Version 1.0 2015-07-17 Page 1 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
How to Upgrade from WinConfig 9.91c to WinConfig 11.06
This document describes how to upgrade to WinConfig 11.06, while retaining the original DNP map and settings of
the REG-PED. There are basically four steps to this upgrade process: extract the existing settings; upgrade the
firmware; reload the settings; confirm that everything has loaded correctly.
Download WinConfig 11.06.
Extract the contents of the zip file.
Navigate to the C:\...\WinConfig 11.06\bin directory and run WinConfig.exe.
The following popup appears; choose the Advanced option:
Step 1: Extract the existing settings
Ensure that the PC with WinConfig is on the same IP network as the REG-PED
1/ Click on the icon with the blue transfer arrow
2/ Select REG-PED
3/ Click the Detect on LAN button
Version 1.0 2015-07-17 Page 2 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
A list appears showing all REG-PEDs on the network.
4/ Select the appropriate REG-PED from the list
5/ Enter the login details as shown
6/ Click on the Remote Transfer button
Once this process completes, the settings should be saved for future reference
WinConfig should be left open throughout the next step
Version 1.0 2015-07-17 Page 3 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
Step 2: Upgrade the firmware
WinConfig itself can normally be used to perform minor to mid-level firmware upgrades, but in this case we are
performing a significant firmware jump, requiring the use of the RPL utility program. The following process describes
how to do this successfully:
1/ Connect a null modem cable (supplied) between your PC and the Param port of the REG-PED.
2/ Navigate to C:\...\WinConfig 11.06\RPL and run RPL.exe.
3/ Set up firewall exceptions for RPL. A TFTP connection is required for the new firmware to be installed.
4/ The Com port of your PC should be selected using the Settings button. Click on the Terminal tab and confirm the
serial connection is active by pressing the Enter key to get a prompt returned. Do not proceed until this has been
achieved.
5/ Configure RPL as shown below, using appropriate IP addresses. Remember to tick the boxes down the left hand
side, and to configure the IP address of your own PC.
6/ Select the Ramdisk and Kernel Update file by navigating to C:\...\WinConfig 11.06\RPL\edc\ and selecting
c2014-11-26_WinConfig_11_0_6_max3COMs_LoSecurity.edc
Version 1.0 2015-07-17 Page 4 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
7/ Click the Update button
The upgrade process can be monitored by clicking the Terminal tab.
#### is an indication that the IP network has been correctly configured and the firmware files are being loaded;
TTTTT indicates that something has not been set up correctly.
Once the following is observed, the process is complete
Version 1.0 2015-07-17 Page 5 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
Step 3: Reload the settings
1/ Click on the icon with the red transfer arrow. WinConfig automatically detects the available REG-PEDs
2/ Select the REG-PED
3/ Enter the login details as shown
4/ Click on the Transfer button
Warnings will appear and can be ignored at this time:
A 23 step process occurs, completing the download:
Version 1.0 2015-07-17 Page 6 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
Step 4: Confirm the settings
1/ WinConfig can work with multiple setting files at the same time, so to avoid mixing these up, delete the existing
offline setting file
2/ Click on the icon with the blue transfer arrow
Board Type: REG-PED
Detect on LAN
Version 1.0 2015-07-17 Page 7 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
3/ Select the REG-PED from the list
By default, WinConfig 11.06 bonds the Ethernet ports of the REG-PED for greater data security, meaning that both
ports share the same IP address, with only one port active at any given time. If this is not appropriate for your
application, perform steps 4 to 7, otherwise continue to step 11 to extract the settings:
4/ Click the Change board IP settings button
Version 1.0 2015-07-17 Page 8 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
5/ Select Use Ethernet interfaces independently
6/ Configure the second IP address. Note that this must be in a separate subnet to the first address
7/ Click the Set button
The REG-PED will now reboot and start up with the new Ethernet port settings
Version 1.0 2015-07-17 Page 9 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
8/ Once the REG-PED has rebooted, click on the icon with the blue transfer arrow again
9/ Click the Detect on LAN button
10/ Select the REG-PED
11/ Enter the login details as shown
12/ Click on the Transfer button
Version 1.0 2015-07-17 Page 10 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
After a short 3 step process, the settings are extracted from the REG-PED
To compare the final setting file with the previously saved setting file:
1/ Click the Compare icon
2/ Select Compare with settings file
3/ Click the Compare button
Version 1.0 2015-07-17 Page 11 of 11 Originator: John Parker
HV Power Measurements & Protection Ltd NZ: 09- 377 2001
Unit 4, 1 Porters Ave, Eden Terrace, Auckland AUS: 1-800-172-120 P O Box 26-074, Epsom, Auckland 1030, New Zealand mail: [email protected]
An Excel spreadsheet is produced, with any differences highlighted on the various tabs for review:
SH #2 TRANS AVR REG-PED 2015-02-05.xml DNP3_REGD_BASIC
descr=SH_TRANS2 descr=DNP3_REGD_BASIC
date=20120707 date=20120707
time=1900 time=1900