Holistic Approaches to Green IT. Going Green Can Save Money. Dr Hugh Beedie CTO ARCCA & INSRV Cardiff University. Introduction. What is Green IT ? Drivers & Metrics Data Centres, Power & Cooling Servers, Virtualisation, and Storage PCs, Monitors & Thin clients Printing and Networks - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/1.jpg)
Holistic Approaches to Green IT
Dr Hugh Beedie
CTO
ARCCA & INSRV
Cardiff University
Going Green Can Save Money
![Page 2: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/2.jpg)
Introduction What is Green IT ? Drivers & Metrics Data Centres, Power & Cooling Servers, Virtualisation, and Storage PCs, Monitors & Thin clients Printing and Networks Purchasing policies Influencing user behavior & the organisation ‘Thinking outside the box’ – save energy with
Condor
![Page 3: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/3.jpg)
What is Green IT ?
No environmental impact Get real
Use of resources in an efficient way Better
Avoid ‘Greenwash’ Often faulty comparisons
Importance of your Context Your situation, drivers & metrics… Can change over time
![Page 4: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/4.jpg)
Drivers – Why do Green IT?
Increasing demand for CPU & Storage Lack of Space Lack of Power Increasing energy bills (oil prices doubled) Enhancing the reputation of your University &
attracting better students Sustainable IT & Legal Compliance Because we should (for the Planet )
![Page 5: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/5.jpg)
Metrics – Chicken and Egg
You can’t measure everything.So, which numbers do you
measure, when you don’t know which are important ?
![Page 6: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/6.jpg)
Guesstimation
Which use more, PCs or Servers ?10,000 PCs using
150W, 8 hrs/day, 220 days/yr UK electricity £300,000 p.a.
500 servers using 300W + losses (X 2) 24 X 7 UK prices £300,000 p.a.
So where do we start ?
![Page 7: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/7.jpg)
Examples of Metrics
Cost (Watts, TCO, capital investment, etc)Value (CPU Hrs, MFlops, Gbps, Papers)Value/Cost is better ? (MFlops/Watt)Cooling & power losses (PUE)Average kWhr per PC per yearPages printed (or not printed ?)Cost per page (electricity, paper)Space saved
![Page 8: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/8.jpg)
Power Usage Effectiveness
PUE=Total Power/Computer Power
![Page 9: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/9.jpg)
The DetailWhat wastes the power ?
Power Conversion in HV Transformer Before it gets to your room, you lose power.
Transformer Efficiency = 98% or 95% Return On Investment (ROI)?
Capital Cost = £5500 or £5000 (650kVA) New installation (@200kW), ROI = 1 month Replacement, ROI = 1 year Lifetime of investment = 20+ yrs !!!!!
![Page 10: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/10.jpg)
Data Centre Consumption
Powerdelivery40%
80% 100%
Loads
Cooling
Cum
ulat
ive p
ower Bull View
Source: Intel Corp.
7.3%
Voltage Regulators
20W
5.5%
Server fans 15W
7.3%
UPS +PDU 20W
18.2%
PSU 50W
36.4%Load
CPU, Memory,Drives , I/O
100W
25.5%
Room cooling system
70W
Total 275W
Intel View
![Page 11: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/11.jpg)
Cooling Inside the RoomHot Aisle/Cold Aisle Layout
![Page 12: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/12.jpg)
Hot Aisle Containment
Hot Aisle Ceiling Tiles/Cable Trough
Seals in hot air, prevents mixing with room air Chamber
DoorsAccess to hot aisle, locks for security. Prevents hot air mixing
InRow RC unit
InRow air conditioner cools hot exhaust air directly
![Page 13: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/13.jpg)
Rack Air Containment Airflow Diagram
Server exhaust air is prevented from escaping by rear containment
All exhaust air is returned to InRow cooling unit
Fans of InRow cooling unit distribute cool air to front of IT equipment
Top Down View
Front
Rear
InRow Cooling
Unit
InRow Cooling
Unit
NetShelter SX Rack
Servers
Rear Containment
Front Containment
![Page 14: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/14.jpg)
APC Inline RC units • Up to 20kW/rack• Uniform cooling allows raising cold air temp
Cooling Inside the Room
Temperature (deg C)
<24 27.4 30.8 34.3 >37.8
![Page 15: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/15.jpg)
Cooling – Outside the Room
3 Airedale Chillers
Ultima Compact Free Cool 120
Quiet model
Variable speed fans
N+1 arrangement
(We needed that )
![Page 16: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/16.jpg)
And in real life
![Page 17: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/17.jpg)
Free-cooling
Cooling Load
System operated on 100% Free-Cooling (12% of Year)
System operated on partial Free-Cooling (50% of Year)
System operated on mechanical cooling only(38% of Year)
-7oC3.5oC
12.5oCAmbient Temp.
Mechanical (compressor) coolingFree-cooling
![Page 18: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/18.jpg)
Back Up Power
Full and half load efficiency >92%
Scalable & Modular – could grow as we grew, keeping %max load high
APC 160kW Symmetra UPS
![Page 19: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/19.jpg)
UPS Efficiencies
![Page 20: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/20.jpg)
High Density Servers
Important if you spend on advanced cooling methods
Can have shared power supplies (PSU) Higher efficiency
Blade Servers have shared PSUs Not always good for HPC
Bull supplied half-width, 1U servers. 2, quad core, 80W Harpertown CPUs
![Page 21: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/21.jpg)
Merlin Cluster
![Page 22: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/22.jpg)
Cardiff’s PUE vs Temperature
Average PUE = 1.3
No correlation with temperature ?
![Page 23: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/23.jpg)
Key Power Saving Solutions
Low power servers
High Density Servers (sweating the asset)
Modular UPS
(not over provisioned)
Cooling Infrastructure
Chilled Water“Air Handling”
HVTransformer
98% efficiency
![Page 24: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/24.jpg)
Virtualisation and Storage
Virtualisation Many virtual servers in one physical server
Key questions How much can you save ? How much of that is energy ?
Storage Fast disk=450GB, 25W, Slow disk=2TB, 15W Tiering = Energy saving
![Page 25: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/25.jpg)
Business CaseBefore Virtualisation
Equipment FY Unit Total
100 RM servers - replacement cost, inc installation and peripherals
(assumes Dell PowerEdge 1950)
08/09 £2700 £270K
100 ‘Out of warranty’ servers – 2 year extended warranty 08/09 £500 £50K
250 Production Servers - replacement cost, inc installation and peripherals
(assumes Dell PowerEdge 1950)
09 - 11 £2700 £675K
1 Air conditioning upgrades in RWD 1.71 and Main 1.71 Computer Rooms
08/09 £100K £100K
6 12KVA and 16KVA UPS replacements 09/10 £9K £54K
Total hardware replacement costs (1 for 1) £1.15M
450 Cost of electricity for servers (200w per server @12p/KW hour) Annual £94K £283K
450 Cost of electricity for cooling (100w per server @12p/KW hour) * Annual £47K £142K
Total electricity costs £425K
Total hardware and electricity costs £1.24M
* Inefficient raised floor and ceiling mount air conditioning units
![Page 26: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/26.jpg)
Business CaseAfter Virtualisation
Equipment FY Unit Total
5
RM Servers – replacement cost, inc installation and peripherals
(assumes Dell PowerEdge P900 with 32GB RAM, 2TB Disk)
08/09 £5K £25K
5
‘Out of warranty’ servers– replacement cost, inc installation and peripherals (assumes Dell PowerEdge P900 with 32GB RAM, 2TB Disk)
09/10 £5K £25K
13
Production Servers – replacement cost, inc installation and peripherals
(assumes Dell PowerEdge P900 with 32GB RAM, 2TB Disk)
09/11 £5K £65K
2 24TB Central Storage – assumes Sun Fire X4500 or Equivalent 08/09 £15K £30K
46 VMware ESX Licences – one per CPU 08 - 11 £1K £46K
Physical to Virtual (P2V) Software ? 08/09 ? ?
VMware backup software? 08/09 ? ?
Total hardware costs (VMware Infrastructure) £191K
25 Cost of electricity for servers (500w per server @12p/KW hour) Annual £13K £39K
25 Cost of electricity for cooling (250w per server @12p/KW hour)* Annual £6K £18K
Total electricity costs £57K
Total hardware and electricity costs £248K
* Inefficient raised floor and ceiling mount air conditioning units
![Page 27: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/27.jpg)
Virtualisation Business Case3 Year ROI with Virtualisation
Before Total
Total hardware costs £1.15M
Total electricity costs £425K
Total costs £1.57M
After Total
Total hardware costs (VMware Infrastructure)
£191K
Total electricity costs £57K
Total costs £248K
Hardware £959K
Electricity £368K
Total Savings = £1.32M
![Page 28: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/28.jpg)
Planet Filestore
JISC-funded project to measure savings of..Tiered storage – scenario
100TB needed for 30000 (staff and students) High performance for 7000 concurrent users Site mirrored Raid 10 450GB SAS vs Non mirrored Raid 5 2TB SATA ~ factor of 16 in hardware cost Therefore, use HSM (old data on Tier 2)
What about energy ?
![Page 29: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/29.jpg)
Planet Filestore Project
Fast disk (FC/SAS) 450GB, 25W
Slow disk (SATA) 2TB, 15W
Tiered storageTier 1 – DRTier 2 – non DR
100TB Tier 1 (DR)Energy cost
£25,000 p.a.10TB Tier 1 (DR)90TB Tier 2(nonDR)Energy cost
£3,250 p.a.
Energy saving = £21,750
![Page 30: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/30.jpg)
PCs & Monitors
Where to start ?Duty cycle guesstimate
Always on (100%) On during working
hours (20%)
Turn it off at night !!
![Page 31: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/31.jpg)
What next for PCs ?
More stringent power saving policiesAsset Management (reporting)Influencing user behaviour (Joulemeter)
![Page 32: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/32.jpg)
What about Thin Clients ?
Year PC Thin Client
2005 300W 15W
2010 50W 5W
Still some scope, but notwhat there used to be
![Page 33: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/33.jpg)
Printing
Thanks to Liverpool John Moores University (LJMU) for the next 2 slides
![Page 34: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/34.jpg)
Carbon Footprint Savings
• Hundreds of devices removed– Old lasers– Deskjets– Fax machines
• Replaced with fleet of 220 devices
• Automatic power saving after 2 hours
• Use of recycled paper
• FollowMe documents held for 18 hours
![Page 35: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/35.jpg)
Actual Savings at LJMU
![Page 36: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/36.jpg)
Networks
Power used by switches 3.5Gbps/W to 0.5Gbps/W
Cardiff LAN has 50,000 outlets 100kW down to 15kW Potential £85k p.a. by choosing well
PoE (up to 25W down a UTP cable) 5W in the cable, 5W DC-DC conversion 40% loss
![Page 37: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/37.jpg)
Use EnergyStar PCsDiscourage use of the fastest PCsUse energy in your TCO calculationsEnsure suppliers only publicise green PCs
Purchasing Policies
![Page 38: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/38.jpg)
Influencing Behaviour
Context – who pays for electricityTarget your messages
Users• Their PC uses ???W• Pages printed last week ??
Technical types – detail• MFlops, kW, Geeks/Pint
Managers• Bottom line ££££• Reputation.
![Page 39: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/39.jpg)
Finally….
What is Green, but makes your PC use more electricity ?
Answer – CondorSo, what is Condor ?Condor takes spare CPU Cycles for use in
Research calculations Runs at low priority so users don’t notice
So why is it Green ?
![Page 40: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/40.jpg)
Condor - 2.4GHz Core2Duo
0
50
100
Idle (W) 64.5
Max (W) 80.7
![Page 41: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/41.jpg)
Conclusions
Measure, Improve, Measure againLook everywhere for wasteContext changes over time
Make sure you revisit your assumptions
Don’t just do the technical stuffThink out of the box (Condor)
![Page 42: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/42.jpg)
Questions ?
![Page 43: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/43.jpg)
Cardiff’s New Datacentre
£3M grant to purchase a supercomputerNew Datacentre required with appropriate
power, cooling ..Our Context ?
INSRV Sustainability Mission - To minimise CU’s IT environmental impact and to be a leader in delivering sustainable information services.
Limited experience in Datacentre build Server & Data Center Energy Efficiency
(US Congress Report 2007)
![Page 44: Holistic Approaches to Green IT](https://reader036.vdocuments.mx/reader036/viewer/2022062517/56813de3550346895da7b80f/html5/thumbnails/44.jpg)
What did Cardiff do ?
Ran 2 tenders, many contractors (& subs) HPC & Environment (power, cooling)
Strong project management TCO as key evaluation criterion Value = HPC Benchmark figures Winner = Highest Value/TCO