hvac calcs

34
EQUIPMENT LIST INSIDE PIB BUILDING, BULK PLANT, JIZAN HEAT** DISSIPATION IDENT. EQUIPMENT TAG DESCRITION Peff Unit REMARK 1 ELECTRICAL ROOM EQUIPMENTS 2 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 3 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 4 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 3 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 6 LIGHTING PANELBOARD 300 W NOTE - 1 7 POWER PANELBOARD 450 W NOTE - 1 8 DRY TYPE TRANSFORMER (5kva, assumed) 500 W NOTE - 1 9 UPS SYSTEM PANEL 300 W NOTE - 2 10 UPS PANELBOARD 300 W NOTE - 2 480VAC PANELBOARD 300 W 11 125VDC PANELBOARD 300 W NOTE - 2 12 DC CHARGER 1200 W NOTE - 2 13 LCP 300 W NOTE - 1 14 15 SUB TOTAL 14350 W 16 RACK ROOM EQUIPMENTS MARSHALLING CABINET 500 NOTE - 1 ELECT/INST INTERFACE CABINET 300 NOTE - 1 PLC CABINET 500 NOTE - 1 MOV MASTER STATION (PAKSKAN) 400 NOTE - 1 VIB/TEMP MONITORING SYSTEM 100 NOTE - 1 LDS SYSTEM CABINET 100 NOTE - 1 METERING SYSTEM/FLOW COMPUTORS 450 NOTE - 1 DACS SERVERS (2 EA)/FTE SWICHES 750 NOTE - 1 PRINTERS (2EA) 400 NOTE - 1 ENGINEERING WORK STATION (2EA) 450 NOTE - 1 METERING SUPERVISORY COMPUTERS (2EA) 900 NOTE - 1 DACS SERVERS/WORKSTATION 900 NOTE - 1 CODITON MONITORING SYS (W/STATION) 450 NOTE - 1 LEAK DETECTION SYSTEM 450 NOTE - 1 SUB TOTAL 6650 W 17 BATTERY ROOM EQUIPMENTS 18 SWITCHGEAR BATTERIES (15 kva, 15 batts) 750 W NOTE - 2 19 UPS BATTERIES (15 kva, 15 batts) 750 W NOTE - 2 20 BATTERY DISCONNECT SWITCH (2 SETS) 150 W NOTE - 2 21 NOTE - 1 22 23 SUB TOTAL 1650 W 24 25 UPS ROOM EQUIPMENTS 26 EQUIPMENT LIST HOLD 2500 W NOTE - 2 27 MISCELLANEOUS 250 W NOTE - 1 28 29 SUB TOTAL 2750 W

Upload: tando-tsepane

Post on 30-Mar-2015

610 views

Category:

Documents


16 download

TRANSCRIPT

Page 1: HVAC CALCS

EQUIPMENT LIST INSIDE PIB BUILDING, BULK PLANT, JIZAN

HEAT** DISSIPATION

IDEN

T.

EQUIPMENT TAG DESCRITION Peff Unit

REMARK

1 ELECTRICAL ROOM EQUIPMENTS 2 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 3 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 4 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 3 4.16 KVA SWITCHGEAR 2600 W NOTE - 2 6 LIGHTING PANELBOARD 300 W NOTE - 1 7 POWER PANELBOARD 450 W NOTE - 1 8 DRY TYPE TRANSFORMER (5kva, assumed) 500 W NOTE - 1 9 UPS SYSTEM PANEL 300 W NOTE - 2

10 UPS PANELBOARD 300 W NOTE - 2 480VAC PANELBOARD 300 W

11 125VDC PANELBOARD 300 W NOTE - 2 12 DC CHARGER 1200 W NOTE - 2 13 LCP 300 W NOTE - 1 14 15 SUB TOTAL 14350 W 16 RACK ROOM EQUIPMENTS MARSHALLING CABINET 500 NOTE - 1 ELECT/INST INTERFACE CABINET 300 NOTE - 1 PLC CABINET 500 NOTE - 1 MOV MASTER STATION (PAKSKAN) 400 NOTE - 1 VIB/TEMP MONITORING SYSTEM 100 NOTE - 1 LDS SYSTEM CABINET 100 NOTE - 1 METERING SYSTEM/FLOW COMPUTORS 450 NOTE - 1 DACS SERVERS (2 EA)/FTE SWICHES 750 NOTE - 1 PRINTERS (2EA) 400 NOTE - 1 ENGINEERING WORK STATION (2EA) 450 NOTE - 1 METERING SUPERVISORY COMPUTERS (2EA) 900 NOTE - 1 DACS SERVERS/WORKSTATION 900 NOTE - 1 CODITON MONITORING SYS (W/STATION) 450 NOTE - 1 LEAK DETECTION SYSTEM 450 NOTE - 1 SUB TOTAL 6650 W

17 BATTERY ROOM EQUIPMENTS 18 SWITCHGEAR BATTERIES (15 kva, 15 batts) 750 W NOTE - 2 19 UPS BATTERIES (15 kva, 15 batts) 750 W NOTE - 2 20 BATTERY DISCONNECT SWITCH (2 SETS) 150 W NOTE - 2 21 NOTE - 1 22 23 SUB TOTAL 1650 W 24 25 UPS ROOM EQUIPMENTS 26 EQUIPMENT LIST HOLD 2500 W NOTE - 2 27 MISCELLANEOUS 250 W NOTE - 1 28 29 SUB TOTAL 2750 W

Page 2: HVAC CALCS

NOTES: 1. EQUIPMENT SIZE AND QUANTITY TO BE DETERMINED LATTER.

2. WAITING FOR INFORMATION.

3. ** ESTIMATION OF HEAT DISSPATION IS BASED ON BEST ENGINEERING PRACTICES IN ACTUAL SUB STATION INSTALLATIONS.

COMMUNICATION ROOM EQUIPMENTS SERVERS Etc. 2500 W

30 SUB TOTAL 2500 W

31 HVAC MECHANICAL ROOM EQUIPMENTS 32 HVAC CONTROL PANEL 450 W NOTE - 1 33 AHU DISCONNECT SWITCH 150 W NOTE - 1 34 AIR HANDLING UNIT 500 W NOTE - 1 35 NOTE - 1 36 37 SUB TOTAL 1100 W 38 39 40 TOTAL

Page 3: HVAC CALCS

PIB BUILDING, JIZANHVAC Load Analysis

for

PIB BUILDING, JIZAN (CONDITION-II)BULK PLANT, JIZAN

S'ARAMCO

Prepared By:

ArifAMCDE

P. B. # 2502AL-KHOBAR-31952

03-858-8877 Extn. 231Saturday, January 23, 2010

Page 4: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 2

General Project Data Input

General Project InformationProject file name: C:\OLD COMPUTER\MYCOMPUTER\NEW

D\ARIF\MYDOCU~1\KBR\PHIL TAYLOR- SUB#2,3&4 PIB SHELTOR-\PIB\PRELIM CALCS COND-II PIB.CHVProject title: PIB BUILDING, JIZANProject date: 02 DEC'2009Project comment: ONDITION-II: Cooling Load is calculated with Summer Design Wet

Bulb and Mean coincident Dry Bulb TemperaturesWeather reference city: JIZAN, SAUDI ARABIAClient name: PIB BUILDING, JIZAN (CONDITION-II)Client address: BULK PLANT, JIZANClient city: S'ARAMCOCompany name: AMCDECompany representative: ArifCompany address: P. B. # 2502Company city: AL-KHOBAR-31952Company phone: 03-858-8877 Extn. 231Company fax: 03-858-0061Company e-mail address: [email protected]

Barometric pressure: 29.910 in.Hg.Altitude: 10 feetLatitude: 17 DegreesMean daily temperature range: 14 DegreesStarting & ending time for HVAC load calculations: 1am - 12amNumber of unique zones in this project: 6

Building Default ValuesCalculations performed: Both heating and cooling loadsLighting requirements: 2.50 Watts per square footEquipment requirements: 3.00 Watts per square footPeople sensible load multiplier: 250 Btuh per personPeople latent load multiplier: 200 Btuh per personZone sensible safety factor: 10 %Zone latent safety factor: 10 %Zone heating safety factor: 10 %People diversity factor: 100 %Lighting profile number: 1Equipment profile number: 1People profile number: 1Building default ceiling height: 0.00 feetBuilding default wall height: 17.00 feet

Internal Operating Load Profiles (C = 100)hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 C C C C C C C C C C C C C C C C C C C C C C C C2 C C C C C C C C C C C C C C C C C C C C C C C C3 C C C C C C C C C C C C C C C C C C C C C C C C4 C C C C C C C C C C C C C C C C C C C C C C C C5 C C C C C C C C C C C C C C C C C C C C C C C C6 C C C C C C C C C C C C C C C C C C C C C C C C7 C C C C C C C C C C C C C C C C C C C C C C C C8 C C C C C C C C C C C C C C C C C C C C C C C C9 C C C C C C C C C C C C C C C C C C C C C C C C

10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 5: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 3

General Project Data Input (cont'd)

Building-Level Design Conditions DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 93 86 50% 72 120.37 7August 86 86 50% 72 132.09 0Winter 68 72

Master RoofsRoofNo.

ASHRAERoof#

RoofU-Fac

DarkColor

Susp.Ceil

1 6 0.080 Yes NoRoof #1 Description: Flat roof, 6" lightweight concrete deck with 2" insulation, no ceiling below

Master WallsWallNo.

ASHRAEGroup

WallU-Fac

WallColor

1 B 0.144 DWall #1 Description: Block wall, 8" sand & gravel, filled core, bare block exterior, interior finish

Master GlassGlassNo.

SummerU-Factor

WinterU-Factor

GlassShd.Coef.

InteriorShading

InteriorShd.Coef

1 0.610 0.760 0.850 2 0.640

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 6: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 4

Air Handler Input

Air Handler Number 1 Input Data

Name: AHU-1 Or 2Terminal type: Constant VolumeMethod for CV Sum of PeaksSupply fan type: Draw-thru fanCalculations performed: Both heating and cooling loadsExcess supply air: ReserveOccurrences: 1People profile number: 1Lighting profile number: 1Equipment profile number: 1Exhaust may not exceed supply air: NoLeaving heating coil temp (deg.F): 110.0Leaving cooling coil temp (deg.F): 56.0Cooling coil CFM 0Misc. Btuh gain - supply side: 0Misc. Btuh gain - return side: 0Combined fan & motor efficiency: 65Static pressure across fan (in.wg.): 1.20Summer supply duct temp rise (deg.F): 0.000Summer return duct temp rise (deg.F): 0.000Winter supply duct temp drop (deg.F): 0.000Winter return duct temp drop (deg.F): 0.000Chilled water temp difference (deg.F): 0.000Hot water temp difference (deg.F): 0.000Cooling ventilation: 1000 DirectCooling infiltration: 0 DirectHeating ventilation: 1000 DirectHeating infiltration: 0 DirectPretreated outside air: nonePretreated air Summer DB (deg.F): 0Pretreated air Summer WB (deg.F): 0Pretreated air Winter DB (deg.F): 0 DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 93 86 50% 74 116.97 7August 86 86 50% 74 128.71 0Winter 68 72

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 7: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 5

Zone Input

Zone 1: BATTERY RM (120 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 12.00 Zone width (feet): 10.00Lighting Watts: 300 Equipment Watts: 1,650Number of people in zone: 0 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200Cooling ventilation method: Direct Cooling ventilation value: 500.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 500.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 500 Summer exhaust air CFM: 500Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 12.00 10.00 120.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 10.00 150.0 S

Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 33.00 Zone width (feet): 16.50Lighting Watts: 1,361 Equipment Watts: 1,200Number of people in zone: 1 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250Cooling ventilation method: Direct Cooling ventilation value: 100.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 100.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 33.00 16.00 528.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 33.00 495.0 W2 1 B 0.144 D 15.00 16.50 247.5 N3 1 B 0.144 D 15.00 16.50 247.5 S DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 93 86 50% 75 114.08 4August 86 86 50% 75 125.80 -3Winter 68 72

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 8: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 6

Zone Input (cont'd)

Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)

Zone 3: COMMUNICATION RM (90 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 9.00 Zone width (feet): 10.00Lighting Watts: 225 Equipment Watts: 1,500Number of people in zone: 1 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250Cooling ventilation method: Direct Cooling ventilation value: 50.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 50.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 9.00 10.00 90.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 9.00 135.0 N

Zone 4: UPS RM (120 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 10.00 Zone width (feet): 12.00Lighting Watts: 300 Equipment Watts: 2,750Number of people in zone: 1 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250Cooling ventilation method: Direct Cooling ventilation value: 50.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 50.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 10.00 12.00 120.0 No

Zone 5: RACK RM (759 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 33.00 Zone width (feet): 23.00Lighting Watts: 1,898 Equipment Watts: 6,650Number of people in zone: 3 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 9: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 7

Zone Input (cont'd)

Zone 5: RACK RM (759 sq.ft) (Group 1)Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200Cooling ventilation method: Direct Cooling ventilation value: 150.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 150.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 33.00 23.00 759.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 23.00 345.0 N2 1 B 0.144 D 15.00 23.00 345.0 S

Zone 6: ELECTRICAL RM (660 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 33.00 Zone width (feet): 20.00Lighting Watts: 1,650 Equipment Watts: 14,350Number of people in zone: 0 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200Cooling ventilation method: Direct Cooling ventilation value: 150.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 150.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 33.00 20.00 660.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 20.00 300.0 N2 1 B 0.144 D 15.00 33.00 495.0 E3 1 B 0.144 D 15.00 20.00 300.0 S DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 93 86 50% 75 114.08 4August 86 86 50% 75 125.80 -3Winter 68 72

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 10: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 8

Building Envelope Report

Envelope Report Using Summer U-Factors

MaterialTypes

GrossArea

GlassArea

NetArea

-U-Factor

Area xU-Factor

AverageU-Factor

Roof 1 2,277.0 0.0 2,277.0 0.080 182.160 0.080Tot.Roof 2,277.0 0.0 2,277.0 N/A 182.160 0.080

Wall 1 3,060.0 0.0 3,060.0 0.144 440.640 0.144Tot.Wall 3,060.0 0.0 3,060.0 N/A 440.640 0.144

Totals 5,337.0 622.800 0.117

WallDirection

WallArea

GlassArea

Wall NetArea

Wall AvgU-Factor

Glass AvgU-Factor

Glass AvgShd.Coef

N 1,027.5 0.0 1,027.5 0.144 0.000 0.000NE 0.0 0.0 0.0 0.000 0.000 0.000E 495.0 0.0 495.0 0.144 0.000 0.000SE 0.0 0.0 0.0 0.000 0.000 0.000S 1,042.5 0.0 1,042.5 0.144 0.000 0.000SW 0.0 0.0 0.0 0.000 0.000 0.000W 495.0 0.0 495.0 0.144 0.000 0.000NW 0.0 0.0 0.0 0.000 0.000 0.000

Totals 3,060.0 0.0 3,060.0 0.144 0.000 0.000

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 11: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 9

Building Summary Loads Building peaks in July at 5pm.

Bldg LoadDescriptions

AreaQuan

SenLoss

%TotLoss

LatGain

SenGain

NetGain

%NetGain

Roof 2,277 802 11.35 0 13,537 13,537 5.13Wall 3,060 1,939 27.47 0 9,689 9,689 3.67Glass 0 0 0.00 0 0 0 0.00Floor Slab 0 0 0.00 0 0 0 0.00

Skin Loads 2,740 38.82 0 23,226 23,226 8.80

Lighting 5,734 0 0.00 0 21,521 21,521 8.16Equipment 28,100 0 0.00 0 105,469 105,469 39.97People 6 0 0.00 1,485 1,650 3,135 1.19Partition 0 0 0.00 0 0 0 0.00Cool. Pret. 0 0 0.00 0 0 0 0.00Heat. Pret. 0 0 0.00 0 0 0 0.00Cool. Vent. 1,000 0 0.00 80,155 19,793 99,948 37.88Heat. Vent. 1,000 4,318 61.18 0 0 0 0.00Cool. Infil. 0 0 0.00 0 0 0 0.00Heat. Infil. 0 0 0.00 0 0 0 0.00Draw-Thru Fan 0 0 0.00 0 6,096 6,096 2.31Blow-Thru Fan 0 0 0.00 0 0 0 0.00Reserve Cap. 0 0 0.00 0 4,474 4,474 1.70Reheat Cap. 0 0 0.00 0 0 0 0.00Supply Duct 0 0 0.00 0 0 0 0.00Return Duct 0 0 0.00 0 0 0 0.00Misc. Supply 0 0 0.00 0 0 0 0.00Misc. Return 0 0 0.00 0 0 0 0.00

Building Totals 7,059 100.00 81,640 182,228 263,869 100.00

BuildingSummary

SenLoss

%TotLoss

LatGain

SenGain

NetGain

%NetGain

Ventilation 4,318 61.18 80,155 19,793 99,948 37.88Infiltration 0 0.00 0 0 0 0.00Pretreated Air 0 0.00 0 0 0 0.00Zone Loads 2,740 38.82 1,485 156,340 157,825 59.81Plenum Loads 0 0.00 0 0 0 0.00Fan & Duct Loads 0 0.00 0 6,096 6,096 2.31

Building Totals 7,059 100.00 81,640 182,228 263,869 100.00

Check FiguresTotal Building Supply Air (based on a 18° TD): 8,272 CFMTotal Building Vent. Air (12.09% of Supply): 1,000 CFM

Total Conditioned Air Space: 2,294 Sq.ftSupply Air Per Unit Area: 3.6067 CFM/Sq.ftArea Per Cooling Capacity: 104.3 Sq.ft/TonCooling Capacity Per Area: 0.0096 Tons/Sq.ftHeating Capacity Per Area: 3.08 Btuh/Sq.ft

Total Heating Required With Outside Air: 7,059 BtuhTotal Cooling Required With Outside Air: 21.99 Tons

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 12: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 10

Air Handler #1 - AHU-1 Or 2 - Summary Loads

ZnNo

DescriptionZone Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

1 BATTERY RM7pm July

1200

1,800

13750

0.42

8,527506

4.22

0500500

Direct50050

Direct500

61

2 HVAC MECH RM8pm July

5451

8,168

813297

0.54

16,492818

1.50

27500

Direct100297

Direct100

99

3COMMUNICATION RM7pm July

901

1,350

11743

0.48

7,802463

5.14

27500

Direct5043

Direct5056

4 UPS RM6pm July

1201

1,800

4215

0.13

12,474740

6.17

27500

Direct5015

Direct5089

5 RACK RM6pm July

7593

11,385

704257

0.34

39,9392,3693.12

66000

Direct150257

Direct150286

6 ELECTRICAL RM7pm July

6600

9,900

926338

0.51

68,0503,3765.12

000

Direct150338

Direct150408

Zone Peak Totals:Total Zones: 6Unique Zones: 6

2,2946

34,403

2,7401,0000.44

153,2848,2733.61

1,485500500

1,0001,000

1,0001,000

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 13: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 11

Air Handler #1 - AHU-1 Or 2 - Total Load Summary Air Handler Description: AHU-1 Or 2 Constant Volume - Sum of PeaksSupply Air Fan: Draw-Thru with program estimated horsepower of 2.40 HPFan Input: 65% motor and fan efficiency with 1.2 in. water across the fanSensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in July. Outdoor Conditions: Clg: 92° DB, 86° WB, 181.09 grains, Htg: 68° DBIndoor Conditions: Clg: 74° DB (avg.), 50% RH, Htg: 72° DB

Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in July at 7pm is different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 153,158.

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Zone Space sensible loss: 2,740 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 4,318 Btuh 1,000 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 7,059 Btuh

Heating Supply Air: 2,740 / (1.000 X 1.08 X 3) = 1,000 CFMWinter Vent Outside Air (100.0% of supply) = 1,000 CFM

Zone space sensible gain: 151,866 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 6,096 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 4,474 BtuhTotal sensible gain on supply side of coil: 162,436 Btuh

Cooling Supply Air: 163,727 / (1.000 X 1.1 X 18) = 8,272 CFMSummer Vent Outside Air (12.1% of supply) = 1,000 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: 19,793 Btuh 1,000 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: 19,793 BtuhTotal sensible gain on air handling system: 182,228 Btuh

Zone space latent gain: 1,485 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 80,155 BtuhTotal latent gain on air handling system: 81,640 BtuhTotal system sensible and latent gain: 263,869 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 18° TD): 8,272 CFMTotal Air Handler Vent. Air (12.09% of Supply): 1,000 CFM

Total Conditioned Air Space: 2,294 Sq.ftSupply Air Per Unit Area: 3.6067 CFM/Sq.ftArea Per Cooling Capacity: 104.3 Sq.ft/TonCooling Capacity Per Area: 0.0096 Tons/Sq.ftHeating Capacity Per Area: 3.08 Btuh/Sq.ft

Total Heating Required With Outside Air: 7,059 BtuhTotal Cooling Required With Outside Air: 21.99 Tons

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 14: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 12

Zone Detailed Loads (At Zone Peak Times)

LoadDescription

UnitQuan

-SC-CFAC

CLTDSHGF

U.Fac-CLF-

Sen.Gain

Lat.Gain

Htg.Mult.

Htg.Loss

Zone 1-BATTERY RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 12.0 x 10.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 120 1.00 69.1 0.080 664 0.320 38Wall-1-S-B-D 150 1 20.1 0.144 435 0.576 86Lights-Prof=1 300 1.000 1,024Equipment-Prof=1 1,650 1.000 5,630 0

Sub-total 7,752 0 125Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 8,527 0 137

Zone 2-HVAC MECH RM peaks (sensible) in July at 8pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 16.5, Construction Type: 22 (Medium), SIDB: 75°F, WIDB: 72°F

Roof-1-6-No.Clg-D 528 1.00 61.1 0.080 2,582 0.320 169Wall-1-W-B-D 495 1 28.1 0.144 2,005 0.576 285Wall-2-N-B-D 248 1 21.6 0.144 771 0.576 143Wall-3-S-B-D 248 1 18.1 0.144 646 0.576 143Lights-Prof=1 1,361 1.000 4,645Equipment-Prof=1 1,200 1.000 4,095 0People-Prof=1 1.0 1.000 250 250

Sub-total 14,993 250 739Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 16,492 275 813

Zone 3-COMMUNICATION RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 9.0 x 10.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 90 1.00 69.1 0.080 498 0.320 29Wall-1-N-B-D 135 1 23.6 0.144 459 0.576 78Lights-Prof=1 225 1.000 768Equipment-Prof=1 1,500 1.000 5,118 0People-Prof=1 1.0 1.000 250 250

Sub-total 7,093 250 107Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 7,802 275 117

Zone 4-UPS RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 10.0 x 12.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 120 1.00 71.1 0.080 683 0.320 38Lights-Prof=1 300 1.000 1,024Equipment-Prof=1 2,750 1.000 9,383 0People-Prof=1 1.0 1.000 250 250

Sub-total 11,340 250 38Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 12,474 275 42

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 15: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 13

Zone Detailed Loads (At Zone Peak Times) (cont'd)

LoadDescription

UnitQuan

-SC-CFAC

CLTDSHGF

U.Fac-CLF-

Sen.Gain

Lat.Gain

Htg.Mult.

Htg.Loss

Zone 5-RACK RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 23.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 759 1.00 71.1 0.080 4,319 0.320 243Wall-1-N-B-D 345 1 22.6 0.144 1,124 0.576 199Wall-2-S-B-D 345 1 19.1 0.144 950 0.576 199Lights-Prof=1 1,898 1.000 6,475Equipment-Prof=1 6,650 1.000 22,691 0People-Prof=1 3.0 1.000 750 600

Sub-total 36,308 600 640Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 39,939 660 704

Zone 6-ELECTRICAL RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 20.0, Construction Type: 1 (Light), SIDB: 75°F, WIDB: 72°F

Roof-1-6-No.Clg-D 660 1.00 66.1 0.080 3,491 0.320 211Wall-1-N-B-D 300 1 20.6 0.144 891 0.576 173Wall-2-E-B-D 495 1 30.1 0.144 2,147 0.576 285Wall-3-S-B-D 300 1 17.1 0.144 740 0.576 173Lights-Prof=1 1,650 1.000 5,630Equipment-Prof=1 14,350 1.000 48,964 0

Sub-total 61,864 0 842Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 68,050 0 926

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 16: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 14

Air System #1 (AHU-1 Or 2) Psychrometric Analysis

System Load Analysis Latent Grains Sensible Temp CFMLeaving Coil Condition 62.240 56.000Draw-Thru Fan 6,096 0.670 308Misc Load on Supply Side 0 0.000 0Supply Air Duct 0 0.000 0Zone Loads 1,485 0.264 153,158 16.838 7,738Sensible Reserve 4,474 0.492 226

Zone Condition 1,485 62.504 163,727 73.654 8,272Return Air Duct 0 0.000Return Air Plenum 0 0.000Misc Load on Return Side 0 0.000Vent Air 1,000 CFM 80,155 14.255 19,793 2.176Blow-Thru Fan 0 0.000

Entering Coil Condition 81,640 76.759 183,520 76.176 8,272

General Psychrometric Equations Used In Analysis:PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)TSH = PR x 1.10 x CFM x (DB entering - DB leaving)TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving) TSH = 1.000 x 1.10 x 8,272 x ( 76.176 - 56.000 ) = 183,519 BtuhTLH = 1.000 x 0.68 x 8,272 x ( 76.759 - 62.240 ) = 81,640 Btuh

----------SUM = 265,160 BtuhGTH = 1.000 x 4.50 x 8,272 x ( 30.290 - 23.097 ) = 267,661 BtuhTotal System Load = 263,869 Btuh

Chilled and Hot Water Flow Rates and Steam RequirementCooling GPM = 267,661 / ( 0.00 x 500 ) = 0.0 GPMHeating GPM = 7,059 / ( 0.00 x 500 ) = 0.0 GPMSteam Req. = 7,059 / 0 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil ConditionsDry bulb temperature: 76.18 Dry bulb temperature: 68.00Wet bulb temperature: 65.47Relative humidity: 56.91Enthalpy: 30.29 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil ConditionsDry bulb temperature: 56.00 Dry bulb temperature: 74.54Wet bulb temperature: 54.86Relative humidity: 93.26Enthalpy: 23.10 Btu/lbm

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 17: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 15

Air System #1 (AHU-1 Or 2) Psychrometric Chart ZC Zone Condition OC Outdoor ConditionLC Leaving Coil Condition EC Entering Coil ConditionSD Supply Duct Temperature Rise RD Return Duct Temperature RiseDTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible GainRE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible GainSM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous GainPRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 18: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 16

Building Pie Charts Building peaks in July at 5pm.

Building Net Gain263,869

Btuh

Roof - 5.13%Wall - 3.67%

Lighting - 8.16%

Equipment - 39.97%

People - 1.19%

Cool. Vent. - 37.88%

Draw-Thru Fan - 2.31%Reserve Cap. - 1.70%

Building Loss 7,059

Btuh

Roof - 11.35%

Wall - 27.47%

Heat. Vent. - 61.18%

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM

Page 19: HVAC CALCS

PIB BUILDING, JIZANHVAC Load Analysis

for

PIB BUILDING, JIZAN (CONDITION-1)BULK PLANT, JIZAN

S'ARAMCO

Prepared By:

ArifAMCDE

P. B. # 2502AL-KHOBAR-31952

03-858-8877 Extn. 231Saturday, January 23, 2010

Page 20: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 2

General Project Data Input

General Project InformationProject file name: C:\OLD COMPUTER\MYCOMPUTER\NEW

D\ARIF\MYDOCU~1\KBR\PHIL TAYLOR- SUB#2,3&4 PIB SHELTOR-\PIB\PRELIM CALCS COND-1 PIB.CHVProject title: PIB BUILDING, JIZANProject date: 02 DEC'2009Project comment: ONDITION-I: Cooling Load is calculated with Summer Design Dry

Bulb and Mean coincident Wet Bulb TemperaturesWeather reference city: JIZAN, SAUDI ARABIAClient name: PIB BUILDING, JIZAN (CONDITION-1)Client address: BULK PLANT, JIZANClient city: S'ARAMCOCompany name: AMCDECompany representative: ArifCompany address: P. B. # 2502Company city: AL-KHOBAR-31952Company phone: 03-858-8877 Extn. 231Company fax: 03-858-0061Company e-mail address: [email protected]

Barometric pressure: 29.910 in.Hg.Altitude: 10 feetLatitude: 17 DegreesMean daily temperature range: 14 DegreesStarting & ending time for HVAC load calculations: 1am - 12amNumber of unique zones in this project: 6

Building Default ValuesCalculations performed: Both heating and cooling loadsLighting requirements: 2.50 Watts per square footEquipment requirements: 3.00 Watts per square footPeople sensible load multiplier: 250 Btuh per personPeople latent load multiplier: 200 Btuh per personZone sensible safety factor: 10 %Zone latent safety factor: 10 %Zone heating safety factor: 10 %People diversity factor: 100 %Lighting profile number: 1Equipment profile number: 1People profile number: 1Building default ceiling height: 0.00 feetBuilding default wall height: 17.00 feet

Internal Operating Load Profiles (C = 100)hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 C C C C C C C C C C C C C C C C C C C C C C C C2 C C C C C C C C C C C C C C C C C C C C C C C C3 C C C C C C C C C C C C C C C C C C C C C C C C4 C C C C C C C C C C C C C C C C C C C C C C C C5 C C C C C C C C C C C C C C C C C C C C C C C C6 C C C C C C C C C C C C C C C C C C C C C C C C7 C C C C C C C C C C C C C C C C C C C C C C C C8 C C C C C C C C C C C C C C C C C C C C C C C C9 C C C C C C C C C C C C C C C C C C C C C C C C

10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 21: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 3

General Project Data Input (cont'd)

Building-Level Design Conditions DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 99 82 50% 72 80.06 13August 99 82 50% 72 80.06 13Winter 68 72

Master RoofsRoofNo.

ASHRAERoof#

RoofU-Fac

DarkColor

Susp.Ceil

1 6 0.080 Yes NoRoof #1 Description: Flat roof, 6" lightweight concrete deck with 2" insulation, no ceiling below

Master WallsWallNo.

ASHRAEGroup

WallU-Fac

WallColor

1 B 0.144 DWall #1 Description: Block wall, 8" sand & gravel, filled core, bare block exterior, interior finish

Master GlassGlassNo.

SummerU-Factor

WinterU-Factor

GlassShd.Coef.

InteriorShading

InteriorShd.Coef

1 0.610 0.760 0.850 2 0.640

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 22: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 4

Air Handler Input

Air Handler Number 1 Input Data

Name: AHU-1 Or 2Terminal type: Constant VolumeMethod for CV Sum of PeaksSupply fan type: Draw-thru fanCalculations performed: Both heating and cooling loadsExcess supply air: ReserveOccurrences: 1People profile number: 1Lighting profile number: 1Equipment profile number: 1Exhaust may not exceed supply air: NoLeaving heating coil temp (deg.F): 110.0Leaving cooling coil temp (deg.F): 56.0Cooling coil CFM 0Misc. Btuh gain - supply side: 0Misc. Btuh gain - return side: 0Combined fan & motor efficiency: 65Static pressure across fan (in.wg.): 1.20Summer supply duct temp rise (deg.F): 0.000Summer return duct temp rise (deg.F): 0.000Winter supply duct temp drop (deg.F): 0.000Winter return duct temp drop (deg.F): 0.000Chilled water temp difference (deg.F): 0.000Hot water temp difference (deg.F): 0.000Cooling ventilation: 1000 DirectCooling infiltration: 0 DirectHeating ventilation: 1000 DirectHeating infiltration: 0 DirectPretreated outside air: nonePretreated air Summer DB (deg.F): 0Pretreated air Summer WB (deg.F): 0Pretreated air Winter DB (deg.F): 0 DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 99 82 50% 74 76.65 13August 99 82 50% 74 76.65 13Winter 68 72

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 23: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 5

Zone Input

Zone 1: BATTERY RM (120 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 12.00 Zone width (feet): 10.00Lighting Watts: 300 Equipment Watts: 1,650Number of people in zone: 0 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200Cooling ventilation method: Direct Cooling ventilation value: 500.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 500.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 500 Summer exhaust air CFM: 500Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 12.00 10.00 120.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 10.00 150.0 S

Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 33.00 Zone width (feet): 16.50Lighting Watts: 1,361 Equipment Watts: 1,200Number of people in zone: 1 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250Cooling ventilation method: Direct Cooling ventilation value: 100.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 100.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 33.00 16.00 528.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 33.00 495.0 W2 1 B 0.144 D 15.00 16.50 247.5 N3 1 B 0.144 D 15.00 16.50 247.5 S DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 99 82 50% 75 73.77 10August 99 82 50% 75 73.77 10Winter 68 72

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 24: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 6

Zone Input (cont'd)

Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)

Zone 3: COMMUNICATION RM (90 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 9.00 Zone width (feet): 10.00Lighting Watts: 225 Equipment Watts: 1,500Number of people in zone: 1 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250Cooling ventilation method: Direct Cooling ventilation value: 50.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 50.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 9.00 10.00 90.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 9.00 135.0 N

Zone 4: UPS RM (120 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 10.00 Zone width (feet): 12.00Lighting Watts: 300 Equipment Watts: 2,750Number of people in zone: 1 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250Cooling ventilation method: Direct Cooling ventilation value: 50.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 50.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 10.00 12.00 120.0 No

Zone 5: RACK RM (759 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 33.00 Zone width (feet): 23.00Lighting Watts: 1,898 Equipment Watts: 6,650Number of people in zone: 3 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 25: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 7

Zone Input (cont'd)

Zone 5: RACK RM (759 sq.ft) (Group 1)Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200Cooling ventilation method: Direct Cooling ventilation value: 150.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 150.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 33.00 23.00 759.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 23.00 345.0 N2 1 B 0.144 D 15.00 23.00 345.0 S

Zone 6: ELECTRICAL RM (660 sq.ft) (Group 1)

Air Handler number: 1 Zone occurrences: 1Zone length: (feet) 33.00 Zone width (feet): 20.00Lighting Watts: 1,650 Equipment Watts: 14,350Number of people in zone: 0 People profile number: 1Lighting profile number: 1 Equipment profile number: 1Ceiling height (feet): 15.00 Heating safety factor (%): 10Sensible safety factor (%): 10 Latent safety factor (%): 10Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200Cooling ventilation method: Direct Cooling ventilation value: 150.000Cooling infiltration method: Direct Cooling infiltration value: 0.000Heating ventilation method: Direct Heating ventilation value: 150.000Heating infiltration method: Direct Heating infiltration value: 0.000Winter exhaust air CFM: 0 Summer exhaust air CFM: 0Minimum supply CFM: 0 Latent Btuh equipment load: 0Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0Both heating and cooling loads are calculated for this zone. Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil

1 1 6 0.080 Yes 33.00 20.00 660.0 No Wall Type ASHRAE# U-Factor Color Height Width Area Direction

1 1 B 0.144 D 15.00 20.00 300.0 N2 1 B 0.144 D 15.00 33.00 495.0 E3 1 B 0.144 D 15.00 20.00 300.0 S DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

July 99 82 50% 75 73.77 10August 99 82 50% 75 73.77 10Winter 68 72

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 26: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 8

Building Envelope Report

Envelope Report Using Summer U-Factors

MaterialTypes

GrossArea

GlassArea

NetArea

-U-Factor

Area xU-Factor

AverageU-Factor

Roof 1 2,277.0 0.0 2,277.0 0.080 182.160 0.080Tot.Roof 2,277.0 0.0 2,277.0 N/A 182.160 0.080

Wall 1 3,060.0 0.0 3,060.0 0.144 440.640 0.144Tot.Wall 3,060.0 0.0 3,060.0 N/A 440.640 0.144

Totals 5,337.0 622.800 0.117

WallDirection

WallArea

GlassArea

Wall NetArea

Wall AvgU-Factor

Glass AvgU-Factor

Glass AvgShd.Coef

N 1,027.5 0.0 1,027.5 0.144 0.000 0.000NE 0.0 0.0 0.0 0.000 0.000 0.000E 495.0 0.0 495.0 0.144 0.000 0.000SE 0.0 0.0 0.0 0.000 0.000 0.000S 1,042.5 0.0 1,042.5 0.144 0.000 0.000SW 0.0 0.0 0.0 0.000 0.000 0.000W 495.0 0.0 495.0 0.144 0.000 0.000NW 0.0 0.0 0.0 0.000 0.000 0.000

Totals 3,060.0 0.0 3,060.0 0.144 0.000 0.000

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 27: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 9

Building Summary Loads Building peaks in July at 5pm.

Bldg LoadDescriptions

AreaQuan

SenLoss

%TotLoss

LatGain

SenGain

NetGain

%NetGain

Roof 2,277 802 11.35 0 14,740 14,740 5.96Wall 3,060 1,939 27.47 0 12,597 12,597 5.09Glass 0 0 0.00 0 0 0 0.00Floor Slab 0 0 0.00 0 0 0 0.00

Skin Loads 2,740 38.82 0 27,337 27,337 11.05

Lighting 5,734 0 0.00 0 21,521 21,521 8.70Equipment 28,100 0 0.00 0 105,469 105,469 42.63People 6 0 0.00 1,485 1,650 3,135 1.27Partition 0 0 0.00 0 0 0 0.00Cool. Pret. 0 0 0.00 0 0 0 0.00Heat. Pret. 0 0 0.00 0 0 0 0.00Cool. Vent. 1,000 0 0.00 52,742 26,390 79,132 31.98Heat. Vent. 1,000 4,318 61.18 0 0 0 0.00Cool. Infil. 0 0 0.00 0 0 0 0.00Heat. Infil. 0 0 0.00 0 0 0 0.00Draw-Thru Fan 0 0 0.00 0 6,258 6,258 2.53Blow-Thru Fan 0 0 0.00 0 0 0 0.00Reserve Cap. 0 0 0.00 0 4,559 4,559 1.84Reheat Cap. 0 0 0.00 0 0 0 0.00Supply Duct 0 0 0.00 0 0 0 0.00Return Duct 0 0 0.00 0 0 0 0.00Misc. Supply 0 0 0.00 0 0 0 0.00Misc. Return 0 0 0.00 0 0 0 0.00

Building Totals 7,059 100.00 54,227 193,184 247,411 100.00

BuildingSummary

SenLoss

%TotLoss

LatGain

SenGain

NetGain

%NetGain

Ventilation 4,318 61.18 52,742 26,390 79,132 31.98Infiltration 0 0.00 0 0 0 0.00Pretreated Air 0 0.00 0 0 0 0.00Zone Loads 2,740 38.82 1,485 160,536 162,021 65.49Plenum Loads 0 0.00 0 0 0 0.00Fan & Duct Loads 0 0.00 0 6,258 6,258 2.53

Building Totals 7,059 100.00 54,227 193,184 247,411 100.00

Check FiguresTotal Building Supply Air (based on a 18° TD): 8,492 CFMTotal Building Vent. Air (11.78% of Supply): 1,000 CFM

Total Conditioned Air Space: 2,294 Sq.ftSupply Air Per Unit Area: 3.7027 CFM/Sq.ftArea Per Cooling Capacity: 111.2 Sq.ft/TonCooling Capacity Per Area: 0.0090 Tons/Sq.ftHeating Capacity Per Area: 3.08 Btuh/Sq.ft

Total Heating Required With Outside Air: 7,059 BtuhTotal Cooling Required With Outside Air: 20.62 Tons

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 28: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 10

Air Handler #1 - AHU-1 Or 2 - Summary Loads

ZnNo

DescriptionZone Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

1 BATTERY RM7pm August

1200

1,800

13750

0.42

8,761520

4.33

0500500

Direct50050

Direct500

61

2 HVAC MECH RM8pm July

5451

8,168

813297

0.54

17,712879

1.61

27500

Direct100297

Direct100103

3COMMUNICATION RM7pm July

901

1,350

11743

0.48

7,978473

5.26

27500

Direct5043

Direct5056

4 UPS RM6pm July

1201

1,800

4215

0.13

12,537744

6.20

27500

Direct5015

Direct5088

5 RACK RM6pm July

7593

11,385

704257

0.34

40,9952,4323.20

66000

Direct150257

Direct150286

6 ELECTRICAL RM7pm July

6600

9,900

926338

0.51

69,4393,4455.22

000

Direct150338

Direct150406

Zone Peak Totals:Total Zones: 6Unique Zones: 6

2,2946

34,403

2,7401,0000.44

157,4238,4933.70

1,485500500

1,0001,000

1,0001,000

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 29: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 11

Air Handler #1 - AHU-1 Or 2 - Total Load Summary Air Handler Description: AHU-1 Or 2 Constant Volume - Sum of PeaksSupply Air Fan: Draw-Thru with program estimated horsepower of 2.47 HPFan Input: 65% motor and fan efficiency with 1.2 in. water across the fanSensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in July. Outdoor Conditions: Clg: 98° DB, 82° WB, 140.75 grains, Htg: 68° DBIndoor Conditions: Clg: 74° DB (avg.), 50% RH, Htg: 72° DB

Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in July at 7pm is different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 157,268.

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Zone Space sensible loss: 2,740 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 4,318 Btuh 1,000 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 7,059 Btuh

Heating Supply Air: 2,740 / (1.000 X 1.08 X 3) = 1,000 CFMWinter Vent Outside Air (100.0% of supply) = 1,000 CFM

Zone space sensible gain: 155,977 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 6,258 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 4,559 BtuhTotal sensible gain on supply side of coil: 166,794 Btuh

Cooling Supply Air: 168,085 / (1.000 X 1.1 X 18) = 8,492 CFMSummer Vent Outside Air (11.8% of supply) = 1,000 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: 26,390 Btuh 1,000 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: 26,390 BtuhTotal sensible gain on air handling system: 193,184 Btuh

Zone space latent gain: 1,485 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 52,742 BtuhTotal latent gain on air handling system: 54,227 BtuhTotal system sensible and latent gain: 247,411 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 18° TD): 8,492 CFMTotal Air Handler Vent. Air (11.78% of Supply): 1,000 CFM

Total Conditioned Air Space: 2,294 Sq.ftSupply Air Per Unit Area: 3.7027 CFM/Sq.ftArea Per Cooling Capacity: 111.2 Sq.ft/TonCooling Capacity Per Area: 0.0090 Tons/Sq.ftHeating Capacity Per Area: 3.08 Btuh/Sq.ft

Total Heating Required With Outside Air: 7,059 BtuhTotal Cooling Required With Outside Air: 20.62 Tons

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 30: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 12

Zone Detailed Loads (At Zone Peak Times)

LoadDescription

UnitQuan

-SC-CFAC

CLTDSHGF

U.Fac-CLF-

Sen.Gain

Lat.Gain

Htg.Mult.

Htg.Loss

Zone 1-BATTERY RM peaks (sensible) in August at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 12.0 x 10.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 120 1.00 75.0 0.080 720 0.320 38Wall-1-S-B-D 150 1 27.4 0.144 591 0.576 86Lights-Prof=1 300 1.000 1,024Equipment-Prof=1 1,650 1.000 5,630 0

Sub-total 7,965 0 125Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 8,761 0 137

Zone 2-HVAC MECH RM peaks (sensible) in July at 8pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 16.5, Construction Type: 22 (Medium), SIDB: 75°F, WIDB: 72°F

Roof-1-6-No.Clg-D 528 1.00 67.1 0.080 2,835 0.320 169Wall-1-W-B-D 495 1 34.1 0.144 2,432 0.576 285Wall-2-N-B-D 248 1 27.6 0.144 985 0.576 143Wall-3-S-B-D 248 1 24.1 0.144 860 0.576 143Lights-Prof=1 1,361 1.000 4,645Equipment-Prof=1 1,200 1.000 4,095 0People-Prof=1 1.0 1.000 250 250

Sub-total 16,102 250 739Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 17,712 275 813

Zone 3-COMMUNICATION RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 9.0 x 10.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 90 1.00 75.1 0.080 541 0.320 29Wall-1-N-B-D 135 1 29.6 0.144 576 0.576 78Lights-Prof=1 225 1.000 768Equipment-Prof=1 1,500 1.000 5,118 0People-Prof=1 1.0 1.000 250 250

Sub-total 7,253 250 107Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 7,978 275 117

Zone 4-UPS RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 10.0 x 12.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 120 1.00 77.1 0.080 740 0.320 38Lights-Prof=1 300 1.000 1,024Equipment-Prof=1 2,750 1.000 9,383 0People-Prof=1 1.0 1.000 250 250

Sub-total 11,397 250 38Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 12,537 275 42

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 31: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 13

Zone Detailed Loads (At Zone Peak Times) (cont'd)

LoadDescription

UnitQuan

-SC-CFAC

CLTDSHGF

U.Fac-CLF-

Sen.Gain

Lat.Gain

Htg.Mult.

Htg.Loss

Zone 5-RACK RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 23.0, Construction Type: 22 (Medium)

Roof-1-6-No.Clg-D 759 1.00 77.1 0.080 4,683 0.320 243Wall-1-N-B-D 345 1 28.6 0.144 1,422 0.576 199Wall-2-S-B-D 345 1 25.1 0.144 1,248 0.576 199Lights-Prof=1 1,898 1.000 6,475Equipment-Prof=1 6,650 1.000 22,691 0People-Prof=1 3.0 1.000 750 600

Sub-total 37,269 600 640Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 40,995 660 704

Zone 6-ELECTRICAL RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 20.0, Construction Type: 1 (Light), SIDB: 75°F, WIDB: 72°F

Roof-1-6-No.Clg-D 660 1.00 72.1 0.080 3,808 0.320 211Wall-1-N-B-D 300 1 26.6 0.144 1,150 0.576 173Wall-2-E-B-D 495 1 36.1 0.144 2,575 0.576 285Wall-3-S-B-D 300 1 23.1 0.144 999 0.576 173Lights-Prof=1 1,650 1.000 5,630Equipment-Prof=1 14,350 1.000 48,964 0

Sub-total 63,127 0 842Safety factors: +10%

---------+10%

---------+10%

---------Total w/ safety factors: 69,439 0 926

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 32: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 14

Air System #1 (AHU-1 Or 2) Psychrometric Analysis

System Load Analysis Latent Grains Sensible Temp CFMLeaving Coil Condition 62.247 56.000Draw-Thru Fan 6,258 0.670 316Misc Load on Supply Side 0 0.000 0Supply Air Duct 0 0.000 0Zone Loads 1,485 0.257 157,268 16.842 7,946Sensible Reserve 4,559 0.488 230

Zone Condition 1,485 62.504 168,085 73.661 8,492Return Air Duct 0 0.000Return Air Plenum 0 0.000Misc Load on Return Side 0 0.000Vent Air 1,000 CFM 52,742 9.137 26,390 2.826Blow-Thru Fan 0 0.000

Entering Coil Condition 54,227 71.641 194,476 76.826 8,492

General Psychrometric Equations Used In Analysis:PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)TSH = PR x 1.10 x CFM x (DB entering - DB leaving)TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving) TSH = 1.000 x 1.10 x 8,492 x ( 76.826 - 56.000 ) = 194,475 BtuhTLH = 1.000 x 0.68 x 8,492 x ( 71.641 - 62.247 ) = 54,227 Btuh

----------SUM = 248,702 BtuhGTH = 1.000 x 4.50 x 8,492 x ( 29.648 - 23.098 ) = 250,231 BtuhTotal System Load = 247,411 Btuh

Chilled and Hot Water Flow Rates and Steam RequirementCooling GPM = 250,231 / ( 0.00 x 500 ) = 0.0 GPMHeating GPM = 7,059 / ( 0.00 x 500 ) = 0.0 GPMSteam Req. = 7,059 / 0 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil ConditionsDry bulb temperature: 76.83 Dry bulb temperature: 68.00Wet bulb temperature: 64.64Relative humidity: 52.05Enthalpy: 29.65 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil ConditionsDry bulb temperature: 56.00 Dry bulb temperature: 74.54Wet bulb temperature: 54.87Relative humidity: 93.29Enthalpy: 23.10 Btu/lbm

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 33: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 15

Air System #1 (AHU-1 Or 2) Psychrometric Chart ZC Zone Condition OC Outdoor ConditionLC Leaving Coil Condition EC Entering Coil ConditionSD Supply Duct Temperature Rise RD Return Duct Temperature RiseDTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible GainRE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible GainSM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous GainPRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM

Page 34: HVAC CALCS

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.AMCDE PIB BUILDING, JIZANAl-Khobar, 31952 Page 16

Building Pie Charts Building peaks in July at 5pm.

Building Net Gain247,411

Btuh

Roof - 5.96%

Wall - 5.09%

Lighting - 8.70%

Equipment - 42.63%

People - 1.27%

Cool. Vent. - 31.98%

Draw-Thru Fan - 2.53%Reserve Cap. - 1.84%

Building Loss 7,059

Btuh

Roof - 11.35%

Wall - 27.47%

Heat. Vent. - 61.18%

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM