2 Bayard APXA12001 - January, 20122
1 - Technical data• Range:
- DN 50 to 1000 for XGS design.- DN 50 to 800 for XG design.- DN 50 to 300 for XGA design
• PN 10, 16 or 25 (depending on functions).• Maximum temperature: +1°C to +65°C.• Seating: class A according to standard ISO 5208-2.• XG and XGS designs:
- Face-to-face dimensions according to standards EN 558-1 series 1 (except DN 1000) and ISO 5752 series 1 (except DN 1000).
• XGA design:- Face-to-face dimensions according to standard ISO 5752 series 8
(except DN 300).• Flange drilling according to standards EN 1092-2 and ISO 7005-2: ISO PN10,
16 or 25 for DN 50 to 1000 (other drillings on request).• Fluid: drinking water or 2 mm filtered untraited water.
2 - Characteristics and performances• How to choose the design:
- Bayard range offers two different versions: XG and XGS design.- The decision which design to take depends on the required application
and on the pressure and flow rate conditions.- The XGS design specially fits for a pressure reducing application and
when there is a risk of cavitation.- The XG design suits better for low head loss conditions.
Mechanical resistance: - Main valve PN25 in standard version (PN40, please consult us).- Pilot circuit PN10, PN16 or 25 according to the expected applications.
(Other possibilities please consult us).
Control accuracy:Control accuracy is guaranteed by:
- The pilot system principle.- The linearity between the open section freed by the movements of the
mobile unit and its stroke.
In the mentioned operating range, the accuracy for pressure control is more or less 5% (other functions: see dedicated data sheet.)
Hydrobloc control valve
Angle pattern. Single chamber.
XGA design.
Globe pattern.Double chamber.
XG design.
Globe pattern.Single chamber.
XGS design.
Globe pattern.Single chamber.
XG design.
For a surge anticipating valve: higher maxi velocities might beacceptable, please consult us.
XGS design XG designm/s m/s
Permanent maxi velocity 4 5Exceptional maxi velocity 6 7
• Recommended velocity (VE)
Bayard APXA12001 - January, 2012 3
Hydrobloc control valve
• Head loss curves for fully open valve
Curves and data established for water at 20°C for standard valve mounted on horizontal pipe. Kv: (flow rate factor) is the flow rate at 20°C expressed in m3/h which generates a head loss of 1 bar inside the valve.
3 - Hydraulic characteristics
Hydrobloc control valve
• How to choose the diameter
The diameter of the valve must be chosen according to the flow rate conditions and the pressure on the valves. Generally two cases are to be considered:
Case 1: The head loss of the valve has to be as low as possible (2 to 5 according to the DN and design) because the availa-ble head loss or the static pressure are ≤ 1 bar.
Case 2: The available head loss is high, so higher velocities can be admitted (beforehand, check that the available head loss is higher than the head loss through the fully open valve at the maximum considered flow rate).
Recommended flow rates (l/s)
VE*/ DN 50 65 80 100 125 150 200 250 300 350 400 500 600 700 800 900 1000XGS Design Case 1 Mini flow rate 0.2 0.4 0.7 1 16 2.5 3.5 6.3 9.8 14 19 25 39 57 77 - 127 157
Maxi permanent flow rate 2 3.9 6.6 10.4 16 25 35 63 98 141 192 251 393 565 770 - 1272 1571Case 2 Mini flow rate 0.4 0.8 1.3 2 3.1 4.9 7.1 13 20 28 38 50 79 113 154 - 254 314
Maxi permanent flow rate 4 7.8 13.6 20 31.2 49 71 126 196 283 385 503 785 1131 1539 - 2545 3142
XG Design Case 1 Mini flow rate 0.2 0.4 0.7 1 1.6 2.5 3.5 6.3 9.8 14 - 25 - 57 - 101 - -
Maxi permanent flow rate 2.5 4.9 8.3 13 20 31 44 79 123 177 - 314 - 707 - 1257 - -Case 2 Mini flow rate 0.4 0.8 1.3 2 3.1 4.9 7.1 13 20 28 - 50 - 113 - 201 - -
Maxi permanent flow rate 5 9.8 17 25 39 61 88 157 245 353 - 628 - 1414 - 2513 - -
* VE (m/s) = Equivalent velocity: average velocity in the inlet section (DN)These values don’t apply to flow limiting, overspeed and differential functions.
Flow rate factor (Kv)
DN XGS design XG designKv Kv
50 30 4865 50 6780 69 102
100 103 172125 169 243150 181 339200 436 688250 608 978300 1012 1443350 1389 -400 1413 3168500 3147 -600 3172 5821700 5626 -800 - 9134900 9184 -
1000 9233 -
XGS design
10
Hea
d lo
ss in
m W
H
Flow rate in l/s
0
1
2
3
4
5
6
7
8
9
1 10 100 1000 10000
DN
50
DN
65
DN
80
DN
100
DN
125
DN
150
DN
200
DN
250
DN
300
DN
400
DN
600
DN
800
XG design
DN
150DN
125
DN
200
DN
250 DN
300
DN
350 DN
400
DN
500 DN
600
DN
700 DN
900
DN
100
0
1 10 100 1000 10000
Hea
d lo
ss in
m W
H
Flow rate in l/s
0
1
2
3
4
5
6
7
8
9
10D
N 5
0D
N 6
5 DN
80
DN
100
4 Bayard APXA12001 - January, 2012
Hydrobloc control valve
C mini: visual position indicator.C maxi: with SCADA position transmitter option (with limit switch option up from DN 800).On some valves, the pilot circuit can be larger than the overall dimen-sions of the main valve.
* XGS design for double chamber, please consult us.** For flow limiting or overspeed application see dedicated technical
data sheet for face-to-face dimensions.*** Weight for main valves only .
H
ø B
Single chamber
Double chamber
(XG design)*
XGS and XG: Globe pattern main valve
A1
A2
C
Single chamber
Double chamber
ø B
H
XGA: Angle pattern main valve
CD
A
* Weight for main valves only.
XGS design XG designDN A** B C D Weigh*** B C D H Weigh*** Weigh***
mini mini Single chamber Double chamber mm mm mm mm kg mm mm mm mm kg kg
50 230 145 195 80 10.2 173 238 84.5 - 12.1 -65 290 173 230 95 15 198 257 94.5 83 16.6 26.080 310 198 250 102 19.8 226 277 102 82 20.4 31.5100 350 226 270 120 27.1 265 302 120 91 32.2 46.5125 400 226 290 138 38.5 307 396 137 103.5 40.5 60.9150 480 226 290 153 45.7 351 443 152 100 64.9 94.8200 600 351 443 182 78.8 436 567 182 117 115 146.4250 730 436 580 212 132.7 524 609 212 125 153.5 219.6300 850 524 631 242 192.1 606 657 242 125 217.1 295.3350 980 606 657 278 247.4 - - - - - -400 1100 606 657 312 268.4 835 847 355 194.5 481 714500 1250 835 847 367 540 - - - - - - 600 1450 835 847 422.5 708 1085 1229 422.5 - 1205 -700 1650 1085 1229 480 1415 - - - - - -800 1850 - - - - 1355 1407 512.5 2050 -900 2050 1355 1407 562.5 2322 - - - - - -1000 - - Consult us - - - - - - -
DN A1 A2 B C mini. H Weight* Weight* mm mm mm mm mm Single chamber kg Double chamber kg
50 XGA 125 125 173 212 - 11.6 - 65 XGA 145 145 198 232 83 15.4 27.180 XGA 155 155 226 244 82 19.2 33.6
100 XGA 175 175 265 264 91 31.1 45.1150 XGA 225 225 351 380 100 69.4 99.6200 XGA 275 275 436 480 117 103.5 135.2250 XGA 325 325 524 529 125 143.7 209.8300 XGA 400 300 606 571 125 241.1 319.6
Bayard APXA12001 - January, 2012 5
Hydrobloc control valve Some examples...of the most common associated functions
Hydrostab pressure reducing valve Serie K1 10Automatically reduces a higher upstream pressure to a steady lower downstream pressure regardless of variations of flow and/or of upstream pressure.Adjustment ranges • Standard spring
P = 1 to 20 bar• Other
P = 0.2 to 2 barP = 15 to 25 bar (limited to 300XG and 400XGS)Other values, consult us.
• Other PN, consult us.
Hydrostab pressure sustaining / relief valve Serie K1 20Maintains a minimum upstream pressure, by either sustaining or relieving excess pressure to the downstream side.
Adjustment ranges• Standard spring
P = 1 to 20 bar. • Other
P = 0.2 to 2 bar. P = 15 to 25 bar (limited to 300XG and 400XGS).Other values, consult us.
• Other PN, consult us.
Hydrostab pressure reducing / sustainingvalve - Serie K1 50Sustains a minimum upstream pressure and reduces thedownstream pressure to a constant lower value.
Adjustment ranges • Standard spring
P = 1 to 20 bar. • Other
P = 0.2 to 2 bar.P = 15 to 25 bar (limited to 300XG and 400XGS)Other values, consult us.
• Other PN, consult us.
Hydro flow rate limiting valve Serie K2 10Limits the flow rate to a preset value regardless of upstreamand downstream pressures.
Adjustment ranges • VE = 1 to 2.5 m/s (standard)• VE = 2 to 4 m/s• Maximum differential pressure: 10 bar.
Special requirements• Extremely low and high ∆p, please consult us.
Hydro-savy float valve Serie K3 20Closes at top level and fully re-opens at lower adjustable level, allowing water renewal in the reservoir (float pilot located in the reservoir).
Options • Air valve kit for pilot circuit.• Frost protection.• Pressure relief (in case of upstream water hammer).• Manual control for closing.
Hydro altitude valve Serie K3 10Closing at a constant and adjustable top level.Balances the inlet flow rate and the outlet flow rate tillapproximately 0.40 or 0.50 m below the top level.
Adjustment ranges • Standard
H=1.5 to 8 m.• Others
H= 6 to 30 m (others values, consult us).H : altitude difference between the pilot and
the closing level.
Small air valve kitITR KV007
Electric controlITR KE010
Electric controlITR KE010
Upstream-downstream function ITR KH007 + KH012
Pilot frost protectionITR KH037
Upstream pressure sustaining ITR KH007
Upstream pressure sustaining ITR KH008
Limit switchITR KV008
Non-return function ITRITR KH016
Non-return functionITR KH016
Altitude functionITR KH010
Savy upstream pressure sustaining (K370) + frost
protection ITR KH038
Upstream overpressurerelief ITR KH006
PN16 protection bydownstream pilot ITR KH014
Time - based electriccontrol - ITR KE027
Small air valve kitITR KV007
Twin filter circuitITR KH002
Motorised pilotITR KE016
Savy flow limiting (K380) +frost protection ITR KH039
2-level altitudeITR KH029
Upstream overpressurerelief ITR KH006
Hydro-vega float valve Serie K3 40Closes at a constant top level (float pilot located in thereservoir).
Adjustment ranges• According to the location of the pilot valve
in the reservoir.
Options• PN 16. • PN 25 with pilot protection.
6 Bayard APXA12001 - January, 2012
TALIS is always the number one choice whenever water transport or control
is required. TALIS has the best solution for water and energy management,
as well as for industry and municipal applications. With a varied range of
products we offer comprehensive solutions for the entire water cycle. From
hydrants to butterfly valves. From the knife-gate valves to the needle
valves. Our experience, innovative technology, global expertise and
individual consultation process form the basis for developing sustainable
solutions for the efficient handling of the vital resource “water”.
BAYARD
ZI - 4 avenue Lionel Terray
BP 47
69881 Meyzieu cedex France
Tél. + 33 (0)4 37 44 24 24
Fax + 33 (0)4 37 44 24 25
Site: www.bayard.fr
E-mail: [email protected]
Your Choice in Waterflow Control
The
tech
nica
l dat
a an
d pe
rfor
man
ce c
an b
e m
odifi
ed w
ithou
t pri
or n
otic
e de
pend
ing
on th
e te
chni
cal e
volu
tion.