ComEd ® Energy Efficiency Program ColnEd ® powering lives An Exelon Company INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET January 1, 2018 through December 31, 2018 ComEd ® Energy Effciency Program offers advanced lighting system incentives for intelligent lighting control systems that optimize the performance of a network of effcient light fxtures and sensors. Advanced lighting systems have three components: • High-effciency fxtures and sensors tied to a central control system • A central control system that can be accessed from a computer or mobile device, show real-time status of the lighting system and generate detailed reports about the system’s performance. Control strategies such as occupancy sensors, dimming and zone control are selected by the user and programmed into the control system. • A minimum two (2) week post-installation measurement and verifcation period, in which energy data is captured to verify reductions in usage (optional). Advanced lighting system incentives may be used to replace an existing lighting system or to install a new system where none exists. Incentives also are available for customers that wish to install an intelligent control system for use with existing fxtures. Incentives are available through two options, as shown below. OPTION ONE OPTION TWO NEW T8/T5 or LED fxtures @ $0.50 watt reduced Keep existing fxtures or install new or retroftted fxtures that don’t meet Option One* + + NEW lighting control system @ $0.18 watt controlled NEW lighting control system, measurement & verifcation @ $0.07 kWh saved above baseline OPTIONAL OPTIONAL Measurement & verifcation @ $0.10 kWh saved above target Use NALCTP-certifed contractor on installation team + @ $1,000 Use NALCTP-certifed contractor on installation team * May be eligible to apply through the Indoor Lighting Incentives @ $1,000 Worksheet 1

Upload: nguyentu

Post on 07-Jun-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • ComEd Energy Efficiency Program

    ColnEd powering lives An Exelon Company

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET January 1, 2018 through December 31, 2018

    ComEd Energy Effciency Program offers advanced lighting system incentives for intelligent lighting control systems that optimize the performance of a network of effcient light fxtures and sensors. Advanced lighting systems have three components:

    High-effciency fxtures and sensors tied to a central control system

    A central control system that can be accessed from a computer or mobile device, show real-time status of the lighting system and generate detailed reports about the systems performance. Control strategies such as occupancy sensors, dimming and zone control are selected by the user and programmed into the control system.

    A minimum two (2) week post-installation measurement and verifcation period, in which energy data is captured to verify reductions in usage (optional).

    Advanced lighting system incentives may be used to replace an existing lighting system or to install a new system where none exists. Incentives also are available for customers that wish to install an intelligent control system for use with existing fxtures. Incentives are available through two options, as shown below.

    OPTION ONE OPTION TWO NEW T8/T5 or LED fxtures @ $0.50 watt reduced Keep existing fxtures or install new or retroftted fxtures

    that dont meet Option One*+ +

    NEW lighting control system @ $0.18 watt controlled NEW lighting control system, measurement & verifcation

    @ $0.07 kWh saved above baseline OPTIONAL OPTIONAL Measurement & verifcation @ $0.10 kWh saved above

    target Use NALCTP-certifed contractor on installation team

    + @ $1,000 Use NALCTP-certifed contractor on installation team * May be eligible to apply through the Indoor Lighting Incentives

    @ $1,000 Worksheet

    1

  • January 1, 2018 through December 31, 2018

    2

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    DIRECTIONS: Please save a copy of this form to your computer by selecting FILE/SAVE AS before entering text and numbers. Then fll in your information electronically and select SAVE. Note that this form requires Adobe Reader version 11.0 to function properly. Download the most recent version of Adobe Acrobat Reader DC at http://get.adobe.com/reader.

    A pre-approval application is required; review instructions on the standard and custom incentives pre-approval and fnal application form. Wait for pre-approval before starting your project.

    All lighting projects are expected to comply with the Illuminating Engineering Society of North America (IESNA) recommended lighting levels or the local code.

    OPTION 1 AD VANCED LIGHTING S YSTEM WITH NEW, HIGH-EFFICIENC Y FIXTURE S AND CONTROL S YSTEM

    To receive the incentives available under Option 1, the following requirements must be met, in addition to all measure-specifc specifcations:

    1. Option 1 incentives are applicable only to new high -effciency T8/T5 and LED fxtures which meet the specifcations below. All other fxtures not meeting the specifcations may be eligible for Option 2 incentives.

    2. A majority of total new system wattage must meet the fxture specifcations detailed below. 3. IECC 2015 lighting power densities should be used to determine baseline conditions for projects where there is no existing

    lighting system. 4. A minimum two (2) week post-installation measurement and verifcation (M&V) period is only required to receive the $0.10

    kWh M&V bonus. Please see specifcations for M&V requirements.

    SECTION I : FIXTURES

    New T8/T5 Fluorescent Fixture with Electronic Ballast

    SPECIFICATIONS 1. Fixtures must be installed with a control system which meets the control system specifcations described on page 8 in this

    worksheet to receive this incentive. 2. Manufacturers specifcations for new fxtures, lamps and ballasts must be submitted with pre-approval and fnal applications. 3. Fixtures must contain all new components and be unopened at time of purchase. 4. Fixtures must be pre-approved by the ComEd Energy Effciency Program as effcient fxtures (generally, with a fxture

    effciency 85%). 5. T8/T5 lamps must have a CRI 80. 6. Ballasts must meet the following specs:

    High frequency ( 40/50 kHz) Power factor (PF) 0.90 UL or ETL listed Warranted against defects for 5 years Ballast should have a total harmonic distortion (THD) 20% at full light output

    EQUIPMENT TYPE and DEFINITION UNIT INCENTIVE

    New T8/T5 Fluorescent Fixture with Electronic Ballast Installation of a new lighting system containing T8/ T5 fxtures with T8/T5 lamps and electronic ballasts.

    Reduction in connected watts $0.50 per watt reduced

    If you are installing new T8/T5 fixtures to replace an existing lighting system, complete the watt reduction worksheet on the following page.

    Company Name:

    http://get.adobe.com/reader

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    Watt Reduction Worksheet for New T8/T5 Fixtures Replacing an Existing Lighting System

    Use this worksheet or attach an itemized project plan. (See example in red.)

    TYPE OF EQUIPMENT

    TO BE REPLACED

    QUANTITY OF EQUIPMENT

    TO BE REPLACED

    WATTAGE OF EQUIPMENT

    TO BE REPLACED

    TOTAL WATTAGE

    OF OLD EQUIPMENT

    TYPE OF NEW FIXTURE

    TO BE INSTALLED

    QUANTITY OF NEW

    EQUIPMENT

    WATTAGE OF NEW

    EQUIPMENT

    TOTAL WATTAGE OF NEW

    EQUIPMENT

    DIFFERENCE (OLD WATTAGE

    MINUS NEW)

    example: 250W metal halide

    100 295 29,500 example: 4-lamp 4-ft T8 100 120 12,000 17,500

    SUBTOTAL OLD WATTAGE MINUS NEW

    EQUIPMENT TYPE (A)

    INCENTIVE PER UNIT (B)

    UNIT (A x B)

    INCENTIVE

    New T8/T5 Fluorescent Fixtures with Electronic Ballast

    $0.50 per watt reduced Watts reduced (from worksheet above):

    ________________

    SUBTOTAL $

    If you are installing new T8/T5 fixtures where no lighting system exists, complete the watt reduction worksheet on the following page. Use IECC 2015 lighting power densities to determine baseline conditions.

    3

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    Watt Reduction Worksheet for New T8/T5 Fixtures - No Existing Lighting System

    Use this worksheet or attach an itemized project plan.

    AREA OF ILLUMINATED

    SPACE (SQUARE FEET)

    IECC 2015 LIGHTING POWER

    DENSITY (W/SQUARE FOOT)

    TOTAL WATTAGE OF

    BASELINE

    TYPE OF NEW FIXTURE TO BE INSTALLED

    QUANTITY OF NEW

    EQUIPMENT

    WATTAGE OF NEW

    EQUIPMENT

    TOTAL WATTAGE OF NEW

    EQUIPMENT

    DIFFERENCE (OLD WATTAGE

    MINUS NEW)

    SUBTOTAL OLD WATTAGE MINUS NEW

    EQUIPMENT TYPE (A)

    INCENTIVE PER UNIT (B)

    UNIT (A x B)

    INCENTIVE

    New T8/T5 Fluorescent Fixtures with Electronic Ballast

    $0.50 per watt reduced Watts reduced (from worksheet above):

    ________________

    SUBTOTAL $

    4

  • January 1, 2018 through December 31, 2018

    5

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    LED Fixtures

    SPECIFICATIONS 1. Fixtures must be installed with a control system that meets the specifcations listed on page 8 in the worksheet to be eligible

    for this incentive. 2. Manufacturers specifcations for new fxtures must accompany pre-approval and fnal applications. 3. Fixtures must be on the DesignLightsTM Consortium (DLC) Qualifed Products List available at http://www.designlights.org. 4. Linear types A and B LED tubes are not eligible for standard incentives but may be eligible for instant discounts from

    participating distributors; visit ComEd.com/InstantDiscounts for details.

    EQUIPMENT TYPE and DEFINITION UNIT INCENTIVE

    LED Fixture Installation of a new indoor lighting system containing LED fxtures.

    Reduction in connected watts $0.50 per watt reduced

    If you are installing new LED fixtures to replace an existing lighting system, complete the watt reduction worksheet on the following page.

    http:http://www.designlights.org

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    Watt Reduction Worksheet for New LED Fixtures Replacing an Existing Lighting System

    Use this worksheet or attach an itemized project plan. (See example in red.)

    TYPE OF EQUIPMENT

    TO BE REPLACED

    QUANTITY OF EQUIPMENT

    TO BE REPLACED

    WATTAGE OF EQUIPMENT

    TO BE REPLACED

    TOTAL WATTAGE

    OF OLD EQUIPMENT

    TYPE OF NEW FIXTURE

    TO BE INSTALLED

    QUANTITY OF NEW

    EQUIPMENT

    WATTAGE OF NEW

    EQUIPMENT

    TOTAL WATTAGE OF NEW

    EQUIPMENT

    DIFFERENCE (OLD WATTAGE

    MINUS NEW)

    example: 2-lamp 4-ft T12

    100 72 7,200 example: LED 2x4 ft troffer

    120 44 5,280 1,920

    SUBTOTAL OLD WATTAGE MINUS NEW

    EQUIPMENT TYPE (A)

    INCENTIVE PER UNIT (B)

    UNIT (A x B)

    INCENTIVE

    LED Fixture $0.50 per watt reduced Watts reduced (from worksheet above):

    ________________

    SUBTOTAL $

    6

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    If you are installing new LED fixtures where no lighting system exists, complete the following watt reduction worksheet. Use IECC 2015 lighting power densities to determine baseline conditions.

    Watt Reduction Worksheet for New LED Fixtures No Existing Lighting System

    Use this worksheet or attach an itemized project plan.

    AREA OF ILLUMINATED

    SPACE (SQUARE FEET)

    IECC 2015 LIGHTING POWER

    DENSITY (W/SQUARE FOOT)

    TOTAL WATTAGE OF

    BASELINE

    TYPE OF NEW FIXTURE TO BE INSTALLED

    QUANTITY OF NEW

    EQUIPMENT

    WATTAGE OF NEW

    EQUIPMENT

    TOTAL WATTAGE OF NEW

    EQUIPMENT

    DIFFERENCE (OLD WATTAGE

    MINUS NEW)

    SUBTOTAL OLD WATTAGE MINUS NEW

    EQUIPMENT TYPE (A)

    INCENTIVE PER UNIT (B)

    UNIT (A x B)

    INCENTIVE

    LED Fixture $0.50 per watt reduced Watts reduced (from worksheet above):

    ________________

    SUBTOTAL $

    SECTION I SUBTOTAL $

    7

  • January 1, 2018 through December 31, 2018

    8

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    SECTION II : CONTROL SYSTEM AND STRATEGIES

    Control System

    SPECIFICATIONS 1. Manufacturers specifcations must accompany pre-approval and fnal applications. 2. The control system must be new and meet the following criteria:

    System must be DLC listed and meet requirements below System must control new or existing T8/T5 or LED fxtures that meet the applicable specifcations set forth in

    Section I Fixtures on this worksheet System must have a graphical user interface that is accessible from a computer and/or mobile device System must have network interoperability (e.g., BACNet MS/TP, Zigbee, etc.) To receive M&V bonus, system must have the ability to generate reports that show details such as energy consumption,

    demand, fxture on/off time, fxture light level (percentage), etc. System must have the ability to show the real-time status of the light fxtures (e.g., on/off, dimmed, etc.) All installed sensors must be tied to the central control system

    3. The installed control system must apply at least one control strategy. The following is a list of suggested control strategies. Please check all control strategies being implemented.

    Occupancy sensors with timeout setting controls Occupancy sensors are installed using passive infrared and/or ultrasonic technology. Sensors should have adjustable timeout settings.

    Dimming (continuous or step) Fixtures dimmed to light levels less than 70%. Dimming settings are managed by the central control system.

    Daylight harvesting Photocells are installed to control interior fxtures; sensors should assess amount of ambient light and adjust fxtures to meet facility illumination requirement.

    Photo controls Photocells are installed to control exterior fxtures. Zone control At least two (2) zones in a facility with different profles. Scheduling Lighting is managed based on shifts, operating hours, seasonal changes, etc. High-end trimming Setting a maximum light allowance at less than 100 percent light output. User set preference/occupant profles

    Other (specify): ______________________________________________________________________________________________________

    EQUIPMENT TYPE and DEFINITION UNIT INCENTIVE

    Installation of a new control system with new or existing fxtures that meet applicable fxture specifcations. Control system must apply at least one control strategy.

    Per watt controlled $0.18 per watt controlled

    Please complete the watts controlled worksheet for new control system on the following page. If you need more room than what is available, you may attach a separate sheet.

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    Watts Controlled Worksheet for New Control System

    TYPE OF FIXTURE (A)

    NUMBER OF FIXTURES (B)

    WATTS PER FIXTURE (A x B )

    WATTS CONTROLLED

    TOTAL WATTS CONTROLLED

    SUBTOTAL @ $0.18/WATT CONTROLLED $

    9

  • January 1, 2018 through December 31, 2018

    10

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    Equipment Installation by NALCTP-certifed Electrician or Contractor

    SPECIFICATIONS 1. To qualify for this incentive, the advanced lighting system must be installed by a qualifed team in which at least one (1)

    member is certifed by the National Advanced Lighting Controls Training Program (NALCTP) to install, tune, commission and maintain advanced lighting control systems. A list of NALCTP-qualifed electricians and contractors can be found at www.nalctp.org/Illinois.

    2. The NALCTP-certifed electrician or contractor must be listed as such at www.nalctp.org/Illinois. 3. Timesheets or other proof which indicate a NALCTP-certifed electrician or contractor was part of the team that installed the

    control system must be furnished upon request.

    DEFINITION UNIT INCENTIVE

    Control system installation team includes at least one (1) NALCTP- certifed electrician or contractor

    NALCTP-certifed installation $1000

    NALCTP INSTALLATION SUBTOTAL $

    SECTION II SUBTOTAL $

    TOTAL INCENTIVE REQUESTED (SECTIONS I and II) $

    www.nalctp.org/Illinoiswww.nalctp.org/Illinois

  • January 1, 2018 through December 31, 2018

    11

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    SECTION III : MEASUREMENT AND VERIFICATION (OPTIONAL)

    Energy Savings Documented through Measurement and Verifcation (M&V)

    SPECIFICATIONS Additional incentives are available for verifying the kilowatt-hour (kWh) savings above the calculated target kWh through a trend report generated by the advanced lighting control system. Please complete and submit this worksheet page with the M&V data fle after the M&V has been collected. 1. Submit a detailed description of the existing lighting controls with the pre-approval application. 2. The required M&V data fle must be provided and the information must be submitted according to the following requirements:

    Minimum two (2) week period of M&V collection during normal facility operation, which does not include holiday breaks, facility shutdowns or other periods of non-standard operation; depending on the project, the ComEd Energy Effciency Program team may request a longer M&V period

    Minimum 15 minute kW interval readings M&V should be provided in a .csv, .xlsx, or .xls fle (pdf data fles will not be accepted)

    EQUIPMENT TYPE and DEFINITION UNIT INCENTIVE

    Advanced lighting system that achieves kWh savings above a calculated target kWh

    Per measured kWh $0.10 per kWh above target

  • January 1, 2018 through December 31, 2018

    12

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    A pre-approval application is required; review instructions on the standard and custom incentives pre-approval and fnal application form. Wait for pre-approval before starting your project.

    OPTION 2 LIGHTING CONTROL SYSTEM ON EXISTING OR NEW FIXTURES THAT DO NOT MEET THE FIXTURE SPECIFICATIONS IN OPTION 1

    Use this section to apply for incentives for energy savings resulting from the installation of a control system on existing or new fxtures that do not meet the specifcations for fxtures described in Option 1. Note that other ComEd Energy Effciency Program standard incentives may be available for fxtures that do not meet the Option 1 fxture specifcations; see the indoor lighting incentives worksheet at ComEd.com/BizIncentives for lighting fxture replacement and retroft incentives.

    To receive the incentives available under Option 2, the following requirement must be met, in addition to all measure-specifc specifcations: 1. A minimum two (2) week post-installation measurement and verifcation (M&V) period is required. See specifcations for M&V

    below.

    Control System

    SPECIFICATIONS 1. Manufacturers specifcations must accompany pre-approval and fnal applications. 2. The control system must be new and meet the following criteria:

    System must be DLC listed and meet requirements below System must control existing lighting fxtures System must have a graphical user interface that is accessible from a computer and/or mobile device System must have network interoperability (e.g., BACNet MS/TP, Zigbee, etc.) System must have the ability to generate reports that show details such as energy consumption, demand, fxture on/off time,

    fxture light level (percentage), etc. System must have the ability to show the real-time status of the light fxtures (e.g., on/off, dimmed, etc.) All installed sensors must be tied to the central control system

    3. The installed control system must apply at least one control strategy. The following is a list of suggested control strategies. Please check all control strategies being implemented.

    Occupancy sensors with timeout setting controls Occupancy sensors are installed using passive infrared and/or ultrasonic technology. Sensors should have adjustable timeout settings.

    Dimming (continuous or step) Fixtures dimmed to light levels less than 70%. Dimming settings are managed by the central control system.

    Daylight harvesting Photocells are installed to control interior fxtures; sensors should assess amount of ambient light and adjust fxtures to meet facility illumination requirement.

    Photo controls Photocells are installed to control exterior fxtures. Zone control At least two (2) zones in a facility with different profles. Scheduling Lighting is managed based on shifts, operating hours, seasonal changes, etc. High-end trimming Setting a maximum light allowance at less than 100 percent light output. User set preference/occupant profles

    Other (specify): ______________________________________________________________________________________________________

    Please complete the tables on the following page. If you need more room than what is available, you may attach a separate sheet.

    www.comed.com/bizincentives

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    TYPE/DESCRIPTION (A)

    NUMBER OF FIXTURES (B)

    WATTS PER FIXTURE (C)

    ANNUAL HOURS OF OPERATION (A x B x C/1000)

    TOTAL ANNUAL kWh

    (D) TOTAL kWh OF EXISTING SYSTEM

    Fixtures to be Controlled (Existing System)

    Proposed Lighting Control System

    TYPE/DESCRIPTION (A)

    NUMBER OF FIXTURES (B)

    WATTS PER FIXTURE (C)

    ANNUAL HOURS OF OPERATION (A x B x C/1000)

    TOTAL ANNUAL kWh

    (E) TOTAL kWh OF PROPOSED SYSTEM

    13

  • January 1, 2018 through December 31, 2018

    INDOOR ADVANCED LIGHTING SYSTEM WORKSHEET

    ColnEd powering lives An Exelon Company

    Energy Savings Documented through Measurement and Verifcation (M&V)

    SPECIFICATIONS 1. An M&V data fle generated by the installed lighting control system must be provided and the information must be submitted

    according to the following requirements: Submit a detailed description of the existing lighting controls with the pre-approval application. Minimum two (2) week period of M&V collection during normal facility operation, which does not include holiday breaks,

    facility shutdowns or other periods of non-standard operation; depending on the project, the ComEd Energy Effciency Program team may request a longer M&V period

    Minimum 15 minute kW interval readings M&V should be provided in a .csv, .xlsx, or .xls fle (pdf data fles will not be accepted)

    2. Submit M&V data fle and any other supporting documentation with your fnal application for incentive.

    DEFINITION UNIT INCENTIVE

    Energy savings resulting from installation of a control system on existing or new fxtures

    Per measured kWh $0.07 per kWh

    Incentive Calculation

    INCENTIVE Annual energy savings in kWh (D -E) X $0.07 =

    PAYBACK PERIOD (YEARS)

    Total project cost

    Estimated annual energy savings (in dollars)

    =

    (F) REQUESTED INCENTIVE TOTAL $

    Equipment Installation by NALCTP-certifed Electrician or Contractor

    SPECIFICATIONS 1. To qualify for this incentive, the advanced lighting system must be installed by a qualifed team in which at least one (1)

    member is certifed by the National Advanced Lighting Controls Training Program (NALCTP) to install, tune, commission and maintain advanced lighting control systems. A list of NALCTP-qualifed electricians and contractors can be found at www.nalctp.org/Illinois.

    2. The NALCTP-certifed electrician or contractor must be listed as such at www.nalctp.org/Illinois. 3. Timesheets or other proof which indicate a NALCTP-certifed electrician or contractor was part of the team that installed the

    control system must be furnished upon request.

    DEFINITION UNIT INCENTIVE

    Control system installation team includes at least one (1) NALCTP- certifed electrician or contractor.

    NALCTP-certifed installation $1000

    NALCTP INSTALLATION SUBTOTAL $

    TOTAL INCENTIVE REQUESTED $

    Commonwealth Edison Company, 2018 The ComEd Energy Effciency Program is funded in compliance with state law.

    14

    www.nalctp.org/Illinoiswww.nalctp.org/Illinois

    equipRow1: old_quantity_Row1: old_wattage_Row1: old_TOTAL_Row1: new_fixture_Row1: new_quantity_Row1: new_wattage_Row1: new_TOTAL_Row1: watts_reduced_Row1: equipRow2: old_quantity_Row2: old_wattage_Row2: old_TOTAL_Row2: new_fixture_Row2: new_quantity_Row2: new_wattage_Row2: new_TOTAL_Row2: watts_reduced_Row2: equipRow3: old_quantity_Row3: old_wattage_Row3: old_TOTAL_Row3: new_fixture_Row3: new_quantity_Row3: new_wattage_Row3: new_TOTAL_Row3: watts_reduced_Row3: equipRow4: old_quantity_Row4: old_wattage_Row4: old_TOTAL_Row4: new_fixture_Row4: new_quantity_Row4: new_wattage_Row4: new_TOTAL_Row4: watts_reduced_Row4: equipRow5: old_quantity_Row5: old_wattage_Row5: old_TOTAL_Row5: new_fixture_Row5: new_quantity_Row5: new_wattage_Row5: new_TOTAL_Row5: watts_reduced_Row5: equipRow6: old_quantity_Row6: old_wattage_Row6: old_TOTAL_Row6: new_fixture_Row6: new_quantity_Row6: new_wattage_Row6: new_TOTAL_Row6: watts_reduced_Row6: equipRow7: old_quantity_Row7: old_wattage_Row7: old_TOTAL_Row7: new_fixture_Row7: new_quantity_Row7: new_wattage_Row7: new_TOTAL_Row7: watts_reduced_Row7: equipRow8: old_quantity_Row8: old_wattage_Row8: old_TOTAL_Row8: new_fixture_Row8: new_quantity_Row8: new_wattage_Row8: new_TOTAL_Row8: watts_reduced_Row8: equipRow9: old_quantity_Row9: old_wattage_Row9: old_TOTAL_Row9: new_fixture_Row9: new_quantity_Row9: new_wattage_Row9: new_TOTAL_Row9: watts_reduced_Row9: 0: 50: 0.5007: 0.07

    SUBTOTAL_A_PAGE2: T8T5 Incentive Total: T8T5 Incentive Total2: T5T8IllumRow01: T5T8AshraeLPDRow01: T5T8TotalWattageBaselineRow01: T5T8NewFixtureRow01: T5T8NewQuantityRow01: T5T8NewWattageRow01: T5T8_TotalNewRow01: T5T8DifferenceTotalRow01: T5T8IllumRow02: T5T8AshraeLPDRow02: T5T8TotalWattageBaselineRow02: T5T8NewFixtureRow02: T5T8NewQuantityRow02: T5T8NewWattageRow02: T5T8_TotalNewRow02: T5T8DifferenceTotalRow02: T5T8IllumRow03: T5T8AshraeLPDRow03: T5T8TotalWattageBaselineRow03: T5T8NewFixtureRow03: T5T8NewQuantityRow03: T5T8NewWattageRow03: T5T8_TotalNewRow03: T5T8DifferenceTotalRow03: T5T8IllumRow04: T5T8AshraeLPDRow04: T5T8TotalWattageBaselineRow04: T5T8NewFixtureRow04: T5T8NewQuantityRow04: T5T8NewWattageRow04: T5T8_TotalNewRow04: T5T8DifferenceTotalRow04: T5T8IllumRow05: T5T8AshraeLPDRow05: T5T8TotalWattageBaselineRow05: T5T8NewFixtureRow05: T5T8NewQuantityRow05: T5T8NewWattageRow05: T5T8_TotalNewRow05: T5T8DifferenceTotalRow05: T5T8IllumRow06: T5T8AshraeLPDRow06: T5T8TotalWattageBaselineRow06: T5T8NewFixtureRow06: T5T8NewQuantityRow06: T5T8NewWattageRow06: T5T8_TotalNewRow06: T5T8DifferenceTotalRow06: T5T8IllumRow07: T5T8AshraeLPDRow07: T5T8TotalWattageBaselineRow07: T5T8NewFixtureRow07: T5T8NewQuantityRow07: T5T8NewWattageRow07: T5T8_TotalNewRow07: T5T8DifferenceTotalRow07: T5T8IllumRow08: T5T8AshraeLPDRow08: T5T8TotalWattageBaselineRow08: T5T8NewFixtureRow08: T5T8NewQuantityRow08: T5T8NewWattageRow08: T5T8_TotalNewRow08: T5T8DifferenceTotalRow08: T5T8IllumRow09: T5T8AshraeLPDRow09: T5T8TotalWattageBaselineRow09: T5T8NewFixtureRow09: T5T8NewQuantityRow09: T5T8NewWattageRow09: T5T8_TotalNewRow09: T5T8DifferenceTotalRow09: T5T8_WattageTotal: T5T8_Subtotal: T5T8_Subtotal2: NewLEDequipRow01: NewLEDold_quantityRow01: NewLEDold_wattageRow01: NewLEDold_TOTALRow01: NewLEDnew_fixtureRow01: NewLEDnew_quantityRow01: NewLEDnew_wattageRow01: NewLEDnew_TOTALRow01: NewLEDwatts_reducedRow01: NewLEDequipRow02: NewLEDold_quantityRow02: NewLEDold_wattageRow02: NewLEDold_TOTALRow02: NewLEDnew_fixtureRow02: NewLEDnew_quantityRow02: NewLEDnew_wattageRow02: NewLEDnew_TOTALRow02: NewLEDwatts_reducedRow02: NewLEDequipRow03: NewLEDold_quantityRow03: NewLEDold_wattageRow03: NewLEDold_TOTALRow03: NewLEDnew_fixtureRow03: NewLEDnew_quantityRow03: NewLEDnew_wattageRow03: NewLEDnew_TOTALRow03: NewLEDwatts_reducedRow03: NewLEDequipRow04: NewLEDold_quantityRow04: NewLEDold_wattageRow04: NewLEDold_TOTALRow04: NewLEDnew_fixtureRow04: NewLEDnew_quantityRow04: NewLEDnew_wattageRow04: NewLEDnew_TOTALRow04: NewLEDwatts_reducedRow04: NewLEDequipRow05: NewLEDold_quantityRow05: NewLEDold_wattageRow05: NewLEDold_TOTALRow05: NewLEDnew_fixtureRow05: NewLEDnew_quantityRow05: NewLEDnew_wattageRow05: NewLEDnew_TOTALRow05: NewLEDwatts_reducedRow05: NewLEDequipRow06: NewLEDold_quantityRow06: NewLEDold_wattageRow06: NewLEDold_TOTALRow06: NewLEDnew_fixtureRow06: NewLEDnew_quantityRow06: NewLEDnew_wattageRow06: NewLEDnew_TOTALRow06: NewLEDwatts_reducedRow06: NewLEDequipRow07: NewLEDold_quantityRow07: NewLEDold_wattageRow07: NewLEDold_TOTALRow07: NewLEDnew_fixtureRow07: NewLEDnew_quantityRow07: NewLEDnew_wattageRow07: NewLEDnew_TOTALRow07: NewLEDwatts_reducedRow07: NewLEDequipRow08: NewLEDold_quantityRow08: NewLEDold_wattageRow08: NewLEDold_TOTALRow08: NewLEDnew_fixtureRow08: NewLEDnew_quantityRow08: NewLEDnew_wattageRow08: NewLEDnew_TOTALRow08: NewLEDwatts_reducedRow08: NewLEDequipRow09: NewLEDold_quantityRow09: NewLEDold_wattageRow09: NewLEDold_TOTALRow09: NewLEDnew_fixtureRow09: NewLEDnew_quantityRow09: NewLEDnew_wattageRow09: NewLEDnew_TOTALRow09: NewLEDwatts_reducedRow09: NewLEDequipRow10: NewLEDold_quantityRow10: NewLEDold_wattageRow10: NewLEDold_TOTALRow10: NewLEDnew_fixtureRow10: NewLEDnew_quantityRow10: NewLEDnew_wattageRow10: NewLEDnew_TOTALRow10: NewLEDwatts_reducedRow10: NewLEDequipRow11: NewLEDold_quantityRow11: NewLEDold_wattageRow11: NewLEDold_TOTALRow11: NewLEDnew_fixtureRow11: NewLEDnew_quantityRow11: NewLEDnew_wattageRow11: NewLEDnew_TOTALRow11: NewLEDwatts_reducedRow11: NewLEDequipRow12: NewLEDold_quantityRow12: NewLEDold_wattageRow12: NewLEDold_TOTALRow12: NewLEDnew_fixtureRow12: NewLEDnew_quantityRow12: NewLEDnew_wattageRow12: NewLEDnew_TOTALRow12: NewLEDwatts_reducedRow12: LEDTotalWattsReduced: LEDWattsReducedTotal: LEDWattsReducedTotal2: LEDIllumRow01: LEDAshraeLPDRow01: LEDTotalWattageBaselineRow01: LEDNewFixtureRow01: LEDNewQuantityRow01: LEDNewWattageRow01: LED_TotalNewRow01: LEDDifferenceTotalRow01: LEDIllumRow02: LEDAshraeLPDRow02: LEDTotalWattageBaselineRow02: LEDNewFixtureRow02: LEDNewQuantityRow02: LEDNewWattageRow02: LED_TotalNewRow02: LEDDifferenceTotalRow02: LEDIllumRow03: LEDAshraeLPDRow03: LEDTotalWattageBaselineRow03: LEDNewFixtureRow03: LEDNewQuantityRow03: LEDNewWattageRow03: LED_TotalNewRow03: LEDDifferenceTotalRow03: LEDIllumRow04: LEDAshraeLPDRow04: LEDTotalWattageBaselineRow04: LEDNewFixtureRow04: LEDNewQuantityRow04: LEDNewWattageRow04: LED_TotalNewRow04: LEDDifferenceTotalRow04: LEDIllumRow05: LEDAshraeLPDRow05: LEDTotalWattageBaselineRow05: LEDNewFixtureRow05: LEDNewQuantityRow05: LEDNewWattageRow05: LED_TotalNewRow05: LEDDifferenceTotalRow05: LEDIllumRow06: LEDAshraeLPDRow06: LEDTotalWattageBaselineRow06: LEDNewFixtureRow06: LEDNewQuantityRow06: LEDNewWattageRow06: LED_TotalNewRow06: LEDDifferenceTotalRow06: LEDIllumRow07: LEDAshraeLPDRow07: LEDTotalWattageBaselineRow07: LEDNewFixtureRow07: LEDNewQuantityRow07: LEDNewWattageRow07: LED_TotalNewRow07: LEDDifferenceTotalRow07: LEDIllumRow08: LEDAshraeLPDRow08: LEDTotalWattageBaselineRow08: LEDNewFixtureRow08: LEDNewQuantityRow08: LEDNewWattageRow08: LED_TotalNewRow08: LEDDifferenceTotalRow08: LEDIllumRow09: LEDAshraeLPDRow09: LEDTotalWattageBaselineRow09: LEDNewFixtureRow09: LEDNewQuantityRow09: LEDNewWattageRow09: LED_TotalNewRow09: LEDDifferenceTotalRow09: LED_WattageTotal: LED_Subtotal: LED_Subtotal2: Section1_Subtotal: WCW_typeRow01: WCW_qtyRow01: WCW_wattsRow01: WCW_controlledRow01: WCW_typeRow02: WCW_qtyRow02: WCW_wattsRow02: WCW_controlledRow02: WCW_typeRow03: WCW_qtyRow03: WCW_wattsRow03: WCW_controlledRow03: WCW_typeRow04: WCW_qtyRow04: WCW_wattsRow04: WCW_controlledRow04: WCW_typeRow05: WCW_qtyRow05: WCW_wattsRow05: WCW_controlledRow05: WCW_typeRow06: WCW_qtyRow06: WCW_wattsRow06: WCW_controlledRow06: WCW_typeRow07: WCW_qtyRow07: WCW_wattsRow07: WCW_controlledRow07: WCW_typeRow08: WCW_qtyRow08: WCW_wattsRow08: WCW_controlledRow08: WCW_typeRow09: WCW_qtyRow09: WCW_wattsRow09: WCW_controlledRow09: WCW_typeRow10: WCW_qtyRow10: WCW_wattsRow10: WCW_controlledRow10: WCW_typeRow11: WCW_qtyRow11: WCW_wattsRow11: WCW_controlledRow11: WCW_typeRow12: WCW_qtyRow12: WCW_wattsRow12: WCW_controlledRow12: WCW_typeRow13: WCW_qtyRow13: WCW_wattsRow13: WCW_controlledRow13: WCW_typeRow14: WCW_qtyRow14: WCW_wattsRow14: WCW_controlledRow14: WCW_typeRow15: WCW_qtyRow15: WCW_wattsRow15: WCW_controlledRow15: WCW_typeRow16: WCW_qtyRow16: WCW_wattsRow16: WCW_controlledRow16: WCW_typeRow17: WCW_qtyRow17: WCW_wattsRow17: WCW_controlledRow17: WCW_typeRow18: WCW_qtyRow18: WCW_wattsRow18: WCW_controlledRow18: WCW_typeRow19: WCW_qtyRow19: WCW_wattsRow19: WCW_controlledRow19: WCW_typeRow20: WCW_qtyRow20: WCW_wattsRow20: WCW_controlledRow20: WCW_typeRow21: WCW_qtyRow21: WCW_wattsRow21: WCW_controlledRow21: WCW_typeRow22: WCW_qtyRow22: WCW_wattsRow22: WCW_controlledRow22: WCW_typeRow23: WCW_qtyRow23: WCW_wattsRow23: WCW_controlledRow23: WCW_typeRow24: WCW_qtyRow24: WCW_wattsRow24: WCW_controlledRow24: WCW_typeRow25: WCW_qtyRow25: WCW_wattsRow25: WCW_controlledRow25: WCW_typeRow26: WCW_qtyRow26: WCW_wattsRow26: WCW_controlledRow26: WCW_typeRow27: WCW_qtyRow27: WCW_wattsRow27: WCW_controlledRow27: WCW_typeRow28: WCW_qtyRow28: WCW_wattsRow28: WCW_controlledRow28: WCW_TotalWattsControlled: 18: 0.18WCW_Subtotal: ExistingTypeRow01: ExistingQtyRow01: ExistingWattsRow01: ExistingHoursRow01: ExistingTotalRow01: ExistingTypeRow02: ExistingQtyRow02: ExistingWattsRow02: ExistingHoursRow02: ExistingTotalRow02: ExistingTypeRow03: ExistingQtyRow03: ExistingWattsRow03: ExistingHoursRow03: ExistingTotalRow03: ExistingTypeRow04: ExistingQtyRow04: ExistingWattsRow04: ExistingHoursRow04: ExistingTotalRow04: ExistingTypeRow05: ExistingQtyRow05: ExistingWattsRow05: ExistingHoursRow05: ExistingTotalRow05: ExistingTypeRow06: ExistingQtyRow06: ExistingWattsRow06: ExistingHoursRow06: ExistingTotalRow06: ExistingTypeRow07: ExistingQtyRow07: ExistingWattsRow07: ExistingHoursRow07: ExistingTotalRow07: ExistingTypeRow08: ExistingQtyRow08: ExistingWattsRow08: ExistingHoursRow08: ExistingTotalRow08: ExistingTypeRow09: ExistingQtyRow09: ExistingWattsRow09: ExistingHoursRow09: ExistingTotalRow09: ExistingTypeRow10: ExistingQtyRow10: ExistingWattsRow10: ExistingHoursRow10: ExistingTotalRow10: ExistingTypeRow11: ExistingQtyRow11: ExistingWattsRow11: ExistingHoursRow11: ExistingTotalRow11: ExistingTypeRow12: ExistingQtyRow12: ExistingWattsRow12: ExistingHoursRow12: ExistingTotalRow12: ExistingTotal: ProposedTypeRow01: ProposedQtyRow01: ProposedWattsRow01: ProposedHoursRow01: ProposedTotalRow01: ProposedTypeRow02: ProposedQtyRow02: ProposedWattsRow02: ProposedHoursRow02: ProposedTotalRow02: ProposedTypeRow03: ProposedQtyRow03: ProposedWattsRow03: ProposedHoursRow03: ProposedTotalRow03: ProposedTypeRow04: ProposedQtyRow04: ProposedWattsRow04: ProposedHoursRow04: ProposedTotalRow04: ProposedTypeRow05: ProposedQtyRow05: ProposedWattsRow05: ProposedHoursRow05: ProposedTotalRow05: ProposedTypeRow06: ProposedQtyRow06: ProposedWattsRow06: ProposedHoursRow06: ProposedTotalRow06: ProposedTypeRow07: ProposedQtyRow07: ProposedWattsRow07: ProposedHoursRow07: ProposedTotalRow07: ProposedTypeRow08: ProposedQtyRow08: ProposedWattsRow08: ProposedHoursRow08: ProposedTotalRow08: ProposedTypeRow09: ProposedQtyRow09: ProposedWattsRow09: ProposedHoursRow09: ProposedTotalRow09: ProposedTypeRow10: ProposedQtyRow10: ProposedWattsRow10: ProposedHoursRow10: ProposedTotalRow10: ProposedTypeRow11: ProposedQtyRow11: ProposedWattsRow11: ProposedHoursRow11: ProposedTotalRow11: ProposedTypeRow12: ProposedQtyRow12: ProposedWattsRow12: ProposedHoursRow12: ProposedTotalRow12: ProposedTotal: AnualElecSavingskWh: TotalProjectCost: EstimatedElectricalSavings: PaybackPeriod: AnualElecSavings: NALCTP2: TotalIncentiveRequestedpg14: Company: Check Box20: Check Box19: Check Box18: Check Box17: Check Box16: Check Box15: Check Box14: Check Box13: Check Box12: OtherTextpg8: NALCTP: Section2_Subtotal: AllSubtotalsCombined: Check Box3: Check Box4: Check Box5: Check Box6: Check Box7: Check Box8: Check Box9: Check Box10: Check Box11: OtherTextpg12: