Hydronicterminals

a-LIFE2 0102 - 1004i-LIFE2 0202 - 1004

a-LIFE2 HP 0302 - 1204i-LIFE SLIM 102 - 502

MHD2 30 - 60a-CHD 0606 - 2209i-CHD 0706 - 2209a-HWD2 102 - 902

<<< BACK INDEX<<< BACK INDEX

Page 2: Hydronic terminals

Hydronic terminals

Hydr

onic

term

inal

s

Page 3: Hydronic terminals

Hydronic terminals

a-LIFE2 0102 - 1004<<< BACK INDEX

VersionDLMV version with cabinet, low air intake, vertical installationDLMO version with cabinet, low air intake, horizontal installationDFMV version with cabinet, front air intake, vertical installationDFMO version with cabinet, front air intake, horizontal installationDLIV built-in version, low air intake, vertical installation.DLIO built-in version, low air intake, horizontal installationDFIV built-in version, front air intake, vertical installationDFIO built-in version, front air intake, horizontal installation

Fan-coil for professional applications,with cabinet or built-in version1,50-7,50 kWThe new a-LIFE2 fancoil has been specifically developed to beadapted to every ambient thanks to its modern and minimaldesign which is result of the full experience and Climaveneta’sknow-how on this range of products.Centrifugal fan with 6 speed via auto-transformer. Thanks tothe different versions, with cabinet or buit in, low air intake orfront air intake, vertical or horizontal installation, it results veryeasy to find the perfect solution any time.

FeaturesCentrifugal Fan with double air inlet, to ensure the best performances with thebest acoustic emissions.Coils with aluminium fins and copper pipes.Configurations for 2 and 4 pipe Systems.Left-hand water connections, easy convertible into right-hand, by simplyturning the coil6-speed autotransformer;Air filter on all models.Automatically closing flap to cover and protect electric controls from drippingwater (in conformity with directive 60335-2-40).Auxiliary drain pan with thermal insulation for all Horizontal versions, made ofgalvanized steel.Plastic drain pan for all Vertical versions.

AccessoryHot water coil kitKit Bus Adapter for BMSKit RS485 - interface for Building Management SystemKit Gateway interface for MyHome Bticino SystemInterface SPB KitKit control board to manage 0-10V or 3 points modulating valve unitMain and additional coil valve unit ON/OFF, PWM, 0-10 V, 3 points 2-wayor 3-wayKit LIFE2 BOXPlenum kit with round, straight or 90° air ducts.Air intake grille kit with version coverHorizontal and vertical fan coil auxiliary trayElectric heaters

ControlsPS plug-in/PSW wall mountedFan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valveunit control (winter for 4 pipes installation). Remote water temperature probe.MT plug-in/MTW wall mountedFan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipesinstallation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe.AT plug-in/ATW wall mountedMode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unitcontrol (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and watertemperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS.EK plug-in control /EKW wall mounted controlUser interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of mainand additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch.Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8LIFE fan coil units.Easy control installation thanks to 2 wires connection.iK control with LCD screenInterface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioningmode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timerregulation configurable by the customer.Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit ormodulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) .Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system byClimaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units.Easy control installation thanks to 2 wires connection through HB power boardRemote controlSet-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compactremote control with fine aethetics.

420

Page 4: Hydronic terminals

a-LIFE2 / DLIV-DFIV 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8Total capacity (heating mode) (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating mode (2) m³/h 0,26 0,34 0,49 0,58 0,65 0,76 0,88 0,98 1,06 1,29Pressure drop in heating mode (2) kPa 7,6 10,9 26,0 34,1 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 50 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 59 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5Total capacity (heating mode) (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating mode (2) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,78 0,88 0,93 1,14Pressure drop in heating mode (2) kPa 4,7 8,3 17,7 24,2 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3Total capacity (heating mode) (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating mode (2) m³/h 0,17 0,26 0,35 0,40 0,49 0,52 0,70 0,78 0,81 0,92Pressure drop in heating mode (2) kPa 3,5 6,2 14,1 16,5 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 450 450 650 650 850 850 1050 1050 1250 1250B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 11 11 13 14 19 20 23 24 27 28

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

421

Page 5: Hydronic terminals

a-LIFE2 / DLIO-DFIO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8Total capacity (heating mode) (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating mode (2) m³/h 0,26 0,34 0,49 0,58 0,65 0,76 0,88 0,98 1,06 1,29Pressure drop in heating mode (2) kPa 7,6 10,9 26,0 34,1 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 50 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 59 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5Total capacity (heating mode) (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating mode (2) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,78 0,88 0,93 1,14Pressure drop in heating mode (2) kPa 4,7 8,3 17,7 24,2 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3Total capacity (heating mode) (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating mode (2) m³/h 0,17 0,26 0,35 0,40 0,49 0,52 0,70 0,78 0,81 0,92Pressure drop in heating mode (2) kPa 3,5 6,2 14,1 16,5 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 545 545 745 745 945 945 1145 1145 1345 1345B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 11 12 14 15 20 21 23 25 27 29

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

422

Page 6: Hydronic terminals

a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8Total capacity (heating mode) (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating mode (2) m³/h 0,26 0,34 0,49 0,58 0,65 0,76 0,88 0,98 1,06 1,29Pressure drop in heating mode (2) kPa 7,6 10,9 26,0 34,1 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 50 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 59 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5Total capacity (heating mode) (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating mode (2) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,78 0,88 0,93 1,14Pressure drop in heating mode (2) kPa 4,7 8,3 17,7 24,2 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3Total capacity (heating mode) (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating mode (2) m³/h 0,17 0,26 0,35 0,40 0,49 0,52 0,70 0,78 0,81 0,92Pressure drop in heating mode (2) kPa 3,5 6,2 14,1 16,5 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B (5) mm 233 233 233 233 233 233 233 233 233 233H (5) mm 499 499 499 499 499 499 499 499 499 499Operating weight (5) kg 16 17 20 21 27 28 32 33 37 38

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

423

Page 7: Hydronic terminals

a-LIFE2 / DLIV-DFIV 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8Total capacity (heating mode) (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating mode (2) m³/h 0,11 0,15 0,20 0,24 0,29 0,34 0,38 0,42 0,45 0,55Pressure drop in heating mode (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 15,1 18,3 16,7 24,3Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5Total capacity (heating mode) (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating mode (2) m³/h 0,09 0,13 0,17 0,20 0,24 0,29 0,33 0,38 0,40 0,49Pressure drop in heating mode (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 11,7 14,6 13,1 19,2Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3Total capacity (heating mode) (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,16 0,22 0,23 0,30 0,33 0,35 0,40Pressure drop in heating mode (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 9,5 11,7 10,1 13,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 450 450 650 650 850 850 1050 1050 1250 1250B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 12 12 14 15 21 22 24 25 28 29

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

424

Page 8: Hydronic terminals

a-LIFE2 / DLIO-DFIO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8Total capacity (heating mode) (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating mode (2) m³/h 0,11 0,15 0,20 0,24 0,29 0,34 0,38 0,42 0,45 0,55Pressure drop in heating mode (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 15,1 18,3 16,7 24,3Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5Total capacity (heating mode) (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating mode (2) m³/h 0,09 0,13 0,17 0,20 0,24 0,29 0,33 0,38 0,40 0,49Pressure drop in heating mode (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 11,7 14,6 13,1 19,2Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3Total capacity (heating mode) (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,16 0,22 0,23 0,30 0,33 0,35 0,40Pressure drop in heating mode (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 9,5 11,7 10,1 13,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 545 545 745 745 945 945 1145 1145 1345 1345B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 12 13 15 16 21 22 25 26 29 30

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

425

Page 9: Hydronic terminals

a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8Total capacity (heating mode) (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating mode (2) m³/h 0,11 0,15 0,20 0,24 0,29 0,34 0,38 0,42 0,45 0,55Pressure drop in heating mode (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 15,1 18,3 16,7 24,3Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5Total capacity (heating mode) (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating mode (2) m³/h 0,09 0,13 0,17 0,20 0,24 0,29 0,33 0,38 0,40 0,49Pressure drop in heating mode (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 11,7 14,6 13,1 19,2Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3Total capacity (heating mode) (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,16 0,22 0,23 0,30 0,33 0,35 0,40Pressure drop in heating mode (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 9,5 11,7 10,1 13,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B (5) mm 233 233 233 233 233 233 233 233 233 233H (5) mm 499 499 499 499 499 499 499 499 499 499Operating weight (5) kg 17 18 21 22 29 30 33 35 38 40

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

426

Page 10: Hydronic terminals

427

Page 11: Hydronic terminals

Hydronic terminals

i-LIFE2 0202 - 1004<<< BACK INDEX

VersionDLMV version with cabinet, low air intake, vertical installationDLMO version with cabinet, low air intake, horizontal installationDFMV version with cabinet, front air intake, vertical installationDFMO version with cabinet, front air intake, horizontal installationDLIV built-in version, low air intake, vertical installation.DLIO built-in version, low air intake, horizontal installationDFIV built-in version, front air intake, vertical installationDFIO built-in version, front air intake, horizontal installation

Professional fan-coil with cabinet orbuit-in version, powered by ECBrushless Centrifugal Fan2,00-7,50 kWNew i-LIFE2 fancoil is powered by a modulating speedcentrifugal fan. This new concept of fancoil operates withcontinuous air flow regulation assuring the best comfort and aconcrete energy savings. Thanks to the different versions, withcabinet or buit-in, low air intake or front air intake, vertical orhorizontal installation, it results very easy to find the perfectsolution for any requirement . A dedicated range of controllersallows a user friendly and complete regulation of all thefunctions, and an easy integration in home automation,centralization and Building Management Systems.

FeaturesHigh efficiency EC motor.Modulating speed centrifugal fan and air flow regulation.Energy consumption reduced by more than 50%Coils with aluminium fins and copper pipes.Configurations for 2 and 4 pipe Systems.Left-hand water connections, easy convertible into right-hand, by simplyturning the coilAir filter on all models.Automatically closing flap to cover and protect electric controls from drippingwater (in conformity with directive 60335-2-40).Elegant cover structure that integrates the use of high quality plastic materials,with traditional galvanized and precoated materials.Structure in galvanised steel of high thickness for maximum resistance to rust;Auxiliary drain pan with thermal insulation for all Horizontal versions, made ofgalvanized steel.Plastic drain pan for all Vertical versions.

AccessoryHot water coil kitKit RS485 - interface for Building Management SystemKit control board to manage 0-10V or 3 points modulating valve unitMain coil 2-way/3-way valve unitAdditional coil 2-way/3-way valve unitKit LIFE2 BOXKit Gateway interface for MyHome Bticino SystemAir intake grille kit with version coverStraight and angular (90°) plenum kits for air outletPlenum kit with round, straight or 90° air ducts.Straight and angular (90°) plenum kits for air inletHeating element kitHorizontal and vertical fan coil auxiliary tray

ControlsEK plug-in control /EKW wall mounted controlUser interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of mainand additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch.Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8LIFE fan coil units.Easy control installation thanks to 2 wires connection.iK control with LCD screenInterface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioningmode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timerregulation configurable by the customer.Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit ormodulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) .Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system byClimaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units.Easy control installation thanks to 2 wires connection through HB power boardRemote controlSet-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compactremote control with fine aethetics.AT-EC plug-in control/ATW-EC wall mounted controlUser interface for selection of functioning mode (Off/Summer/Winter/Auto), fan speed (Max,Med,Min,Auto), and temperature set. Control of mainand additional coil valve unit. (summer/winter 2 and 4 pipes installation). Managment of traditional ON/OFF valve unit. Air and water temperatureprobe. Multifuncion digital input configurable by user. Configuration dip switch. The controls can not be connected to BMS system.

428

Page 12: Hydronic terminals

i-LIFE2 / DLIV-DFIV 0202 0402 0602 0802 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 48 54 65 74 732 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 360 590 815 980 1310Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8Total capacity (heating mode) (2) kW 2,82 4,40 6,06 7,74 10,1Water flow in heating mode (2) m³/h 0,34 0,58 0,76 0,98 1,29Pressure drop in heating mode (2) kPa 10,9 34,1 14,6 23,3 40,9Noise Pressure (3) dB(A) 48 51 53 54 56Noise Power (4) dB(A) 57 60 62 63 65MED SPEEDAir flow m³/h 270 380 550 760 920Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3Total capacity (heating mode) (2) kW 2,08 3,07 4,15 6,12 7,13Water flow in heating mode (2) m³/h 0,26 0,40 0,52 0,78 0,92Pressure drop in heating mode (2) kPa 6,2 16,5 7,1 15,0 22,1Noise Pressure (3) dB(A) 39 42 44 45 47Noise Power (4) dB(A) 48 51 53 54 56MIN SPEEDAir flow m³/h 180 238 286 328 542Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0Total capacity (heating mode) (2) kW 1,43 1,97 2,67 3,29 4,32Water flow in heating mode (2) m³/h 0,18 0,25 0,33 0,42 0,56Pressure drop in heating mode (2) kPa 3,0 7,1 3,1 4,7 8,7Noise Pressure (3) dB(A) 31 33 33 34 37Noise Power (4) dB(A) 40 42 42 43 46SIZE AND WEIGHTA (5) mm 450 650 850 1050 1250B (5) mm 215 215 215 215 215H (5) mm 450 450 450 450 450Operating weight (5) kg 11 14 21 24 28

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

429

Page 13: Hydronic terminals

i-LIFE2 / DLIO-DFIO 0202 0402 0602 0802 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 48 54 65 74 732 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 360 590 815 980 1310Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8Total capacity (heating mode) (2) kW 2,82 4,40 6,06 7,74 10,1Water flow in heating mode (2) m³/h 0,34 0,58 0,76 0,98 1,29Pressure drop in heating mode (2) kPa 10,9 34,1 14,6 23,3 40,9Noise Pressure (3) dB(A) 48 51 53 54 56Noise Power (4) dB(A) 57 60 62 63 65MED SPEEDAir flow m³/h 270 380 550 760 920Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3Total capacity (heating mode) (2) kW 2,08 3,07 4,15 6,12 7,13Water flow in heating mode (2) m³/h 0,26 0,40 0,52 0,78 0,92Pressure drop in heating mode (2) kPa 6,2 16,5 7,1 15,0 22,1Noise Pressure (3) dB(A) 39 42 44 45 47Noise Power (4) dB(A) 48 51 53 54 56MIN SPEEDAir flow m³/h 180 238 286 328 542Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0Total capacity (heating mode) (2) kW 1,43 1,97 2,67 3,29 4,32Water flow in heating mode (2) m³/h 0,18 0,25 0,33 0,42 0,56Pressure drop in heating mode (2) kPa 3,0 7,1 3,1 4,7 8,7Noise Pressure (3) dB(A) 31 33 33 34 37Noise Power (4) dB(A) 40 42 42 43 46SIZE AND WEIGHTA (5) mm 545 745 945 1145 1345B (5) mm 215 215 215 215 215H (5) mm 450 450 450 450 450Operating weight (5) kg 12 15 21 25 29

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

430

Page 14: Hydronic terminals

i-LIFE2 / DLMV-DFMV / DLMO-DFMO 0202 0402 0602 0802 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 48 54 65 74 732 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 360 590 815 980 1310Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8Total capacity (heating mode) (2) kW 2,82 4,40 6,06 7,74 10,1Water flow in heating mode (2) m³/h 0,34 0,58 0,76 0,98 1,29Pressure drop in heating mode (2) kPa 10,9 34,1 14,6 23,3 40,9Noise Pressure (3) dB(A) 48 51 53 54 56Noise Power (4) dB(A) 57 60 62 63 65MED SPEEDAir flow m³/h 270 380 550 760 920Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3Total capacity (heating mode) (2) kW 2,08 3,07 4,15 6,12 7,13Water flow in heating mode (2) m³/h 0,26 0,40 0,52 0,78 0,92Pressure drop in heating mode (2) kPa 6,2 16,5 7,1 15,0 22,1Noise Pressure (3) dB(A) 39 42 44 45 47Noise Power (4) dB(A) 48 51 53 54 56MIN SPEEDAir flow m³/h 180 238 286 328 542Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0Total capacity (heating mode) (2) kW 1,43 1,97 2,67 3,29 4,32Water flow in heating mode (2) m³/h 0,18 0,25 0,33 0,42 0,56Pressure drop in heating mode (2) kPa 3,0 7,1 3,1 4,7 8,7Noise Pressure (3) dB(A) 31 33 33 34 37Noise Power (4) dB(A) 40 42 42 43 46SIZE AND WEIGHTA (5) mm 922 1112 1302 1492 1682B (5) mm 233 233 233 233 233H (5) mm 499 499 499 499 499Operating weight (5) kg 14 17 24 28 32

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

431

Page 15: Hydronic terminals

i-LIFE2 / DLIV-DFIV 0204 0404 0604 0804 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 48 54 65 74 734 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 360 590 815 980 1310Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8Total capacity (heating mode) (2) kW 1,67 2,76 3,87 4,82 6,32Water flow in heating mode (2) m³/h 0,15 0,24 0,34 0,42 0,55Pressure drop in heating mode (2) kPa 10,7 18,6 35,6 18,3 24,3Noise Pressure (3) dB(A) 48 51 53 54 56Noise Power (4) dB(A) 57 60 62 63 65MED SPEEDAir flow m³/h 270 380 550 760 920Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3Total capacity (heating mode) (2) kW 1,24 1,88 2,65 3,81 4,55Water flow in heating mode (2) m³/h 0,11 0,16 0,23 0,33 0,40Pressure drop in heating mode (2) kPa 6,1 9,0 17,5 11,7 13,1Noise Pressure (3) dB(A) 39 42 44 45 47Noise Power (4) dB(A) 48 51 53 54 56MIN SPEEDAir flow m³/h 180 238 286 328 542Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0Total capacity (heating mode) (2) kW 0,85 1,20 1,71 2,05 2,75Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,18 0,24Pressure drop in heating mode (2) kPa 3,0 3,8 7,7 3,6 5,1Noise Pressure (3) dB(A) 31 33 33 34 37Noise Power (4) dB(A) 40 42 42 43 46SIZE AND WEIGHTA (5) mm 450 650 850 1050 1250B (5) mm 215 215 215 215 215H (5) mm 450 450 450 450 450Operating weight (5) kg 12 15 22 26 30

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

432

Page 16: Hydronic terminals

i-LIFE2 / DLIO-DFIO 0204 0404 0604 0804 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 48 54 65 74 734 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 360 590 815 980 1310Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8Total capacity (heating mode) (2) kW 1,67 2,76 3,87 4,82 6,32Water flow in heating mode (2) m³/h 0,15 0,24 0,34 0,42 0,55Pressure drop in heating mode (2) kPa 10,7 18,6 35,6 18,3 24,3Noise Pressure (3) dB(A) 48 51 53 54 56Noise Power (4) dB(A) 57 60 62 63 65MED SPEEDAir flow m³/h 270 380 550 760 920Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3Total capacity (heating mode) (2) kW 1,24 1,88 2,65 3,81 4,55Water flow in heating mode (2) m³/h 0,11 0,16 0,23 0,33 0,40Pressure drop in heating mode (2) kPa 6,1 9,0 17,5 11,7 13,1Noise Pressure (3) dB(A) 39 42 44 45 47Noise Power (4) dB(A) 48 51 53 54 56MIN SPEEDAir flow m³/h 180 238 286 328 542Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0Total capacity (heating mode) (2) kW 0,85 1,20 1,71 2,05 2,75Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,18 0,24Pressure drop in heating mode (2) kPa 3,0 3,8 7,7 3,6 5,1Noise Pressure (3) dB(A) 31 33 33 34 37Noise Power (4) dB(A) 40 42 42 43 46SIZE AND WEIGHTA (5) mm 545 745 945 1145 1345B (5) mm 215 215 215 215 215H (5) mm 450 450 450 450 450Operating weight (5) kg 12 16 22 26 30

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

433

Page 17: Hydronic terminals

i-LIFE2 / DLMV-DFMV / DLMO-DFMO 0204 0404 0604 0804 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 48 54 65 74 734 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 360 590 815 980 1310Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8Total capacity (heating mode) (2) kW 1,67 2,76 3,87 4,82 6,32Water flow in heating mode (2) m³/h 0,15 0,24 0,34 0,42 0,55Pressure drop in heating mode (2) kPa 10,7 18,6 35,6 18,3 24,3Noise Pressure (3) dB(A) 48 51 53 54 56Noise Power (4) dB(A) 57 60 62 63 65MED SPEEDAir flow m³/h 270 380 550 760 920Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3Total capacity (heating mode) (2) kW 1,24 1,88 2,65 3,81 4,55Water flow in heating mode (2) m³/h 0,11 0,16 0,23 0,33 0,40Pressure drop in heating mode (2) kPa 6,1 9,0 17,5 11,7 13,1Noise Pressure (3) dB(A) 39 42 44 45 47Noise Power (4) dB(A) 48 51 53 54 56MIN SPEEDAir flow m³/h 180 238 286 328 542Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0Total capacity (heating mode) (2) kW 0,85 1,20 1,71 2,05 2,75Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,18 0,24Pressure drop in heating mode (2) kPa 3,0 3,8 7,7 3,6 5,1Noise Pressure (3) dB(A) 31 33 33 34 37Noise Power (4) dB(A) 40 42 42 43 46SIZE AND WEIGHTA (5) mm 922 1112 1302 1492 1682B (5) mm 233 233 233 233 233H (5) mm 499 499 499 499 499Operating weight (5) kg 15 18 25 29 33

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

434

Page 18: Hydronic terminals

435

Page 19: Hydronic terminals

Hydronic terminals

a-LIFE2 HP 0302 - 1204<<< BACK INDEX

VersionDFIO built-in version, front air intake, horizontal installationDFIV built-in version, front air intake, vertical installationDLIO built-in version, low air intake, horizontal installationDLIV built-in version, low air intake, vertical installation.

High head fan-coil for professionalapplication built-in version2,88-8,60 kWa-LIFE2 HP are professional high-head fan coils byClimaveneta. The enhanced motor and the built-in versionmake these units ideal for ducted systems in tertiary andcommercial sectors.

FeaturesHigh pressure centrifugal fan unit for ducted system;Multi speed directly coupled electric motor;Configurations for 2 and 4 pipe Systems.Structure in hot galvanised steel for maximum resistance to rust;Left-hand water connections, easy convertible into right-hand, by simplyturning the coilAir filter on all models.Auxiliary drain pan with thermal insulation for all Horizontal versions, made ofgalvanized steel.Plastic drain pan for all Vertical versions.

AccessoryHot water coil kitMain coil 2-way/3-way valve unitMain and additional coil valve unit ON/OFF, PWM, 0-10 V, 3 points 2-wayor 3-wayKit control board to manage 0-10V or 3 points modulating valve unitKit RS485 - interface for Building Management SystemKit Bus Adapter for BMSKit Gateway interface for MyHome Bticino SystemInterface SPB KitHeating element kitCondensate drain pumpHorizontal and vertical fan coil auxiliary trayHose kitStraight and angular (90°) plenum kits for air inletPlenum kit with round, straight or 90° air ducts.

ControlsATW wall mountedMode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unitcontrol (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and watertemperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS.MTW wall mountedFan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipesinstallation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe.PSW wall mountedFan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valveunit control (winter for 4 pipes installation). Remote water temperature probe.Remote Control EKWUser interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of mainand additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch.Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8LIFE2 fan coil units.Easy control installation thanks to 2 wires connection.iK control with LCD screenInterface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioningmode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timerregulation configurable by the customer.Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit ormodulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) .Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system byClimaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units.Easy control installation thanks to 2 wires connection through HB power boardRemote controlSet-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compactremote control with fine aethetics.

436

Page 20: Hydronic terminals

a-LIFE2 HP DFIV/DLIV 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 127 127 115 115 196 196 225 225 285 2852 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60Sensible capacity in cooling mode (1) kW 2,39 2,77 2,93 3,53 3,91 4,44 5,14 5,91 6,99 7,32Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9Total capacity (heating mode) (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4Water flow in heating mode (2) m³/h 0,50 0,56 0,64 0,71 0,79 0,89 1,07 1,24 1,38 1,48Pressure drop in heating mode (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68MED SPEEDAir flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10Sensible capacity in cooling mode (1) kW 1,90 2,24 2,31 2,66 2,84 3,74 4,67 5,15 6,46 7,03Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0Total capacity (heating mode) (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8Water flow in heating mode (2) m³/h 0,40 0,46 0,52 0,55 0,61 0,77 0,98 1,07 1,29 1,39Pressure drop in heating mode (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66MIN SPEEDAir flow m³/h 392 435 464 516 584 649 923 1026 1381 1534Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40Sensible capacity in cooling mode (1) kW 1,69 1,82 1,71 2,37 2,49 2,78 3,88 4,42 5,83 6,25Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7Total capacity (heating mode) (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82Water flow in heating mode (2) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27Pressure drop in heating mode (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63SIZE AND WEIGHTA (5) mm 650 650 850 850 1050 1050 1250 1250 1450 1450B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

437

Page 21: Hydronic terminals

a-LIFE2 HP DFIO/DLIO 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 127 127 115 115 196 196 225 225 285 2852 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60Sensible capacity in cooling mode (1) kW 2,39 2,77 2,93 3,53 3,91 4,44 5,14 5,91 6,99 7,32Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9Total capacity (heating mode) (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4Water flow in heating mode (2) m³/h 0,50 0,56 0,64 0,71 0,79 0,89 1,07 1,24 1,38 1,48Pressure drop in heating mode (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68MED SPEEDAir flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10Sensible capacity in cooling mode (1) kW 1,90 2,24 2,31 2,66 2,84 3,74 4,67 5,15 6,46 7,03Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0Total capacity (heating mode) (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8Water flow in heating mode (2) m³/h 0,40 0,46 0,52 0,55 0,61 0,77 0,98 1,07 1,29 1,39Pressure drop in heating mode (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66MIN SPEEDAir flow m³/h 392 435 464 516 584 649 923 1026 1381 1534Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40Sensible capacity in cooling mode (1) kW 1,69 1,82 1,71 2,37 2,49 2,78 3,88 4,42 5,83 6,25Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7Total capacity (heating mode) (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82Water flow in heating mode (2) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27Pressure drop in heating mode (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63SIZE AND WEIGHTA (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

438

Page 22: Hydronic terminals

a-LIFE2 HP DFIV/DLIV 0304 0404 0504 0604 0704 0804 0904 1004 1104 1204ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 127 127 115 115 196 196 225 225 285 2854 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 34,2 43,1 14,2 15,9Total capacity (heating mode) (2) kW 2,34 2,66 3,29 3,64 3,71 4,18 4,96 5,76 6,44 6,88Water flow in heating mode (2) m³/h 0,21 0,23 0,29 0,32 0,33 0,37 0,43 0,50 0,56 0,60Pressure drop in heating mode (2) kPa 13,6 17,3 26,3 31,7 11,1 13,9 15,4 20,4 17,9 20,1Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68MED SPEEDAir flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,9 32,5 12,3 14,0Total capacity (heating mode) (2) kW 1,88 2,19 2,67 2,84 2,87 3,61 4,56 5,00 6,00 6,48Water flow in heating mode (2) m³/h 0,16 0,19 0,23 0,25 0,25 0,32 0,40 0,44 0,53 0,57Pressure drop in heating mode (2) kPa 9,0 12,0 17,8 20,0 6,8 10,5 13,1 15,6 15,7 18,1Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66MIN SPEEDAir flow m³/h 392 435 464 516 584 649 923 1026 1381 1534Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,8 24,3 10,4 11,7Total capacity (heating mode) (2) kW 1,69 1,79 2,00 2,57 2,59 2,81 3,86 4,32 5,52 5,92Water flow in heating mode (2) m³/h 0,15 0,16 0,18 0,23 0,23 0,25 0,34 0,38 0,48 0,52Pressure drop in heating mode (2) kPa 7,3 8,2 10,4 16,6 5,6 6,5 9,6 11,9 13,5 15,4Noise Pressure (3) dB(A) 42 45 34 41 38 41 49 51 54 54Noise Power (4) dB(A) 51 54 43 50 47 50 58 60 63 63SIZE AND WEIGHTA (5) mm 650 650 850 850 1050 1050 1250 1250 1450 1450B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 15 16 21 22 25 26 29 31 32 35

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

439

Page 23: Hydronic terminals

a-LIFE2 HP DFIO/DLIO 0304 0404 0504 0604 0704 0804 0904 1004 1104 1204ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 127 127 115 115 196 196 225 225 285 2854 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 34,2 43,1 14,2 15,9Total capacity (heating mode) (2) kW 2,34 2,66 3,29 3,64 3,71 4,18 4,96 5,76 6,44 6,88Water flow in heating mode (2) m³/h 0,21 0,23 0,29 0,32 0,33 0,37 0,43 0,50 0,56 0,60Pressure drop in heating mode (2) kPa 13,6 17,3 26,3 31,7 11,1 13,9 15,4 20,4 17,9 20,1Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68MED SPEEDAir flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,9 32,5 12,3 14,0Total capacity (heating mode) (2) kW 1,88 2,19 2,67 2,84 2,87 3,61 4,56 5,00 6,00 6,48Water flow in heating mode (2) m³/h 0,16 0,19 0,23 0,25 0,25 0,32 0,40 0,44 0,53 0,57Pressure drop in heating mode (2) kPa 9,0 12,0 17,8 20,0 6,8 10,5 13,1 15,6 15,7 18,1Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66MIN SPEEDAir flow m³/h 392 435 464 516 584 649 923 1026 1381 1534Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,8 24,3 10,4 11,7Total capacity (heating mode) (2) kW 1,69 1,79 2,00 2,57 2,59 2,81 3,86 4,32 5,52 5,92Water flow in heating mode (2) m³/h 0,15 0,16 0,18 0,23 0,23 0,25 0,34 0,38 0,48 0,52Pressure drop in heating mode (2) kPa 7,3 8,2 10,4 16,6 5,6 6,5 9,6 11,9 13,5 15,4Noise Pressure (3) dB(A) 42 45 34 41 38 41 49 51 54 54Noise Power (4) dB(A) 51 54 43 50 47 50 58 60 63 63SIZE AND WEIGHTA (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 15 16 21 22 25 27 29 31 32 36

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

440

Page 24: Hydronic terminals

441

Page 25: Hydronic terminals

Hydronic terminals

i-LIFE SLIM 102 - 502<<< BACK INDEX

VersionDLIU Built-in version for universal installation.DLMV Version with cabinet for vertical installationDLMO Version with cabinet for horizontal installationDLRV Radiant Version with cabinet for vertical installation.

Residential fan-coils with cabinet orconcealed version, with inverter motore tangential fan.0,84-3,86 kWi-LIFE SLIM is the new fan coil Climaveneta , with invertertechnology for heating, cooling and dehumidifying. Its elegantdesign with only 13 cm depth makes i-LIFE Slim the perfectsolution for residential applications. The fan coil is alsoavailable with i-LIFE R-SLIM inverter version with radiantpanel.The brushless motor allows a perfect adaptation to thermalload, without any temperature fluctuations. Tangential fansoperate through continuous air flow modulation, with no speedsteps or relay switching as traditional fan coil units. Highefficiency is guaranteed in any HVAC installation setup, incombination with any low temperature heat generator.

FeaturesDC motor with inverter technology with continuous speed regulation, toensure the best performance with a very low noise level.Elegant design and reduced depth of only 13 cm, for installation in aresidential enviroment.Tangential fan with asymetric blades that ensures the continuous modulationof the air flow for a better comfort and real energy savings.Coil with large frontal area that allows to reach high air flow with very lowpressure drop.Honeycomb polypropylene air filter which can be regenerated by washing orblowing.Elegant cover structure that integrates the use of high quality plastic materials,with traditional galvanized and epoxy powder coated materials.Configuration for 2 pipes systems.

AccessoryDrain Pan for horizontal installationMain coil 2-way/3-way valve unitFitting for air intake in built-in installationTelescopic air flow duct and 90° duct for false ceiling and build ininstallationAlluminium air flow vent for wall mountingAlluminium Air intake gridUVC air sterilisation deviceCasing for build in version - i-LIFE Slim BoxCasing cover panel with frame and front panel gridEurokonus adapterPair of decorative and structural feet

ControlsiKS2 - on board ControlOn-board control for unit with cabinet complete with touch keypad with 8 touch key, LCD display with colored symbols. Modulating fan speed withPID logic, temperature regulation, winter/summer mode, automatic mode for the speed regulation, night mode for a silent operation. Minimumwater probe and solenoid management, it's possible to manage the function even without the water probe.Remote Control iKSW2Remote control for built-in and with cabinet units complete with touch keypad with 8 touch keys, LCD display with colored symbols. Modulatingfan speed with PID logic, temperature regulation, winter/summer mode, automatic mode for the speed regulation, night mode for a silentoperation. Minimum water probe and solenoid valve management. A maximum of 31 fancoils can be connected to the iKSW control for openspace rooms. Each unit must have the iHBS2 powerboard installed. RS485 output for connection in BMS.iHBS2 - On board semplified ControlSimple on board control for buit - in and with cabinet units, to be coupled with remote control iKSW2. iHBS2 control has a LED for thevisualization of the device's operation. All the parameters are set up from iKSW2. It is possible to manage the function even without the waterprobe. The iHBS2 powerboard is able to supply power to IKSW2 control.ATS2 - Control with 4 speed regulationController for units with cabinet. Interface with 8 keys for the temperature selection, winter/summer mode, 4 speed regulation, (Max. Min. Nightand Auto) with display for room temperature vizualization. Minimum water temperature probe and solenoid valve management. It's possible tomanage the function even without the water probe.HBS2 Control - Powerboard cardSemple on board control for built-in units or with cabinet units, to be coupled with ATW Climaveneta remote control or other remote controlswhich manage the regulation of fixed fan speeds. HBS2 has a a LED for the visualization of the devise's operation. All the parameters are set upfrom the remote control. There are 2 versions of this powerboard. Version for ON/OFF signal (HBS2) and version for 0-10V signal (HBS2010)

442

Page 26: Hydronic terminals

i-LIFE SLIM / DLMO - DLMV 102 202 302 402 502ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 18 27 35 35 372 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 162 320 461 576 648Total capacity in cooling mode (1) kW 0,84 1,79 2,69 3,39 3,86Sensible capacity in cooling mode (1) kW 0,63 1,29 1,99 2,69 3,06Max water flow (1) m³/h 0,15 0,31 0,46 0,58 0,66Mad pressure drop (1) kPa 7,4 5,5 22,6 19,1 25,0Total capacity (heating mode) (2) kW 1,12 2,38 3,29 4,19 4,96Water flow in heating mode (2) m³/h 0,15 0,31 0,46 0,58 0,67Pressure drop in heating mode (2) kPa 7,4 5,5 22,1 19,0 25,1Noise Pressure (3) dB(A) 41 42 44 45 46Noise Power (4) dB(A) 50 51 53 54 55MED SPEEDAir flow m³/h 113 252 367 453 494Total capacity in cooling mode (1) kW 0,71 1,57 2,26 2,82 3,12Sensible capacity in cooling mode (1) kW 0,53 1,15 1,75 2,12 2,38Max water flow (1) m³/h 0,12 0,27 0,39 0,49 0,54Mad pressure drop (1) kPa 5,3 4,3 16,3 13,4 15,9Total capacity (heating mode) (2) kW 0,91 2,04 2,76 3,49 4,04Water flow in heating mode (2) m³/h 0,12 0,27 0,39 0,49 0,54Pressure drop in heating mode (2) kPa 5,2 4,3 16,3 13,4 15,9Noise Pressure (3) dB(A) 35 36 36 37 40Noise Power (4) dB(A) 44 45 45 46 49MIN SPEEDAir flow m³/h 55 155 248 370 426Total capacity in cooling mode (1) kW 0,37 1,07 1,47 2,42 2,73Sensible capacity in cooling mode (1) kW 0,27 0,76 1,21 1,82 2,09Max water flow (1) m³/h 0,06 0,18 0,25 0,42 0,47Mad pressure drop (1) kPa 1,4 2,0 7,3 9,9 12,0Total capacity (heating mode) (2) kW 0,39 1,40 1,82 3,00 3,59Water flow in heating mode (2) m³/h 0,06 0,18 0,25 0,42 0,47Pressure drop in heating mode (2) kPa 1,4 2,0 7,3 10,0 12,0Noise Pressure (3) dB(A) 26 27 27 28 30Noise Power (4) dB(A) 35 36 36 37 39SIZE AND WEIGHTA (5) mm 737 937 1137 1337 1537B (5) mm 131 131 131 131 131H (5) mm 579 579 579 579 579Operating weight (5) kg 17 20 23 26 29

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

443

Page 27: Hydronic terminals

i-LIFE SLIM / DLIU 102 202 302 402 502ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 18 27 35 35 372 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 162 320 461 576 648Total capacity in cooling mode (1) kW 0,84 1,79 2,69 3,39 3,86Sensible capacity in cooling mode (1) kW 0,63 1,29 1,99 2,69 3,06Max water flow (1) m³/h 0,15 0,31 0,46 0,58 0,66Mad pressure drop (1) kPa 7,4 5,5 22,6 19,1 25,0Total capacity (heating mode) (2) kW 1,12 2,38 3,29 4,19 4,96Water flow in heating mode (2) m³/h 0,15 0,31 0,46 0,58 0,67Pressure drop in heating mode (2) kPa 7,4 5,5 22,1 19,0 25,1Noise Pressure (3) dB(A) 41 42 44 45 46Noise Power (4) dB(A) 50 51 53 54 55MED SPEEDAir flow m³/h 113 252 367 453 494Total capacity in cooling mode (1) kW 0,71 1,57 2,26 2,82 3,12Sensible capacity in cooling mode (1) kW 0,53 1,15 1,75 2,12 2,38Max water flow (1) m³/h 0,12 0,27 0,39 0,49 0,54Mad pressure drop (1) kPa 5,3 4,3 16,3 13,4 15,9Total capacity (heating mode) (2) kW 0,91 2,04 2,76 3,49 4,04Water flow in heating mode (2) m³/h 0,12 0,27 0,39 0,49 0,54Pressure drop in heating mode (2) kPa 5,2 4,3 16,3 13,4 15,9Noise Pressure (3) dB(A) 35 36 36 37 40Noise Power (4) dB(A) 44 45 45 46 49MIN SPEEDAir flow m³/h 55 155 248 370 426Total capacity in cooling mode (1) kW 0,37 1,07 1,47 2,42 2,73Sensible capacity in cooling mode (1) kW 0,27 0,76 1,21 1,82 2,09Max water flow (1) m³/h 0,06 0,18 0,25 0,42 0,47Mad pressure drop (1) kPa 1,4 2,0 7,3 9,9 12,0Total capacity (heating mode) (2) kW 0,39 1,40 1,82 3,00 3,59Water flow in heating mode (2) m³/h 0,06 0,18 0,25 0,42 0,47Pressure drop in heating mode (2) kPa 1,4 2,0 7,3 10,0 12,0Noise Pressure (3) dB(A) 26 27 27 28 30Noise Power (4) dB(A) 35 36 36 37 39SIZE AND WEIGHTA (5) mm 525 725 925 1125 1325B (5) mm 126 126 126 126 126H (5) mm 576 576 576 576 576Operating weight (5) kg 9 12 15 18 21

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

444

Page 28: Hydronic terminals

i-LIFE SLIM / DLRV 102 202 302 402 502ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 18 27 35 35 372 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 162 320 461 576 648Total capacity in cooling mode (1) kW 0,84 1,79 2,69 3,39 3,86Sensible capacity in cooling mode (1) kW 0,63 1,29 1,99 2,69 3,06Max water flow (1) m³/h 0,15 0,31 0,46 0,58 0,66Mad pressure drop (1) kPa 7,4 5,5 22,6 19,1 25,0Total capacity (heating mode) (2) kW 1,17 2,47 3,50 4,46 5,27Water flow in heating mode (2) m³/h 0,15 0,31 0,46 0,58 0,67Pressure drop in heating mode (2) kPa 7,4 5,4 22,7 19,1 25,2Noise Pressure (3) dB(A) 41 42 44 45 46Noise Power (4) dB(A) 50 51 53 54 55MED SPEEDAir flow m³/h 113 252 367 453 494Total capacity in cooling mode (1) kW 0,71 1,57 2,26 2,82 3,12Sensible capacity in cooling mode (1) kW 0,53 1,15 1,75 2,12 2,38Max water flow (1) m³/h 0,12 0,27 0,39 0,49 0,54Mad pressure drop (1) kPa 5,3 4,3 16,3 13,4 15,9Total capacity (heating mode) (2) kW 0,95 2,12 2,93 3,72 4,29Water flow in heating mode (2) m³/h 0,12 0,27 0,39 0,48 0,54Pressure drop in heating mode (2) kPa 5,4 4,2 16,3 13,1 16,0Noise Pressure (3) dB(A) 35 36 36 37 40Noise Power (4) dB(A) 44 45 45 46 49MIN SPEEDAir flow m³/h 55 155 248 370 426Total capacity in cooling mode (1) kW 0,37 1,07 1,47 2,42 2,73Sensible capacity in cooling mode (1) kW 0,27 0,76 1,21 1,82 2,09Max water flow (1) m³/h 0,06 0,18 0,25 0,42 0,47Mad pressure drop (1) kPa 1,4 2,0 7,3 9,9 12,0Total capacity (heating mode) (2) kW 0,41 1,46 1,94 3,19 3,81Water flow in heating mode (2) m³/h 0,06 0,18 0,25 0,41 0,47Pressure drop in heating mode (2) kPa 1,4 2,1 7,3 9,8 12,1Noise Pressure (3) dB(A) 26 27 27 28 30Noise Power (4) dB(A) 35 36 36 37 39SIZE AND WEIGHTA (5) mm 737 937 1137 1337 1537B (5) mm 131 131 131 131 131H (5) mm 579 579 579 579 579Operating weight (5) kg 17 20 23 26 29

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

445

Page 29: Hydronic terminals

Hydronic terminals

MHD2 30 - 60<<< BACK INDEX

Version- Base Version

High - Wall type Terminal2,15-4,63 kWMHD2 belongs to hi-wall fan-coils of Climaveneta. Thecompactness of this model and its exclusive elegance softenthe visual impact and make it ideal for residential and smalltertiary installations.

FeaturesFan coil in ABS with high mechanical characteristics and resistance to ageing;Adjustable air flow direction;Arrangement for right-left condensate drain pipe;Management of all functions by remote controlRemovable panel;

AccessoryFrame kitSolenoid valve 2 ways 1/2"Solenoid valve kit 3 ways, 4 fits 1/2" with frameCondensate drain pump

ControlsRemote controlSet-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compactremote control with fine aethetics.

446

Page 30: Hydronic terminals

MHD2 30 40 50 60ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 27 28 40 502 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 436 632 780 920Total capacity in cooling mode (1) kW 2,15 2,67 4,00 4,63Sensible capacity in cooling mode (1) kW 1,82 2,13 3,02 3,56Max water flow (1) m³/h 0,37 0,46 0,69 0,80Mad pressure drop (1) kPa 8,9 15,0 38,5 49,9Total capacity (heating mode) (2) kW 2,48 3,20 4,20 5,07Water flow in heating mode (2) m³/h 0,37 0,46 0,69 0,79Pressure drop in heating mode (2) kPa 9,0 14,9 38,5 49,7Noise Pressure (3) dB(A) 34 41 44 49Noise Power (4) dB(A) 45 52 55 60MED SPEEDAir flow m³/h 376 522 691 810Total capacity in cooling mode (1) kW 1,85 2,00 3,00 3,86Sensible capacity in cooling mode (1) kW 1,60 1,62 2,57 2,97Max water flow (1) m³/h 0,32 0,34 0,52 0,66Mad pressure drop (1) kPa 7,6 10,3 25,7 37,9Total capacity (heating mode) (2) kW 2,18 2,40 3,64 4,25Water flow in heating mode (2) m³/h 0,32 0,34 0,52 0,67Pressure drop in heating mode (2) kPa 7,7 10,2 26,0 38,1Noise Pressure (3) dB(A) 31 31 41 45Noise Power (4) dB(A) 42 42 52 56MIN SPEEDAir flow m³/h 334 403 570 697Total capacity in cooling mode (1) kW 1,65 1,78 2,67 3,36Sensible capacity in cooling mode (1) kW 1,42 1,45 2,13 2,58Max water flow (1) m³/h 0,28 0,31 0,46 0,58Mad pressure drop (1) kPa 6,8 8,8 21,9 30,7Total capacity (heating mode) (2) kW 1,91 2,13 3,21 3,67Water flow in heating mode (2) m³/h 0,28 0,30 0,46 0,58Pressure drop in heating mode (2) kPa 6,8 8,7 21,8 31,1Noise Pressure (3) dB(A) 27 28 37 42Noise Power (4) dB(A) 38 39 48 53SIZE AND WEIGHTA (5) mm 845 845 920 920B (5) mm 180 180 200 200H (5) mm 270 270 298 298Operating weight (5) kg 10 10 13 13

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 50/* °C (identical flow rate note 1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

447

Page 31: Hydronic terminals

Hydronic terminals

a-CHD 0606 - 2209<<< BACK INDEX

VersionU - 2T 2 Pipes versionU- 4T 4 Pipes Version

Cassette type terminal3,20-11,5 kWNew a- CHD cassette of Climaveneta, with 5 speeds AC motor,is available in two version: for two pipe installation (unit withsingle coil) and for four pipe installation (unit with double coil).Wide range of sizes and easy installation make them suitablefor all types of installations.

FeaturesFrame in galvanised steel insulated with self-extinguishing closed-cellpolyethylene blanket of suitable thickness, to limit heat loss and noise to aminimum. Airflow grille in ABS built in the cassette, supplied in 1 cartonbox5-speed electric motor inclusive of thermal switch. FanLow-rev radial-blade fan to maximise acoustic comfort.Coil with corrugated aluminium fins and copper pipes, tested with dried air at14 bar.Switchboard with power and control terminal block with screw terminalsSet-up for fresh air intake.Set-up for duct air distribution.Esternal Drain Pan

AccessoryMain coil 2-way/3-way valve unitAdditional coil 2-way/3-way valve unitFresh Air renewal connectionDuct Connection FlangeKit Bus Adapter for BMSKit Gateway interface for MyHome Bticino System

ControlsMTW wall mountedFan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipesinstallation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe.ATW wall mountedMode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unitcontrol (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and watertemperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS.Remote controlSet-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compactremote control with fine aethetics.

448

Page 32: Hydronic terminals

a-CHD 0606 0706 1108 2209ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 60 85 147 3102 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 575 810 1300 2250Total capacity in cooling mode (1) kW 3,20 4,56 6,97 11,3Sensible capacity in cooling mode (1) kW 2,38 3,20 5,01 8,21Max water flow (1) m³/h 0,55 0,79 1,20 1,95Mad pressure drop (1) kPa 10,0 36,4 31,5 47,4Total capacity (heating mode) (2) kW 3,89 5,42 8,23 13,6Water flow in heating mode (2) m³/h 0,56 0,78 1,21 1,94Pressure drop in heating mode (2) kPa 7,4 34,1 27,5 44,2Noise Pressure (3) dB(A) 41 49 56 59Noise Power (4) dB(A) 52 60 67 70MED SPEEDAir flow m³/h 290 617 960 1970Total capacity in cooling mode (1) kW 1,90 3,60 5,47 9,55Sensible capacity in cooling mode (1) kW 1,34 2,50 3,91 7,37Max water flow (1) m³/h 0,33 0,62 0,94 1,64Mad pressure drop (1) kPa 4,1 23,5 20,3 34,5Total capacity (heating mode) (2) kW 2,18 4,30 6,38 12,1Water flow in heating mode (2) m³/h 0,33 0,61 0,94 1,64Pressure drop in heating mode (2) kPa 3,3 17,5 16,5 31,6Noise Pressure (3) dB(A) 34 42 49 54Noise Power (4) dB(A) 45 53 60 65MIN SPEEDAir flow m³/h 200 450 700 1380Total capacity in cooling mode (1) kW 1,38 2,80 4,23 7,50Sensible capacity in cooling mode (1) kW 0,96 1,90 3,03 5,52Max water flow (1) m³/h 0,24 0,48 0,73 1,29Mad pressure drop (1) kPa 2,3 14,8 12,8 21,9Total capacity (heating mode) (2) kW 1,56 3,28 4,90 9,06Water flow in heating mode (2) m³/h 0,24 0,48 0,73 1,29Pressure drop in heating mode (2) kPa 2,0 9,0 10,0 19,8Noise Pressure (3) dB(A) 29 32 37 44Noise Power (4) dB(A) 40 43 48 55SIZE AND WEIGHTA (5) mm 575 575 730 830B (5) mm 575 575 730 830H (5) mm 250 290 290 290Operating weight (5) kg 28 30 36 50

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 50/* °C (identical flow rate note 1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

449

Page 33: Hydronic terminals

a-CHD 0706 1108 2209ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50Max absorbed power W 85 147 3054 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 810 1300 2250Total capacity in cooling mode (1) kW 3,85 5,83 7,95Sensible capacity in cooling mode (1) kW 2,79 4,23 5,85Max water flow (1) m³/h 0,66 1,00 1,37Mad pressure drop (1) kPa 27,2 42,1 40,7Total capacity (heating mode) (2) kW 4,24 4,62 9,82Water flow in heating mode (2) m³/h 0,37 0,41 0,86Pressure drop in heating mode (2) kPa 12,5 14,0 27,3Noise Pressure (3) dB(A) 49 56 59Noise Power (4) dB(A) 60 67 70MED SPEEDAir flow m³/h 617 960 1970Total capacity in cooling mode (1) kW 2,87 4,61 6,83Sensible capacity in cooling mode (1) kW 2,07 3,33 5,00Max water flow (1) m³/h 0,49 0,79 1,18Mad pressure drop (1) kPa 17,0 27,6 30,9Total capacity (heating mode) (2) kW 3,69 3,68 8,90Water flow in heating mode (2) m³/h 0,32 0,32 0,78Pressure drop in heating mode (2) kPa 9,4 10,5 22,0Noise Pressure (3) dB(A) 42 49 54Noise Power (4) dB(A) 53 60 65MIN SPEEDAir flow m³/h 450 700 1380Total capacity in cooling mode (1) kW 2,42 3,60 5,35Sensible capacity in cooling mode (1) kW 1,74 2,58 3,89Max water flow (1) m³/h 0,42 0,62 0,92Mad pressure drop (1) kPa 13,0 17,7 19,9Total capacity (heating mode) (2) kW 3,27 2,90 6,80Water flow in heating mode (2) m³/h 0,29 0,25 0,60Pressure drop in heating mode (2) kPa 7,3 7,8 12,2Noise Pressure (3) dB(A) 32 37 44Noise Power (4) dB(A) 43 48 55SIZE AND WEIGHTA (5) mm 575 730 830B (5) mm 575 730 830H (5) mm 290 290 290Operating weight (5) kg 30 36 50

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

450

Page 34: Hydronic terminals

451

Page 35: Hydronic terminals

Hydronic terminals

i-CHD 0706 - 2209<<< BACK INDEX

VersionU - 2T 2 Pipes versionU4T Version for 4 pipe installations, can be realized with the

cassette i- CHD 2-pipe, via the valve mounting 4FOR2.

Cassette type Terminal with continuousvariation of air flow and cooling power4,56-10,6 kWi-CHD is the new cassette of Climaveneta, with high efficencyEC motor and Centrifugal fans that operates through acontinuous air flow modulation, with low energy consumtion andperfect comfort.i-CHD is supplyed on 2 pipes version. For the 4 Pipesinstallations we reccomend the 2 Pipes i-CHD cassette with4For2 kit valves.

FeaturesHigh efficiency EC motor.Modulating speed centrifugal fan and air flow regulation.Energy consumption reduced by more than 50%Unit coils guarantee high efficiency thermal exchange with low pressure drop.Finned unit coils are made of copper tubes and high exchange surface areaaluminium fins. Coils are always tested for leaks with dried air at 14 bar;Frame in galvanised steel insulated with self-extinguishing closed-cellpolyethylene blanket of suitable thickness, to limit heat loss and noise to aminimum. Airflow grille in ABS built in the cassette, supplied in 1 cartonboxElectrical power and control switchboard, complete with electronic air flowregulator and terminal board for connection to network and available remotecontrols;Availability to have fresh air intake, distribute air flow in four directions and alsoin different room place thanks to air diffuser present on the unit;Condensate auxiliary tray standard supplied;

AccessoryMain coil 2-way/3-way valve unitKit valves 4For2Fresh Air renewal connectionDuct Connection Flangei-HB Power boxKit RS485 - interface for Building Management System

ControlsMTW wall mountedFan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipesinstallation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe.ATW wall mountedMode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unitcontrol (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and watertemperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS.EK plug-in control /EKW wall mounted controlUser interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of mainand additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch.Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8LIFE fan coil units.Easy control installation thanks to 2 wires connection.iK control with LCD screenInterface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioningmode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timerregulation configurable by the customer.Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit ormodulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) .Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system byClimaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units.Easy control installation thanks to 2 wires connection through HB power boardRemote controlSet-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compactremote control with fine aethetics.

452

Page 36: Hydronic terminals

i-CHD 0706 1108 2209ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50Max absorbed power W 40 88 2002 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 810 1300 2100Total capacity in cooling mode (1) kW 4,56 6,97 10,9Sensible capacity in cooling mode (1) kW 3,20 5,01 7,87Max water flow (1) m³/h 0,79 1,20 1,88Mad pressure drop (1) kPa 36,4 31,5 44,3Total capacity (heating mode) (2) kW 5,42 8,23 13,0Water flow in heating mode (2) m³/h 0,78 1,21 1,88Pressure drop in heating mode (2) kPa 34,1 27,5 41,5Noise Pressure (3) dB(A) 49 56 56Noise Power (4) dB(A) 60 67 67MED SPEEDAir flow m³/h 520 820 1380Total capacity in cooling mode (1) kW 3,10 4,82 7,69Sensible capacity in cooling mode (1) kW 2,20 3,43 5,52Max water flow (1) m³/h 0,53 0,83 1,32Mad pressure drop (1) kPa 17,8 16,2 23,0Total capacity (heating mode) (2) kW 3,72 5,61 9,08Water flow in heating mode (2) m³/h 0,53 0,83 1,33Pressure drop in heating mode (2) kPa 11,8 13,1 21,0Noise Pressure (3) dB(A) 38 42 44Noise Power (4) dB(A) 49 53 55MIN SPEEDAir flow m³/h 200 360 820Total capacity in cooling mode (1) kW 1,47 2,44 5,04Sensible capacity in cooling mode (1) kW 1,01 1,71 3,58Max water flow (1) m³/h 0,25 0,42 0,87Mad pressure drop (1) kPa 4,5 4,7 10,4Total capacity (heating mode) (2) kW 1,63 2,78 5,86Water flow in heating mode (2) m³/h 0,25 0,42 0,87Pressure drop in heating mode (2) kPa 1,6 3,3 9,0Noise Pressure (3) dB(A) 29 32 34Noise Power (4) dB(A) 40 43 45SIZE AND WEIGHTA (5) mm 575 730 830B (5) mm 575 730 830H (5) mm 290 290 290Operating weight (5) kg 30 36 50

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 50/* °C (identical flow rate note 1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

453

Page 37: Hydronic terminals

Hydronic terminals

a-HWD2 102 - 902<<< BACK INDEX

VersionDFIO built-in version, front air intake, horizontal installationDFIV built-in version, front air intake, vertical installationDLIO built-in version, low air intake, horizontal installationDLIV built-in version, low air intake, vertical installation.

High head ducted type terminal6,88-24,0 kWa-HWD2 are the new Climaveneta ducted high head hydronicterminals. The possibility of vertical and / or horizontalinstallation, compactness and the wide range of accessories orductwork panels, make these units very flexible in installationand adaptable to any system type. The internal insulation ofa-HWD2 units ensures operation with excellent acousticcomfort.P.S. The picture is refered to the unit with mounted valves andplenum with spigots.

FeaturesDucted Terminal unit for horizontal and vertical installation. Bearing structuremade of thick galvanized steel sheet, resistant to rust, corrosion, chemicalagents. Self-supporting and removable panels provided with holes for ceilingand wall mounting, directly from the main casing. Pre-cuts slots andprearranged holes to configure the unit upon request, to install theaccessories, and to reverse the units even on - site. Discharge Flange onunits.EU2 efficiency flat air filters, which may be easily removed from any side of theunit (bottom, side, top) for periodic cleaning. EU3 undulated air filter section,and EU5 with pocket air filter section.Configurations for 2 and 4 pipe Systems.Highly efficient coil made of cooper pipes and aluminium fins. Standardconnections on the right side; on request connections on the left side.Possibility to reverse the connections on-site. Coils tested at 30 Bar pressure,suitable to work with water at max. 15 Bar pressure. Incorporated additionalcoil, or additional coil section for 4 pipe systems.Incorporated electrical heater, or electrical heater sectionsFan deck including 1, 2 or 3 centrifugal fans with double air inlet plastic bladesdirectly coupled to the electric motor. Extensive diameter of fans for higher airflow and static pressure, with low RPM for better acoustic comfort.Auxiliary drain pan with thermal insulation for all Horizontal versions, made ofgalvanized steel.Plastic drain pan for all Vertical versions.Terminal board IP20 "Mammoth Type" installed outside the unit. Upon requestpossible to supply the Terminal Board inside IP55 electrical box.

AccessoryHot water coil kitHeating element moduleMain and additional coil valve unit ON/OFF, PWM, 0-10 V, 3 points 2-wayor 3-wayDuctable air filter section, flat, undulated, or with pocket bagsPlenum kit with round, straight or 90° air ducts.Section with Air Louver, manual and motorizedExternal/Internal mixing sectionNoise level attenuator section for both air intake and supply outletsSection for humidifierCondensate drain pumpAnti-vibration junctionMammoth Type terminal board kit, with IP55 electrical boxInterface SPB Kit

ControlsATW wall mountedMode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unitcontrol (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and watertemperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS.MTW wall mountedFan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipesinstallation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe.PSW wall mountedFan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valveunit control (winter for 4 pipes installation). Remote water temperature probe.

454

Page 38: Hydronic terminals

a-HWD2 / DLIV-DFIV 102 202 302 402 502 602 702 802 902ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 270 270 270 570 570 570 840 840 8402 PIPES SYSTEM CONFIGURATIONNOMINAL SPEED (ESP = 0)Air flow m³/h 1450 1420 1400 2700 2650 2600 4150 4070 4000Total capacity in cooling mode (1) kW 6,88 7,31 9,22 11,6 12,4 16,4 17,0 20,0 24,0Sensible capacity in cooling mode (1) kW 6,09 6,46 6,80 10,4 11,1 12,0 14,1 16,1 18,1Total capacity (heating mode) (2) kW 8,61 9,13 10,8 14,5 15,5 19,5 22,6 26,6 30,0MAX SPEEDESP External Static Pressure Pa 66 59 59 76 64 61 63 56 56Air flow m³/h 1190 1260 1240 2000 2200 2180 3690 3660 3640Total capacity in cooling mode (1) kW 6,00 6,70 8,45 9,36 10,8 14,4 15,4 18,2 21,9Sensible capacity in cooling mode (1) kW 5,09 5,87 6,17 8,12 9,53 10,4 12,6 14,5 16,4Max water flow (1) m³/h 1,03 1,15 1,45 1,61 1,86 2,48 2,65 3,14 3,77Mad pressure drop (1) kPa 29,1 32,9 33,9 20,1 25,1 27,8 32,2 33,2 35,2Total capacity (heating mode) (2) kW 7,43 8,36 9,81 11,6 13,5 17,0 20,4 24,2 27,3Water flow in heating mode (2) m³/h 1,03 1,15 1,46 1,61 1,86 2,50 2,64 3,14 3,76Pressure drop in heating mode (2) kPa 29,2 32,7 34,1 20,1 25,0 28,2 32,1 33,1 35,0Sound Pressure on inlet side Lp (IR) (3) dB(A) 50 51 52 53 54 55 54 54 55Sound Power on inlet side Lw (IR) (4) dB(A) 61 62 63 64 65 66 65 65 66Sound Pressure on outlet side Lp (OD) (3) dB(A) 49 50 50 49 50 51 51 51 52Sound Power on outlet side Lw (OD) (4) dB(A) 60 61 61 60 61 62 62 62 63MED SPEEDESP External Static Pressure Pa 50 50 50 50 50 50 50 50 50Air flow m³/h 1040 1160 1145 1620 1980 1960 3220 3380 3330Total capacity in cooling mode (1) kW 5,66 6,35 7,96 8,17 10,0 13,4 14,2 17,5 21,0Sensible capacity in cooling mode (1) kW 4,74 5,38 5,78 6,94 8,69 9,57 11,5 13,9 15,6Max water flow (1) m³/h 0,97 1,09 1,37 1,41 1,73 2,30 2,44 3,01 3,61Mad pressure drop (1) kPa 25,9 29,5 30,1 15,2 21,5 24,0 27,2 30,5 32,2Total capacity (heating mode) (2) kW 6,95 7,87 9,22 10,0 12,4 15,8 18,5 23,0 26,0Water flow in heating mode (2) m³/h 0,97 1,10 1,37 1,40 1,73 2,31 2,46 2,98 3,62Pressure drop in heating mode (2) kPa 25,5 29,7 30,1 15,0 21,6 24,1 27,7 29,9 32,4Sound Pressure on inlet side Lp (IR) (3) dB(A) 47 49 50 49 51 52 51 53 54Sound Power on inlet side Lw (IR) (4) dB(A) 58 60 61 60 62 63 62 64 65Sound Pressure on outlet side Lp (OD) (3) dB(A) 46 47 48 46 47 48 48 50 51Sound Power on outlet side Lw (OD) (4) dB(A) 57 58 59 57 58 59 59 61 62MIN SPEEDESP External Static Pressure Pa 24 26 29 18 20 21 27 35 36Air flow m³/h 720 840 835 960 1280 1270 2400 2830 2800Total capacity in cooling mode (1) kW 4,36 5,25 6,54 5,52 7,34 9,82 11,4 15,3 18,6Sensible capacity in cooling mode (1) kW 3,57 4,35 4,65 4,49 6,11 6,83 9,05 12,0 13,6Max water flow (1) m³/h 0,75 0,90 1,13 0,95 1,26 1,69 1,96 2,64 3,19Mad pressure drop (1) kPa 15,3 20,1 20,2 6,9 11,4 12,8 17,6 23,3 25,2Total capacity (heating mode) (2) kW 5,27 6,39 7,44 6,67 8,94 11,3 14,6 19,9 22,6Water flow in heating mode (2) m³/h 0,75 0,90 1,12 0,95 1,26 1,70 1,94 2,64 3,19Pressure drop in heating mode (2) kPa 15,4 20,0 20,0 7,0 11,4 13,0 17,2 23,3 25,1Sound Pressure on inlet side Lp (IR) (3) dB(A) 37 42 44 38 43 45 39 47 48Sound Power on inlet side Lw (IR) (4) dB(A) 48 53 55 49 54 56 50 58 59Sound Pressure on outlet side Lp (OD) (3) dB(A) 36 40 41 33 37 41 35 43 44Sound Power on outlet side Lw (OD) (4) dB(A) 47 51 52 44 48 52 46 54 55SIZE AND WEIGHTA (5) mm 880 880 880 1280 1280 1280 1680 1680 1680B (5) mm 630 630 630 630 630 630 630 630 630H (5) mm 275 275 275 275 275 275 275 275 275Operating weight (5) kg 37 38 40 52 54 57 68 70 73

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

455

Page 39: Hydronic terminals

a-HWD2 / DLIO-DFIO 102 202 302 402 502 602 702 802 902ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 270 270 270 570 570 570 840 840 8402 PIPES SYSTEM CONFIGURATIONNOMINAL SPEED (ESP = 0)Air flow m³/h 1450 1420 1400 2700 2650 2600 4150 4070 4000Total capacity in cooling mode (1) kW 6,88 7,31 9,22 11,6 12,4 16,4 17,0 20,0 24,0Sensible capacity in cooling mode (1) kW 6,09 6,46 6,80 10,4 11,1 12,0 14,1 16,1 18,1Total capacity (heating mode) (2) kW 8,61 9,13 10,8 14,5 15,5 19,5 22,6 26,6 30,0MAX SPEEDESP External Static Pressure Pa 66 59 59 76 64 61 63 56 56Air flow m³/h 1190 1260 1240 2000 2200 2180 3690 3660 3640Total capacity in cooling mode (1) kW 6,00 6,70 8,45 9,36 10,8 14,4 15,4 18,2 21,9Sensible capacity in cooling mode (1) kW 5,09 5,87 6,17 8,12 9,53 10,4 12,6 14,5 16,4Max water flow (1) m³/h 1,03 1,15 1,45 1,61 1,86 2,48 2,65 3,14 3,77Mad pressure drop (1) kPa 29,1 32,9 33,9 20,1 25,1 27,8 32,2 33,2 35,2Total capacity (heating mode) (2) kW 7,43 8,36 9,81 11,6 13,5 17,0 20,4 24,2 27,3Water flow in heating mode (2) m³/h 1,03 1,15 1,46 1,61 1,86 2,50 2,64 3,14 3,76Pressure drop in heating mode (2) kPa 29,2 32,7 34,1 20,1 25,0 28,2 32,1 33,1 35,0Sound Pressure on inlet side Lp (IR) (3) dB(A) 50 51 52 53 54 55 54 54 55Sound Power on inlet side Lw (IR) (4) dB(A) 61 62 63 64 65 66 65 65 66Sound Pressure on outlet side Lp (OD) (3) dB(A) 49 50 50 49 50 51 51 51 52Sound Power on outlet side Lw (OD) (4) dB(A) 60 61 61 60 61 62 62 62 63MED SPEEDESP External Static Pressure Pa 50 50 50 50 50 50 50 50 50Air flow m³/h 1040 1160 1145 1620 1980 1960 3220 3380 3330Total capacity in cooling mode (1) kW 5,66 6,35 7,96 8,17 10,0 13,4 14,2 17,5 21,0Sensible capacity in cooling mode (1) kW 4,74 5,38 5,78 6,94 8,69 9,57 11,5 13,9 15,6Max water flow (1) m³/h 0,97 1,09 1,37 1,41 1,73 2,30 2,44 3,01 3,61Mad pressure drop (1) kPa 25,9 29,5 30,1 15,2 21,5 24,0 27,2 30,5 32,2Total capacity (heating mode) (2) kW 6,95 7,87 9,22 10,0 12,4 15,8 18,5 23,0 26,0Water flow in heating mode (2) m³/h 0,97 1,10 1,37 1,40 1,73 2,31 2,46 2,98 3,62Pressure drop in heating mode (2) kPa 25,5 29,7 30,1 15,0 21,6 24,1 27,7 29,9 32,4Sound Pressure on inlet side Lp (IR) (3) dB(A) 47 49 50 49 51 52 51 53 54Sound Power on inlet side Lw (IR) (4) dB(A) 58 60 61 60 62 63 62 64 65Sound Pressure on outlet side Lp (OD) (3) dB(A) 46 47 48 46 47 48 48 50 51Sound Power on outlet side Lw (OD) (4) dB(A) 57 58 59 57 58 59 59 61 62MIN SPEEDESP External Static Pressure Pa 24 26 29 18 20 21 27 35 36Air flow m³/h 720 840 835 960 1280 1270 2400 2830 2800Total capacity in cooling mode (1) kW 4,36 5,25 6,54 5,52 7,34 9,82 11,4 15,3 18,6Sensible capacity in cooling mode (1) kW 3,57 4,35 4,65 4,49 6,11 6,83 9,05 12,0 13,6Max water flow (1) m³/h 0,75 0,90 1,13 0,95 1,26 1,69 1,96 2,64 3,19Mad pressure drop (1) kPa 15,3 20,1 20,2 6,9 11,4 12,8 17,6 23,3 25,2Total capacity (heating mode) (2) kW 5,27 6,39 7,44 6,67 8,94 11,3 14,6 19,9 22,6Water flow in heating mode (2) m³/h 0,75 0,90 1,12 0,95 1,26 1,70 1,94 2,64 3,19Pressure drop in heating mode (2) kPa 15,4 20,0 20,0 7,0 11,4 13,0 17,2 23,3 25,1Sound Pressure on inlet side Lp (IR) (3) dB(A) 37 42 44 38 43 45 39 47 48Sound Power on inlet side Lw (IR) (4) dB(A) 48 53 55 49 54 56 50 58 59Sound Pressure on outlet side Lp (OD) (3) dB(A) 36 40 41 33 37 41 35 43 44Sound Power on outlet side Lw (OD) (4) dB(A) 47 51 52 44 48 52 46 54 55SIZE AND WEIGHTA (5) mm 880 880 880 1280 1280 1280 1680 1680 1680B (5) mm 605 605 605 605 605 605 605 605 605H (5) mm 275 275 275 275 275 275 275 275 275Operating weight (5) kg 37 38 40 52 54 57 68 70 73

Notes:1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1).3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

456

Page 40: Hydronic terminals

a-HWD2 / DLIV-DFIV 104 204 404 504 704 804ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 270 270 570 570 840 8404 PIPES SYSTEM CONFIGURATIONNOMINAL SPEED (ESP = 0)Air flow m³/h 1410 1380 2620 2570 4030 3950Total capacity in cooling mode (1) kW 6,74 7,15 11,4 12,1 16,6 19,6Sensible capacity in cooling mode (1) kW 5,94 6,31 10,2 10,8 13,8 15,7Total capacity (heating mode) (2) kW 6,87 6,87 12,0 11,6 17,9 17,7MAX SPEEDESP External Static Pressure Pa 66 59 76 64 63 56Air flow m³/h 1150 1220 1940 2130 3620 3610Total capacity in cooling mode (1) kW 5,87 6,56 9,15 10,6 15,2 18,1Sensible capacity in cooling mode (1) kW 4,96 5,73 7,92 9,30 12,5 14,4Max water flow (1) m³/h 1,01 1,13 1,58 1,82 2,61 3,11Mad pressure drop (1) kPa 27,8 31,5 19,2 24,0 31,3 32,5Total capacity (heating mode) (2) kW 5,89 6,40 9,53 10,6 16,3 16,3Water flow in heating mode (2) m³/h 0,52 0,56 0,84 0,93 1,42 1,42Pressure drop in heating mode (2) kPa 13,5 15,8 15,6 19,0 42,9 42,9Sound Pressure on inlet side Lp (IR) (3) dB(A) 50 51 53 54 54 54Sound Power on inlet side Lw (IR) (4) dB(A) 61 62 64 65 65 65Sound Pressure on outlet side Lp (OD) (3) dB(A) 49 50 49 50 51 0Sound Power on outlet side Lw (OD) (4) dB(A) 60 61 60 61 62 0MED SPEEDESP External Static Pressure Pa 50 50 50 50 50 50Air flow m³/h 1010 1130 1570 1920 3130 3280Total capacity in cooling mode (1) kW 5,53 6,21 7,99 9,80 13,8 17,1Sensible capacity in cooling mode (1) kW 4,63 5,25 6,77 8,48 11,3 13,5Max water flow (1) m³/h 0,95 1,07 1,38 1,69 2,38 2,95Mad pressure drop (1) kPa 24,7 28,2 14,6 20,6 26,0 29,2Total capacity (heating mode) (2) kW 5,31 6,00 8,13 9,64 14,8 15,4Water flow in heating mode (2) m³/h 0,47 0,53 0,71 0,85 1,29 1,35Pressure drop in heating mode (2) kPa 11,1 14,0 11,5 15,9 35,9 38,6Sound Pressure on inlet side Lp (IR) (3) dB(A) 47 49 49 51 51 53Sound Power on inlet side Lw (IR) (4) dB(A) 58 60 60 62 62 64Sound Pressure on outlet side Lp (OD) (3) dB(A) 46 47 46 47 48 0Sound Power on outlet side Lw (OD) (4) dB(A) 57 58 57 58 59 0MIN SPEEDESP External Static Pressure Pa 24 26 18 20 27 35Air flow m³/h 700 810 930 1240 2330 2750Total capacity in cooling mode (1) kW 4,27 5,13 5,40 7,18 11,1 15,0Sensible capacity in cooling mode (1) kW 3,48 4,25 4,38 5,96 8,83 11,7Max water flow (1) m³/h 0,74 0,88 0,93 1,24 1,92 2,58Mad pressure drop (1) kPa 14,6 19,2 6,6 10,9 16,8 22,3Total capacity (heating mode) (2) kW 4,05 4,71 5,48 6,85 11,8 13,4Water flow in heating mode (2) m³/h 0,36 0,41 0,48 0,60 1,03 1,17Pressure drop in heating mode (2) kPa 6,7 8,9 5,4 8,3 23,5 29,8Sound Pressure on inlet side Lp (IR) (3) dB(A) 37 42 38 43 39 47Sound Power on inlet side Lw (IR) (4) dB(A) 48 53 49 54 50 58Sound Pressure on outlet side Lp (OD) (3) dB(A) 36 40 33 37 35 0Sound Power on outlet side Lw (OD) (4) dB(A) 47 51 44 48 46 0SIZE AND WEIGHTA (5) mm 880 880 1280 1280 1680 1680B (5) mm 630 630 630 630 630 630H (5) mm 275 275 275 275 275 275Operating weight (5) kg 39 40 55 57 72 74

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

457

Page 41: Hydronic terminals

a-HWD2 / DLIO-DFIO 104 204 404 504 704 804ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbed power W 270 270 570 570 840 8404 PIPES SYSTEM CONFIGURATIONNOMINAL SPEED (ESP = 0)Air flow m³/h 1410 1380 2620 2570 4030 3950Total capacity in cooling mode (1) kW 6,74 7,15 11,4 12,1 16,6 19,6Sensible capacity in cooling mode (1) kW 5,94 6,31 10,2 10,8 13,8 15,7Total capacity (heating mode) (2) kW 6,87 6,87 12,0 11,6 17,9 17,7MAX SPEEDESP External Static Pressure Pa 66 59 76 64 63 56Air flow m³/h 1150 1220 1940 2130 3620 3610Total capacity in cooling mode (1) kW 5,87 6,56 9,15 10,6 15,2 18,1Sensible capacity in cooling mode (1) kW 4,96 5,73 7,92 9,30 12,5 14,4Max water flow (1) m³/h 1,01 1,13 1,58 1,82 2,61 3,11Mad pressure drop (1) kPa 27,8 31,5 19,2 24,0 31,3 32,5Total capacity (heating mode) (2) kW 5,89 6,40 9,53 10,6 16,3 16,3Water flow in heating mode (2) m³/h 0,52 0,56 0,84 0,93 1,42 1,42Pressure drop in heating mode (2) kPa 13,5 15,8 15,6 19,0 42,9 42,9Sound Pressure on inlet side Lp (IR) (3) dB(A) 50 51 53 54 54 54Sound Power on inlet side Lw (IR) (4) dB(A) 61 62 64 65 65 65Sound Pressure on outlet side Lp (OD) (3) dB(A) 49 50 49 50 51 0Sound Power on outlet side Lw (OD) (4) dB(A) 60 61 60 61 62 0MED SPEEDESP External Static Pressure Pa 50 50 50 50 50 50Air flow m³/h 1010 1130 1570 1920 3130 3280Total capacity in cooling mode (1) kW 5,53 6,21 7,99 9,80 13,8 17,1Sensible capacity in cooling mode (1) kW 4,63 5,25 6,77 8,48 11,3 13,5Max water flow (1) m³/h 0,95 1,07 1,38 1,69 2,38 2,95Mad pressure drop (1) kPa 24,7 28,2 14,6 20,6 26,0 29,2Total capacity (heating mode) (2) kW 5,31 6,00 8,13 9,64 14,8 15,4Water flow in heating mode (2) m³/h 0,47 0,53 0,71 0,85 1,29 1,35Pressure drop in heating mode (2) kPa 11,1 14,0 11,5 15,9 35,9 38,6Sound Pressure on inlet side Lp (IR) (3) dB(A) 47 49 49 51 51 53Sound Power on inlet side Lw (IR) (4) dB(A) 58 60 60 62 62 64Sound Pressure on outlet side Lp (OD) (3) dB(A) 46 47 46 47 48 0Sound Power on outlet side Lw (OD) (4) dB(A) 57 58 57 58 59 0MIN SPEEDESP External Static Pressure Pa 24 26 18 20 27 35Air flow m³/h 700 810 930 1240 2330 2750Total capacity in cooling mode (1) kW 4,27 5,13 5,40 7,18 11,1 15,0Sensible capacity in cooling mode (1) kW 3,48 4,25 4,38 5,96 8,83 11,7Max water flow (1) m³/h 0,74 0,88 0,93 1,24 1,92 2,58Mad pressure drop (1) kPa 14,6 19,2 6,6 10,9 16,8 22,3Total capacity (heating mode) (2) kW 4,05 4,71 5,48 6,85 11,8 13,4Water flow in heating mode (2) m³/h 0,36 0,41 0,48 0,60 1,03 1,17Pressure drop in heating mode (2) kPa 6,7 8,9 5,4 8,3 23,5 29,8Sound Pressure on inlet side Lp (IR) (3) dB(A) 37 42 38 43 39 47Sound Power on inlet side Lw (IR) (4) dB(A) 48 53 49 54 50 58Sound Pressure on outlet side Lp (OD) (3) dB(A) 36 40 33 37 35 0Sound Power on outlet side Lw (OD) (4) dB(A) 47 51 44 48 46 0SIZE AND WEIGHTA (5) mm 880 880 1280 1280 1680 1680B (5) mm 605 605 605 605 605 605H (5) mm 275 275 275 275 275 275Operating weight (5) kg 39 40 55 57 72 74

Notes:1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C.2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C.3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

458

Page 42: Hydronic terminals
Page 43: Hydronic terminals

Climaveneta S.p.A.

Via Sarson 57/c36061 Bassano del Grappa (VI)ItalyTel +39 0424 509 500Fax +39 0424 509 [email protected]

For more information:

www.climaveneta.com

Subsidiaries

France

www.climaveneta.fr

Spain

www.climaveneta.es

Poland

www.climaveneta.pl

Germany

www.climaveneta.de

Great Britain

www.climaveneta.co.uk

Russia

ru.climaveneta.com

China

www.climaveneta.com.cn

India

www.climaveneta.in

Middle East

ae.climaveneta.com

Southeast Asia

www.climaveneta.com

Hong Kong

www.climaveneta.com