i0522-77 js condair cp3 8pp brochure aw.qxp layout 1 · the condair cp3 electrode boiler steam...
TRANSCRIPT
CONDAIR CP3Electrode boiler steam humidifierReliable and economic steam humidification
Humidification & Evaporative Cooling
BenefitsEconomic steam humidificationReliable operationSimple to install & easy to useProvides pure, sterile steamLong cylinder life
Condair CP3Electrode boiler steam humidifier
Easy to remove electrode plugs
Large, clear LCD display
Easy to operate keypad
Pumped drain increases scale removaland removes waste water rapidly tomaintain control accuracy
Powder coated steel casing as standard(optional stainless steel)
LED operational indicators
Cleanable or disposable steam cylinderwith zinc coated steel elements. Optional soft water cylinders down to 40μS
The Condair CP3 electrode boiler steamhumidifier is an economic yetdependable solution for steamhumidification.
It is easy to install, simple to use andprovides accurate and responsivehumidity control. Innovative featuressuch as water conductivity monitoringand staged electrode use maximise thelifetime of the steam cylinder and
extend the operational periodsbetween service requirements.
When servicing is needed, the CondairCP3’s design makes it easy to drain,remove and replace the disposablesteam cylinder, keeping downtime to aminimum.
Consistent separation of power andwater sections ensures operatingsafety
Hinged control panel provides easy access to electronics
e-LINKS for optional BMS connection
Intelligent Water Quality and Level ControlWater conductivity managementAn electrode boiler humidifier operatesby passing electrical current throughwater to heat it. As the waterevaporates its mineral contentbecomes more concentrated. Thisincreased level of conductivity affectsthe level of steam production. To maintain an accurate output theconcentration of minerals in the water is automatically reduced throughdrainage and replacement with fresh water.
Steel electrodes with “lattice” designThe robust zinc coated steel elementsprovide a long operational life. Theirspecial lattice structure offers thegreatest possible surface area foroptimal transfer of current to thewater.
Staged electrode use to prolong lifeOnly the lower sections of theelectrodes are initially submerged andused to create steam. During operationthe parts of the electrodes submergedin the water become encrusted with
scale. As their conductivity reduces thewater level is automatically raised tosubmerge fresh unused electrodes.
This staged approach to water levelcontrol inside the cylinder prolongs thelife of the electrodes and helpsmaintain their efficiency in providingaccurate humidity control.
The Condair CP3 automatically calculates the conductivity of thewater in the boiling cylinder to provide accurate humidity control.
The steam cylinders are at the heart of Condair CP3 system. During theevaporation process minerals willaccumulate in the steam cylinder that after prolonged use will need to be removed.
Depending on your level of desiredmaintenance, the Condair CP3 offers two options:
Cleanable steam cylinders thatcan be emptied of scale andreused many times
Disposable steam cylinders toreduce maintenance time andkeep the system operating
Cleanable or Disposable Steam Cylinders
Flexible use, reliable performance and easy product selection - these are the strengths ofthe CP3 steam humidifier
Easy-to-use with Optional Connection to BMSControl panelOperating the Condair CP3 is child’splay. The multiple line LCD displayindicates all operating parameters,service requirements and faultdiagnostics. Control input is via theintegrated keypad. The user-friendlysoftware guides you reliably throughthe menu, even if you infrequently usethe unit.
A CP3 card stores all commissioningsettings and allows for easy re-commissioning as well ascommissioning of several units to thesame configuration.
BMS connectivityThe humidifier has an option to beoperated from a BMS and acceptsModbus Standard, BACnet or LonWorks protocols.
Modern building managementbased on integrated technology.Using e-LINKS communication withthe humidification system is simple,quick and clear.
Steam distribution must be tailored tothe requirements of each project.Whether high or low steam outputs,close humidity control or short ductsections - for every application there isan ideal solution.
Condair OptiSorp steam distributionsystem for short evaporation distance
Condair steam distribution lances fornormal humidification requirements
Condair fan unit for direct room steamhumidification
Steam Distribution is the Key to Success
Condair’s comprehensive range of steam distribution systemsfor any project requirement
Condair AGMember of the Walter Meier GroupVerkauf Schweiz, Talstrasse 35-37, 8088 Pfäffikon SZTel: +41 55 416 6111 - [email protected] - www.condair.com
Specifications
1 2
3
4
5
Standard VersionDisposable steam cylinderInternal PI humidity controllerControl panel with touch pad keyboard and5-line LCD displaySelf-diagnostic systemHours run timer
OptionsAll-weather protective housingSteam distribution system CondairOptiSorpPressure equalization to 10,000 Pa
(BACnet / LonWorks) for BMSconnectionHumidity sensors and humidistats
Accesssories1 Steam distribution2 Steam hose3 Condensate hose4 Water filter isolation valve5 Direct room steam
distribution system
Condair CP3 5 8 15 20 33 45 52 60 70
Heating voltage Maximum steam output in kg/h
400 VAC / 3Ph / 50..60 Hz kg/h 5 8 15 20 33 45 52 105 152
230 VAC / 3Ph / 50..60 Hz kg/h 5 8
Dimensions (WxHxD) mm 1x 456x620x280 1x 559x667x350 2x 559x667x350
Control voltage 230 VAC/ 1 Ph / 50..60 Hz
Operating weight (per unit) kg 1x 26 1x 65 2x 65
Conformity CE, GOST, VDE
Condair CP3 80 90 105 120 135 152 160 180
Heating voltage Maximum steam output in kg/h
400 VAC / 3Ph / 50..60 Hz kg/h 80 90 105 120 135 152 160 180
Dimensions (WxHxD) mm 2x 559x667x350 3x 559x667x350 4x 559x667x350
Control voltage 230 VAC/ 1 Ph / 50..60 Hz
Operating weight (per unit) kg 2x 65 3x 65 4x 65
Conformity CE, VDE, GOST