1192 SB3

DCA1192 SB3

DFA1101A-Ex

DO1101A-Ex

1 2

Pos. Description

1 Non-Ex area

2 Ex area zone 1 or 2

Functions

The detection element of the Infrared Flame Detectorconsists of two pyroelectric sensors (sensor 1 and 2) anda silicon photo diode (sensor 3).

Infrared Flame Detectors▶ Compact, robust and nearly maintenance-free

▶ Suitable for outdoor use under extreme conditions

▶ Optimal adjustment to the environmental conditionswith 10 DIP switches

▶ Two sensitivity levels

▶ Easy-to-see red individual display

▶ For room heights from 1.50 m to 20 m

www.boschsecurity.com

Page 2: Infrared Flame Detectors - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1283095307.pdf · consists of two pyroelectric sensors (sensor 1 and 2) and a

2 | Infrared Flame Detectors

While sensor 1 detects the flame, the other two sensorsmeasure the malfunction beam in other wavelengthranges.

Sensor Spectral range Detection from

1 4.0 μm to 4.8 μm CO2

2 5.1 μm to 6.0 μm Sources of interference

3 0.7 μm to 1.1 μm Solar radiation

The combination of the three sensors and the intelligentsignal processing with fuzzy algorithms and waveletcreates outstanding reliability of detection with highprotection against false alarms.

Certifications and Approvals

The DF1101A‑Ex meets the explosion classification in linewith IEC 60079 and EN 50020 (Eex ib IIC T4).

Region Certification

Germany VdS G 299085 DF1101-Ex/DF1192

Europe CE DF 1192

DF 1101-Ex

Installation/Configuration Notes

• Both Infrared Flame Detectors comply with EN 54‑10.• The response sensitivity and the resulting monitoring

area of an Infrared Flame Detector depend on:- Detection distance- Possible spread of fire- Fire material- Detector sensitivity- Detector arrangement.

• Purely for physical reasons, IR flame detectors candetect no fires of inorganic materials (e. g. sulfur,phosphorous, magnesium, natrium, hydrogen, etc.).

• The detector must have a direct visual line to allpossible fire locations of the monitoring area.

• Practical area monitoring is achieved with a detectorarrangement at a 45° to the corners of the area.

• If the room height is more than 5 m, the detector axisshould be aligned towards the opposite corner of theroom.

• The space above the detector is outside of thedetection area.

• Despite wide-ranging insensitivity, the sensors mustbe protected against direct or indirect sunlight; it maybe necessary to install a covering housing.

• The Infrared Flame Detectors can be connected usinga FLM‑420/4‑CON Conventional Interface Module tothe Local SecurityNetwork LSN.

Parts Included

Detector type Qty. Components

DF1192 1 Infrared Flame Detector DF1192

DF1101A-Ex 1 Infrared Flame Detector DF1101A‑Ex

Note With the Infrared Flame Detectors DF1192and DF1101A‑Ex, the DFB1190 detector baseis not included in the scope of delivery andmust be ordered separately.

Technical Specifications

Electrical

Operating voltage 16 V DC . . . 28 V DC

Standby current consumption 0.5 mA

Mechanics

Individual display LED red

Connection terminals 0.2 mm2. . . 2.5 mm2

Dimensions (W x H x D)

• Detector 135 x 135 x 32 mm

• Detector incl. base 135 x 135 x 77 mm

Housing material

• Detector Cast aluminum

• Base Plastic, PC, fiber-reinforced

Color (detector and base) White, RAL 9010

Weight incl. base

• DF1192 500 g

• DF1101A-Ex 750 g

Environmental conditions

Protection class as per EN 60529 IP 67

Permissible operating tempera-ture

-35 °C . . . +70 °C

Permissible storage temperature -40 °C . . . +75 °C

Relative humidity < 100 %, no heavy condensation ofthe sensor window

Planning

Max. installation height 1.5 . . . 20 m

Max. monitoring area 80 m2 (Heed local guidelines!)

Special features

Detection principle Detection of infrared radiation

Detection area 90°

Page 3: Infrared Flame Detectors - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1283095307.pdf · consists of two pyroelectric sensors (sensor 1 and 2) and a

Infrared Flame Detectors | 3

Ordering Information

DF1192 Infrared Flame Detector DF1192

DF1101A‑Ex Infrared Flame Detector forEx Areas

DF1101A-Ex

SB3 Safety Barrier incl. DCA1192 Input/Output Modulelimits the electrical energy between non-in-herently safe and inherently safe circuits

SB3

Accessories

DFB1192-BASE Base for Infrared FlameDetectorBase for Infrared Flame Detectors DF1192and DF1101A‑Ex, including line terminationEOL22(Ex)

DF1192-BASE

www.boschsecurity.com

Page 4: Infrared Flame Detectors - Bosch Security Systemsresource.boschsecurity.com/documents/Data_sheet_enUS_1283095307.pdf · consists of two pyroelectric sensors (sensor 1 and 2) and a

4 | Infrared Flame Detectors

Americas:Bosch Security Systems, Inc.130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 [email protected]

Europe, Middle East, Africa:Bosch Security Systems B.V.P.O. Box 800025600 JB Eindhoven, The NetherlandsPhone: + 31 40 2577 284Fax: +31 40 2577 [email protected]

Asia-Pacific:Robert Bosch (SEA) Pte Ltd, Security Systems11 Bishan Street 21Singapore 573943Phone: +65 6258 5511Fax: +65 6571 [email protected]

Represented by

© Bosch Security Systems Inc. 011 | Data subject to change without noticeT284685451 | Cur: en-US, V24, 19 Apr 2011