hot water distribution problems
TRANSCRIPT
![Page 1: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/1.jpg)
Hot Water Distribution ProblemsThis presentation premiered at
Water Smart Innovations 2015
October 8, 2015
T-1551
3:05pm – 3:35pm
Russ Horner
Water Management, Inc.
Water Management, Inc. 12015
![Page 2: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/2.jpg)
We know that when low flow faucets and showers
are installed in Single Family Homes the wait
time for hot water increases significantly.
Water Management, Inc. 22015
![Page 3: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/3.jpg)
Water Management, Inc. 3
To learn more about hot water wait times in single family homes contact:
2015
![Page 4: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/4.jpg)
Water Management, Inc. 4
Pipes cool down much faster at lower flow rates.
2015
![Page 5: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/5.jpg)
Water Management, Inc. 5
To solve the problem with long wait times in single family homes, contact:
2015
![Page 6: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/6.jpg)
Water Management, Inc. 6
ACT D’Mand Kontrol System is an innovative pump that when installed under the fixture furthest from your water heater, sets up a recirculation system.
2015
![Page 7: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/7.jpg)
Water Management, Inc. 72015
![Page 8: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/8.jpg)
Water Management, Inc. 8
Commercial properties all have recirculation pumps, but some still experience problems with hot water distribution.
2015
![Page 9: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/9.jpg)
Water Management, Inc. 9
There are 4 Rules for Diagnosing Hot Water Distribution Problems:
1. The ASPE pressure differential Rule
2. The Proper recirculation piping Rule
3. The Return temperature Rule
4. The 80/20 water balancing Rule
2015
![Page 10: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/10.jpg)
Water Management, Inc. 10
Rule #1
Check the water pressure on the hot side and on the cold side. If the water pressures are more than 10% off you need to figure out the cause.
2015
![Page 11: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/11.jpg)
Water Management, Inc. 11
Example #1: Apartment community (314 units) in Tucson AZ. Cold water is provided off of main trunk line and hot water is provided from secondary lines.
Main trunk line: 85psi
Secondary lines: 60psi
2015
![Page 12: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/12.jpg)
Water Management, Inc. 12
Example #2: Apartment community in Gaithersburg, MD (831 units) with centralized hot water.
*
2015
![Page 13: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/13.jpg)
Water Management, Inc. 13
58 psi after90 psi pre
Large 8” check valve had failed and was reducing the pressure for the cold water make-up by 32 psi (33%).
2015
![Page 14: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/14.jpg)
14
If you break this rule – CROSSOVER can occur
Crossover can occur at faucets if flow rate is below 1.0gpm or at showers if the flow rate is below 2.0gpm.
Water Management, Inc.2015
![Page 15: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/15.jpg)
Page 15 Copyright © by NEOPERL / July 2015
Popular flow rates of Faucet aerators. Neoperl makes 3
different streams that are available in many different flow rates.
0.35 gpm
0.5 gpm
1.0 gpm
1.2 gpm
1.5 gpm
1.8 gpm
2.2 gpm
Water Management, Inc.
![Page 16: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/16.jpg)
16
Defective Valves
Crossover can also occur if a water fixture is faulty. One such fixture is the MIXET® tub and shower valve. These valves can develop a wear pattern which allows hot and cold water to cross over even in the off position.
Water Management, Inc.2015
![Page 17: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/17.jpg)
17
A replacement stem is available that features a quadruple seal gasket to seal the eroded areas of the valve body that are allowing the water to crossover.
2015 Water Management, Inc.
Over time the brass body deteriorates and channels develop allowing water to pass around the hard plastic stem.
Mixet Tub Shower Valve
![Page 18: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/18.jpg)
18
Return line in boiler room has connections to the storage tank and also to the water returning to the building
Make sure that the return line is plumbed into the mixing valve so that water can circulate properly.
Rule #2
Water Management, Inc.2015
![Page 19: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/19.jpg)
19
Rule #2
Water Management, Inc.2015
This 7 year old Westin located in Northern Virginia near our Nation’s Capital experienced long wait times for hot water especially after the Westin Heavenly Showerheads were installed.
![Page 20: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/20.jpg)
20
The Westin Dulles
Water Management, Inc.2015
After
![Page 21: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/21.jpg)
The Westin is an 8 story, 315 room hotel in VA. In 2014 the dual style Speakman showerheads were replaced with the Heavenly showerhead from Kohler. Flow rate was reduced by > 50%.
Water Management, Inc. 212015
![Page 22: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/22.jpg)
By November of 2014 the property was experiencing a major issue with hot water. By January of 2015 guest complaints were at an all time high. The water saving showerheads were blamed.
Water Management, Inc. 222015
![Page 23: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/23.jpg)
23
The Westin: Mechanical Room
Storage TanksMixing Valves
Water Management, Inc.2015
By mistake all of the recirculating water was being redirected back to the storage tanks and not to cold inlet of the mixing valve. Once this was corrected, the problem was solved.
![Page 24: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/24.jpg)
24
Charlotte, North Carolina – 176 rooms
Rule #3
-01
-15
-20
-30
Mechanical room in basement
Water Management, Inc.2015
Make sure the return temperature of all of the risers is the same. For this building the temperature in the return line for the risers furthest from the mechanical room were the same as the ambient air.
![Page 25: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/25.jpg)
25
Return line temperature should be within 10⁰ of the supply line temperature.
Compare supply temp to return temp
Water Management, Inc.2015
![Page 26: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/26.jpg)
26
For the first few risers we found that the Supply temperature was 125⁰ and the return line temperature 118.6⁰. Delta T of less than 7 degrees is good. This was not the case of the risers towards the middle and end of the building.
Water Management, Inc.2015
![Page 27: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/27.jpg)
27
The risers furthest away from the mechanical room had little to no recirculation so we had to force the water to the risers furthest from the mechanical room.
The Path of Least Resistance
Risers furthest from mechanical room
Risers closest to mechanical room
Water Management, Inc.2015
![Page 28: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/28.jpg)
28
HW return line
To force water to the risers towards the back of the building, the hot water recirculation system needs to be balanced.
Gate Valve
Water Management, Inc.2015
![Page 29: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/29.jpg)
Water Management, Inc. 29
Ball Valve
Circuit Setter
2015
To balance a hot water recirculation system, it is critical that the end of each riser have a ball valve or a “CircuitSetter” on it.
Be sure that the valves on the first 80% of the risers are not open more than 20% of the way.
Rule #4
![Page 30: Hot Water Distribution Problems](https://reader031.vdocuments.mx/reader031/viewer/2022012011/61d9b546e5ca2a528116b865/html5/thumbnails/30.jpg)
Water Management, Inc. 30
Hot Water Distribution ProblemsWater Smart Innovations 2015
October 8, 2015
T-1551
3:05pm – 3:35pm
Sonoma D
Russ Horner
Water Management, Inc.
Thank You
2015