a-LIFE2 0102 - 1004 <<< BACK INDEX
Version DLMV version with cabinet, low air intake, vertical installation DLMO version with cabinet, low air intake, horizontal installation DFMV version with cabinet, front air intake, vertical installation DFMO version with cabinet, front air intake, horizontal installation DLIV built-in version, low air intake, vertical installation. DLIO built-in version, low air intake, horizontal installation DFIV built-in version, front air intake, vertical installation DFIO built-in version, front air intake, horizontal installation
Fan-coil for professional applications, with cabinet or built-in version 1,50-7,50 kW The new a-LIFE2 fancoil has been specifically developed to be adapted to every ambient thanks to its modern and minimal design which is result of the full experience and Climaveneta’s know-how on this range of products. Centrifugal fan with 6 speed via auto-transformer. Thanks to the different versions, with cabinet or buit in, low air intake or front air intake, vertical or horizontal installation, it results very easy to find the perfect solution any time.
Features Centrifugal Fan with double air inlet, to ensure the best performances with the best acoustic emissions. Coils with aluminium fins and copper pipes. Configurations for 2 and 4 pipe Systems. Left-hand water connections, easy convertible into right-hand, by simply turning the coil 6-speed autotransformer; Air filter on all models. Automatically closing flap to cover and protect electric controls from dripping water (in conformity with directive 60335-2-40). Auxiliary drain pan with thermal insulation for all Horizontal versions, made of galvanized steel. Plastic drain pan for all Vertical versions.
Accessory Hot water coil kit Kit Bus Adapter for BMS Kit RS485 - interface for Building Management System Kit Gateway interface for MyHome Bticino System Interface SPB Kit Kit control board to manage 0-10V or 3 points modulating valve unit Main and additional coil valve unit ON/OFF, PWM, 0-10 V, 3 points 2-way or 3-way Kit LIFE2 BOX Plenum kit with round, straight or 90° air ducts. Air intake grille kit with version cover Horizontal and vertical fan coil auxiliary tray Electric heaters
Controls PS plug-in/PSW wall mounted Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe. MT plug-in/MTW wall mounted Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe. AT plug-in/ATW wall mounted Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation. Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS. EK plug-in control /EKW wall mounted control User interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of main and additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch. Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE fan coil units. Easy control installation thanks to 2 wires connection. iK control with LCD screen Interface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timer regulation configurable by the customer. Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) . Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units. Easy control installation thanks to 2 wires connection through HB power board Remote control Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compact remote control with fine aethetics.
420
a-LIFE2 / DLIV-DFIV 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 55 55 85 85 75 75 145 145 175 175 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 300 360 520 590 660 815 890 980 1140 1310 Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50 Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81 Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29 Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8 Total capacity (heating mode) (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1 Water flow in heating mode (2) m³/h 0,26 0,34 0,49 0,58 0,65 0,76 0,88 0,98 1,06 1,29 Pressure drop in heating mode (2) kPa 7,6 10,9 26,0 34,1 10,7 14,6 20,3 23,3 29,1 40,9 Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 50 55 Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 59 64 MED SPEED Air flow m³/h 210 290 410 500 560 670 780 910 1010 1180 Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62 Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16 Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14 Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5 Total capacity (heating mode) (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89 Water flow in heating mode (2) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,78 0,88 0,93 1,14 Pressure drop in heating mode (2) kPa 4,7 8,3 17,7 24,2 7,2 10,9 16,2 18,8 22,8 32,5 Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51 Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60 MIN SPEED Air flow m³/h 180 270 350 380 500 550 640 760 790 920 Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40 Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14 Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93 Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3 Total capacity (heating mode) (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13 Water flow in heating mode (2) m³/h 0,17 0,26 0,35 0,40 0,49 0,52 0,70 0,78 0,81 0,92 Pressure drop in heating mode (2) kPa 3,5 6,2 14,1 16,5 6,2 7,1 13,3 15,0 17,9 22,1 Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45 Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54 SIZE AND WEIGHT A (5) mm 450 450 650 650 850 850 1050 1050 1250 1250 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 11 11 13 14 19 20 23 24 27 28
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
421
a-LIFE2 / DLIO-DFIO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 55 55 85 85 75 75 145 145 175 175 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 300 360 520 590 660 815 890 980 1140 1310 Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50 Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81 Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29 Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8 Total capacity (heating mode) (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1 Water flow in heating mode (2) m³/h 0,26 0,34 0,49 0,58 0,65 0,76 0,88 0,98 1,06 1,29 Pressure drop in heating mode (2) kPa 7,6 10,9 26,0 34,1 10,7 14,6 20,3 23,3 29,1 40,9 Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 50 55 Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 59 64 MED SPEED Air flow m³/h 210 290 410 500 560 670 780 910 1010 1180 Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62 Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16 Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14 Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5 Total capacity (heating mode) (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89 Water flow in heating mode (2) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,78 0,88 0,93 1,14 Pressure drop in heating mode (2) kPa 4,7 8,3 17,7 24,2 7,2 10,9 16,2 18,8 22,8 32,5 Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51 Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60 MIN SPEED Air flow m³/h 180 270 350 380 500 550 640 760 790 920 Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40 Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14 Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93 Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3 Total capacity (heating mode) (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13 Water flow in heating mode (2) m³/h 0,17 0,26 0,35 0,40 0,49 0,52 0,70 0,78 0,81 0,92 Pressure drop in heating mode (2) kPa 3,5 6,2 14,1 16,5 6,2 7,1 13,3 15,0 17,9 22,1 Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45 Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54 SIZE AND WEIGHT A (5) mm 545 545 745 745 945 945 1145 1145 1345 1345 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 11 12 14 15 20 21 23 25 27 29
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
422
a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 55 55 85 85 75 75 145 145 175 175 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 300 360 520 590 660 815 890 980 1140 1310 Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50 Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81 Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29 Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8 Total capacity (heating mode) (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1 Water flow in heating mode (2) m³/h 0,26 0,34 0,49 0,58 0,65 0,76 0,88 0,98 1,06 1,29 Pressure drop in heating mode (2) kPa 7,6 10,9 26,0 34,1 10,7 14,6 20,3 23,3 29,1 40,9 Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 50 55 Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 59 64 MED SPEED Air flow m³/h 210 290 410 500 560 670 780 910 1010 1180 Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62 Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16 Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14 Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5 Total capacity (heating mode) (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89 Water flow in heating mode (2) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,78 0,88 0,93 1,14 Pressure drop in heating mode (2) kPa 4,7 8,3 17,7 24,2 7,2 10,9 16,2 18,8 22,8 32,5 Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51 Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60 MIN SPEED Air flow m³/h 180 270 350 380 500 550 640 760 790 920 Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40 Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14 Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93 Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3 Total capacity (heating mode) (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13 Water flow in heating mode (2) m³/h 0,17 0,26 0,35 0,40 0,49 0,52 0,70 0,78 0,81 0,92 Pressure drop in heating mode (2) kPa 3,5 6,2 14,1 16,5 6,2 7,1 13,3 15,0 17,9 22,1 Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45 Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54 SIZE AND WEIGHT A (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682 B (5) mm 233 233 233 233 233 233 233 233 233 233 H (5) mm 499 499 499 499 499 499 499 499 499 499 Operating weight (5) kg 16 17 20 21 27 28 32 33 37 38
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
423
a-LIFE2 / DLIV-DFIV 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 55 55 85 85 75 75 145 145 175 175 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 300 360 520 590 660 815 890 980 1140 1310 Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50 Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81 Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29 Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8 Total capacity (heating mode) (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32 Water flow in heating mode (2) m³/h 0,11 0,15 0,20 0,24 0,29 0,34 0,38 0,42 0,45 0,55 Pressure drop in heating mode (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 15,1 18,3 16,7 24,3 Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55 Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64 MED SPEED Air flow m³/h 210 290 410 500 560 670 780 910 1010 1180 Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62 Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16 Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14 Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5 Total capacity (heating mode) (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57 Water flow in heating mode (2) m³/h 0,09 0,13 0,17 0,20 0,24 0,29 0,33 0,38 0,40 0,49 Pressure drop in heating mode (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 11,7 14,6 13,1 19,2 Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51 Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60 MIN SPEED Air flow m³/h 180 270 350 380 500 550 640 760 790 920 Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40 Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14 Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93 Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3 Total capacity (heating mode) (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55 Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,16 0,22 0,23 0,30 0,33 0,35 0,40 Pressure drop in heating mode (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 9,5 11,7 10,1 13,1 Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45 Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54 SIZE AND WEIGHT A (5) mm 450 450 650 650 850 850 1050 1050 1250 1250 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 12 12 14 15 21 22 24 25 28 29
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
424
a-LIFE2 / DLIO-DFIO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 55 55 85 85 75 75 145 145 175 175 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 300 360 520 590 660 815 890 980 1140 1310 Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50 Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81 Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29 Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8 Total capacity (heating mode) (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32 Water flow in heating mode (2) m³/h 0,11 0,15 0,20 0,24 0,29 0,34 0,38 0,42 0,45 0,55 Pressure drop in heating mode (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 15,1 18,3 16,7 24,3 Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55 Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64 MED SPEED Air flow m³/h 210 290 410 500 560 670 780 910 1010 1180 Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62 Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16 Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14 Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5 Total capacity (heating mode) (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57 Water flow in heating mode (2) m³/h 0,09 0,13 0,17 0,20 0,24 0,29 0,33 0,38 0,40 0,49 Pressure drop in heating mode (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 11,7 14,6 13,1 19,2 Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51 Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60 MIN SPEED Air flow m³/h 180 270 350 380 500 550 640 760 790 920 Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40 Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14 Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93 Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3 Total capacity (heating mode) (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55 Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,16 0,22 0,23 0,30 0,33 0,35 0,40 Pressure drop in heating mode (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 9,5 11,7 10,1 13,1 Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45 Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54 SIZE AND WEIGHT A (5) mm 545 545 745 745 945 945 1145 1145 1345 1345 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 12 13 15 16 21 22 25 26 29 30
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
425
a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 55 55 85 85 75 75 145 145 175 175 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 300 360 520 590 660 815 890 980 1140 1310 Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50 Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81 Max water flow (1) m³/h 0,26 0,34 0,49 0,59 0,65 0,76 0,89 0,98 1,06 1,29 Mad pressure drop (1) kPa 9,0 12,7 30,8 34,3 12,6 17,2 24,2 26,9 32,9 46,8 Total capacity (heating mode) (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32 Water flow in heating mode (2) m³/h 0,11 0,15 0,20 0,24 0,29 0,34 0,38 0,42 0,45 0,55 Pressure drop in heating mode (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 15,1 18,3 16,7 24,3 Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55 Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64 MED SPEED Air flow m³/h 210 290 410 500 560 670 780 910 1010 1180 Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62 Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16 Max water flow (1) m³/h 0,20 0,30 0,40 0,49 0,53 0,65 0,77 0,87 0,93 1,14 Mad pressure drop (1) kPa 5,4 9,6 20,5 24,1 8,2 12,4 18,5 21,2 25,5 36,5 Total capacity (heating mode) (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57 Water flow in heating mode (2) m³/h 0,09 0,13 0,17 0,20 0,24 0,29 0,33 0,38 0,40 0,49 Pressure drop in heating mode (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 11,7 14,6 13,1 19,2 Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51 Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60 MIN SPEED Air flow m³/h 180 270 350 380 500 550 640 760 790 920 Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40 Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14 Max water flow (1) m³/h 0,17 0,26 0,36 0,40 0,49 0,52 0,70 0,77 0,81 0,93 Mad pressure drop (1) kPa 4,0 7,0 16,2 15,8 7,0 8,0 15,0 16,8 19,4 24,3 Total capacity (heating mode) (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55 Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,16 0,22 0,23 0,30 0,33 0,35 0,40 Pressure drop in heating mode (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 9,5 11,7 10,1 13,1 Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45 Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54 SIZE AND WEIGHT A (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682 B (5) mm 233 233 233 233 233 233 233 233 233 233 H (5) mm 499 499 499 499 499 499 499 499 499 499 Operating weight (5) kg 17 18 21 22 29 30 33 35 38 40
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
426
427
i-LIFE2 0202 - 1004 <<< BACK INDEX
Version DLMV version with cabinet, low air intake, vertical installation DLMO version with cabinet, low air intake, horizontal installation DFMV version with cabinet, front air intake, vertical installation DFMO version with cabinet, front air intake, horizontal installation DLIV built-in version, low air intake, vertical installation. DLIO built-in version, low air intake, horizontal installation DFIV built-in version, front air intake, vertical installation DFIO built-in version, front air intake, horizontal installation
Professional fan-coil with cabinet or buit-in version, powered by EC Brushless Centrifugal Fan 2,00-7,50 kW New i-LIFE2 fancoil is powered by a modulating speed centrifugal fan. This new concept of fancoil operates with continuous air flow regulation assuring the best comfort and a concrete energy savings. Thanks to the different versions, with cabinet or buit-in, low air intake or front air intake, vertical or horizontal installation, it results very easy to find the perfect solution for any requirement . A dedicated range of controllers allows a user friendly and complete regulation of all the functions, and an easy integration in home automation, centralization and Building Management Systems.
Features High efficiency EC motor. Modulating speed centrifugal fan and air flow regulation. Energy consumption reduced by more than 50% Coils with aluminium fins and copper pipes. Configurations for 2 and 4 pipe Systems. Left-hand water connections, easy convertible into right-hand, by simply turning the coil Air filter on all models. Automatically closing flap to cover and protect electric controls from dripping water (in conformity with directive 60335-2-40). Elegant cover structure that integrates the use of high quality plastic materials, with traditional galvanized and precoated materials. Structure in galvanised steel of high thickness for maximum resistance to rust; Auxiliary drain pan with thermal insulation for all Horizontal versions, made of galvanized steel. Plastic drain pan for all Vertical versions.
Accessory Hot water coil kit Kit RS485 - interface for Building Management System Kit control board to manage 0-10V or 3 points modulating valve unit Main coil 2-way/3-way valve unit Additional coil 2-way/3-way valve unit Kit LIFE2 BOX Kit Gateway interface for MyHome Bticino System Air intake grille kit with version cover Straight and angular (90°) plenum kits for air outlet Plenum kit with round, straight or 90° air ducts. Straight and angular (90°) plenum kits for air inlet Heating element kit Horizontal and vertical fan coil auxiliary tray
Controls EK plug-in control /EKW wall mounted control User interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of main and additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch. Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE fan coil units. Easy control installation thanks to 2 wires connection. iK control with LCD screen Interface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timer regulation configurable by the customer. Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) . Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units. Easy control installation thanks to 2 wires connection through HB power board Remote control Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compact remote control with fine aethetics. AT-EC plug-in control/ATW-EC wall mounted control User interface for selection of functioning mode (Off/Summer/Winter/Auto), fan speed (Max,Med,Min,Auto), and temperature set. Control of main and additional coil valve unit. (summer/winter 2 and 4 pipes installation). Managment of traditional ON/OFF valve unit. Air and water temperature probe. Multifuncion digital input configurable by user. Configuration dip switch. The controls can not be connected to BMS system.
428
i-LIFE2 / DLIV-DFIV 0202 0402 0602 0802 1002 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 48 54 65 74 73 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 360 590 815 980 1310 Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50 Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81 Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29 Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8 Total capacity (heating mode) (2) kW 2,82 4,40 6,06 7,74 10,1 Water flow in heating mode (2) m³/h 0,34 0,58 0,76 0,98 1,29 Pressure drop in heating mode (2) kPa 10,9 34,1 14,6 23,3 40,9 Noise Pressure (3) dB(A) 48 51 53 54 56 Noise Power (4) dB(A) 57 60 62 63 65 MED SPEED Air flow m³/h 270 380 550 760 920 Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40 Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14 Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93 Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3 Total capacity (heating mode) (2) kW 2,08 3,07 4,15 6,12 7,13 Water flow in heating mode (2) m³/h 0,26 0,40 0,52 0,78 0,92 Pressure drop in heating mode (2) kPa 6,2 16,5 7,1 15,0 22,1 Noise Pressure (3) dB(A) 39 42 44 45 47 Noise Power (4) dB(A) 48 51 53 54 56 MIN SPEED Air flow m³/h 180 238 286 328 542 Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27 Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46 Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56 Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0 Total capacity (heating mode) (2) kW 1,43 1,97 2,67 3,29 4,32 Water flow in heating mode (2) m³/h 0,18 0,25 0,33 0,42 0,56 Pressure drop in heating mode (2) kPa 3,0 7,1 3,1 4,7 8,7 Noise Pressure (3) dB(A) 31 33 33 34 37 Noise Power (4) dB(A) 40 42 42 43 46 SIZE AND WEIGHT A (5) mm 450 650 850 1050 1250 B (5) mm 215 215 215 215 215 H (5) mm 450 450 450 450 450 Operating weight (5) kg 11 14 21 24 28
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
429
i-LIFE2 / DLIO-DFIO 0202 0402 0602 0802 1002 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 48 54 65 74 73 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 360 590 815 980 1310 Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50 Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81 Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29 Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8 Total capacity (heating mode) (2) kW 2,82 4,40 6,06 7,74 10,1 Water flow in heating mode (2) m³/h 0,34 0,58 0,76 0,98 1,29 Pressure drop in heating mode (2) kPa 10,9 34,1 14,6 23,3 40,9 Noise Pressure (3) dB(A) 48 51 53 54 56 Noise Power (4) dB(A) 57 60 62 63 65 MED SPEED Air flow m³/h 270 380 550 760 920 Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40 Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14 Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93 Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3 Total capacity (heating mode) (2) kW 2,08 3,07 4,15 6,12 7,13 Water flow in heating mode (2) m³/h 0,26 0,40 0,52 0,78 0,92 Pressure drop in heating mode (2) kPa 6,2 16,5 7,1 15,0 22,1 Noise Pressure (3) dB(A) 39 42 44 45 47 Noise Power (4) dB(A) 48 51 53 54 56 MIN SPEED Air flow m³/h 180 238 286 328 542 Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27 Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46 Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56 Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0 Total capacity (heating mode) (2) kW 1,43 1,97 2,67 3,29 4,32 Water flow in heating mode (2) m³/h 0,18 0,25 0,33 0,42 0,56 Pressure drop in heating mode (2) kPa 3,0 7,1 3,1 4,7 8,7 Noise Pressure (3) dB(A) 31 33 33 34 37 Noise Power (4) dB(A) 40 42 42 43 46 SIZE AND WEIGHT A (5) mm 545 745 945 1145 1345 B (5) mm 215 215 215 215 215 H (5) mm 450 450 450 450 450 Operating weight (5) kg 12 15 21 25 29
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
430
i-LIFE2 / DLMV-DFMV / DLMO-DFMO 0202 0402 0602 0802 1002 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 48 54 65 74 73 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 360 590 815 980 1310 Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50 Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81 Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29 Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8 Total capacity (heating mode) (2) kW 2,82 4,40 6,06 7,74 10,1 Water flow in heating mode (2) m³/h 0,34 0,58 0,76 0,98 1,29 Pressure drop in heating mode (2) kPa 10,9 34,1 14,6 23,3 40,9 Noise Pressure (3) dB(A) 48 51 53 54 56 Noise Power (4) dB(A) 57 60 62 63 65 MED SPEED Air flow m³/h 270 380 550 760 920 Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40 Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14 Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93 Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3 Total capacity (heating mode) (2) kW 2,08 3,07 4,15 6,12 7,13 Water flow in heating mode (2) m³/h 0,26 0,40 0,52 0,78 0,92 Pressure drop in heating mode (2) kPa 6,2 16,5 7,1 15,0 22,1 Noise Pressure (3) dB(A) 39 42 44 45 47 Noise Power (4) dB(A) 48 51 53 54 56 MIN SPEED Air flow m³/h 180 238 286 328 542 Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27 Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46 Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56 Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0 Total capacity (heating mode) (2) kW 1,43 1,97 2,67 3,29 4,32 Water flow in heating mode (2) m³/h 0,18 0,25 0,33 0,42 0,56 Pressure drop in heating mode (2) kPa 3,0 7,1 3,1 4,7 8,7 Noise Pressure (3) dB(A) 31 33 33 34 37 Noise Power (4) dB(A) 40 42 42 43 46 SIZE AND WEIGHT A (5) mm 922 1112 1302 1492 1682 B (5) mm 233 233 233 233 233 H (5) mm 499 499 499 499 499 Operating weight (5) kg 14 17 24 28 32
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
431
i-LIFE2 / DLIV-DFIV 0204 0404 0604 0804 1004 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 48 54 65 74 73 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 360 590 815 980 1310 Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50 Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81 Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29 Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8 Total capacity (heating mode) (2) kW 1,67 2,76 3,87 4,82 6,32 Water flow in heating mode (2) m³/h 0,15 0,24 0,34 0,42 0,55 Pressure drop in heating mode (2) kPa 10,7 18,6 35,6 18,3 24,3 Noise Pressure (3) dB(A) 48 51 53 54 56 Noise Power (4) dB(A) 57 60 62 63 65 MED SPEED Air flow m³/h 270 380 550 760 920 Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40 Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14 Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93 Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3 Total capacity (heating mode) (2) kW 1,24 1,88 2,65 3,81 4,55 Water flow in heating mode (2) m³/h 0,11 0,16 0,23 0,33 0,40 Pressure drop in heating mode (2) kPa 6,1 9,0 17,5 11,7 13,1 Noise Pressure (3) dB(A) 39 42 44 45 47 Noise Power (4) dB(A) 48 51 53 54 56 MIN SPEED Air flow m³/h 180 238 286 328 542 Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27 Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46 Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56 Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0 Total capacity (heating mode) (2) kW 0,85 1,20 1,71 2,05 2,75 Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,18 0,24 Pressure drop in heating mode (2) kPa 3,0 3,8 7,7 3,6 5,1 Noise Pressure (3) dB(A) 31 33 33 34 37 Noise Power (4) dB(A) 40 42 42 43 46 SIZE AND WEIGHT A (5) mm 450 650 850 1050 1250 B (5) mm 215 215 215 215 215 H (5) mm 450 450 450 450 450 Operating weight (5) kg 12 15 22 26 30
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
432
i-LIFE2 / DLIO-DFIO 0204 0404 0604 0804 1004 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 48 54 65 74 73 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 360 590 815 980 1310 Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50 Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81 Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29 Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8 Total capacity (heating mode) (2) kW 1,67 2,76 3,87 4,82 6,32 Water flow in heating mode (2) m³/h 0,15 0,24 0,34 0,42 0,55 Pressure drop in heating mode (2) kPa 10,7 18,6 35,6 18,3 24,3 Noise Pressure (3) dB(A) 48 51 53 54 56 Noise Power (4) dB(A) 57 60 62 63 65 MED SPEED Air flow m³/h 270 380 550 760 920 Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40 Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14 Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93 Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3 Total capacity (heating mode) (2) kW 1,24 1,88 2,65 3,81 4,55 Water flow in heating mode (2) m³/h 0,11 0,16 0,23 0,33 0,40 Pressure drop in heating mode (2) kPa 6,1 9,0 17,5 11,7 13,1 Noise Pressure (3) dB(A) 39 42 44 45 47 Noise Power (4) dB(A) 48 51 53 54 56 MIN SPEED Air flow m³/h 180 238 286 328 542 Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27 Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46 Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56 Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0 Total capacity (heating mode) (2) kW 0,85 1,20 1,71 2,05 2,75 Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,18 0,24 Pressure drop in heating mode (2) kPa 3,0 3,8 7,7 3,6 5,1 Noise Pressure (3) dB(A) 31 33 33 34 37 Noise Power (4) dB(A) 40 42 42 43 46 SIZE AND WEIGHT A (5) mm 545 745 945 1145 1345 B (5) mm 215 215 215 215 215 H (5) mm 450 450 450 450 450 Operating weight (5) kg 12 16 22 26 30
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
433
i-LIFE2 / DLMV-DFMV / DLMO-DFMO 0204 0404 0604 0804 1004 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 48 54 65 74 73 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 360 590 815 980 1310 Total capacity in cooling mode (1) kW 2,00 3,40 4,40 5,70 7,50 Sensible capacity in cooling mode (1) kW 1,59 2,61 3,52 4,38 5,81 Max water flow (1) m³/h 0,34 0,59 0,76 0,98 1,29 Mad pressure drop (1) kPa 12,7 34,3 17,2 26,9 46,8 Total capacity (heating mode) (2) kW 1,67 2,76 3,87 4,82 6,32 Water flow in heating mode (2) m³/h 0,15 0,24 0,34 0,42 0,55 Pressure drop in heating mode (2) kPa 10,7 18,6 35,6 18,3 24,3 Noise Pressure (3) dB(A) 48 51 53 54 56 Noise Power (4) dB(A) 57 60 62 63 65 MED SPEED Air flow m³/h 270 380 550 760 920 Total capacity in cooling mode (1) kW 1,49 2,31 3,02 4,50 5,40 Sensible capacity in cooling mode (1) kW 1,18 1,75 2,39 3,44 4,14 Max water flow (1) m³/h 0,26 0,40 0,52 0,77 0,93 Mad pressure drop (1) kPa 7,0 15,8 8,0 16,8 24,3 Total capacity (heating mode) (2) kW 1,24 1,88 2,65 3,81 4,55 Water flow in heating mode (2) m³/h 0,11 0,16 0,23 0,33 0,40 Pressure drop in heating mode (2) kPa 6,1 9,0 17,5 11,7 13,1 Noise Pressure (3) dB(A) 39 42 44 45 47 Noise Power (4) dB(A) 48 51 53 54 56 MIN SPEED Air flow m³/h 180 238 286 328 542 Total capacity in cooling mode (1) kW 1,02 1,48 1,94 2,42 3,27 Sensible capacity in cooling mode (1) kW 0,81 1,15 1,49 1,88 2,46 Max water flow (1) m³/h 0,18 0,25 0,33 0,42 0,56 Mad pressure drop (1) kPa 3,3 6,5 3,3 4,8 9,0 Total capacity (heating mode) (2) kW 0,85 1,20 1,71 2,05 2,75 Water flow in heating mode (2) m³/h 0,07 0,11 0,15 0,18 0,24 Pressure drop in heating mode (2) kPa 3,0 3,8 7,7 3,6 5,1 Noise Pressure (3) dB(A) 31 33 33 34 37 Noise Power (4) dB(A) 40 42 42 43 46 SIZE AND WEIGHT A (5) mm 922 1112 1302 1492 1682 B (5) mm 233 233 233 233 233 H (5) mm 499 499 499 499 499 Operating weight (5) kg 15 18 25 29 33
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
434
435
a-LIFE2 HP 0302 - 1204 <<< BACK INDEX
Version DFIO built-in version, front air intake, horizontal installation DFIV built-in version, front air intake, vertical installation DLIO built-in version, low air intake, horizontal installation DLIV built-in version, low air intake, vertical installation.
High head fan-coil for professional application built-in version 2,88-8,60 kW a-LIFE2 HP are professional high-head fan coils by Climaveneta. The enhanced motor and the built-in version make these units ideal for ducted systems in tertiary and commercial sectors.
Features High pressure centrifugal fan unit for ducted system; Multi speed directly coupled electric motor; Configurations for 2 and 4 pipe Systems. Structure in hot galvanised steel for maximum resistance to rust; Left-hand water connections, easy convertible into right-hand, by simply turning the coil Air filter on all models. Auxiliary drain pan with thermal insulation for all Horizontal versions, made of galvanized steel. Plastic drain pan for all Vertical versions.
Accessory Hot water coil kit Main coil 2-way/3-way valve unit Main and additional coil valve unit ON/OFF, PWM, 0-10 V, 3 points 2-way or 3-way Kit control board to manage 0-10V or 3 points modulating valve unit Kit RS485 - interface for Building Management System Kit Bus Adapter for BMS Kit Gateway interface for MyHome Bticino System Interface SPB Kit Heating element kit Condensate drain pump Horizontal and vertical fan coil auxiliary tray Hose kit Straight and angular (90°) plenum kits for air inlet Plenum kit with round, straight or 90° air ducts.
Controls ATW wall mounted Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation. Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS. MTW wall mounted Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe. PSW wall mounted Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe. Remote Control EKW User interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of main and additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch. Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units. Easy control installation thanks to 2 wires connection. iK control with LCD screen Interface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timer regulation configurable by the customer. Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) . Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units. Easy control installation thanks to 2 wires connection through HB power board Remote control Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compact remote control with fine aethetics.
436
a-LIFE2 HP DFIV/DLIV 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 127 127 115 115 196 196 225 225 285 285 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933 Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60 Sensible capacity in cooling mode (1) kW 2,39 2,77 2,93 3,53 3,91 4,44 5,14 5,91 6,99 7,32 Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48 Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9 Total capacity (heating mode) (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4 Water flow in heating mode (2) m³/h 0,50 0,56 0,64 0,71 0,79 0,89 1,07 1,24 1,38 1,48 Pressure drop in heating mode (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8 Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59 Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68 MED SPEED Air flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719 Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10 Sensible capacity in cooling mode (1) kW 1,90 2,24 2,31 2,66 2,84 3,74 4,67 5,15 6,46 7,03 Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39 Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0 Total capacity (heating mode) (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8 Water flow in heating mode (2) m³/h 0,40 0,46 0,52 0,55 0,61 0,77 0,98 1,07 1,29 1,39 Pressure drop in heating mode (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0 Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57 Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66 MIN SPEED Air flow m³/h 392 435 464 516 584 649 923 1026 1381 1534 Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40 Sensible capacity in cooling mode (1) kW 1,69 1,82 1,71 2,37 2,49 2,78 3,88 4,42 5,83 6,25 Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27 Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7 Total capacity (heating mode) (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82 Water flow in heating mode (2) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27 Pressure drop in heating mode (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7 Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54 Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63 SIZE AND WEIGHT A (5) mm 650 650 850 850 1050 1050 1250 1250 1450 1450 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
437
a-LIFE2 HP DFIO/DLIO 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 127 127 115 115 196 196 225 225 285 285 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933 Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60 Sensible capacity in cooling mode (1) kW 2,39 2,77 2,93 3,53 3,91 4,44 5,14 5,91 6,99 7,32 Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48 Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9 Total capacity (heating mode) (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4 Water flow in heating mode (2) m³/h 0,50 0,56 0,64 0,71 0,79 0,89 1,07 1,24 1,38 1,48 Pressure drop in heating mode (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8 Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59 Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68 MED SPEED Air flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719 Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10 Sensible capacity in cooling mode (1) kW 1,90 2,24 2,31 2,66 2,84 3,74 4,67 5,15 6,46 7,03 Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39 Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0 Total capacity (heating mode) (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8 Water flow in heating mode (2) m³/h 0,40 0,46 0,52 0,55 0,61 0,77 0,98 1,07 1,29 1,39 Pressure drop in heating mode (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0 Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57 Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66 MIN SPEED Air flow m³/h 392 435 464 516 584 649 923 1026 1381 1534 Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40 Sensible capacity in cooling mode (1) kW 1,69 1,82 1,71 2,37 2,49 2,78 3,88 4,42 5,83 6,25 Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27 Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7 Total capacity (heating mode) (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82 Water flow in heating mode (2) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27 Pressure drop in heating mode (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7 Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54 Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63 SIZE AND WEIGHT A (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
438
a-LIFE2 HP DFIV/DLIV 0304 0404 0504 0604 0704 0804 0904 1004 1104 1204 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 127 127 115 115 196 196 225 225 285 285 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933 Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60 Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32 Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48 Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 34,2 43,1 14,2 15,9 Total capacity (heating mode) (2) kW 2,34 2,66 3,29 3,64 3,71 4,18 4,96 5,76 6,44 6,88 Water flow in heating mode (2) m³/h 0,21 0,23 0,29 0,32 0,33 0,37 0,43 0,50 0,56 0,60 Pressure drop in heating mode (2) kPa 13,6 17,3 26,3 31,7 11,1 13,9 15,4 20,4 17,9 20,1 Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59 Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68 MED SPEED Air flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719 Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10 Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03 Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39 Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,9 32,5 12,3 14,0 Total capacity (heating mode) (2) kW 1,88 2,19 2,67 2,84 2,87 3,61 4,56 5,00 6,00 6,48 Water flow in heating mode (2) m³/h 0,16 0,19 0,23 0,25 0,25 0,32 0,40 0,44 0,53 0,57 Pressure drop in heating mode (2) kPa 9,0 12,0 17,8 20,0 6,8 10,5 13,1 15,6 15,7 18,1 Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57 Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66 MIN SPEED Air flow m³/h 392 435 464 516 584 649 923 1026 1381 1534 Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40 Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25 Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27 Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,8 24,3 10,4 11,7 Total capacity (heating mode) (2) kW 1,69 1,79 2,00 2,57 2,59 2,81 3,86 4,32 5,52 5,92 Water flow in heating mode (2) m³/h 0,15 0,16 0,18 0,23 0,23 0,25 0,34 0,38 0,48 0,52 Pressure drop in heating mode (2) kPa 7,3 8,2 10,4 16,6 5,6 6,5 9,6 11,9 13,5 15,4 Noise Pressure (3) dB(A) 42 45 34 41 38 41 49 51 54 54 Noise Power (4) dB(A) 51 54 43 50 47 50 58 60 63 63 SIZE AND WEIGHT A (5) mm 650 650 850 850 1050 1050 1250 1250 1450 1450 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 15 16 21 22 25 26 29 31 32 35
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
439
a-LIFE2 HP DFIO/DLIO 0304 0404 0504 0604 0704 0804 0904 1004 1104 1204 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 127 127 115 115 196 196 225 225 285 285 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 561 623 705 783 1004 1116 1390 1544 1740 1933 Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60 Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32 Max water flow (1) m³/h 0,50 0,56 0,64 0,71 0,80 0,90 1,07 1,24 1,39 1,48 Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 34,2 43,1 14,2 15,9 Total capacity (heating mode) (2) kW 2,34 2,66 3,29 3,64 3,71 4,18 4,96 5,76 6,44 6,88 Water flow in heating mode (2) m³/h 0,21 0,23 0,29 0,32 0,33 0,37 0,43 0,50 0,56 0,60 Pressure drop in heating mode (2) kPa 13,6 17,3 26,3 31,7 11,1 13,9 15,4 20,4 17,9 20,1 Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59 Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68 MED SPEED Air flow m³/h 500 555 525 583 767 852 1078 1198 1547 1719 Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10 Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03 Max water flow (1) m³/h 0,40 0,46 0,52 0,56 0,61 0,77 0,98 1,08 1,29 1,39 Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,9 32,5 12,3 14,0 Total capacity (heating mode) (2) kW 1,88 2,19 2,67 2,84 2,87 3,61 4,56 5,00 6,00 6,48 Water flow in heating mode (2) m³/h 0,16 0,19 0,23 0,25 0,25 0,32 0,40 0,44 0,53 0,57 Pressure drop in heating mode (2) kPa 9,0 12,0 17,8 20,0 6,8 10,5 13,1 15,6 15,7 18,1 Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57 Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66 MIN SPEED Air flow m³/h 392 435 464 516 584 649 923 1026 1381 1534 Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40 Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25 Max water flow (1) m³/h 0,36 0,38 0,39 0,50 0,55 0,60 0,83 0,93 1,19 1,27 Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,8 24,3 10,4 11,7 Total capacity (heating mode) (2) kW 1,69 1,79 2,00 2,57 2,59 2,81 3,86 4,32 5,52 5,92 Water flow in heating mode (2) m³/h 0,15 0,16 0,18 0,23 0,23 0,25 0,34 0,38 0,48 0,52 Pressure drop in heating mode (2) kPa 7,3 8,2 10,4 16,6 5,6 6,5 9,6 11,9 13,5 15,4 Noise Pressure (3) dB(A) 42 45 34 41 38 41 49 51 54 54 Noise Power (4) dB(A) 51 54 43 50 47 50 58 60 63 63 SIZE AND WEIGHT A (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545 B (5) mm 215 215 215 215 215 215 215 215 215 215 H (5) mm 450 450 450 450 450 450 450 450 450 450 Operating weight (5) kg 15 16 21 22 25 27 29 31 32 36
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 70/60 °C. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
440
441
Version DLIU Built-in version for universal installation. DLMV Version with cabinet for vertical installation DLMO Version with cabinet for horizontal installation DLRV Radiant Version with cabinet for vertical installation.
Residential fan-coils with cabinet or concealed version, with inverter motor e tangential fan. 0,84-3,86 kW i-LIFE SLIM is the new fan coil Climaveneta , with inverter technology for heating, cooling and dehumidifying. Its elegant design with only 13 cm depth makes i-LIFE Slim the perfect solution for residential applications. The fan coil is also available with i-LIFE R-SLIM inverter version with radiant panel. The brushless motor allows a perfect adaptation to thermal load, without any temperature fluctuations. Tangential fans operate through continuous air flow modulation, with no speed steps or relay switching as traditional fan coil units. High efficiency is guaranteed in any HVAC installation setup, in combination with any low temperature heat generator.
Features DC motor with inverter technology with continuous speed regulation, to ensure the best performance with a very low noise level. Elegant design and reduced depth of only 13 cm, for installation in a residential enviroment. Tangential fan with asymetric blades that ensures the continuous modulation of the air flow for a better comfort and real energy savings. Coil with large frontal area that allows to reach high air flow with very low pressure drop. Honeycomb polypropylene air filter which can be regenerated by washing or blowing. Elegant cover structure that integrates the use of high quality plastic materials, with traditional galvanized and epoxy powder coated materials. Configuration for 2 pipes systems.
Accessory Drain Pan for horizontal installation Main coil 2-way/3-way valve unit Fitting for air intake in built-in installation Telescopic air flow duct and 90° duct for false ceiling and build in installation Alluminium air flow vent for wall mounting Alluminium Air intake grid UVC air sterilisation device Casing for build in version - i-LIFE Slim Box Casing cover panel with frame and front panel grid Eurokonus adapter Pair of decorative and structural feet
Controls iKS2 - on board Control On-board control for unit with cabinet complete with touch keypad with 8 touch key, LCD display with colored symbols. Modulating fan speed with PID logic, temperature regulation, winter/summer mode, automatic mode for the speed regulation, night mode for a silent operation. Minimum water probe and solenoid management, it's possible to manage the function even without the water probe. Remote Control iKSW2 Remote control for built-in and with cabinet units complete with touch keypad with 8 touch keys, LCD display with colored symbols. Modulating fan speed with PID logic, temperature regulation, winter/summer mode, automatic mode for the speed regulation, night mode for a silent operation. Minimum water probe and solenoid valve management. A maximum of 31 fancoils can be connected to the iKSW control for open space rooms. Each unit must have the iHBS2 powerboard installed. RS485 output for connection in BMS. iHBS2 - On board semplified Control Simple on board control for buit - in and with cabinet units, to be coupled with remote control iKSW2. iHBS2 control has a LED for the visualization of the device's operation. All the parameters are set up from iKSW2. It is possible to manage the function even without the water probe. The iHBS2 powerboard is able to supply power to IKSW2 control. ATS2 - Control with 4 speed regulation Controller for units with cabinet. Interface with 8 keys for the temperature selection, winter/summer mode, 4 speed regulation, (Max. Min. Night and Auto) with display for room temperature vizualization. Minimum water temperature probe and solenoid valve management. It's possible to manage the function even without the water probe. HBS2 Control - Powerboard card Semple on board control for built-in units or with cabinet units, to be coupled with ATW Climaveneta remote control or other remote controls which manage the regulation of fixed fan speeds. HBS2 has a a LED for the visualization of the devise's operation. All the parameters are set up from the remote control. There are 2 versions of this powerboard. Version for ON/OFF signal (HBS2) and version for 0-10V signal (HBS2010)
442
i-LIFE SLIM / DLMO - DLMV 102 202 302 402 502 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 18 27 35 35 37 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 162 320 461 576 648 Total capacity in cooling mode (1) kW 0,84 1,79 2,69 3,39 3,86 Sensible capacity in cooling mode (1) kW 0,63 1,29 1,99 2,69 3,06 Max water flow (1) m³/h 0,15 0,31 0,46 0,58 0,66 Mad pressure drop (1) kPa 7,4 5,5 22,6 19,1 25,0 Total capacity (heating mode) (2) kW 1,12 2,38 3,29 4,19 4,96 Water flow in heating mode (2) m³/h 0,15 0,31 0,46 0,58 0,67 Pressure drop in heating mode (2) kPa 7,4 5,5 22,1 19,0 25,1 Noise Pressure (3) dB(A) 41 42 44 45 46 Noise Power (4) dB(A) 50 51 53 54 55 MED SPEED Air flow m³/h 113 252 367 453 494 Total capacity in cooling mode (1) kW 0,71 1,57 2,26 2,82 3,12 Sensible capacity in cooling mode (1) kW 0,53 1,15 1,75 2,12 2,38 Max water flow (1) m³/h 0,12 0,27 0,39 0,49 0,54 Mad pressure drop (1) kPa 5,3 4,3 16,3 13,4 15,9 Total capacity (heating mode) (2) kW 0,91 2,04 2,76 3,49 4,04 Water flow in heating mode (2) m³/h 0,12 0,27 0,39 0,49 0,54 Pressure drop in heating mode (2) kPa 5,2 4,3 16,3 13,4 15,9 Noise Pressure (3) dB(A) 35 36 36 37 40 Noise Power (4) dB(A) 44 45 45 46 49 MIN SPEED Air flow m³/h 55 155 248 370 426 Total capacity in cooling mode (1) kW 0,37 1,07 1,47 2,42 2,73 Sensible capacity in cooling mode (1) kW 0,27 0,76 1,21 1,82 2,09 Max water flow (1) m³/h 0,06 0,18 0,25 0,42 0,47 Mad pressure drop (1) kPa 1,4 2,0 7,3 9,9 12,0 Total capacity (heating mode) (2) kW 0,39 1,40 1,82 3,00 3,59 Water flow in heating mode (2) m³/h 0,06 0,18 0,25 0,42 0,47 Pressure drop in heating mode (2) kPa 1,4 2,0 7,3 10,0 12,0 Noise Pressure (3) dB(A) 26 27 27 28 30 Noise Power (4) dB(A) 35 36 36 37 39 SIZE AND WEIGHT A (5) mm 737 937 1137 1337 1537 B (5) mm 131 131 131 131 131 H (5) mm 579 579 579 579 579 Operating weight (5) kg 17 20 23 26 29
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
443
i-LIFE SLIM / DLIU 102 202 302 402 502 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 18 27 35 35 37 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 162 320 461 576 648 Total capacity in cooling mode (1) kW 0,84 1,79 2,69 3,39 3,86 Sensible capacity in cooling mode (1) kW 0,63 1,29 1,99 2,69 3,06 Max water flow (1) m³/h 0,15 0,31 0,46 0,58 0,66 Mad pressure drop (1) kPa 7,4 5,5 22,6 19,1 25,0 Total capacity (heating mode) (2) kW 1,12 2,38 3,29 4,19 4,96 Water flow in heating mode (2) m³/h 0,15 0,31 0,46 0,58 0,67 Pressure drop in heating mode (2) kPa 7,4 5,5 22,1 19,0 25,1 Noise Pressure (3) dB(A) 41 42 44 45 46 Noise Power (4) dB(A) 50 51 53 54 55 MED SPEED Air flow m³/h 113 252 367 453 494 Total capacity in cooling mode (1) kW 0,71 1,57 2,26 2,82 3,12 Sensible capacity in cooling mode (1) kW 0,53 1,15 1,75 2,12 2,38 Max water flow (1) m³/h 0,12 0,27 0,39 0,49 0,54 Mad pressure drop (1) kPa 5,3 4,3 16,3 13,4 15,9 Total capacity (heating mode) (2) kW 0,91 2,04 2,76 3,49 4,04 Water flow in heating mode (2) m³/h 0,12 0,27 0,39 0,49 0,54 Pressure drop in heating mode (2) kPa 5,2 4,3 16,3 13,4 15,9 Noise Pressure (3) dB(A) 35 36 36 37 40 Noise Power (4) dB(A) 44 45 45 46 49 MIN SPEED Air flow m³/h 55 155 248 370 426 Total capacity in cooling mode (1) kW 0,37 1,07 1,47 2,42 2,73 Sensible capacity in cooling mode (1) kW 0,27 0,76 1,21 1,82 2,09 Max water flow (1) m³/h 0,06 0,18 0,25 0,42 0,47 Mad pressure drop (1) kPa 1,4 2,0 7,3 9,9 12,0 Total capacity (heating mode) (2) kW 0,39 1,40 1,82 3,00 3,59 Water flow in heating mode (2) m³/h 0,06 0,18 0,25 0,42 0,47 Pressure drop in heating mode (2) kPa 1,4 2,0 7,3 10,0 12,0 Noise Pressure (3) dB(A) 26 27 27 28 30 Noise Power (4) dB(A) 35 36 36 37 39 SIZE AND WEIGHT A (5) mm 525 725 925 1125 1325 B (5) mm 126 126 126 126 126 H (5) mm 576 576 576 576 576 Operating weight (5) kg 9 12 15 18 21
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
444
i-LIFE SLIM / DLRV 102 202 302 402 502 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 18 27 35 35 37 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 162 320 461 576 648 Total capacity in cooling mode (1) kW 0,84 1,79 2,69 3,39 3,86 Sensible capacity in cooling mode (1) kW 0,63 1,29 1,99 2,69 3,06 Max water flow (1) m³/h 0,15 0,31 0,46 0,58 0,66 Mad pressure drop (1) kPa 7,4 5,5 22,6 19,1 25,0 Total capacity (heating mode) (2) kW 1,17 2,47 3,50 4,46 5,27 Water flow in heating mode (2) m³/h 0,15 0,31 0,46 0,58 0,67 Pressure drop in heating mode (2) kPa 7,4 5,4 22,7 19,1 25,2 Noise Pressure (3) dB(A) 41 42 44 45 46 Noise Power (4) dB(A) 50 51 53 54 55 MED SPEED Air flow m³/h 113 252 367 453 494 Total capacity in cooling mode (1) kW 0,71 1,57 2,26 2,82 3,12 Sensible capacity in cooling mode (1) kW 0,53 1,15 1,75 2,12 2,38 Max water flow (1) m³/h 0,12 0,27 0,39 0,49 0,54 Mad pressure drop (1) kPa 5,3 4,3 16,3 13,4 15,9 Total capacity (heating mode) (2) kW 0,95 2,12 2,93 3,72 4,29 Water flow in heating mode (2) m³/h 0,12 0,27 0,39 0,48 0,54 Pressure drop in heating mode (2) kPa 5,4 4,2 16,3 13,1 16,0 Noise Pressure (3) dB(A) 35 36 36 37 40 Noise Power (4) dB(A) 44 45 45 46 49 MIN SPEED Air flow m³/h 55 155 248 370 426 Total capacity in cooling mode (1) kW 0,37 1,07 1,47 2,42 2,73 Sensible capacity in cooling mode (1) kW 0,27 0,76 1,21 1,82 2,09 Max water flow (1) m³/h 0,06 0,18 0,25 0,42 0,47 Mad pressure drop (1) kPa 1,4 2,0 7,3 9,9 12,0 Total capacity (heating mode) (2) kW 0,41 1,46 1,94 3,19 3,81 Water flow in heating mode (2) m³/h 0,06 0,18 0,25 0,41 0,47 Pressure drop in heating mode (2) kPa 1,4 2,1 7,3 9,8 12,1 Noise Pressure (3) dB(A) 26 27 27 28 30 Noise Power (4) dB(A) 35 36 36 37 39 SIZE AND WEIGHT A (5) mm 737 937 1137 1337 1537 B (5) mm 131 131 131 131 131 H (5) mm 579 579 579 579 579 Operating weight (5) kg 17 20 23 26 29
Notes: 1 Room temperature 27 °C d.b./19 °C w.b.; Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b.; Hot water (in/out) 50/* °C (with identical flow note1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
445
Version - Base Version
High - Wall type Terminal 2,15-4,63 kW MHD2 belongs to hi-wall fan-coils of Climaveneta. The compactness of this model and its exclusive elegance soften the visual impact and make it ideal for residential and small tertiary installations.
Features Fan coil in ABS with high mechanical characteristics and resistance to ageing; Adjustable air flow direction; Arrangement for right-left condensate drain pipe; Management of all functions by remote control Removable panel;
Accessory Frame kit Solenoid valve 2 ways 1/2" Solenoid valve kit 3 ways, 4 fits 1/2" with frame Condensate drain pump
Controls Remote control Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compact remote control with fine aethetics.
446
MHD2 30 40 50 60 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 27 28 40 50 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 436 632 780 920 Total capacity in cooling mode (1) kW 2,15 2,67 4,00 4,63 Sensible capacity in cooling mode (1) kW 1,82 2,13 3,02 3,56 Max water flow (1) m³/h 0,37 0,46 0,69 0,80 Mad pressure drop (1) kPa 8,9 15,0 38,5 49,9 Total capacity (heating mode) (2) kW 2,48 3,20 4,20 5,07 Water flow in heating mode (2) m³/h 0,37 0,46 0,69 0,79 Pressure drop in heating mode (2) kPa 9,0 14,9 38,5 49,7 Noise Pressure (3) dB(A) 34 41 44 49 Noise Power (4) dB(A) 45 52 55 60 MED SPEED Air flow m³/h 376 522 691 810 Total capacity in cooling mode (1) kW 1,85 2,00 3,00 3,86 Sensible capacity in cooling mode (1) kW 1,60 1,62 2,57 2,97 Max water flow (1) m³/h 0,32 0,34 0,52 0,66 Mad pressure drop (1) kPa 7,6 10,3 25,7 37,9 Total capacity (heating mode) (2) kW 2,18 2,40 3,64 4,25 Water flow in heating mode (2) m³/h 0,32 0,34 0,52 0,67 Pressure drop in heating mode (2) kPa 7,7 10,2 26,0 38,1 Noise Pressure (3) dB(A) 31 31 41 45 Noise Power (4) dB(A) 42 42 52 56 MIN SPEED Air flow m³/h 334 403 570 697 Total capacity in cooling mode (1) kW 1,65 1,78 2,67 3,36 Sensible capacity in cooling mode (1) kW 1,42 1,45 2,13 2,58 Max water flow (1) m³/h 0,28 0,31 0,46 0,58 Mad pressure drop (1) kPa 6,8 8,8 21,9 30,7 Total capacity (heating mode) (2) kW 1,91 2,13 3,21 3,67 Water flow in heating mode (2) m³/h 0,28 0,30 0,46 0,58 Pressure drop in heating mode (2) kPa 6,8 8,7 21,8 31,1 Noise Pressure (3) dB(A) 27 28 37 42 Noise Power (4) dB(A) 38 39 48 53 SIZE AND WEIGHT A (5) mm 845 845 920 920 B (5) mm 180 180 200 200 H (5) mm 270 270 298 298 Operating weight (5) kg 10 10 13 13
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 50/* °C (identical flow rate note 1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
447
a-CHD 0606 - 2209 <<< BACK INDEX
Version U - 2T 2 Pipes version U- 4T 4 Pipes Version
Cassette type terminal 3,20-11,5 kW New a- CHD cassette of Climaveneta, with 5 speeds AC motor, is available in two version: for two pipe installation (unit with single coil) and for four pipe installation (unit with double coil). Wide range of sizes and easy installation make them suitable for all types of installations.
Features Frame in galvanised steel insulated with self-extinguishing closed-cell polyethylene blanket of suitable thickness, to limit heat loss and noise to a minimum. Airflow grille in ABS built in the cassette, supplied in 1 cartonbox 5-speed electric motor inclusive of thermal switch. Fan Low-rev radial-blade fan to maximise acoustic comfort. Coil with corrugated aluminium fins and copper pipes, tested with dried air at 14 bar. Switchboard with power and control terminal block with screw terminals Set-up for fresh air intake. Set-up for duct air distribution. Esternal Drain Pan
Accessory Main coil 2-way/3-way valve unit Additional coil 2-way/3-way valve unit Fresh Air renewal connection Duct Connection Flange Kit Bus Adapter for BMS Kit Gateway interface for MyHome Bticino System
Controls MTW wall mounted Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe. ATW wall mounted Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation. Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS. Remote control Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compact remote control with fine aethetics.
448
a-CHD 0606 0706 1108 2209 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 Max absorbed power W 60 85 147 310 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 575 810 1300 2250 Total capacity in cooling mode (1) kW 3,20 4,56 6,97 11,3 Sensible capacity in cooling mode (1) kW 2,38 3,20 5,01 8,21 Max water flow (1) m³/h 0,55 0,79 1,20 1,95 Mad pressure drop (1) kPa 10,0 36,4 31,5 47,4 Total capacity (heating mode) (2) kW 3,89 5,42 8,23 13,6 Water flow in heating mode (2) m³/h 0,56 0,78 1,21 1,94 Pressure drop in heating mode (2) kPa 7,4 34,1 27,5 44,2 Noise Pressure (3) dB(A) 41 49 56 59 Noise Power (4) dB(A) 52 60 67 70 MED SPEED Air flow m³/h 290 617 960 1970 Total capacity in cooling mode (1) kW 1,90 3,60 5,47 9,55 Sensible capacity in cooling mode (1) kW 1,34 2,50 3,91 7,37 Max water flow (1) m³/h 0,33 0,62 0,94 1,64 Mad pressure drop (1) kPa 4,1 23,5 20,3 34,5 Total capacity (heating mode) (2) kW 2,18 4,30 6,38 12,1 Water flow in heating mode (2) m³/h 0,33 0,61 0,94 1,64 Pressure drop in heating mode (2) kPa 3,3 17,5 16,5 31,6 Noise Pressure (3) dB(A) 34 42 49 54 Noise Power (4) dB(A) 45 53 60 65 MIN SPEED Air flow m³/h 200 450 700 1380 Total capacity in cooling mode (1) kW 1,38 2,80 4,23 7,50 Sensible capacity in cooling mode (1) kW 0,96 1,90 3,03 5,52 Max water flow (1) m³/h 0,24 0,48 0,73 1,29 Mad pressure drop (1) kPa 2,3 14,8 12,8 21,9 Total capacity (heating mode) (2) kW 1,56 3,28 4,90 9,06 Water flow in heating mode (2) m³/h 0,24 0,48 0,73 1,29 Pressure drop in heating mode (2) kPa 2,0 9,0 10,0 19,8 Noise Pressure (3) dB(A) 29 32 37 44 Noise Power (4) dB(A) 40 43 48 55 SIZE AND WEIGHT A (5) mm 575 575 730 830 B (5) mm 575 575 730 830 H (5) mm 250 290 290 290 Operating weight (5) kg 28 30 36 50
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20 °C d.b., hot water (in/out) 50/* °C (identical flow rate note 1). 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
449
a-CHD 0706 1108 2209 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 Max absorbed power W 85 147 305 4 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 810 1300 2250 Total capacity in cooling mode (1) kW 3,85 5,83 7,95 Sensible capacity in cooling mode (1) kW 2,79 4,23 5,85 Max water flow (1) m³/h 0,66 1,00 1,37 Mad pressure drop (1) kPa 27,2 42,1 40,7 Total capacity (heating mode) (2) kW 4,24 4,62 9,82 Water flow in heating mode (2) m³/h 0,37 0,41 0,86 Pressure drop in heating mode (2) kPa 12,5 14,0 27,3 Noise Pressure (3) dB(A) 49 56 59 Noise Power (4) dB(A) 60 67 70 MED SPEED Air flow m³/h 617 960 1970 Total capacity in cooling mode (1) kW 2,87 4,61 6,83 Sensible capacity in cooling mode (1) kW 2,07 3,33 5,00 Max water flow (1) m³/h 0,49 0,79 1,18 Mad pressure drop (1) kPa 17,0 27,6 30,9 Total capacity (heating mode) (2) kW 3,69 3,68 8,90 Water flow in heating mode (2) m³/h 0,32 0,32 0,78 Pressure drop in heating mode (2) kPa 9,4 10,5 22,0 Noise Pressure (3) dB(A) 42 49 54 Noise Power (4) dB(A) 53 60 65 MIN SPEED Air flow m³/h 450 700 1380 Total capacity in cooling mode (1) kW 2,42 3,60 5,35 Sensible capacity in cooling mode (1) kW 1,74 2,58 3,89 Max water flow (1) m³/h 0,42 0,62 0,92 Mad pressure drop (1) kPa 13,0 17,7 19,9 Total capacity (heating mode) (2) kW 3,27 2,90 6,80 Water flow in heating mode (2) m³/h 0,29 0,25 0,60 Pressure drop in heating mode (2) kPa 7,3 7,8 12,2 Noise Pressure (3) dB(A) 32 37 44 Noise Power (4) dB(A) 43 48 55 SIZE AND WEIGHT A (5) mm 575 730 830 B (5) mm 575 730 830 H (5) mm 290 290 290 Operating weight (5) kg 30 36 50
Notes: 1 Room temperature 27 °C d.b./19°C w.b., Chilled water (in/out) 7/12 °C. 2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row. 3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level. 4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2. 5 Unit in standard configuration/execution, without optional accessories.
450
451
i-CHD 0706 - 2209 <<< BACK INDEX
Version U - 2T 2 Pipes version U4T Version for 4 pipe installations, can be realized with the
cassette i- CHD 2-pipe, via the valve mounting 4FOR2.
Cassette type Terminal with continuous variation of air flow and cooling power 4,56-10,6 kW i-CHD is the new cassette of Climaveneta, with high efficency EC motor and Centrifugal fans that operates through a continuous air flow modulation, with low energy consumtion and perfect comfort. i-CHD is supplyed on 2 pipes version. For the 4 Pipes installations we reccomend the 2 Pipes i-CHD cassette with 4For2 kit valves.
Features High efficiency EC motor. Modulating speed centrifugal fan and air flow regulation. Energy consumption reduced by more than 50% Unit coils guarantee high efficiency thermal exchange with low pressure drop. Finned unit coils are made of copper tubes and high exchange surface area aluminium fins. Coils are always tested for leaks with dried air at 14 bar; Frame in galvanised steel insulated with self-extinguishing closed-cell polyethylene blanket of suitable thickness, to limit heat loss and noise to a minimum. Airflow grille in ABS built in the cassette, supplied in 1 cartonbox Electrical power and control switchboard, complete with electronic air flow regulator and terminal board for connection to network and available remote controls; Availability to have fresh air intake, distribute air flow in four directions and also in different room place thanks to air diffuser present on the unit; Condensate auxiliary tray standard supplied;
Accessory Main coil 2-way/3-way valve unit Kit valves 4For2 Fresh Air renewal connection Duct Connection Flange i-HB Power box Kit RS485 - interface for Building Management System
Controls MTW wall mounted Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe. Remote water temperature probe. ATW wall mounted Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation. ON/OFF valve unit control (summer/winter for 2 and 4 pipes installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe. Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation. Configuration dip switch. TTL serial port with Modbus protocol for installation in BMS. EK plug-in control /EKW wall mounted control User interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control of main and additional coil valve unit (summer/winter - 2 and 4 pipes installation) . Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points . Air and water temperature probe. Multifunction digital input configurable by user. Configuration dip switch. Modbus protocol for installation in BMS (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE fan coil units. Easy control installation thanks to 2 wires connection. iK control with LCD screen Interface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in. Selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK could function manually or with weekly timer regulation configurable by the customer. Control of main coil valve unit (summer/winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) . Parameters configurable directly by user. Modbus protocol for installation in Building Management System (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system up to 8 LIFE2 fan coil units. Easy control installation thanks to 2 wires connection through HB power board Remote control Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). User-sfriendly compact remote control with fine aethetics.
452
i-CHD 0706 1108 2209 ELECTRICAL DATA Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 Max absorbed power W 40 88 200 2 PIPES SYSTEM CONFIGURATION MAX SPEED Air flow m³/h 810 1300 2100 Total capacity in cooling mode (1) kW 4,56 6,97 10,9 Sensible capacity in cooling mode (1) kW 3,20 5,01 7,87 Max water flow (1) m³/h 0,79 1,20 1,88 Mad pressure drop (1) kPa 36,4 31,5 44,3 Total capacity (heating mode) (2) kW 5,42 8,23 13,0 Water flow in heating mode (2) m³/h 0,78 1,21 1,88 Pressure drop in heating mode (2) kPa 34,1 27,5 41,5 Noise Pressur