hpe xm 35 570 modular - jadranenergetika.si · ma70 vibration absorber mat for hpe xm 70 cod....

3
HPE XM 35÷570 MODULAR Air / water Heat Pumps with axial fans - 95 - Technical and construction features Units HPE XM 35 Master Equipped with 1 digital scroll compressor a 1 standard scroll compressor HPE XM 70 Master Equipped with 1 digital scroll compressor and 3 standard scroll compressors HPE XM 70 Slave Equipped with 4 standard scroll compressors Hydro versions: Heat pump unit including pump (pump head 150 kPa) and 8 l pressure vessel. Modular units system. It is possible to realise a large range of combinations till a max cooling output of 488 KW as follows: - 1 x 28,5 kW Master - 1 x 28,5 kW Master plus 7 x 61 kW Slave In each combination one Master unit is required. The max cooling output allowed is 488 kW. Choose the digital Scroll technology combined with new modular units design. Differently from the traditional chillers often switching off/on, the new A2B chillers allow of fine and progressive output modulating by means of a proper combination of both digital and standard scroll compressors. Electronic expansion valve for a precise output regulation. The traditional chillers systems use thermostatic valves for regulation of outlet capacity. The electronic expansion valve also allows the system of faster and easier adjusting of the output based on the actual load. COOLING OUTPUT kW 28,50 61,00 61,00 STANDARD VERSION Code 38500801 38520801 38530801 MODELS HPE XM 35 Master HPE XM 70 Master HPE XM 70 Slave STANDARD VERSION HEATING OUTPUT kW 35,00 71,00 71,00 HYDRO VERSION Code 38500802 38520802 38530802 HYDRO VERSION

Upload: vukiet

Post on 31-Mar-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

HPE XM 35÷570 MODULARAir / water Heat Pumps with axial fans

- 95 -

Technical and construction features

UnitsHPE XM 35 MasterEquipped with 1 digital scroll compressor a 1 standard scrollcompressor

HPE XM 70 MasterEquipped with 1 digital scroll compressor and 3 standard scrollcompressors

HPE XM 70 SlaveEquipped with 4 standard scroll compressors

Hydro versions:Heat pump unit including pump (pump head 150 kPa) and 8 l pressurevessel.

Modular units system.It is possible to realise a large range of combinations till a max coolingoutput of 488 KW as follows:- 1 x 28,5 kW Master- 1 x 28,5 kW Master plus 7 x 61 kW Slave

In each combination one Master unit is required. The max coolingoutput allowed is 488 kW.Choose the digital Scroll technology combined with new modularunits design.

Differently from the traditional chillers often switching off/on, the newA2B chillers allow of fine and progressive output modulating by meansof a proper combination of both digital and standard scrollcompressors.

Electronic expansion valve for a precise output regulation.

The traditional chillers systems use thermostatic valves for regulationof outlet capacity.The electronic expansion valve also allows the system of faster andeasier adjusting of the output based on the actual load.

COOLING

OUTPUT

kW

28,50

61,00

61,00

STANDARD

VERSION

Code

38500801

38520801

38530801

MODELS

HPE XM 35 Master

HPE XM 70 Master

HPE XM 70 Slave

STANDARD

VERSION

HEATING

OUTPUT

kW

35,00

71,00

71,00

HYDRO

VERSION

Code

38500802

38520802

38530802

HYDRO

VERSION

HPE XM 35÷570 MODULARAir / water Heat Pumps with axial fans

combinations HPE XM 35÷570 MODULAR

Possible combinations HPE XM 35÷570 MODULAR

- 96 -

Accessories HPE XM 35÷570 MODULAR

KA rubber coupling+ 32 screws 14 x 60 mmcod. 38500811 € 500,00

MA35 vibration absorber matfor HPE XM 35cod. 38500815 € 145,00

MA70 vibration absorber matfor HPE XM 70cod. 38500816 € 196,00

KT flanged iron sleeve(400 mm) complete of 2 gasketscod. 38500812 € 550,00

CR central controlwith auto-restart + remote ON-OFF(required accessory)cod. 38500810 € 230,00

CC35 condensation controlfor HPE XM 35 MASTERcod. 38500817 € 620,00

CC70 condensation controlper HPE XM 70 MASTER/SLAVEcod. 38500818 € 1.230,00

FL flow metercod. 38500814 € 124,00

KF blind flange with gaskets+ n. 16 screws 14 x 60 mmcod. 38500813 € 210,00

TS Controller Touch Screencod. 38500819 € 3.000,00

28,5 KW ≤ Total output ≥ 488 kW

+...+

+...+

+...+1-8

1-16

65 130 195 260 325 390 455 520 KW

100%

1%

HE

AT

ING

OU

TP

UT

POWER INPUT

MO

DU

LA

TI O

N

CoolingOutput28,5 kW61 kW

89,5 kW122 kW

150,5 kW183 kW

211,5 kW244 kW

272,5 kW305 kW

333,5 kW306 kW

394,5 kW427 kW

455,5 kW488 kW

HeatingOutput35 kW71 kW106 kW142 kW177 kW213 kW248 kW284 kW319 kW355 kW390 kW426 kW461 kW497 kW532 kW568 kW

PossibleCombinations

35 M70 M

35 M + 70 S70 M + 70 S

35 M + 2 x 70 S70 M + 2 x 70 S35 M + 3 x 70 S70 M + 3 x 70 S35 M + 4 x 70 S70 M + 4 x 70 S35 M + 5 x 70 S70 M + 5 x 70 S35 M + 6 x 70 S70 M + 6 x 70 S35 M + 7 x 70 S70 M + 7 x 70 S

Accessories

CR1111111111111111

KT--11223344556677

KF1111111111111111

FL1111111111111111

MA301-1-1-1-1-1-1-1-

MA70-112233445566778

TS1111111111111111

KA1122334455667788

CC351-1-1-1-1-1-1-1-

CC70-112233445566778

HPE XM 35÷570 MODULARAir / water Heat Pumps with axial fans

- 97 -

UM

kW

kW

kW

kW

A

l/h

kPa

DN

m3/h

kW

dB(A)

mm

mm

mm

kg

kg

320

1+0+4

272,5

84,70

319

85,5

133,2

46.872

29,4

125

108.000

0,7 x 9

49

6.650

3.240

3.530

355

0+1+4

305

94,50

355

95

148,5

52.452

29,4

125

120.000

0,7 x 10

6.650

3.500

3.825

390

1+0+5

333,5

103,60

390

104,5

162,9

57.348

29,4

125

132.000

0,7 x 11

50

8.100

3.940

4.295

425

0+1+5

366

113,40

426

114

178,2

62.928

29,4

125

144.000

0,7 x 12

8.100

4.200

4.590

460

1+0+6

394,5

122,50

461

123,5

192,6

67.824

29,4

125

156.000

0,7 x 13

9.550

4.640

5.060

500

0+1+6

427

132,30

497

133

207,9

73.440

29,4

125

168.000

0,7 x 14

51

9.550

4.900

5.355

535

1+0+7

455,5

141,40

532

142,5

222,3

78.336

29,4

125

180.000

0,7 x 15

11.000

5.340

5.825

570

0+1+7

488

151,20

568

152

237,6

83.916

29,4

125

192.000

0,7 x 16

52

11.000

5.600

6.120

UM

kW

kW

kW

kW

A

l/h

kPa

mm

m3/h

kW

dB(A)

mm

mm

mm

kg

kg

35

1+0+0

28,5

9,15

35

9,5

400,3

14,4

4.896

12.000

0,7 x 1

40

1.514

850

1.820

440

470

70

0+1+0

61,0

18,90

71

19

400,3

29,7

10.476

24.000

0,7 x 2

42

2.492

850

1.820

700

765

105

1+0+1

89,5

28,10

106

28,5

400,3

44,1

15.408

36.000

0,7 x 3

42

2.492

2.300

1.820

1.140

1.235

145

0+1+1

122

37,80

142

38

400,3

59,4

20.988

48.000

0,7 x 4

43

2.492

2.300

1.820

1.400

1.530

180

1+0+2

150,50

46,90

177

47,5

400,3

73,8

28.884

60.000

0,7 x 5

45

2.492

3.750

1.820

1.840

2.000

215

0+1+2

183

56,70

213

57

400,3

89,1

31.464

72.000

0,7 x6

46

2.492

3.750

1.820

2.100

2.295

250

1+0+3

211,5

65,90

248

66,5

400,3

103,5

36.360

84.000

0,7 x7

47

2.492

5.200

1.820

2.540

2.765

285

0+1+3

244

75,60

284

76

400,3

118,8

41.976

96.000

0,7 x8

48

2.492

5.200

1.820

2.800

3.060

DESCRIPTION

35 M - 70 M - 70 S (*)

Cooling output (1)

Power absorption (1)

Heating output (2)

Power absorption (2)

Power supply

Absorbed current

Water flow rate

Water pressure drop

Water pipes connection

Air flow rate

Fan power absorption

Sound level (3)

Dimensions*

Large max

Depth min

Height

Transport weight

Weight

DESCRIPTION

35 M - 70 M - 70 S (*)

Cooling output (1)

Power absorption (1)

Heating output (2)

Power absorption (2)

Power supply

Absorbed current

Water flow rate

Water pressure drop

Water pipes connection

Air flow rate

Fan power absorption

Sound level (3)

Dimensions*

Large max

Depth min

Height

Transport weight

Weight

(1) refrigerated water from 12 to 7 °C, outdoor temperature 35 °C.(2) warm water from 40 to 45 °C, outdoor temperature 7 °C dry bulb/6 °C wet bulb(3) Sound pressure level measured in free field at 10 m of distance from the unit (Q=2) according to ISO 3744(*) For Accessories and combination refer the relative table

Technical datasheet heat pump HPE XM MODULAR 62÷140

400V/3+N/50Hz

2.492

1.820

29,4

125