HVF38HVF 38kV Vacuum Circuit Breaker
High Reliability, Long Life
Circuit Breaker Features
38kV Switchgear Features
Low Maintenance• Robust design and rugged compo-
nents increase durability and reduce maintenance
• Back-to-back capacitor switching of 90 MVAR (28kV), far exceeding of ANSI standards
Myers Power Products HVF series vacuum circuit breakers are offered in 1200A, 2000A, 2500A, and 3000A (fan cooled) continuous current. These breakers are designed and manufactured with advanced vacuum technology. They have been tested according to the latest version of ANSI standards in ISO 9001 facilities, and are continuously improved to meet the evolving demands of the market. Myers 38kV breakers are backed by nearly 40 years of switchgear manufacturing expe-rience and have a long record of reliable performance for hundreds of utility, industrial, and transit customers.
• Offered in 31.5kA and 40kA interrupting ratings, allowing you to purchase only the capacity you need
• Self-aligning, self-coupling secondary disconnects ensure positive connection of relay circuits to circuit breaker trip coil
• Secondary disconnects are the most robust in the industry• Heavy-duty utility grade contacts eliminate the need for manual connection of a
plug and socket or umbilical cord• Optional indicator shows breaker position when door is closed• High speed option available
• 10 year lubrication interval• 5 year routine inspection• Service required only on parts sub-
ject to normal wear and aging
• Compact 42 inch wide enclosure• Enclosure accommodates drawout CPTs (up to 15kVA) and drawout PTs above
circuit breaker, reducing lineup length• Closed door racking available• Remote trip/close available• Electric remote racking device available• Manual or electric ground and test device options
Type No. Application StandardRated Voltage (kV)Rated Current (A)Rated Interrupting Current (kA)Rated Close & Latch (kA) Frequency (Hz) Rated Low Freq.Withstand (kV, RMS) Impulse Withstand Vltg. (kV, BIL) Breaking Time (cycles) Operating Duty Operating Life at Rated Current (Times) Closing Operation Operation system Control Voltage Closing & Tripping - Control VoltageAuxiliary ContactsMain Body Weight (Lbs.)
HVF705ANSI C37.06 / ANSI C37.09381200, 2000, 2500, 300031.5 or 4082 or 10460801705 cycles with opt. three cycles available0 -0.3s-CO-3min-CO20,000Motor Spring Stored EnergyDC 48, 110, 125, 220; AC 120, 220DC 48, 110, 125, 220; AC 120, 2204NO + 4NC (Max. 10NO + 10NC)M1200A 750 / 2000A 800 / 2500A 850 / 3000A 850
All circuit breaker ratings are based on K = 1.0
Myers Power Products can retrofi t any of your existing Oil, Vacuum, SF-6, Air Magnetic, or Air Blast circuit breakers with our new modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us today to learn more.
38kV Circuit Breaker Retrofi ts
Three Pole Drawout Units For Use In 38Kv Switchgear For New or Retrofi t Installation
Ratings & Additional Products Description
Current Consumption 38Kv Switchgear Dimensions
38Kv Cell Interior
• Self-aligning, self-coupling secondaries — no manual plug & socket connection required
• Grounded metal shutters• Separate disconnect, test, and connected positions• Full set of ANSI interlocks• Rugged construction
RatedVoltage (V)
Current Consumption (A)
Motor Closing Solenoid Open Solenoid
48 DC 10.5 2.7 2.7110 DC 4.5 1.3 1.3125 DC 4.5 1.5 1.5220 DC 2.3 0.65 0.65120 AC 6.4 1.3 1.3
Nominal Dimensions
Width 42 inchesHeight 110 inchesDepth Indoor: 148 inches
Outdoor, Non Walk In: 152 inches
Outdoor Protected Aisle: 20 Feet
Outdoor Common Aisle: 33 feet
Manual Close Button
Manual Open ButtonCharge IndicatorClose / Open Indicator
Counter
Manual Charging Port
• Drawout potential transformers can be mounted above a circuit breaker• Drawout control power transformers (up to 15kVA) can be mounted above circuit
breaker• Space saving design reduces installation footprint
HVF705ANSI C37.06 / ANSI C37.09381200, 2000, 2500, 300031.5 or 4082 or 10460801705 cycles with opt. three cycles available0 -0.3s-CO-3min-CO20,000Motor Spring Stored EnergyDC 48, 110, 125, 220; AC 120, 220DC 48, 110, 125, 220; AC 120, 2204NO + 4NC (Max. 10NO + 10NC)M1200A 750 / 2000A 800 / 2500A 850 / 3000A 850
Typical Breaker Elements
1
23
45
678
9
1011
12
1314
1516
17
18
19
1. Gear Box2. Manual Charging Port3. Link4. Closing Spring5. Spring Charge Motor6. Tripping Spring7. Spring Charged Indicator8. Limit Switch (S21, S22, S3)9. Open / Closed Indicator10. Dash Pot11. Operations Counter12. Operating Mechanism Enclosure13. Auxiliary Switch (S1)14. Manual Close Button15. Closing Solenoid (Y9)16. Tripping Solenoid (Y1)17. Manual Open Button18. Coupling Bar19. Breaker Shaft
Y1
5
4
8
3
2
M1
S22
S21
1
S3
7
K1
S1
K1
Y9
K1
S3
6
S1
11
12
9
10 16 14
1315
20 18
19 17
24
23
22
21
2 7 5 8 12 10 16 14 20 1824 22
1 6 4 3 11 9 15 1913 1723 21
TRIP
CO
IL
X0
X0
CON
TAC
TSBR
EAKE
R AU
XILI
ARY
MO
TOR
OPE
RATE
D
CLO
SIN
G S
OLE
NO
ID
(SH
UN
T RE
LEA
SE)
AN
TI-P
UM
PIN
G R
ELAY
MEC
HA
NIS
M
COIL
SIG
NA
LSP
RIN
G C
HA
RGE
21
22
22
21
A1
A2
13
1421
22 61
62
8
7
4
6
1
5
A1
A2
K1CONTACTUNIT 53
54
A1
A2
CPLLCTERMINALS (BY CPLLC)
BKR SECONDARYPLUG CONNECTOR
TERMINALS (BY CPLLC)CPLLC
19
10 21
22 24
23
34
33
32
31
42
41
44
43
52
51
64
63
(BY HYUNDAI)
(BY HYUNDAI)
BKR SECONDARYPLUG CONNECTOR
BKR CELLRECEPTACLE(BY HYUNDAI)
BKR CELLRECEPTACLE(BY HYUNDAI)
13
14
EC-5
EC-4
EC-8
EC-3
EC-2
EC-1
EC-7
EC-6
T6 T1
T5
T8
T7
EC-11
EC-12
EC-9
EC-10 ED-4 ED-2
ED-3 ED-1
ED-8 ED-6
ED-7 ED-5 ED-9
ED-10ED-12
ED-11
LEGEND
M1 CHARGING MOTOR 52CC CLOSING OLENOID S AUXILIARY SWITCH
LS1, LS2, LS3 LIMIT SWITCH 52TC TRIPPING OLENOID R1 RESISTOR
XO PLUG/SOCKET Y ANTI PUMPING RELAY R2 RESISTOR
Description of HVF Vacuum Circuit Breaker
Typical Circuit Diagram
Specifi cations are subject to change without notice.
0411
2018
www.myerspowerproducts.com | (866) MY-MYERS